HomeMy WebLinkAboutFile Documents.611 E Durant Ave.0048.2019 (35).ACBK0048-2019-ARBK_BuildingComments_1_Markup Summary File Name: 611 E Durant_Full Permit Set.pdf Subject: PlanCheck Author: nickt Color: Page Index: 2 Page Label: A0.1 GENERAL INFORMATION SHEET Revise to 2017 NEC. 611 E Durant_Full Permit Set.pdf (18) File Name: 611 E Durant_Full Permit Set.pdf Subject: PlanCheck Author: nickt Color: Page Index: 2 Page Label: A0.1 GENERAL INFORMATION SHEET Revise to NFPA 13 (not 13R). File Name: 611 E Durant_Full Permit Set.pdf Subject: PlanCheck Author: nickt Color: Page Index: 2 Page Label: A0.1 GENERAL INFORMATION SHEET Type of construction per City records is Type IIA. This requires all primary structure, bearing walls, floor/ceilings, and roof/ceilings to be non-combustible and 1 hour rated. 2015 IBC 601. Provide listed fire rated assemblies for any components that are disturbed and note their locations. File Name: 611 E Durant_Full Permit Set.pdf Subject: PlanCheck Author: nickt Color: Page Index: 5 Page Label: A0.4 SHEET TITLE EGRESS AND CODE DRAWINGS Remove the date from the City of Aspen muni code. File Name: 611 E Durant_Full Permit Set.pdf Subject: PlanCheck Author: nickt Color: Page Index: 5 Page Label: A0.4 SHEET TITLE EGRESS AND CODE DRAWINGS Type of construction is II-A. AL INDICATIONS ARTH WORK TONE / GRAVEL / POROUS FILL ASONRY REBRICK RICK TONE ONCRETE MASONRY UNIT AST IN PLACE & PRECAST CONCRETE ROUT / MORTAR AND RASS LUMINUM TEEL LYWOOD NISH CARPENTRY ATT / BLANKET / LOOSE FILL INSULATION IGID INSULATION BER BOARD YPSUM Above Finished Counter AD ADD AFC Area Drain Additional ABBREVIATIONS Above Finished FloorAFF Above Finished GradeAFG Above Finished SlabAFS AluminumALUM FO Finished Opening FOC Face of Concrete FOM Face of Masonry FOS Face of StudFOWFace of Wall FRTW Fire Retardant Treated Wood FRP Fiber Reinforced Plastic FRZ Freezer MAU Make Up Air MAX Maximum MBR Master Bedroom MCB Metal Corner BeadMECHMechanical MECH RM Mechanical Room MEMB Membrane MEZZ Mezzanine MF Mill Finish QC Quality Control QT Quarry Tile RA Return Air RB HK Robe Hook RCP Reflected Ceiling Plan RD Roof Drain REC Recessed ADJ Adjacent, Adjustable Air Handling UnitAHU R Riser FP Fireplace PROJECT INFORMATION & ZONING SUMMARY PROJECT:ASPEN MOUNTAIN CLUB LOCKER ROOM 611 E DURANT AVE LITTLE NELL SUB ASPEN, CO 81611 LEGAL DESCRIPTION: CITY PERMIT #: CONSTRUCTION TYPE: SPRINKLER: THE LITTLE NELL SUB Lot: 2 LITTLE NELL COMMERCIAL V-B REQUIRED - NFPA 13R TBD APPLICABLE CODES: OCCUPANCY TYPE: B - BUSINESS INSULATION REQUIREMENTS: PER 2015 IECC PITKIN COUNTY : CLIMATE ZONE 17 GROSS LOT AREA:19,771 SF (0.45 ac.) - RE: PITKINASSESSOR.ORG BUILDING FOOTPRINT: PROPOSED DEVELOPMENT: COMMERCIAL RENOVATION PARCEL ID:273718250102 ZONE DISTRICT:L, LODGE APPROVALS:REFER TO PERMIT SUBMITTAL DOCUMENTS FOR ALL APPROVALS N/A COMMERCIAL CODE:2015 I.B.C. ENERGY CODE:2015 I.E.C.C. EXISTING BUILDING:2015 I.E.B.C. PLUMBING CODE:2015 I.P.C. MECHANICAL CODE:2015 I.M.C. ELECTRICAL CODE:2014 N.E.C. FIRE/LIFE SAFETY:2015 I.F.C. FLUE GAS CODE: 2015 I.F.G.C. ACCESSIBILITY:ICC/ANSI A117.1-2009 CITY OF ASPEN MUNICIPAL CODE TITLE 8 Consultants Issue: 11.02.2017 SD CLIENT MEETING 04.03.2018 50% DD PROGRESS 05.04.2018 100% DD DRAWINGS 08.31.2018 CONSTRUCTION DOCUME 02.15.2019 CONSTRUCTION DOCUME de 500 w main staspen, co 81611 970.544.9006 rowland+brou architecture / urban design / Revise to 2017 NEC. GEND DICATIONS RK RAVEL / POROUS FILL MASONRY UNIT ACE & PRECAST CONCRETE ORTAR PENTRY NKET / LOOSE FILL INSULATION LATION RD Above Finished Counter AD ASPH ADD AFC Area Drain Asphalt Additional ABBREVIATIONS Above Finished FloorAFF Above Finished GradeAFG Above Finished SlabAFS AluminumALUM BAT Batten FO Finished Opening FOC Face of Concrete FOM Face of Masonry FOS Face of Stud FOW Face of Wall FRTW Fire Retardant Treated Wood FRP Fiber Reinforced Plastic FRZ Freezer FTG Footing FURG Furring FW Fire Wall MAU Make Up Air MAX Maximum MBR Master Bedroom MCB Metal Corner Bead MECH Mechanical MECH RM Mechanical Room MEMB Membrane MEZZ Mezzanine MF Mill Finish MFD Manufactured MIN Minimum MIRR Mirror MISC Miscellaneous QC Quality Control QT Quarry Tile RA Return Air RB HK Robe Hook RCP Reflected Ceiling Plan RD Roof Drain REC Recessed RECPT Receptacle REF Refrigerator REINF Reinforce ADJ Adjacent, Adjustable Air Handling UnitAHU A/V Audio Visual RES Residential R Riser FP Fireplace FS Floor Sink PROJECT INFORMATION & ZONING SUMMARY PROJECT:ASPEN MOUNTAIN CLUB LOCKER ROOM 611 E DURANT AVE LITTLE NELL SUB ASPEN, CO 81611 LEGAL DESCRIPTION: CITY PERMIT #: CONSTRUCTION TYPE: SPRINKLER: THE LITTLE NELL SUB Lot: 2 LITTLE NELL COMMERCIAL V-B REQUIRED - NFPA 13R TBD APPLICABLE CODES: OCCUPANCY TYPE: B - BUSINESS INSULATION REQUIREMENTS: PER 2015 IECC PITKIN COUNTY : CLIMATE ZONE 17 GROSS LOT AREA:19,771 SF (0.45 ac.) - RE: PITKINASSESSOR.ORG BUILDING FOOTPRINT: PROPOSED DEVELOPMENT: COMMERCIAL RENOVATION PARCEL ID:273718250102 ZONE DISTRICT:L, LODGE APPROVALS:REFER