Loading...
HomeMy WebLinkAboutFile Documents.216 S Monarch St.0055.2019 (61).ACBKCERTIFIED December, 2019 TEST, ADJUST & BALANCE for REPORT Aspen, Colorado Permit # 0055.2019.ACBK 216 South Monarch Street Duemani Restaurant General Information 3 Certification Sheet 4 Abbreviation Summary 5 Equipment List 6 Air Apparatus Test Report 7-9 VelGrid Test Report 10-13 Rectangular Duct Traverse Test Report 14 Air Outlet Test Report 15 Fan Test Report 16 VelGrid Test Report 17-20 Air Outlet Test Report 21 Table of Contents FLOWHOOD: AIR DATAMETER: PROJECT PERSONNEL FLUKE - MODEL # 971 INSTRUMENTATION 216 South Monarch Street Duemani Restaurant Casey D. Thompson TECHNICIAN(S): CERTIFIED: GENERAL INFORMATION Casey D. Thompson Aspen, Colorado 216 South Monarch Street Duemani RestaurantPROJECT: 8000 feet ADDRESS: ADDRESS: ALTITUDE: EXTECH - MODEL # 461920 ALNOR - MODEL # EBT-731 ALNOR - MODEL # EBT-731 FLUKE - MODEL # 337 REMARKS TACHOMETER: HYGROMETER: HYDRONIC DATAMETER: THERMOMETER: ALNOR - MODEL # HM-675 FLUKE - MODEL # 52II AMPROBE: BB1095198T BB1095198T DATE:December 3, 2019CERTIFIED BY:Casey D. Thompson (TABB) TAB Firm:Chinook Test & Balance, Inc. REG. NO.: (TABB) TAB Firm:Chinook Test & Balance, Inc. DATE:December 3, 2019CERTIFIED BY: CERTIFICATION EXPIRATION DATE: Chinook Test and Balance, Inc. warrants that the equipment or system listed above is operating at the specified levels as shown, at and only at this time, and makes no other warranties, stated or implied, concerning the continued performance, operation or safety in use of this equipment past this time. The hydronic distribution systems have been tested and balanced. Final adjustments have been made in accordance with TABB "Procedural Standards for Testing, Adjusting, and Balancing of Environmental Systems" and project specifications. The air distribution systems have been tested and balanced. Final adjustments have been made in accordance with TABB "Procedural Standards for Testing, Adjusting, and Balancing of Environmental Systems" and project specifications. 216 South Monarch Street March 31, 2020 DATE:December 3, 2019 REG. NO.: SIGNATURE: REG. NO.: The data presented in this report is an exact record of system measurements and final adjustments that have been obtained in accordance with the current edition of the TABB Procedural Standards for Testing, Adjusting, and Balancing of Environmental Systems. Any variances from design quantities, which exceed TABB tolerances, are noted in the Test, Adjust and Balance Report Project Summary. Chinook Test & Balance, Inc. TAB Supervisor:Casey D. Thompson SUBMITTED & CERTIFIED BY: Casey D. ThompsonBB1095198T TABB TAB FIRM: Duemani Restaurant ACT Actual HHWP Heating Hot Water Pump ACU Air Conditioning Unit HP Horsepower AHU Air Handling Unit LAT Leaving Air Temperature AK Velocity Correction Factor LWT Leaving Water Temperature B&G Bell & Gossett MAU Makeup Air Unit BCP Boiler Circulation Pump MAX Maximum CD Ceiling Diffuser MIN Minimum CER Ceiling Exhaust Register NG Not Given CFM Cubic Feet per Minute NO Number CHWP Chilled Water Pump PSI Pounds per Square Inch CRR Ceiling Return Register RPM Revolutions Per Minute CRU Computer Room Unit SER Sidewall Exhaust Register DDC CF Direct Digital Control Correction Factor SF Service Factor DES Design