HomeMy WebLinkAboutInspection.533 W Hallam St.0285.2018 (4).ARBK04/20/2020
04/21/2020
justinh
03/24/2020
T
TT
2
6
6
7
7
8
8
9
9
10
10
LL
GG
DD
CC
3
4
E
H
1
1
AA
BB
FAMILY / GAME
001
LAUNDRY
005
STO.
004
DRESS
021
BDRM #2
020
BATH #2
023
W.C.
025
BDRM #1
010
DRESS
011
CLO.
012
BATH #1
013
W.C.
014
W.C.
034
BATH #3
033 DRESS
031
CLO.
032
BDRM #3
030
BDRM #4
040
POWDER
002
BATH #4
042
W.C.
043
B15 - S
2 1/2"x12"
B15 - S
2 1/2"x12"
B195 - R
2 1/2"x36"
B290 - R
2 1/2"x30"
2 1/2"x12"B 15 - S
TO HP-1,
ZD-1A &
RZ-4A
10"x 26" (12"x28") DN
10"x 26" (12"x28") DN
(2) 4" EA DN TO DRYER
8" EA DN(2) 4" CA & 4" VENT UP & DN
B145 - S
2 1/2"x30"
B105 - R
2 1/2"x24"
B140 - S
2 1/2"x24"
2 1/2"x12"B 20 - S
20"x 8" (22"x10")
30"x 8" (32"x10")
B55 - S
2 1/2"x12"
B685
3"x78"
B270 - S
3"x30"B270 - R
3"x30"
3"x30"B 200 - R
B140 - S
2 1/2"x24"
2 1/2"x12"B 45 - S
B15 - S
2 1/2"x12"
2 1/2"x30"B 195 - R2 1/2"x30"B 130 - S
B105 - R
2 1/2"x24"B50 - S
2 1/2"x12"2 1/2"x12"B 50 - S
B290 - R
2 1/2"x30"
14"x 10" (16"x12") UP
14"x 10" (16"x12") UP
2 1/2"x30"B 280 - S
14"x 6" (16"x8") UP
10 9 8 7 6 5 4 3 2 1
A
C
D
E
F
G
H
J
K
L
1
1 1
1
1
TO HP-1,
ZD-1C, &
RZ-3B
1
1
1
1
1
1
1
11
1
1
1
1
TO HP-1,
ZD-1B, &
RZ-1A
3"x48"B 400 - S
285 -SA
400 -TA
400 -TA
L
2
ww
w
.
a
e
c
-
v
a
i
l
.
c
o
m
of
Drawn By:Checked By:
AEC PROJECT #:
COPYRIGHT 2018 ARCHITECTURAL ENGINEERING CONSULTANTS, INC.c
c
ae
PO
B
o
x
8
4
8
9
,
4
0
8
0
1
U
S
H
w
y
6
&
2
4
,
S
t
e
2
1
4
,
A
v
o
n
,
C
o
lo
r
a
d
o
,
8
1
6
2
0
Me
c
h
a
n
i
c
a
l
,
E
l
e
c
t
r
i
c
a
l
&
L
i
g
h
t
i
n
g
D
e
s
i
g
n
S
e
r
v
i
c
e
s
Ar
c
h
i
t
e
c
t
u
r
a
l
E
n
g
i
n
e
e
r
i
n
g
C
o
n
s
u
l
t
a
n
t
s
Te
l
e
p
h
o
n
e
:
9
7
0
-
7
4
8
-
8
5
2
0
F
a
x
:
9
7
0
-
7
4
8
-
8
5
2
1
An
O
f
f
i
c
e
w
i
t
h
L
E
E
D
™
A
c
c
r
e
d
i
t
e
d
P
r
o
f
e
s
s
i
o
n
a
l
s
DATE:ISSUE:
FOR PERMIT ONLY
SCALE 1/4" = 1'-0"
18032.00
DU
N
C
A
N
S
K
I
H
A
U
S
53
3
W
E
S
T
H
A
L
L
A
M
AS
P
E
N
,
C
O
L
O
R
A
D
O
,
8
1
6
1
1
M-111A
LOWER
LEVEL HVAC
FLOOR PLAN
4 14
BLU TOC
11-23-18 PERMIT
1/4" = 1'-0"1 LOWER LEVEL HVAC FLOOR PLAN
1. ALL DUCTWORK DIMENSIONS ARE SHOWN INSIDE TO INSIDE.
2. ALL INTERIOR SUPPLY AND RETURN DUCTWORK SHALL INCLUDE 1" LINER UNLESS
OTHERWISE NOTED. ALL OUTSIDE AIR INTAKE AND ROUND DUCTWORK SHALL BE
WRAPPED WITH 1.5" THICK INSULATION UNLESS OTHERWISE NOTED.