TO PERMIT SUBMITTAL DOCUMENTS FOR ALL APPROVALS N/A COMMERCIAL CODE:2015 I.B.C. ENERGY CODE:2015 I.E.C.C. EXISTING BUILDING:2015 I.E.B.C. PLUMBING CODE:2015 I.P.C. MECHANICAL CODE:2015 I.M.C. ELECTRICAL CODE:2014 N.E.C. FIRE/LIFE SAFETY:2015 I.F.C. FLUE GAS CODE: 2015 I.F.G.C. ACCESSIBILITY:ICC/ANSI A117.1-2009 CITY OF ASPEN MUNICIPAL CODE TITLE 8 Revise to NFPA 13 (not 13R). EXISTING DOOR TO REMAIN WINDOW NUMBER INTERIOR ELEVATIONS COLUMN GRID ROOM NAME & NUMBER SYMBOL LEGEND NAME XXX 1 2 3 4 A9.1 09 x/yyy MATERIAL INDICATIONS EARTH WORK STONE / GRAVEL / POROUS FILL MASONRY FIREBRICK BRICK STONE CONCRETE MASONRY UNIT CAST IN PLACE & PRECAST CONCRETE GROUT / MORTAR SAND GRASS ALUMINUM STEEL PLYWOOD FINISH CARPENTRY BATT / BLANKET / LOOSE FILL INSULATION RIGID INSULATION FIBER BOARD GYPSUM 6 4 8 5A - ELEVATION NUMBER ELEVATION SHEET NUMBER CMU Concrete Masonry Unit DEMO CONCCPT COLCO Demolition Column Carpet Cleanout Concrete Above Finished Counter Bottom of CJCL CLR CB BMBO BRG BLDG Catch Basin Control JointCenterline Clear Building Beam Bearing AD ASPH ADD AFC Area Drain Asphalt Additional ABBREVIATIONS D Deep BB Baseboard DOOR NUMBERx/yyy EX. Above Finished FloorAFFAbove Finished GradeAFGAbove Finished SlabAFS AluminumALUM BAT Batten BITUM Bituminous BottomBOT BRKT Bracket C CONC Cast ConcreteCABCabinet CFMF Cold Forged Metal Framing CIP Cast in Place CLG Ceiling FO Finished OpeningFOCFace of ConcreteFOMFace of Masonry FOS Face of StudFOWFace of Wall FRTW Fire Retardant Treated WoodFRPFiber Reinforced Plastic FRZ Freezer FTG FootingFURGFurringFWFire Wall GALV GalvanizedGCGeneral Contractor G DISP Garbage Disposal GDR Guard RailGR FL Ground FloorGSBGypsum Sheathing BoardGUTGutterGYP BD Gutter HB Hose BibHCWDHollow Core Wood DoorHDHand DryerHDRHeaderHDWHardware HMD Hollow Metal DoorHMDFHollow Metal Door and Frame HNDRL HandrailHORIZHorizontalHSKPGHousekeeping HYD Hydrant IAQ Indoor Air Quality IBC International Building CodeIDInside DiameterIFSInside Face of Stud IIC Impact Isolation ClassILLUMIllumination MAU Make Up AirMAXMaximumMBRMaster Bedroom MCB Metal Corner BeadMECHMechanicalMECH RM Mechanical RoomMEMBMembraneMEZZMezzanineMFMill FinishMFDManufacturedMINMinimumMIRRMirrorMISCMiscellaneousMLMetal LathML&P Metal Lath & PlasterMLDGMoldingMLWKMillworkMOMasonry OpeningMTLMetalMTLBMetal BaseMTLDMetal DoorMTLFMetal FlashingMTLRMetal RoofMULLMullionMULTMultiple N NorthNANot ApplicableNCNoise CriteriaNCOMBLNoncombustibleNENot Exceeding NFPA National Fire Protection Ass.NIC Not in ContractNOMNominal NR Noise ReductionNRNoise Reduction CoefficientNTSNot to Scale OA Overall, Outside Air OC On Center OD Outside DiameterOFDOverflow Drain QC Quality ControlQTQuarry Tile RA Return AirRB HK Robe HookRCPReflected Ceiling PlanRDRoof DrainRECRecessedRECPTReceptacleREFRefrigeratorREINFReinforce RESIL ResilientRESTRest RoomRFResilient FlooringRFGRoofingRFIRequest for InformationRHRight HandRMRoomRORough OpeningROWRight of WayRSRough SawnRVRoof Vent S SouthS1SSurfaced One SideS2SSurfaced Two SidesS4SSurfaced Four SidesSASupply AirSCHEDSchedule SCHEM SchematicSCPScupperSCRNScreen SD Smoke Detector, Storm DrainSFSquare FootSGDSliding Glass Door SHR ShowerSHRDShower DrainSIMSimilar SMP Sump PumpSND INS Sound Insulation ADJ Adjacent, Adjustable Air Handling UnitAHU A/V Audio Visual CHAND Chandelier BLW Below HGT Height COMM Commercial RES Residential R Riser FP Fireplace FS Floor Sink PROJECT INFORMATION & ZONING SUMMARY PROJECT:ASPEN MOUNTAIN CLUB LOCKER ROOM611 E DURANT AVE LITTLE NELL SUBASPEN, CO 81611 LEGALDESCRIPTION: CITY PERMIT #: CONSTRUCTION TYPE: SPRINKLER: THE LITTLE NELL SUB Lot: 2 LITTLE NELL COMMERCIAL V-B REQUIRED - NFPA 13R TBD APPLICABLECODES: OCCUPANCYTYPE:B - BUSINESS INSULATIONREQUIREMENTS:PER 2015 IECCPITKIN COUNTY : CLIMATE ZONE 17 GROSS LOT AREA:19,771 SF (0.45 ac.) - RE: PITKINASSESSOR.ORG BUILDING FOOTPRINT: PROPOSEDDEVELOPMENT:COMMERCIAL RENOVATION PARCEL ID:273718250102 ZONE DISTRICT:L, LODGE APPROVALS:REFER TO PERMIT SUBMITTAL DOCUMENTS FOR ALLAPPROVALS A 3 N/A COMMERCIAL CODE:2015 I.B.C. ENERGY CODE:2015 I.E.C.C.EXISTING BUILDING:2015 I.E.B.C. PLUMBING CODE:2015 I.P.C.MECHANICAL CODE:2015 I.M.C. ELECTRICAL CODE:2014 N.E.C.FIRE/LIFE SAFETY:2015 I.F.C. FLUE GAS CODE: 2015 I.F.G.C.ACCESSIBILITY:ICC/ANSI A117.1-2009 CITY OF ASPEN MUNICIPAL CODE TITLE 8 Consultants Issue: ASPEN MOUNTAIN CLUB LOCKER ROOMS BASE OF GONDOLA 11.02.2017 SD CLIENT MEETING 04.03.2018 50% DD PROGRESS 05.04.2018 100% DD DRAWINGS 08.31.2018 CONSTRUCTION DOCUMENTS 02.15.2019 CONSTRUCTION DOCUMENTS 1830 blake stdenver, co 80202303.308.1373 500 w main staspen, co 81611970.544.9006 rowland+broughtonarchitecture / urban design / interior design 05.24.2019 PERMIT SUBMISSION Type of construction per City records is Type IIA. This requires all primary structure,bearing walls,floor/ceilings, androof/ceilings to benon-combustible and1 hour rated. 