SP Static Pressure EAT Entering Air Temperature SR Supply Register EF Exhaust Fan SRR Sidewall Return Register ESP External Static Pressure SZ Size EWT Entering Water Temperature VAV Variable Air Volume FPM Feet Per Minute VEL Outlet Face Velocity Ft. Hd.Feet of Head ΔP Pressure Differential GPM Gallons Per Minute ΔT Temperature Differential Abbreviation Summary Equipment List Hygrometer Thermometer Hydro Multimeter Tachometer Amprobe Datameter Flowhood Equipment Fluke Fluke Alnor Extech Fluke Alnor Alnor EBT-731 EBT-731 971 52 II HM-675 461920 337 Calibration DateManufacturer April 19, 2019 April 16, 2019 August 1 ,2019 April 18, 2019 April 16, 2019 April 16, 2019 April 16, 2019 Serial Number 33850499 90250065 71651062 161017033 85703564 EBT731717002 EBT731717002 Model Number AIR APPARATUS TEST REPORT Chinook Test Balance, Inc. 2017 -0.23"-0.33"-0.38"1.51" Project Duemani Restaurant System MUA-1 Roof Top Unit Model Technician:Casey D. Thompson F A N Belt Drive 5173 0 5173 FAN TEST DATA Manufacturer Installed STARTER DATA FAN SYSTEM DIAGRAM Amps Volts Fan RPM FinalPreliminary TEST DATA 10.7 204 10.7 204 17951795 Outside Air CFM Return Air CFM Installed Thermal Size 6850 CFM @ 2.0" TSP Make Up Air Unit NG 13.4-13.2/6.6208-230/460 SC1.15 Y56HZ3 34505 Manufacturer Rating Fan Type Magnetek Drive Change Centerline No. Belts & Size Fan Bore Fan Drive Motor Bore Motor Drive Drive Type DRIVE DATA 20 3/4" 2 @ AX59 (H) 1" 2AK84 7/8" 2VP50 MOTOR DATA RPM Frame Type AmpsVolts S.F. Phase Motor HP Manufacturer NG Reznor UNIT DATA Manufacturer Outside Air Rating (Amps) H E A T F I L T E R Supply Air CFM Rating (Amps) Required Thermal Serial Model 6850 CFM Comments: AIR APPARATUS TEST REPORT Chinook Test Balance, Inc. 2017 ATMOS -0.26"0.72" Project Duemani Restaurant System MUA-2 Car Port Unit 13.1 FAN SYSTEM DIAGRAM **Assumed capacity Total flow taken from rectabgular traverse. AK124 Fan Bore 1" No. Belts & Size 1 @ BX64 Centerline 16 3/4" Drive Change FAN TEST DATA TEST DATA 3344 Required Thermal Rating (Amps) Comments: Technician:Casey D. Thompson NA Phase Frame 3 184T Make Up Air Unit S.F.Type 1.15 ASGAME 3200 CFM**Volts Amps 208-230/460 14.5-13.1/6.6 3200 CFM 1740Model Serial Manufacturer Outside Air Manufacturer Fan Type Rating STARTER DATA DRIVE DATA Manufacturer Installed Drive Type Belt Drive Rating (Amps) UNIT DATA MOTOR DATA Cook Manufacturer Dayton NA Motor HP RPM 5 Model Size Installed Thermal Motor Drive 1VP50 Motor Bore 1 1/8" Fan Drive Return Air CFM Outside Air CFM Supply Air CFM 0 Fan RPM 1331 1331 3344 Volts Preliminary Final 233 233 Amps 13.1 F I L T E R F A N AIR APPARATUS TEST REPORT Chinook Test Balance, Inc. 2017 -0.95 -1.12"NA NA 0.41" Project Duemani Restaurant System MUA-3 (Building Unit) 192 192 Amps 10.4 10.4 FAN SYSTEM DIAGRAM 2BK90 Fan Bore (H) 1 3/16" No. Belts & Size 2 @ B45 Centerline 20" Drive Change FAN TEST DATA TEST DATA NA Preliminary Final Frame 3 s213t Make Up Air Unit S.F.Type 1.15 sc 6850 CFM @ 2.0" ESP Volts Amps 208-230/460 22-21/10.5 6850 CFM STARTER DATA DRIVE DATA Rating (Amps) Required Thermal Rating (Amps) Model Size Installed Thermal ESP2000 Motor Drive 2VP60 ADJ 10-40 Motor Bore 1 3/8" SET @ 10 UNIT DATA MOTOR DATA Model Serial Manufacturer Reznor Manufacturer Magnetek RPBL1050-SMVJ Motor HP RPM 7.5 