Loading...
HomeMy WebLinkAboutFile Documents.611 E Durant Ave.0048.2019 (9).ACBKExisting steel beams in Locker Room exposed during remodel N/A Shaw Construction Placement Location: Documents Used: General Contractor: InsulVailInstallation Contractor: Performed by:Shane Sorensen Weather, Temperature:indoors, 75 ºF Comments:During the Locker Room remodel, areas on existing steel beams were found to be missing spray-applied fireproofing, potentially as a result of omission during original construction, or due to damage during previous work or remodels. The contractor patched the majority of these areas to a state that appeared to generally match or exceed the original applied thicknesses. We observed some areas on beams with exposed steel. Shaw Construction will schedule us for another inspection after patching is complete, new MEP systems are in place, and additional damage is unlikely to occur. 100% Visual Inspection:Does Not Conform Product Manufacturer, ID:Isolatek, Cafco Fiber-Patch Date(s) Applied: Weather Protection:N/A 7/17/20 - 7/20/20 Name Company On-Site Notifications Chuck Apostolik Shaw Construction Photos O'Connor Consulting, LLC 710 Hearthstone Drive Basalt, CO 81621 Michael O'Connor Aspen Mountain Club - Locker Room Fireproofing Client: Jul 22, 2020Report Date:Work Order No.: Sprayed Fire-Resistive Materials (SFRM) Verification 20-6572.Fireproofing.0001; ver: Reviewed by:Work Order Date:Jul 21, 2020 Results apply only to the specific items and locations referenced and at the time of testing, observations or special inspections. This report should not be reproduced, except in full, without the written permission of GROUND Engineering Consultants, Inc. 41 Inverness Drive East, Englewood, Colorado www.groundeng.com 303-289-1989 Englewood | Commerce City | Loveland | Granby | Gypsum | Colorado Springs Page 1 of 2 08/07/2020 Bare steel on beam Bare steel on beam O'Connor Consulting, LLC 710 Hearthstone Drive Basalt, CO 81621 Michael O'Connor Aspen Mountain Club - Locker Room Fireproofing Client: Jul 22, 2020Report Date:Work Order No.: Sprayed Fire-Resistive Materials (SFRM) Verification 20-6572.Fireproofing.0001; ver: Reviewed by:Work Order Date:Jul 21, 2020 Results apply only to the specific items and locations referenced and at the time of testing, observations or special inspections. This report should not be reproduced, except in full, without the written permission of GROUND Engineering Consultants, Inc. 41 Inverness Drive East, Englewood, Colorado www.groundeng.com 303-289-1989 Englewood | Commerce City | Loveland | Granby | Gypsum | Colorado Springs Page 2 of 2