2015 IBC601. Provide listed fire rated assemblies for any components that are disturbed and note their locations. BUILDING INFORMATION / CODE ANALYSIS ·2017 CITY OF ASPEN MUNICIPAL CODE ·2015 INTL BUILDING CODE·2015 INTL MECHANICAL CODE·2015 INTL FUEL AND GAS CODE ADDRESS: APPLICABLE BUILDING CODES: BUILDING DESCRIPTION: FIRE SUPPRESSION:FULLY SPRINKLERED (EXISTING, NO CHANGE) BUILDING USE:BUSINESS (NO CHANGE) PRIMARY TENANT SPACE OCCUPANCY :GROUP B - BUSINESS 611 EAST DURANT AVE, ASPEN, CO 81611 ·2015 INTL ENERGY CONSERVATION CODE ·2015 INTL PLUMBING CODE·2015 INTL FIRE CODE·2017 NEC - NATL ELECTRICAL CODE FIRE RESISTIVE REQUIREMENTS FOR BUILDING ELEMENTS:TYPE-1-A SPRINKLERED STRUCTURAL FRAME: BEARING WALLS - EXTERIOR: BEARING WALLS - INTERIOR: NON-BEARING WALLS - SHAFT & STAIR: NON-BEARING WALLS - INTERIOR: 3 HOUR 2 HOUR 3 HOUR 3 HOUR 0 HOUR FLOOR CONSTRUCTION:2 HOUR ROOF CONSTRUCTION:1.5 HOUR TYPE OF CONSTRUCTION:1-A NON-COMBUSTABLE (EXISTING, NO CHANGE) GROSS AREA (TENANT SPACE):6,628 SF ASPEN ZONING:C - CONSERVATION, PD - PLANNED DEVELOPMENT INDIVIDUAL HISTORIC LANDMARK:NONE HISTORIC DISTRICT:NONE PLUMBING FIXTURE CALCULATIONS OCCUPANCY: GROUP B, BUSINESS INTERIOR FINISHES MINIMUM PERFORMACE REQUIREMENTS: INTERIOR WALL AND CEILING FINISHES: CLASS C(FLAME SPREAD INDEX 76-200; SMOKE DEVELOPED INDEX 0-450; PER ASTM E 84 OR UL 723) INTERIOR FLOORING: CLASS II PER NFPA 253 OR TRADITIONAL TYPE MATERIALS SUCH AS WOOD, VINYL, LINOLEUM, TERRAZZO, AND RESILIENT FLOOR COVERING WITH NO FIBERS INTERIOR TRIM: CLASS C FLAME SPREAD & SMOKE DEVELOPED INDEX. COMBUSTIBLE TRIM ACCEPTABLE PROVIDED IT DOES NOT EXCEED 10% OF WALL/CEILING AREA IT IS ATTACHED TO MEANS OF EGRESS EXIT ACCESS TRAVEL DISTANCE:250' MAX (A-OCCUPANCY, FULLY SPRINKLERED) MINIMUM NUMBER OF EXITS:2 (OCCUPANT LOAD GREATER THAN 49 AND LESS THAN 500); COMMON PATH OF EGRESS TRAVEL: MIN. SIZE OF DOORS:NOT LESS THAN 32" CLEAR MIN. EGRESS WIDTH:89 OCCUPANTS / 2 = 44.5 AT EACH EXIT x .15 =6.675"32" CLEAR MIN. PROVIDED TENANT SPACE ADDRESS:TBD 2 PROVIDED MIN. STAIRWAY WIDTH:89 OCCUPANTS / 2 = 44.5 x .3 = 13.35" MIN WIDTH PER 20 0 9 I C C A 1 1 7 . 1 A N S I CODE S E C T I O N 9 0 3 . 2 PER 2009 ICC A117.1 ANSICODE SECTION 903.2 PER 2009 ICC A117.1 ANSICODE SECTION 903.2PER 2 0 0 9 I C C A 1 1 7 . 1 A N S I CODE S E C T I O N 3 0 5 . 5 PER 2 0 0 9 I C C A 1 1 7 . 1 A N S I CODE S E C T I O N 3 0 5 . 5 PER 2 0 0 9 I C C A 1 1 7 . 1 A N S I CODE S E C T I O N 3 0 5 . 5 PER 2009 ICC A117.1 ANSICODE SECTION 305.5 PER 2009 ICC A117.1 ANSI CODE SECTION 404.2.3 PER 2 0 0 9 I C C A 1 1 7 . 1 A N S I CODE S E C T I O N 9 0 3 . 2 PER 20 0 9 I C C A 1 1 7 . 1 A N S I CODE S E C T I O N 9 0 3 . 2 PER 2009 ICC A117.1 ANSICODE SECTION 903.2 PER 2009 ICC A117.1 ANSICODE SECTION 903.2 PER 20 0 9 I C C A 1 1 7 . 1 A N S I CODE S E C T I O N 9 0 3 . 2 PER 2 0 0 9 I C C A 1 1 7 . 1 A N S I CODE S E C T I O N 9 0 3 . 2 PER 20 0 9 I C C A 1 1 7 . 1 A N S I COD E S E C T I O N 9 0 3 . 2 PER 2009 ICC A117.1 ANSICODE SECTION 903.2 PER 2009 ICC A117.1 ANSICODE SECTION 903.2 PER 2 0 0 9 I C C A 1 1 7 . 1 A N S I CODE S E C T I O N 3 0 5 . 5 PER 2 0 0 9 I C C A 1 1 7 . 1 A N S I CODE S E C T I O N 3 0 5 . 5 PER 2009 ICC A117.1 ANSI CODESECTION 404.2.3 PER 2 0 0 9 I C C A 1 1 7 . 1 A N S I CODE S E C T I O N 3 0 5 . 5 PER 2 0 0 9 I C C A 1 1 7 . 1 A N S I CODE S E C T I O N 3 0 5 . 5 PER 2 0 0 9 I C C A 1 1 7 . 1 A N S I CODE S E C T I O N 3 0 5 . 5 PER 20 0 9 I C C A 1 1 7 . 1 A N S I CODE S E C T I O N 3 0 5 . 5 PER 2 0 0 9 I C C A 1 1 7 . 1 A N S I CODE S E C T I O N 3 0 5 . 5 PER 2009 ICC A117.1 ANSICODE SECTION 903.2 PER 2009 ICC A117.1 ANSICODE SECTION 903.2 NO GREATER THAN 75' (30' TO AISLES IN AREAS SERVING MORETHAN 50 OCCUPANTS) DIAG O N A L = 1 6 3 ' - 4 " ; 1 / 3 D I A G O N A L = 5 4 ' - 5 3 / 8 " 3'-0 3 / 4 " 87' Consultants Issue: 11.02.2017 SD CLIENT MEETING 04.03.2018 50% DD PROGRESS 05.04.2018 100% DD DRAWINGS 08.31.2018 CONSTRUCTION DOCUMENTS 02.15.2019 CONSTRUCTION DOCUMENTS 1830 blake stdenver, co 80202303.308.1373 500 w main staspen, co 81611970.544.9006 rowland+broughtonarchitecture / urban design / interior design 05.24.2019 PERMIT SUBMISSION Remove the date fromthe City of Aspen muni code. BUILDING INFORMATION / CODE ANALYSIS ·2017 CITY OF ASPEN MUNICIPAL CODE·2015 INTL BUILDING CODE·2015 INTL MECHANICAL CODE·2015 INTL FUEL AND GAS CODE ADDRESS: APPLICABLE BUILDING CODES: BUILDING DESCRIPTION: FIRE SUPPRESSION:FULLY SPRINKLERED (EXISTING, NO CHANGE) BUILDING USE:BUSINESS (NO CHANGE) PRIMARY TENANT SPACE OCCUPANCY :GROUP B - BUSINESS 611 EAST DURANT AVE, ASPEN, CO 81611 ·2015 INTL ENERGY CONSERVATION CODE·2015 INTL PLUMBING CODE·2015 INTL FIRE CODE·2017 NEC - NATL ELECTRICAL CODE FIRE RESISTIVE REQUIREMENTS FOR BUILDING ELEMENTS:TYPE-1-A SPRINKLERED STRUCTURAL FRAME: BEARING WALLS - EXTERIOR: BEARING WALLS - INTERIOR: NON-BEARING WALLS - SHAFT & STAIR: NON-BEARING WALLS - INTERIOR: 3 HOUR 2 HOUR 3 HOUR 3 HOUR 0 HOUR FLOOR CONSTRUCTION:2 HOUR ROOF CONSTRUCTION:1.5 HOUR TYPE OF CONSTRUCTION:1-A NON-COMBUSTABLE (EXISTING, NO CHANGE) GROSS