3. ALL FINAL DUCTWORK CONNECTIONS TO SUPPLY GRILLES (OR PLENUMS) SHALL BE
COMPLETED WITH ACOUSTICAL FLEXIBLE DUCT UNLESS OTHERWISE NOTED AND A
MAXIMUM LENGTH OF FIVE FEET.
4. ALL ROUND DUCT CONNECTIONS TO ROUND DUCTWORK SHALL BE CONICAL TEES.
5. ALL SQUARE 90 DEGREE ELBOWS SHALL HAVE TURNING VANES.
6. ALL DUCTWORK SHALL BE RUN TIGHT TO UNDERSIDE OF STRUCTURE WHERE IT
EXISTS UNLESS OTHERWISE NOTED.
7. ALL DUCTWORK PASSING THROUGH FIRE-RATED ASSEMBLIES SHALL INCLUDE FIRE
DAMPERS RATED TO MATCH THAT OF THE ASSEMBLY, EVEN WHERE NOT EXPLICITLY
NOTED ON THIS PLAN.
8. ALL FIRE DAMPERS ARE INTENDED TO BE SPRING OPERATED CURTAIN DAMPERS.
ALL FIRE SMOKE DAMPERS ARE INTENDED TO BE EQUIPPED WITH 120V ACTUATORS.
9. ALL SUPPLY GRILLES SHALL INCLUDE A BALANCING DAMPER(S), EVEN IF NOT
SPECIFICALLY SHOWN, UNLESS OTHERWISE NOTED. IF THE DAMPER IS LOCATED IN
AN INACCESSIBLE LOCATION, CABLE-STYLE DAMPERS (ROTOTWIST OR EQUIVALENT)
SHALL BE INSTALLED AND SHALL BE ADJUSTABLE FROM THE GRILLE FACE.
10. COORDINATE ALL ACCESS PANEL LOCATIONS WITH THE ARCHITECT.
11. ALL MOTORIZED DAMPER ACTUATORS SHALL BE LOW VOLTAGE. IT IS MECHANICAL
CONTRACTOR'S RESPONSIBILITY TO PROVIDE ALL NECESSARY EQUIPMENT AND
WIRING FOR THEIR INSTALLATION. IF 120 V ACTUATORS ARE DESIRED, COORDINATE
WITH ELECTRICAL CONTRACTOR OR CONTACT ELECTRICAL ENGINEER.
12. ALL DUCTWORK SHALL BE SUPPORTED IN ACCORDANCE WITH THE 2015 IMC 603.10
AND SMACNA HVAC DUCT CONSTRUCTION STANDARDS.
GENERAL NOTES:SHEET NOTES:
1 LOCATE HIGH ON WALL.
09-16-19 PERMIT COMMENTS R1
12-16-19 PERMIT COMMENTS R2
12-20-19 PRICING SET
01-16-20 PERMIT COMMENTS R3
03-25-20 CD CEHCK SET
04-17-20 PERMIT COMMENTS R2.2
04/21/2020
justinh
04/20/2020
2
6
6
7
7
8
8
9
9
10
10
LL
GG
DD
CC
3
4
E
H
1
1
AA
BB
FAMILY / GAME
001
LAUNDRY
005
STO.
004
DRESS
021
BDRM #2
020
BATH #2
023
W.C.
025
BDRM #1
010
DRESS
011
CLO.
012
BATH #1
013
W.C.
034
BATH #3
033
DRESS
031
CLO.