1745 3ASH415NF11 Phase Outside Air Manufacturer Fan Type Rating Siemens Drive Type Belt Drive Fan Drive Return Air CFM Outside Air CFM Supply Air CFM NA Fan RPM 848 848 NA Volts Comments: Technician:Casey D. Thompson F I L T E R F A N H E A T H E A T VELGRID TEST REPORT Chinook Test Balance, Inc. 2017 129 X 5 Comments: Technician:Casey D. Thompson 510 733Velocity Subtotals 648 605 580 650 733 () = (637.00 4.48 sq. ft ) =2853 CFM7av. FPM) (4459 Location/Zone Kitchen Hood Upstairs Sq ft 4.48 Required CFM NG Measured CFM 2853 Size Required FPM NG Measured FPM 637 Project Duemani Restaurant System MUA Position 1 2 3 4 5 6 7 1 648 510 733 605 580 650 733 VELGRID TEST REPORT Chinook Test Balance, Inc. 2017 38 X 5 Comments: 888 986 1016 NG Measured CFM 1260 Position 1 2 3 4 System MUAProjectDuemani Restaurant Size Required FPM NG Measured FPM 955 Location/Zone Kitchen Hood Upstairs Sq ft 1.32 Required CFM 1 931 Technician:Casey D. Thompson 3821 1016 () = (955.25 Velocity Subtotals 931 888 986 av. FPM) (1.32 sq. ft ) =1260 CFM4 VELGRID TEST REPORT Chinook Test Balance, Inc. 2017 44 X 5 System MUA av. FPM) (1.53 sq. ft ) =1060 CFM4 Technician:Casey D. Thompson NG Measured CFM 1060 Position 1 2 3 4 Size Required FPM NG Measured FPM 694 Location/Zone 1 662 762 729 622 Kitchen Hood Upstairs Sq ft 1.53 Required CFM Comments: 2775() = (693.75 Velocity Subtotals 662 762 729 622 Project Duemani Restaurant VELGRID TEST REPORT Chinook Test Balance, Inc. 2017 110 X 5 System MUA 3.82 sq. ft ) =1820 CFM 530 470Velocity Subtotals 459 9 Comments: Technician:Casey D. Thompson 4289 Location/Zone Kitchen Hood Basement Sq ft 3.82 Required CFM NG Measured CFM 1820 Position 1 2 3 4 5 6 7 8 9 Size Required FPM NG Measured FPM 477 1 459 530 470 490 525 501 440 421 453 490 525 501 440 421 453 () = (476.56 av. FPM) ( Project Duemani Restaurant RE C T A N G U L A R D U C T T R A V E R S E T E S T R E P O R T Ch i n o o k T e s t B a l a n c e , I n c . 2 0 1 7 23 X 19 Ca r p o r t S u p p l y D u c t Du c t S . P . 0. 7 2 " MU A - C a r p o r t Sy s t e m Ca s e y D . T h o m p s o n 17 6 3 3 ) = ( 11 0 2 . 0 6 av . F P M ) ( 3. 0 3 sq . f t . ) = 33 4 4 Fi n a l C F M 16 33 4 4 11 0 2 Me a s u r e d C F M Me a s u r e d F P M 32 0 0 10 5 4 3. 0 3 Du c t s q f t Du c t s i z e 12 7 4 10 9 5 11 0 6 11 8 8 95 1 12 7 7 Pr o j e c t Du e m a n i R e s t a u r a n t 1 Lo c a t i o n / Z o n e 12 1 9 4 Po s i t i o n 1 2 3 3 99 8 11 5 7 10 1 8 11 9 8 2 11 1 4 4 10 1 6 97 9 98 9 10 5 4 Re q u i r e d C F M Re q u i r e d F P M Te c h n i c i a n : Co m m e n t s : ( Ve l o c i t y Su b t o t a l s 43 4 7 45 9 8 40 5 3 46 3 5 AIR OUTLET TEST REPORT Chinook Test Balance, Inc. 2017 Project CFM CFM VEL CFM VEL MUA-1 1 HOOD 129X5 4.48 NG 2853 637 2853 637 Upstairs MUA-2 2 HOOD 38X5 1.32 NG 1260 955 1260 955 Upstairs 3 HOOD 44X5 1.53 NG 1060 694 1060 694 Upstairs 5173 1 HOOD 110X5 3.82 NG 1689 1820 Basement 2 CD 24X24 NG 429 429 Upstairs 3 CD 24X24 NG 436 436 Upstairs TOTAL 2685 MUA-3 1 CD 24X24 NG 755 910 Upstairs 2 CD 24X24 NG 812 1112 Upstairs 3 CD 14X14 NG 255 300 Basement 4 DUCT 10"0.55 230 363 243 106%Basement TOTAL 2565 1st Floor Exhaust Basement Exhaust 1st Floor Make-Up Basement Make-Up Comments: Technician: =5173 + 429 + 436 + 910 + 1112 = 1820 + 300 + 243 8453 2013 8060 2363 