AREA (TENANT SPACE):6,628 SF ASPEN ZONING:C - CONSERVATION, PD - PLANNED DEVELOPMENT INDIVIDUAL HISTORIC LANDMARK:NONE HISTORIC DISTRICT:NONE PLUMBING FIXTURE CALCULATIONS PLUMBING FIXTURES :89 PUBLIC OCCUPANTS REQ'D OCCUPANCY: GROUP B, BUSINESS INTERIOR FINISHES MINIMUM PERFORMACE REQUIREMENTS: INTERIOR WALL AND CEILING FINISHES: CLASS C(FLAME SPREAD INDEX 76-200; SMOKE DEVELOPED INDEX 0-450; PER ASTM E 84 OR UL 723) INTERIOR FLOORING: CLASS II PER NFPA 253 OR TRADITIONAL TYPE MATERIALS SUCH AS WOOD, VINYL, LINOLEUM, TERRAZZO, AND RESILIENT FLOOR COVERING WITH NO FIBERS INTERIOR TRIM: CLASS C FLAME SPREAD & SMOKE DEVELOPED INDEX. COMBUSTIBLE TRIM ACCEPTABLE PROVIDED IT DOES NOT EXCEED 10% OF WALL/CEILING AREA IT IS ATTACHED TO MEANS OF EGRESS EXIT ACCESS TRAVEL DISTANCE:250' MAX (A-OCCUPANCY, FULLY SPRINKLERED) MINIMUM NUMBER OF EXITS:2 (OCCUPANT LOAD GREATER THAN 49 AND LESS THAN 500); COMMON PATH OF EGRESS TRAVEL: MIN. SIZE OF DOORS:NOT LESS THAN 32" CLEAR MIN. EGRESS WIDTH:89 OCCUPANTS / 2 = 44.5 AT EACH EXIT x .15 =6.675" 32" CLEAR MIN. PROVIDED TENANT SPACE ADDRESS:TBD 2 PROVIDED MIN. STAIRWAY WIDTH:89 OCCUPANTS / 2 = 44.5 x .3 = 13.35" MIN WIDTH PER 2 0 0 9 I C C A 1 1 7 . 1 A N S I CODE S E C T I O N 9 0 3 . 2 PER 2009 ICC A117.1 ANSICODE SECTION 903.2 PER 2009 ICC A117.1 ANSICODE SECTION 903.2 PER 2 0 0 9 I C C A 1 1 7 . 1 A N S I COD E S E C T I O N 3 0 5 . 5 PER 2 0 0 9 I C C A 1 1 7 . 1 A N S I CODE S E C T I O N 9 0 3 . 2 PER 2009 ICC A117.1 ANSICODE SECTION 903.2 PER 2009 ICC A117.1 ANSI CODE SECTION 903.2 PER 20 0 9 I C C A 1 1 7 . 1 A N S I CODE S E C T I O N 9 0 3 . 2 PER 20 0 9 I C C A 1 1 7 . 1 A N S I COD E S E C T I O N 9 0 3 . 2 PER 20 0 9 I C C A 1 1 7 . 1 A N S I COD E S E C T I O N 3 0 5 . 5 PER 20 0 9 I C C A 1 1 7 . 1 A N S I CODE S E C T I O N 3 0 5 . 5 PER 20 0 9 I C C A 1 1 7 . 1 A N S I CODE S E C T I O N 3 0 5 . 5 PER 20 0 9 I C C A 1 1 7 . 1 A N S I CODE S E C T I O N 3 0 5 . 5 PER 20 0 9 I C C A 1 1 7 . 1 A N S I CODE S E C T I O N 3 0 5 . 5 PER 2009 ICC A117.1 ANSICODE SECTION 903.2 PER 2009 ICC A117.1 ANSICODE SECTION 903.2 NO GREATER THAN 75' (30' TO AISLES IN AREAS SERVING MORE THAN 50 OCCUPANTS) 89-25 = 64 = 1 WATER CLOSET FOR FIRST 25 64/50 = 1.28 = WATER CLOSETS FOR REMAINING 89-40 = 49 = 1 LAVATORY FOR FIRST 4049/80 = 0.6125 = LAVATORIES FOR REMAINING 3 WATER CLOSETS 2 LAVATORIES 87' EXIT Consultants Issue: 11.02.2017 SD CLIENT MEETING 04.03.2018 50% DD PROGRESS 05.04.2018 100% DD DRAWINGS 08.31.2018 CONSTRUCTION DOCUMENTS 02.15.2019 CONSTRUCTION DOCUMENTS 1830 blake stdenver, co 80202303.308.1373 500 w main staspen, co 81611970.544.9006 rowland+broughtonarchitecture / urban design / interior design 05.24.2019 PERMIT SUBMISSION Type of construction isII-A. RB: All comments on this page have been updated in the attached drawings. 01/30/2020 File Name: 611 E Durant_Full Permit Set.pdf Subject: PlanCheck Author: nickt Color: Page Index: 5 Page Label: A0.4 SHEET TITLE EGRESS AND CODE DRAWINGS Fire ratings are 1 hour for everything but the non-bearing interior walls which are 0. 2015 IBC 601 for type II-A construction. File Name: 611 E Durant_Full Permit Set.pdf Subject: PlanCheck Author: nickt Color: Page Index: 5 Page Label: A0.4 SHEET TITLE EGRESS AND CODE DRAWINGS To calculate plumbing fixtures, first divide the occupant load by 2 to get males and females. For example: 89/2= 44.5 = 45 males 45-25 : 1 1/50 x 20 = .4 Number water closets required for females= 1.4 = 2. Your design complies but your calculations are inaccurate. File Name: 611 E Durant_Full Permit Set.pdf Subject: PlanCheck Author: nickt Color: Page Index: 5 Page Label: A0.4 SHEET TITLE EGRESS AND CODE DRAWINGS Locker room occupant load is calculated by gross area, not net. 2015 IBC table 1004.1.2. File Name: 611 E Durant_Full Permit Set.pdf Subject: PlanCheck Author: nickt Color: Page Index: 7 Page Label: A0.8 ACCESSIBILITY REQUIREMENTS Vertical grab bar required- ICC A117.1-2009 section 604.5.1. File Name: 611 E Durant_Full Permit Set.pdf Subject: PlanCheck Author: nickt Color: Page Index: 9 Page Label: A2.1 Employee work area requires an accessible route into and out. Show and dimension door maneuvering clearances on both sides of door and show turnaround inside. Turnaround may include toe clearance under built in desk. 2015 IBC 1103.2.2 BUILDING INFORMATION / CODE ANALYSIS ·2017 CITY OF ASPEN MUNICIPAL CODE ·2015 INTL BUILDING CODE ·2015 INTL MECHANICAL CODE ·2015 INTL FUEL AND GAS CODE ADDRESS: APPLICABLE BUILDING CODES: BUILDING DESCRIPTION: FIRE SUPPRESSION:FULLY SPRINKLERED (EXISTING, NO CHANGE) BUILDING USE:BUSINESS (NO CHANGE) PRIMARY TENANT SPACE OCCUPANCY :GROUP B - BUSINESS 611 EAST DURANT AVE, ASPEN, CO 81611 ·2015 INTL ENERGY CONSERVATION CODE ·2015 INTL PLUMBING CODE ·2015 INTL FIRE CODE ·2017 NEC - NATL ELECTRICAL CODE FIRE RESISTIVE REQUIREMENTS FOR BUILDING ELEMENTS:TYPE-1-A SPRINKLERED STRUCTURAL FRAME: BEARING WALLS - EXTERIOR: BEARING WALLS - INTERIOR: NON-BEARING WALLS - SHAFT & STAIR: NON-BEARING WALLS - INTERIOR: 3 HOUR 2 HOUR 3 HOUR 3 HOUR 0 HOUR FLOOR CONSTRUCTION:2 HOUR ROOF CONSTRUCTION:1.5 HOUR TYPE OF CONSTRUCTION:1-A NON-COMBUSTABLE (EXISTING, NO CHANGE) GROSS AREA (TENANT SPACE):6,628 SF ASPEN ZONING:C - CONSERVATION, PD - PLANNED DEVELOPMENT INDIVIDUAL HISTORIC LANDMARK:NONE HISTORIC DISTRICT:NONE PLUMBING FIXTURE CALCULATIONS PLUMBING FIXTURES :89 PUBLIC OCCUPANTS REQ'D OCCUPANCY: GROUP B, BUSINESS INTERIOR FINISHES MINIMUM PERFORMACE REQUIREMENTS: INTERIOR WALL AND CEILING FINISHES: CLASS C (FLAME SPREAD INDEX 76-200; SMOKE DEVELOPED INDEX 0-450; PER ASTM E 84 OR UL 723) INTERIOR FLOORING: CLASS II PER NFPA 253 OR TRADITIONAL TYPE MATERIALS SUCH AS WOOD, VINYL, LINOLEUM, TERRAZZO, AND RESILIENT FLOOR COVERING WITH NO FIBERS INTERIOR TRIM: CLASS C FLAME SPREAD & SMOKE DEVELOPED INDEX. COMBUSTIBLE TRIM ACCEPTABLE PROVIDED IT DOES NOT EXCEED 10% OF WALL/CEILING AREA IT IS ATTACHED TO MEANS OF EGRESS EXIT ACCESS TRAVEL DISTANCE:250' MAX (A-OCCUPANCY, FULLY SPRINKLERED) MINIMUM NUMBER OF EXITS:2 (OCCUPANT LOAD GREATER THAN 49 AND LESS THAN 500); COMMON PATH OF EGRESS TRAVEL: MIN. SIZE OF DOORS:NOT LESS THAN 32" CLEAR MIN. EGRESS WIDTH:89 OCCUPANTS / 2 = 44.5 AT EACH EXIT x .15 =6.675" 32" CLEAR MIN. PROVIDED TENANT SPACE ADDRESS:TBD 2 PROVIDED MIN. STAIRWAY WIDTH:89 OCCUPANTS / 2 = 44.5 x .3 = 13.35" MIN WIDTH PER 2 0 0 9 I C C A 1 1 7 . 1 A N S I COD E S E C T I O N 9 0 3 . 2 PER 2009 ICC A117.1 ANSICODE SECTION 903.2 PER 2009 ICC A117.1 ANSICODE SECTION 903.2 NO GREATER THAN 75' (30' TO AISLES IN AREAS SERVING MORE THAN 50 OCCUPANTS) 89-25 = 64 = 1 WATER CLOSET FOR FIRST 25 64/50 = 1.28 = WATER CLOSETS FOR REMAINING 3 WATER CLOSETS Consultants Issue: 11.02.2017 SD CLIENT MEETING 04.03.2018 50% DD PROGRESS 05.04.2018 100% DD DRAWINGS 08.31.2018 CONSTRUCTION DOCUMENTS 02.15.2019 CONSTRUCTION DOCUMENTS 1830 blake stdenver, co 80202 303.308.1373 500 w main staspen, co 81611 970.544.9006 rowl and+br oughton architecture / urban design / interior design 05.24.2019 PERMIT SUBMISSION Fire ratings are 1 hour for everything but the non-bearing interior walls which are 0. 2015 IBC 601 for type II-A construction. PER 2009 I C C A 1 1 7 . 1 A N S I CODE SECTIO N 9 0 3 . 2 PER 2009 ICC A117.1 ANSICODE SECTION 903.2 PER 2009 ICC A117.1 ANSICODE SECTION 903.2PER 2009 ICC A 1 1 7 . 1 A N S I CODE SEC T I O N 3 0 5 . 5 PER 2009 ICC A 1 1 7 . 1 A N S I CODE SEC T I O N 3 0 5 . 5 PER 2009 I C C A 1 1 7 . 1 A N S I CODE SECTIO N 3 0 5 . 5 PER 2009 ICC A117.1 ANSICODE SECTION 305.5PER 2009 ICC A 1 1 7 . 1 A N S I CODE SECT I O N 3 0 5 . 5 PER 2009 ICC A 1 1 7 . 1 A N S I CODE SECTIO N 3 0 5 . 5 PER 2009 ICC A117.1 ANSI CODESECTION 404.2.3 PER 2009 ICC A117.1 ANSICODE SECTION 404.2.3 PER 2009 ICC A117.1 ANSICODE SECTION 404.2.3 PER 2009 ICC A 1 1 7 . 1 A N S I CODE SECT I O N 9 0 3 . 2 PER 2009 ICC A 1 1 7 . 1 A N S I CODE SECT I O N 9 0 3 . 2 PER 2009 ICC A117.1 ANSICODE SECTION 903.2 PER 2009 ICC A117.1 ANSICODE SECTION 903.2 PER 2009 IC C A 1 1 7 . 1 A N S I CODE SEC T I O N 9 0 3 . 2 PER 200 9 I C C A 1 1 7 . 1 A N S I CODE SECTI O N 9 0 3 . 2 PER 2009 ICC A117.1 ANSICODE SECTION 903.2 PER 2009 ICC A117.1 ANSICODE SECTION 903.2 PER 2009 I C C A 1 1 7 . 1 A N S I CODE SECTIO N 9 0 3 . 2 PER 2009 I C C A 1 1 7 . 1 A N S I CODE SECTION 9 0 3 . 2 PER 2009 I C C A 1 1 7 . 1 A N S I CODE SECTION 9 0 3 . 2 PER 2009 ICC A117.1 ANSICODE SECTION 903.2 PER 2009 ICC A117.1 ANSICODE SECTION 903.2 PER 2009 ICC A117.1 ANSICODE SECTION 903.2 PER 2009 ICC A117.1 ANSI CODE SECTION 903.2 PER 200 9 I C C A 1 1 7 . 1 A N S I CODE SECTI O N 9 0 3 . 2 PER 2009 I C C A 1 1 7 . 1 A N S I CODE SECTI O N 9 0 3 . 2 PER 2009 IC C A 1 1 7 . 1 A N S I CODE SE C T I O N 3 0 5 . 5 PER 2009 IC C A 1 1 7 . 1 A N S I CODE SE C T I O N 3 0 5 . 5 PER 2009 ICC A117.1 ANSI CODESECTION 404.2.3 PER 2009 I C C A 1 1 7 . 1 A N S I CODE SE C T I O N 3 0 5 . 5 PER 2009 I C C A 1 1 7 . 1 A N S I CODE SECTIO N 3 0 5 . 5 PER 2009 IC C A 1 1 7 . 1 A N S I CODE SE C T I O N 3 0 5 . 5 PER 2009 I C C A 1 1 7 . 1 A N S I CODE SECTIO N 3 0 5 . 5 PER 2009 I C C A 1 1 7 . 1 A N S I CODE SECTI O N 3 0 5 . 5 PER 2009 ICC A117.1 ANSICODE SECTION 903.2 PER 2009 ICC A117.1 ANSICODE SECTION 903.2 UPANCY DIAGRAM - LEVEL ONE KEY PLAN (N.T.S.) ADDRESS: BUILDING DESCRIPTION: FIRE SUPPRESSION:FULLY SPRINKLERED (EXISTING, NO CHANGE) BUILDING USE:BUSINESS (NO CHANGE) PRIMARY TENANT SPACE OCCUPANCY :GROUP B - BUSINESS 611 EAST DURANT AVE, ASPEN, CO 81611 FIRE RESISTIVE REQUIREMENTS FOR BUILDING ELEMENTS:TYPE-1-A SPRINKLERED STRUCTURAL FRAME: BEARING WALLS - EXTERIOR: BEARING WALLS - INTERIOR: NON-BEARING WALLS - SHAFT & STAIR: NON-BEARING WALLS - INTERIOR: 3 HOUR 2 HOUR 3 HOUR 3 HOUR 0 HOUR FLOOR CONSTRUCTION:2 HOUR ROOF CONSTRUCTION:1.5 HOUR TYPE OF CONSTRUCTION:1-A NON-COMBUSTABLE (EXISTING, NO CHANGE) GROSS AREA (TENANT SPACE):6,628 SF ASPEN ZONING:C - CONSERVATION, PD - PLANNED DEVELOPMENT INDIVIDUAL HISTORIC LANDMARK:NONE HISTORIC DISTRICT:NONE