032
BDRM #3
030
BDRM #4
040
POWDER
002
BATH #4
042
1
EF
2
EF 7
EF
8
EF
9
EF
6
EF
5
EF
4
EF
3
EF
BDD
BDD
BDD
BDD
BDD
BDD
BDD
BDD
BDD
10"x 8" (12"x10")16"x 10" (18"x12")
16
"
x
4
"
(
1
8
"
x
6
"
)
8"
x
8
"
(
1
0
"
x
1
0
"
)
8"
x
8
"
(
1
0
"
x
1
0
"
)
8"ø8"ø
6"ø6"ø
8"ø8"ø8"
ø
8"
ø
8"
(
1
1
"
)
6"ø6"ø
8"ø8"ø
10
"
x
8
"
10
"
x
8
"
8" (11")
16"x 12" (18"x14")
16
"
x
1
0
"
(
1
8
"
x
1
2
"
)
8"
x
8
"
(
1
0
"
x
1
0
"
)
8"
ø
8"
ø
8"ø8"ø
8"
x
6
"
(
1
0
"
x
8
"
)
8"ø8"ø
6"ø6"ø
8"
ø
8"
ø
6"ø6"ø
16"x 10" (18"x12")
14
"
x
8
"
(
1
6
"
x
1
0
"
)
8" (11")
8"
ø
8"
ø
16"x 10" (18"x12")
6"
ø
6"
ø
8"ø8"ø
4" (7")
8" (11")
4" (7")
11"x 4" (12"x5") UP
13"x 4" (14"x5") UP
11"x 4" (12"x5") UP 11"x 4" (12"x5") UP
11"x 4" (12"x5") UP
11"x 4" (12"x5") UP
11"x 4" (12"x5") UP
13"x 4" (14"x5") UP
13"x 4" (14"x5") UP
2 1/2"x30" UP TO GRILLE
2 1/2"x36" UP TO GRILLE
2 1/2"x36" UP TO GRILLE2 1/2"x30" UP TO GRILLE
13"x 4" (14"x5") UP
8" (11")
13"x 4" (14"x5") UP
13"x 4" (14"x5") UP
13"x 4" (14"x5") UP
13"x 4" (14"x5") UP
13"x 4" (14"x5")
13"x 4" (14"x5") UP
13"x 4" (14"x5") UP
13"x 4" (14"x5") UP
13"x 4" (14"x5") UP
6"x12" UP
16
"
x
1
0
"
(
1
8
"
x
1
2
"
)
8"x4" UP
(2) 4" CA & 4" VENT UP & DN
14"x 6" (16"x8")
6"x 6" (8"x8")
8" (11")
8" (11")
8" (11")
2 1/2"x18" UP TO GRILLE
2 1/2"x18" UP TO GRILLE
2 1/2"x18" UP TO GRILLE
2 1/2"x18" UP TO GRILLE
6" (9")
8" (11")
8"
(
1
1
"
)
8" (11")
12"x 8" (14"x10")
12
"
x
1
2
"
(
1
4
"
x
1
4
"
)
8" (11")
8" (11")
16
"
x
1
2
"
(
1
8
"
x
1
4
"
)
14"x 10" (16"x12")
12
"
x
1
0
"
(
1
4
"
x
1
2
"
)
20"x 8" (22"x10") DN
2 1/2"x24" UP TO GRILLE
2 1/2"x24" UP TO GRILLE
10
"
(
1
3
"
)
10"x 4" (11"x5") UP10"x 4" (11"x5") UP
10"x 4" (11"x5") UP
10"x 4" (11"x5") UP
2 1/2"x36" UP TO GRILLE
2 1/2"x36" UP TO GRILLE
10"x 4" (11"x5") UP
10"x 4" (11"x5") UP
8" (11")
8" (11")
30"x 8" (32"x10") DN
8"
(
1
1
"
)
18
"
x
1
0
"
(
2
0
"
x
1
2
"
)
12
"
x
6
"
12
"
x
6
"
18
"
x
8
"
(
2
0
"
x
1
0
"
)
18
"
x
1
0
"
(
2
0
"
x
1
2
"
)
18"x 8" (20"x10") DN
18"x 10" (20"x12") UP
18"x 8" (20"x10") UP
12"x6" UP
8"
(
1
1
"
)
8"
(
1
1
"
)
12
"
x
6
"
12
"
x
6
"
6" (9")
14"x 6" (16"x8") DN
14"x 10" (16"x12")
1
1 1 1
ww
w
.
a
e
c
-
v
a
i
l
.