TOTAL TOTAL TOTAL TOTAL Casey D. Thompson Duemani Restaurant System Make-Up Air AREA SERVED OUTLET DESIGN PRELIMINARY FINAL % OF DESIGN NOTESNOTYPESIZEAKVEL FAN TEST REPORT Chinook Test Balance, Inc. 2017 Exhaust FanSystem 2013 208-230/460 Rating (Amps) Motor Volts 233 205 Motor Amps 11.0 7.2 Comments: F A N F A N -0.11"ATMOS -0.26"ATMOS Fan RPM 1406 1730 Fan CFM 8453 TEST DATA STARTER DATA STARTER DATA Installed Thermal Size Required Thermal Rating (Amps) TEST DATA TEST DATA 226DO22USAUGB Fan Bore (B) 1 7/16"(B) 1 7/16" Fan Drive AK71 1B5V46 Drive Change Model Manufacturer None None Center Line 17 5/8 16 5/8" No. Belts & Size 1 @ 5L530 1 @ 5L480 STARTER DATA EF-2 (Basement Level) Motor HP R.P.M.7.5 1740 3 184TPhaseFrame3213T Motor Bore 1 3/8"(B) 1 1/8" Motor Drive 1VP62 1B5V46 Drive Type Belt Drive Belt Drive DRIVE DATA DRIVE DATA DRIVE DATA Project Duemani Restaurant Rating 8503 CFM 2000 CFM Fan Type Exhaust Fan Exhaust Fan Manufacturer Emerson Baldor MOTOR DATA MOTOR DATA Manufacturer Industrial Air Industrial Air UNIT DATA UNIT DATA UNIT DATA Serial 200168-10 87995 Model 226 022 FAN NUMBER EF-1 (Main Level) Technician:Casey D. Thompson MOTOR DATA 5 1725 1.15 NGS.F.Type 1.15 NG Amps 22.6-20.5/10.2 15.0-13.2/6.6 Volts 208-230/460 VELGRID TEST REPORT Chinook Test Balance, Inc. 2017 37 X 17 EF-1System sq. ft ) =581 CFM4(532 ) = (133.00 av. FPM) ( 139 Project Duemani Restaurant Technician:Casey D. Thompson Velocity Subtotals 128 131 134 Comments: Size Required FPM 4.37 Required CFMSq ft 1341128 Location/Zone Kitchen Hood #1 133 1Position 432 581 Measured FPM Measured CFM 240 1050 131 139 4.37 VELGRID TEST REPORT Chinook Test Balance, Inc. 2017 38 X 18 Position 1 2 3 4 1 240 251 246 253 Project Duemani Restaurant System EF-1 Location/Zone Kitchen Hood #2 Size Required FPM NG Measured FPM 248 Sq ft NG Measured CFM 11764.75 Required CFM Velocity Subtotals 240 251 246 253 Casey D. Thompson 990() = (247.50 av. FPM) ( Comments: Technician: 4.75 sq. ft ) =1176 CFM4 VELGRID TEST REPORT Chinook Test Balance, Inc. 2017 34 X 18 System EF-1 Comments: Technician:Casey D. Thompson 461 466Velocity Subtotals 470 458 () = (463.75 4.25 sq. ft ) =1971 CFM4 Sq ft 4.25 Required CFM NG Measured CFM 1971 Size Required FPM NG Measured FPM 464 Project Duemani Restaurant Location/Zone Kitchen Hood #3 Position 1 2 3 4 1 470 461 466 458 av. FPM) (1855 VELGRID TEST REPORT Chinook Test Balance, Inc. 2017 108 X 18 System EF-2 Comments: Technician:Casey D. Thompson (1193 ) = (149.13 av. FPM) (13.50 sq. ft ) =2013 CFM8 Velocity Subtotals 150 141 149 153 147 152 155 146 Required CFM 2000 Measured CFM 2013 Position 1 2 3 4 5 6 7 8 1 150 141 149 153 147 152 155 146 Project Duemani Restaurant Location/Zone Kitchen Hood #1 Size Required FPM 148 Measured FPM 149 Sq ft 13.50 AIR OUTLET TEST REPORT Chinook Test Balance, Inc. 2017 Project CFM CFM VEL CFM VEL EF-1 1 HOOD 37X17 4.37 1050 540 124 581 133 55% 2 HOOD 38X18 4.75 NG 1030 218 1176 248 3 HOOD 34X18 4.25 NG 1963 462 1971 464 4 HOOD 120X18 15.00 NG 4605 307 4725 315 TOTAL 8503 8453 99% EF-2 1 HOOD 108X18 13.50 2000 4293 318 2013 149 101% TOTAL 2000 2013 101% Comments: Technician: AREA SERVED OUTLET AKSIZETYPENO NOTES Exhaust Air % OF DESIGN SystemDuemani Restaurant Casey D. Thompson DESIGN PRELIMINARY FINAL VEL NG 148 240 NG NG