PLUMBING FIXTURE CALCULATIONS PLUMBING FIXTURES :89 PUBLIC OCCUPANTS REQ'D OCCUPANCY: GROUP B, BUSINESS INTERIOR FINISHES MINIMUM PERFORMACE REQUIREMENTS: INTERIOR WALL AND CEILING FINISHES: CLASS C(FLAME SPREAD INDEX 76-200; SMOKE DEVELOPED INDEX 0-450; PER ASTM E 84 OR UL 723) INTERIOR FLOORING: CLASS II PER NFPA 253 OR TRADITIONAL TYPE MATERIALS SUCH AS WOOD,VINYL, LINOLEUM, TERRAZZO, AND RESILIENT FLOOR COVERING WITH NO FIBERS INTERIOR TRIM: CLASS C FLAME SPREAD & SMOKE DEVELOPED INDEX. COMBUSTIBLE TRIMACCEPTABLE PROVIDED IT DOES NOT EXCEED 10% OF WALL/CEILING AREA IT IS ATTACHED TO MEANS OF EGRESS EXIT ACCESS TRAVEL DISTANCE:250' MAX (A-OCCUPANCY, FULLY SPRINKLERED) MINIMUM NUMBER OF EXITS:2 (OCCUPANT LOAD GREATER THAN 49 AND LESS THAN 500); COMMON PATH OF EGRESS TRAVEL: MIN. SIZE OF DOORS:NOT LESS THAN 32" CLEAR MIN. EGRESS WIDTH:89 OCCUPANTS / 2 = 44.5 AT EACH EXIT x .15 =6.675"32" CLEAR MIN. PROVIDED TENANT SPACE ADDRESS:TBD 2 PROVIDED MIN. STAIRWAY WIDTH:89 OCCUPANTS / 2 = 44.5 x .3 = 13.35" MIN WIDTH A ROOMOCCUPANTLOAD ACCESSORYUSEADJUSTMENT RESTROOMFIXTUREADJUSTMENT ADJUSTEDOCCUPANTLOAD NOTES 8 89 89 TOTAL OCCUPANTS 89 FOR EGRESS PER 2 0 0 9 I C C A 1 1 7 . 1 A N S I CODE S E C T I O N 9 0 3 . 2 PER 2009 ICC A117.1 ANSICODE SECTION 903.2 PER 2009 ICC A117.1 ANSICODE SECTION 903.2PER 20 0 9 I C C A 1 1 7 . 1 A N S I CODE S E C T I O N 3 0 5 . 5 PER 20 0 9 I C C A 1 1 7 . 1 A N S I CODE S E C T I O N 3 0 5 . 5 PER 2 0 0 9 I C C A 1 1 7 . 1 A N S I CODE S E C T I O N 3 0 5 . 5 PER 2009 ICC A117.1 ANSI CODESECTION 404.2.3 PER 2009 ICC A117.1 ANSI CODE SECTION 404.2.3 PER 2 0 0 9 I C C A 1 1 7 . 1 A N S I CODE S E C T I O N 9 0 3 . 2 PER 20 0 9 I C C A 1 1 7 . 1 A N S I CODE S E C T I O N 9 0 3 . 2 PER 200 9 I C C A 1 1 7 . 1 A N S I CODE S E C T I O N 9 0 3 . 2 PER 2009 ICC A117.1 ANSICODE SECTION 903.2 PER 2009 ICC A117.1 ANSICODE SECTION 903.2 PER 2009 ICC A117.1 ANSICODE SECTION 903.2 PER 2009 ICC A117.1 ANSI CODE SECTION 903.2 PER 2 0 0 9 I C C A 1 1 7 . 1 A N S I CODE S E C T I O N 9 0 3 . 2 PER 2 0 0 9 I C C A 1 1 7 . 1 A N S I CODE S E C T I O N 9 0 3 . 2 PER 200 9 I C C A 1 1 7 . 1 A N S I CODE S E C T I O N 3 0 5 . 5 PER 200 9 I C C A 1 1 7 . 1 A N S I CODE S E C T I O N 3 0 5 . 5 PER 2009 ICC A117.1 ANSI CODESECTION 404.2.3 PER 20 0 9 I C C A 1 1 7 . 1 A N S I CODE SE C T I O N 3 0 5 . 5 PER 2 0 0 9 I C C A 1 1 7 . 1 A N S I CODE S E C T I O N 3 0 5 . 5 PER 200 9 I C C A 1 1 7 . 1 A N S I CODE S E C T I O N 3 0 5 . 5 PER 20 0 9 I C C A 1 1 7 . 1 A N S I CODE S E C T I O N 3 0 5 . 5 PER 2 0 0 9 I C C A 1 1 7 . 1 A N S I CODE S E C T I O N 3 0 5 . 5 PER 2009 ICC A117.1 ANSICODE SECTION 903.2 PER 2009 ICC A117.1 ANSICODE SECTION 903.2 AREA OF SCOPE:LOCKER ROOM EAST DEAN STREET(PEDESTRIAN WALKWAY) PLANNORTH TRUENORTH NO GREATER THAN 75' (30' TO AISLES IN AREAS SERVING MORETHAN 50 OCCUPANTS) ADJACENT PUBLICLOCKERS ANDRESTROOM MECHANICALAND B.O.H EXIT ENCLOSURE ADJACENT TICKET OFFICE ADJACENTRETAILSPACE OCCUPANT LOADOCCUPANT LOAD FACTORMIN. REQUIRED WIDTH (IN) PROPOSED C.O. WIDTH EXIT DOOR RATING 89/2=44.50.156.675" 32" NR (ACCESSIBLE) CORRIDOR PLANNORTH TRUENORTH 89-25 = 64 = 1 WATER CLOSET FOR FIRST 2564/50 = 1.28 = WATER CLOSETS FOR REMAINING 89-40 = 49 = 1 LAVATORY FOR FIRST 4049/80 = 0.6125 = LAVATORIES FOR REMAINING 89/100 = 0.89 3 WATER CLOSETS 2 LAVATORIES 1 WATER FOUNTAIN 1 SERVICE SINK REQ'D 1/3 D I A G O N A L = 5 4 ' - 5 3 / 8 " 3'-0 3 / 4 " 87' EXIT COPYRIGHT 2019 ROWLAND+BROUGHTON ARCHITECTURE AND URBAN DESIGNTHE INFORMATION AND DESIGN INTENT CONTAINED ON THIS DOCUMENT ISTHE PROPERTY OF ROWLAND+BROUGHTON ARCHITECTURE AND URBANDESIGN. NO PART OF THIS INFORMATION MAY BE USED WITHOUT THE PRIORWRITTEN PERMISSION OF ROWLAND+BROUGHTON ARCHITECTURE AND URBANDESIGN. ROWLAND+BROUGHTON ARCHITECTURE AND URBAN DESIGN SHALLRETAIN ALL COMMON LAW STATUTORY AND OTHER RESERVED RIGHTS,INCLUDING COPYRIGHT THERETO. Consultants Issue: SHEET TITLE PROJECT NO: DWG FILE: SCALE: 21704-1_A0-4 EGRESS AND CODE.dwg ASPEN MOUNTAIN CLUB LOCKER ROOMS BASE OF GONDOLA 611 E Durant Ave ASPEN, CO, 81611 21704.10 11.02.2017SD CLIENT MEETING 04.03.2018 50% DD PROGRESS 05.04.2018 100% DD DRAWINGS 08.31.2018CONSTRUCTION DOCUMENTS 02.15.2019 CONSTRUCTION DOCUMENTS 1830 blake stdenver, co 80202303.308.1373 500 w main staspen, co 81611970.544.9006 05.24.2019 PERMIT SUBMISSION A0.4 AS NOTED EGRESS AND CODEDRAWINGS To calculate plumbing fixtures, first divide the occupantload by 2 to get males and females. For example:89/2= 44.5 = 45 males 45-25 : 11/50 x 20 = .4Number water closets required for females= 1.4 = 2. Your design complies but your calculations are inaccurate. EGRESS AND OCCUPANCY DIAGRAM - LEVEL ONE OCCUPANT LOAD CALCULATIONS ASSEMBLY, W/O FIXED SEATING, UNCONCENTRATED LOCKER ROOM (ACCESSIBLE) CODE PLAN LEGEND SCALE: 1/8" =1'-0" SPACE FUNCTION OF SPACE (per IBC Table 1004.1.1) UNIT PER OCCUPANT MEASUREMENT TYPE AREA ROOM OCCUPANT LOAD ACCESSORY USE ADJUSTMENT RESTROOM FIXTURE ADJUSTMENT ADJUSTED