c
o
m
of
Drawn By:Checked By:
AEC PROJECT #:
COPYRIGHT 2018 ARCHITECTURAL ENGINEERING CONSULTANTS, INC.c
c
ae
PO
B
o
x
8
4
8
9
,
4
0
8
0
1
U
S
H
w
y
6
&
2
4
,
S
t
e
2
1
4
,
A
v
o
n
,
C
o
lo
r
a
d
o
,
8
1
6
2
0
Me
c
h
a
n
i
c
a
l
,
E
l
e
c
t
r
i
c
a
l
&
L
i
g
h
t
i
n
g
D
e
s
i
g
n
S
e
r
v
i
c
e
s
Ar
c
h
i
t
e
c
t
u
r
a
l
E
n
g
i
n
e
e
r
i
n
g
C
o
n
s
u
l
t
a
n
t
s
Te
l
e
p
h
o
n
e
:
9
7
0
-
7
4
8
-
8
5
2
0
F
a
x
:
9
7
0
-
7
4
8
-
8
5
2
1
An
O
f
f
i
c
e
w
i
t
h
L
E
E
D
™
A
c
c
r
e
d
i
t
e
d
P
r
o
f
e
s
s
i
o
n
a
l
s
DATE: ISSUE:
FOR PERMIT ONLY
SCALE 1/4" = 1'-0"
18032.00
DU
N
C
A
N
S
K
I
H
A
U
S
53
3
W
E
S
T
H
A
L
L
A
M
AS
P
E
N
,
C
O
L
O
R
A
D
O
,
8
1
6
1
1
M-111B
LOWER
LEVEL HVAC
CEILING
PLAN
5 14
BLU TOC
11-23-18 PERMIT
1/4" = 1'-0"1 LOWER LEVEL HVAC CEILING PLAN
1. ALL DUCTWORK DIMENSIONS ARE SHOWN INSIDE TO INSIDE.
2. ALL INTERIOR SUPPLY AND RETURN DUCTWORK SHALL INCLUDE 1" LINER UNLESS
OTHERWISE NOTED. ALL OUTSIDE AIR INTAKE AND ROUND DUCTWORK SHALL BE
WRAPPED WITH 1.5" THICK INSULATION UNLESS OTHERWISE NOTED.
3. ALL FINAL DUCTWORK CONNECTIONS TO SUPPLY GRILLES (OR PLENUMS) SHALL BE
COMPLETED WITH ACOUSTICAL FLEXIBLE DUCT UNLESS OTHERWISE NOTED AND A
MAXIMUM LENGTH OF FIVE FEET.
4. ALL ROUND DUCT CONNECTIONS TO ROUND DUCTWORK SHALL BE CONICAL TEES.
5. ALL SQUARE 90 DEGREE ELBOWS SHALL HAVE TURNING VANES.
6. ALL DUCTWORK SHALL BE RUN TIGHT TO UNDERSIDE OF STRUCTURE WHERE IT
EXISTS UNLESS OTHERWISE NOTED.
7. ALL DUCTWORK PASSING THROUGH FIRE-RATED ASSEMBLIES SHALL INCLUDE FIRE
DAMPERS RATED TO MATCH THAT OF THE ASSEMBLY, EVEN WHERE NOT EXPLICITLY
NOTED ON THIS PLAN.
8. ALL FIRE DAMPERS ARE INTENDED TO BE SPRING OPERATED CURTAIN DAMPERS.
ALL FIRE SMOKE DAMPERS ARE INTENDED TO BE EQUIPPED WITH 120V ACTUATORS.
9. ALL SUPPLY GRILLES SHALL INCLUDE A BALANCING DAMPER(S), EVEN IF NOT
SPECIFICALLY SHOWN, UNLESS OTHERWISE NOTED. IF THE DAMPER IS LOCATED IN
AN INACCESSIBLE LOCATION, CABLE-STYLE DAMPERS (ROTOTWIST OR EQUIVALENT)
SHALL BE INSTALLED AND SHALL BE ADJUSTABLE FROM THE GRILLE FACE.