OCCUPANT LOAD LOCKER ROOM ASSEMBLY, UNCONCENTRATED 50 SF NET 4,418 89 89 TOTAL OCCUPANTS 89 FOR EGRESS PLAN NORTH TRUE NORTH Locker room occupant load is calculated by gross area, not net. 2015 IBC table 1004.1.2. Figure 404.2.6 Figure 504.5 NOSING CURVED 12 2 0 48 m i n X > 2 4 SLIDING 32 m 815 m 815 m 32" m BEVELED Nosing max112" Max 32" min 815 mm (A) (B) VERTICAL RISER RADIUS 1/2" MAX TYPICAL max112" CURVE BEVELED 30 FLOOR SPACE - PARALLEL 60" min CLEAR FLOOR SPACE 56 " m i n FIG. 604.3.1 18" 48" min 17 - 1 9 FIG. 604.4 24" 46 ADAAG 4.2.6 Figure 6c (a)(b)(c) (a) CLEAR HOLD 30" 34 " M A X N PLANS. SCALE: SIZE OF CLEARANCE FOR WATER CLOSETS N.T.S. 14 A0.8 SCALE: TWO DOORS IN A SERIES N.T.S. 10 A0.8SCALE: MAX. SIDE REACH OVER OBSTRUCTION N.T.S. 9 A0.8 SCALE: STAIR NOSINGS N.T.S. 15 A0.8 SCALE: UNOBSTRUCTED HIGH SIDE REACH N.T.S. 4 A0.8 SCALE: WHEELCHAIR KNEE AND TOE CLEARA N.T.S. 5 A0.8 Vertical grab bar required- ICC A117.1-2009 section 604.5.1. Employee work arearequires an accessibleroute into and out.Show and dimensiondoor maneuveringclearances on bothsides of door andshow turnaround inside. Turnaroundmay include toeclearance under builtin desk. 2015 IBC1103.2.2 RB: All comments on this page have been updated in the attached drawings. 01/30/2020 File Name: 611 E Durant_Full Permit Set.pdf Subject: PlanCheck Author: nickt Color: Page Index: 9 Page Label: A2.1 The existing entrance door is not accessible (double leaf door with a single leaf open does not permit 32" clear). 2015 IEBC 705.2 requires that up to 20% of the project valuation be spent on improving the accessible route due to the alteration of the primary function of the space. Please provide a door where a single leaf open at 90 degrees will provide 32" clear. 2015 IBC 1010.1.1. File Name: 611 E Durant_Full Permit Set.pdf Subject: PlanCheck Author: nickt Color: Page Index: 9 Page Label: A2.1 Provide the clear opening dimension of the operable portion of door 018. Must allow 32" clear. 2015 IBC 1010.1.1. File Name: 611 E Durant_Full Permit Set.pdf Subject: PlanCheck Author: nickt Color: Page Index: 9 Page Label: A2.1 Provide an enlarged plan and interior elevations of the toilet rooms with dimensions showing accessibility compliance with ICC A117.1-2009 chapter 6. File Name: 611 E Durant_Full Permit Set.pdf Subject: PlanCheck Author: nickt Color: Page Index: 11 Page Label: A7.1 DETAILS Existing fireproofing of structure must be maintained. Note what type of fireproofing is currently in place and how your installation will not disturb it. File Name: 611 E Durant_Full Permit Set.pdf Subject: PlanCheck Author: nickt Color: Page Index: 14 Page Label: AMC-LN- LR-1001 Detail the location and dimensions of the reception desk and coffee station. Both must be accessible. 2015 IBC 1109.12.3 and 1109.4. The existing entrance door is not accessible (doubleleaf door with a single leaf open does not permit 32"clear). 2015 IEBC 705.2 requires that up to 20% ofthe project valuation be spent on improving theaccessible route due to the alteration of the primaryfunction of the space. Please provide a door wherea single leaf open at 90 degrees will provide 32"clear. 2015 IBC 1010.1.1. Provide the clearopening dimension of the operable portion ofdoor 018. Must allow 32" clear. 2015 IBC1010.1.1. Provide an enlarged plan andinterior elevations of the toiletrooms with dimensions showingaccessibility compliance with ICCA117.1-2009 chapter 6. EXISTINGCONCRETE SLAB EXISTING STRUCTURE REF. RCP SECURE NEW MTL FRAMING TO EXISTING STRUCTURE FORNEW 5/8" DRYWALL CEILING SCALE: SECTIONTYP. NEW DRYWALL CEILING 1 1/2" = 1'-0" 1 A7.1 SCALE: SECTIONTYP. LOCKER BASE FRAMING 1 1/2" = 1'-0" 2 A7.1 5 1 / 2 " OFCI MILLWORK LOCKERABOVE BASE WTIH ACCESS PANEL TO POWER SUPPLYWITHIN FRAMING VARIES, REF. DIM. PLAN EXISTING WALL OFCI MILLWORK BASE, SCRIBE TOFLOOR - ALL LOCKER BASES TO ALIGN 5/8"3"3/4" (1) LAYER GWB, RE:FINISH SCHEDULE INTERIOR MTL STUDS BAR AND BATHROOM WALLS: UNFACED FIBERGLASSSOUND BATTS 2 1/2"5/8" (1) LAYER GWB, RE:FINISH SCHEDULE INTERIOR MTL STUDS EXISTING SCALE: TYP. INTERIOR FURRING 3" = 1'-0" W-2 A7.1SCALE: TYP. INTERIOR PARTITION ASSEMBLY 3" = 1'-0" W-1 A7.1 (1) LAYER PLYWD BEHIND LOCKERS, 5/8" GWB WHENEXPOSED FINISH PER SCHED. 6" U.N.O SCALE: PLANTYP. DOOR HINGE FRAMING 1 1/2" = 1'-0" 3 A7.1 MILLWORK DOOR ANDCASING BY OTHERS, OFCI Existing fireproofing ofstructure must bemaintained. Note whattype of fireproofing iscurrently in place and how your installation will not disturb it. Detail the location anddimensions of thereception desk andcoffee station. Bothmust be accessible.2015 IBC 1109.12.3and 1109.4. RB: this door has been field verified, each leaf is 34" wide and provides 32" clear and opens 90° minimum. Please see drawings for added note. RB: this door has been field verified, each leaf is 34" wide and provides 32" clear and opens 90° minimum. RB: please see added enlarged plan on page A7.1 keyed from A2.1d, and LB_0.S3 page for interior elevations RB: This has been updated in the attached drawings. RB: This page is incorrect and shall be omitted. Compliant reception desk and coffee station are documented on LB_0.S4 01/30/2020 Where are the reception desk and coffee station located and where can I find drawings of them? Both must be documented to demonstrate accessibility. LB_0.S4 appears to only show lockers and a cabinet- is this the coffee station? File Name: 611 E Durant_Full Permit Set.pdf Subject: PlanCheck Author: nickt Color: Page Index: 15 Page Label: AMC-LN-LR-1002 5% of all lockers must be accessible (2015 IBC 1109.12.1). In addition to the clearspace you've shown, this also requires the following: -The operable hardware must be operable with one hand and not require tight grasping, pinching, or twisting of the wrist to operate. (ICC A117.1-2009 section 309.4) -The operable hardware no more than 48" above the floor (ICC A117.1-2009 section 308). -Shelves and hooks between 15" and 48" above floor (ICC A117.1-2009 section 308). File Name: 611 E Durant_Full Permit Set.pdf Subject: PlanCheck Author: nickt Color: Page Index: 18 Page Label: AMC-LN-LR-1006 Accessible benches must have the seat between 17" and 19" above the floor. ICC A117.1-2009 section 903.5 File Name: 611 E Durant_Full Permit Set.pdf Subject: PlanCheck Author: nickt Color: Page Index: 32 Page Label: LT3.2 COPYRIGHT 2019 ROWLAND+BROUGHTON ARCHITECTURE AND URBAN DESI 3/16"=1'-0" LOCKER AREA LIGHTING PLAN SCALE: Provide a switching plan demonstrating compliance with 2015 IECC C405.2, including the following: 1. Occupant sensor controls in the restrooms and office. 2. The overall locker area may use either occupant sensors or time switch controls. File Name: 611 E. Durant_ Lighting Specifications.PDF Subject: PlanCheck Author: nickt Color: Page Index: 20 Page Label: 20 Provide a cutsheet for fixture ZF-S showing fixture wattage and listing by a nationally recognized testing lab. 611 E. Durant_ Lighting Specifications.PDF (1) 5% of all lockers must be accessible (2015 IBC 1109.12.1). In addition to the clearspace you've shown, this also requires the following:-The operable hardware must be operable with one hand and not require tight grasping, pinching, or twisting of the wrist to operate. (ICC A117.1-2009 section 309.4) -The operable hardware no more than48" above the floor (ICC A117.1-2009 section 308). -Shelves and hooks between 15" and 48" above floor (ICC A117.1-2009 section 308). Accessible benches must have the seat between 17" and 19" above the floor. ICC A117.1-2009 section 903.5 E D C B1.W TF TE TD B.W A1.W 2.W1210 3.W 4.W B1.W 1.W119 1 A4.1 SCALE: PROPOSEDLEVEL ONE DIMENSION PLAN 3/16" = 1'-0" 1 A2.1d PLAN NORTH TRUE NORTH DW DD DW DA DA DWDW DW DW DW DW DW DW DW DW DW DW DWDW DW DW DWDW DW DW DW DA ZF.S ZF.S ZF.S ZF.S DA DW DADA DW DW DD DD DDDW DW DW DW DW DW DW DW SS SS S DA DA DA DA DW DW DW DW DW DWDWDW DW DW DW DW DW DW DWDW DW DW DW DW DW DW DW DW DD DD K DD DD DD DD DD DDDD DDDDDD DD DD DD DD DD FF&E ID 107 25 WATTS S TWO BANK OF (4) SWITCHES BY OFFICE DOOR 1.2.3.4.5.6.7.8.9.1.2.3.4.5.6. 123456NO789 DDDD DWDWDW DW DWDW DWDW DW DA DA DW DW DWDWDWDW DWDWDW DD DW DW DW DW DW DW DW DW DW DWDWDW DWDWDW DW DW DD DD DD DW DWDWDWDWDWDW DW DW DDDW DW DW DW DW DW DW DW DW DW DW DW DD DD DW DW DW DD DD DWDWDW DW DWDWDWDW DWDWDWDWDWDWDWDWDWDW DW DW DW DW D DW DW A B C D E F DD DW K DW K DDDDDD DW D C DD DD DD DD DW DW F G FG D A C E B DD B C D SSS SSSS Provide a switching plan demonstrating compliance with 2015 IECC C405.2, including the following: 1. Occupant sensor controls in the restrooms and office. 2. The overall locker area may use either occupant sensors or time switch controls. AMC - Aspen Mountain Club - Locker Room Fixture Type: ZF-SMay 24, 2019 CONSTRUCTION DOCUMENTS Provide a cutsheet forfixture ZF-S showing fixture wattage andlisting by a nationally recognized testing lab. RB: Please see A2.1 for ADA locker locations. Thumbturn can be pushed into (un)locked position. When unlocked, the thumbturn extends past backplate to provide an edge to pull the door open (no grasp necessary). Shelves and hooks are adjustable. These notes have been added to the drawings. RB: Bench height complies when furnished with cushion. RB: all spaces have occupancy sensors, indicated by a circle symbol labeled V RB: please see provided cut sheet. 01/30/2020 Make it clear on the plans how you are complying with the below. Your response says it is noted on the plans but does not tell me where to look and I'm not seeing it: 5% of all lockers must be accessible (2015 IBC 1109.12.1). In addition to the clearspace you've shown, this also requires the following: -The operable hardware must be operable with one hand and not require tight grasping, pinching, or twisting of the wrist to operate. (ICC A117.1-2009 section 309.4) -The operable hardware no more than 48" above the floor (ICC A117.1-2009 section 308). -Shelves and hooks between 15" and 48" above floor (ICC A117.1-2009 section 308).