10. COORDINATE ALL ACCESS PANEL LOCATIONS WITH THE ARCHITECT.
11. ALL MOTORIZED DAMPER ACTUATORS SHALL BE LOW VOLTAGE. IT IS MECHANICAL
CONTRACTOR'S RESPONSIBILITY TO PROVIDE ALL NECESSARY EQUIPMENT AND
WIRING FOR THEIR INSTALLATION. IF 120 V ACTUATORS ARE DESIRED, COORDINATE
WITH ELECTRICAL CONTRACTOR OR CONTACT ELECTRICAL ENGINEER.
12. ALL DUCTWORK SHALL BE SUPPORTED IN ACCORDANCE WITH THE 2015 IMC 603.10
AND SMACNA HVAC DUCT CONSTRUCTION STANDARDS.
GENERAL NOTES:SHEET NOTES:
1 COORDINATE ROUTING WITH STRUCTURE & ENSURE
THAT DUCTS/FLUES STAY WITHIN CONDITIONED
ENVELOPE.
09-16-19 PERMIT COMMENTS R1
12-16-19 PERMIT COMMENTS R2
12-20-19 PRICING SET
01-16-20 PERMIT COMMENTS R3
03-25-20 CD CEHCK SET
04-17-20 PERMIT COMMENTS R2.2
04/21/2020
justinh
04/20/2020
T
T
T
T
S S
S
10
EF B35 - S
2 1/2"x12"
2 1/2"x14"B 130 - S
B125 - S
2 1/2"x24"
B100 - S
2 1/2"x18"
B100 - S
2 1/2"x30"
2 1/2"x18"B 145 - R
B445 - R
2 1/2"x48"
B270 - S
2 1/2"x36"2 1/2"x36"B 270 - S
B20 - S
2 1/2"x12"
B230 - S
2 1/2"x24"
B225 - S
2 1/2"x24"
B365 - R
2 1/2"x48"
B175 - S
2 1/2"x36"B175 - S
2 1/2"x36"
B450 - R
2 1/2"x48"2 1/2"x48"B 450 - R
B205 - S
2 1/2"x30"
BDD
11
EF
BDD
12
"
x
6
"
12
"
x
6
"
6"ø6"ø
8"
x
4
"
8"
x
4
"
14
"
ø
14
"
ø
4"
ø
4"
ø
SEE SHEET NOTE 2
SEE SHEET NOTE 1
TO HP-2 &
RZ-6A
TO HP-3 &
RZ-7A
B295 - R
3"x30"
B150 - R
2 1/2"x18"
B75 - S
2 1/2"x18"
B75 - S
2 1/2"x15"
B190 - R
2 1/2"x24"B100 - S
2 1/2"x18"
B100 - S
2 1/2"x18"
B225 - R
2 1/2"x24"
B230 - R
2 1/2"x24"B200 - S
2 1/2"x24"
18
"
x
1
0
"
(
2
0
"
x
1
2
"
)
18"x 10" (20"x12")
18"x 10" (20"x12")10"x 8" (12"x10")
14"x 8" (16"x10")
8"x 14" (10"x16") UP
8"x 10" (10"x12") UP
10"x 14" (12"x16") UP
6"x 12" (8"x14") UP
DINING
113
ENTRY
111
CASUAL DINING
109
LIVING
106
KITCHEN
107
GARAGE
103
MUDROOM
102
ENTRY
101
POWDER
105
PANTRY
108
OFFICE
114
BAR
115
ENTRY HALL
110
L
1
L
3
L
4
12
"
x
6
"
12
"
x
6
"
L
5
6"x12"6"x12"
2 1/2"x36"B 310 - S
2 1/2"x36"B 310 - S
18"x 10" (20"x12") DN
10
10
9
9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1
1
A A
C C
D D
E E
F F
G G
H H
J J
K K
L L
ww
w
.
a
e
c
-
v
a
i
l
.
c
o
m
of
Drawn By:Checked By:
AEC PROJECT #:
COPYRIGHT 2018 ARCHITECTURAL ENGINEERING CONSULTANTS, INC.c
c
ae
PO
B
o
x
8
4
8
9
,
4
0
8
0
1
U
S
H
w
y
6
&
2
4
,
S
t
e
2
1
4
,
A
v
o
n
,
C
o
lo
r
a
d
o
,
8
1
6
2
0
Me
c
h
a
n
i
c
a
l
,
E
l
e
c
t
r
i
c
a
l
&
L
i
g
h
t
i
n
g
D
e
s
i
g
n
S
e
r
v
i
c
e
s
Ar
c
h
i
t
e
c
t
u
r
a
l
E
n
g
i
n
e
e
r
i
n
g
C
o
n
s
u
l
t
a
n
t
s
Te
l
e
p
h
o
n
e
:
9
7
0
-
7
4
8
-
8
5
2
0
F
a
x
:
9
7
0
-
7
4
8
-
8
5
2
1
An
O
f
f
i
c
e
w
i
t
h
L
E
E
D
™
A
c
c
r
e
d
i
t
e
d
P
r
o
f
e
s
s
i
o
n
a
l
s
DATE: ISSUE:
FOR PERMIT ONLY
SCALE 1/4" = 1'-0"
18032.00
DU
N
C
A
N
S
K
I
H
A
U
S
53
3
W
E
S
T
H
A
L
L
A
M
AS
P
E
N
,
C
O
L
O
R
A
D
O
,
8
1
6
1
1
M-112
FIRST FLOOR
HVAC PLAN
6 14
BLU TOC
11-23-18 PERMIT
1/4" = 1'-0"1 1ST FLOOR HVAC PLAN
1. ROUTE 4"⌀DRYER EXHAUST TO EXTERIOR. INSTALL PER MANUFACTURERS
INSTRUCTIONS. SELEC TED DRYER MUST HAVE AN EQUIVALENT LENGTH
ALLOWANCE THAT EXCEEDS THE ESIMTATED EQUIVALENT LENGTH CALCULATED
BELOW:
HORIZONTAL DISTANCE:5'
VERTICAL DISTANCE:12'
90 DEGREE ELBOWS:(4)(5') = 20'
MAX DEVELOPED LENGTH:37'
THE EQUIVALENT LENGTH OF THE DRYER DUCT MUST BE IDENTIFIED ON A
PERMANENT LABEL OR TAG WITHIN 6' OF THE EXHAUST CONNECTION PER IMC
504.8.5.
2. ROUTE BOILER FLUES FROM BOILERS TO TERMINATION PER MANUFACTURER'S
INSTRUCTIONS. SLOPE VENT PIPES AT 1/4"/FOOT BACK TO THE BOILER FOR ALL
HORIZONTAL RUNS. MAINTAIN 1" CLEARANCE TO COMBUSTIBLES. DO NOT EXCEED
100' MAXIMUM DEVELOPED LENGTH FOR ANY RUN. ESTIMATED LENGTHS AND
ELBOWS FOR LONGEST RUN BOILER ARE SHOWN BELOW:
B-1,2 VENT (CPVC):HORIZONTAL DISTANCE:15'
VERTICAL DISTANCE: 30'
90 DEGREE ELBOWS:(3)(5') = 15'
45 DEGREE ELBOWS:(1)(2.5') = 2.5'
MAX DEVELOPED LENGTH:67.5'
B-1,2 CA (PVC):HORIZONTAL DISTANCE:15'
VERTICAL DISTANCE: 30'
90 DEGREE ELBOWS:(3)(5') = 15'
45 DEGREE ELBOWS:(1)(2.5') = 2.5'
MAX DEVELOPED LENGTH:67.5'
FOLLOW ALL MANUFACTURER'S INSTRUCTIONS FOR BOILER VENTING MATERIALS.
PROVIDE CPVC ROUTING FOR THE BOILER FLUES (PVC IS ACCEPTABLE FOR THE
COMBUSTION AIR). PVC IS NOT ALLOWED FOR ANY BOILER FLUE ROUTINGS.
3. ROUTE WITHIN WARM SIDE OF INSULATION WITHIN FIRE RATED ENCLOSURE.
1. ALL DUCTWORK DIMENSIONS ARE SHOWN INSIDE TO INSIDE.
2. ALL INTERIOR SUPPLY AND RETURN DUCTWORK SHALL INCLUDE 1" LINER UNLESS
OTHERWISE NOTED. ALL OUTSIDE AIR INTAKE AND ROUND DUCTWORK SHALL BE
WRAPPED WITH 1.5" THICK INSULATION UNLESS OTHERWISE NOTED.
3. ALL FINAL DUCTWORK CONNECTIONS TO SUPPLY GRILLES (OR PLENUMS) SHALL BE
COMPLETED WITH ACOUSTICAL FLEXIBLE DUCT UNLESS OTHERWISE NOTED AND A
MAXIMUM LENGTH OF FIVE FEET.
4. ALL ROUND DUCT CONNECTIONS TO ROUND DUCTWORK SHALL BE CONICAL TEES.
5. ALL SQUARE 90 DEGREE ELBOWS SHALL HAVE TURNING VANES.
6. ALL DUCTWORK SHALL BE RUN TIGHT TO UNDERSIDE OF STRUCTURE WHERE IT
EXISTS UNLESS OTHERWISE NOTED.
7. ALL DUCTWORK PASSING THROUGH FIRE-RATED ASSEMBLIES SHALL INCLUDE FIRE
DAMPERS RATED TO MATCH THAT OF THE ASSEMBLY, EVEN WHERE NOT EXPLICITLY
NOTED ON THIS PLAN.
8. ALL FIRE DAMPERS ARE INTENDED TO BE SPRING OPERATED CURTAIN DAMPERS.
ALL FIRE SMOKE DAMPERS ARE INTENDED TO BE EQUIPPED WITH 120V ACTUATORS.
9. ALL SUPPLY GRILLES SHALL INCLUDE A BALANCING DAMPER(S), EVEN IF NOT
SPECIFICALLY SHOWN, UNLESS OTHERWISE NOTED. IF THE DAMPER IS LOCATED IN
AN INACCESSIBLE LOCATION, CABLE-STYLE DAMPERS (ROTOTWIST OR EQUIVALENT)
SHALL BE INSTALLED AND SHALL BE ADJUSTABLE FROM THE GRILLE FACE.
10. COORDINATE ALL ACCESS PANEL LOCATIONS WITH THE ARCHITECT.
11. ALL MOTORIZED DAMPER ACTUATORS SHALL BE LOW VOLTAGE. IT IS MECHANICAL
CONTRACTOR'S RESPONSIBILITY TO PROVIDE ALL NECESSARY EQUIPMENT AND
WIRING FOR THEIR INSTALLATION. IF 120 V ACTUATORS ARE DESIRED, COORDINATE
WITH ELECTRICAL CONTRACTOR OR CONTACT ELECTRICAL ENGINEER.
12. ALL DUCTWORK SHALL BE SUPPORTED IN ACCORDANCE WITH THE 2015 IMC 603.10
AND SMACNA HVAC DUCT CONSTRUCTION STANDARDS.
GENERAL NOTES:SHEET NOTES:
09-16-19 PERMIT COMMENTS R1
12-16-19 PERMIT COMMENTS R2
12-20-19 PRICING SET
01-16-20 PERMIT COMMENTS R3
03-25-20 CD CEHCK SET
04-17-20 PERMIT COMMENTS R2.2
04/21/2020
justinh
04/20/2020
S
T
T
T
T
T
T
S S
S
2
25
6
6
7
7
8
8
9
9
10
10
L
L
K
K
JJ
FF
GG
DD
CC
3
3
4
4
EE
HH
1
1
AA
BB
5B
RZ
30 SQFT
7A
RZ
425 SQFT
7B
RZ
130 SQFT
6B
RZ
20 SQFT
6A
RZ
1035 SQFT5A
RZ
495 SQFT
GARAGE
103
MUDROOM
102 ENTRY
101
LIVING
106
STAIR
120
STAIR
49
POWDER
105
KITCHEN
107
CASUAL DINING
109
ENTRY HALL
110
ENTRY
111
DINING
113
OFFICE
114
BIKES
104
1-A
SZ
517.19 SQFT
7-A
SZ
44.75
2-A
SZ
164.27 SQFT3-A
SZ
15.33 SQFT
3
SM
2
3
1
4
5
6TO HP-2 &
RZ-6A
TO HP-3 &
RZ-7A
TO RZ-7B
TO RZ-5B
TO RZ-5A
TO RZ-6B
9
RM
1/2"ø HWS
1/2"ø HWR
3/4"ø HWS
3/4"ø HWR
7
RM
8
RM
6
2-B
SZ
31.81 SQFT
2-C
SZ
51.44 SQFT
4-A
SZ
10.49 SQFT
1-B
SZ
152.68
5A
RZ
495 SQFT
1"ø HWS DN
1"ø HWR DN
7
SM7
ww
w
.
a
e
c
-
v
a
i
l
.
c
o
m
of
Drawn By:Checked By:
AEC PROJECT #:
COPYRIGHT 2018 ARCHITECTURAL ENGINEERING CONSULTANTS, INC.c
c
ae
PO
B
o
x
8
4
8
9
,
4
0
8
0
1
U
S
H
w
y
6
&
2
4
,
S
t
e
2
1
4
,
A
v
o
n
,
C
o
lo
r
a
d
o
,
8
1
6
2
0
Me
c
h
a
n
i
c
a
l
,
E
l
e
c
t
r
i
c
a
l
&
L
i
g
h
t
i
n
g
D
e
s
i
g
n
S
e
r
v
i
c
e
s
Ar
c
h
i
t
e
c
t
u
r
a
l
E
n
g
i
n
e
e
r
i
n
g
C
o
n
s
u
l
t
a
n
t
s
Te
l
e
p
h
o
n
e
:
9
7
0
-
7
4
8
-
8
5
2
0
F
a
x
:
9
7
0
-
7
4
8
-
8
5
2
1
An
O
f
f
i
c
e
w
i
t
h
L
E
E
D
™
A
c
c
r
e
d
i
t
e
d
P
r
o
f
e
s
s
i
o
n
a
l
s
DATE:ISSUE:
FOR PERMIT ONLY
SCALE 1/4" = 1'-0"
18032.00
DU
N
C
A
N
S
K
I
H
A
U
S
53
3
W
E
S
T
H
A
L
L
A
M
AS
P
E
N
,
C
O
L
O
R
A
D
O
,
8
1
6
1
1
M-122
FIRST FLOOR
MECHANICAL
PIPING
10 14
BLU TOC
11-23-18 PERMIT
1/4" = 1'-0"1 MECHANICAL PIPING - 1ST FLOOR
SHEET NOTES:
1 CONNECT 1/2" SMS/R TO SM-3.
2 CONNECT 1/2" HWS/R TO RM-9.
3 CONNECT 3/4" HWS/R TO RM-8.
4 CONNECT 3/4" HWS/R TO RM-7.
5 INSTALL SNOW & ICE SENSOR IN THE SNOWMELT ZONE AS SHOWN.
COORDINATE EXACT LOCATION WITH G.C. ENSURE THE SENSOR IS
EQUIDISTANT BETWEEN TUBING & NOT UNDER OVERHANGS OR IN
WIND EDDIES.
6 SEE ARCH SITE PLAN FOR CONTINUATION
7 LOCATE SM-7 IN LANDSCAPING BOX. COORDINATE WITH ARCHITECT.
1. OFFSET PIPING AS REQUIRED TO AVOID ALL DUCTWORK, LIGHTS, AND STRUCTURE.
COORDINATE ALL STRUCTURAL PENETRATIONS WITH THE STRUCTURAL ENGINEER.
2. ALL PIPING PASSING THROUGH FIRE-RATED ASSEMBLIES SHALL INCLUDE A FIRE-
RATED PIPE SEALANT RATED TO MATCH THAT OF THE ASSEMBLY.
3. VERIFY FINAL LOCATIONS OF ALL MANIFOLDS WITH THE G.C. CONTACT ENGINEER IF
MANIFOLDS MOVE MORE THAN 10' FROM LOCATIONS SHOWN ON PLANS.
4. LOCATION OF ALL THERMOSTATS AND FLOOR SENSORS ARE APPROXIMATE,
COORDINATE EXACT LOCATIONS WITH THE ARCHITECT. LOCATE FLOOR SENSORS
EQUIDISTANT BETWEEN RADIANT LOOPS, AND DO NOT LOCATE WHERE THEY MAY
LIKELY BE COVERED BY FUTURE RUGS OR FURNITURE.
5. ALL PIPING SIZED FOR TYPE L COPPER. CONTACT ENGINEER FOR ANY CHANGE TO
PEX FOR NECESSARY PIPE SIZING AND/OR PUMP CHANGES.
6. INSULATE ALL PIPE LEADERS PASSING THROUGH ADJACENT ZONES.