HomeMy WebLinkAboutFile Documents.232 E Main St.0078-2020-BCHO0078-2020-BCHO_BuildingComments_1 Subject: PlanCheck Page: G-005 - WALL TYPES Page Index: 6 Author: nickt Color: File Name: 90.Architectural Plans.20201106.pdf Assemblies in the thermal envelope have changed. Provide an updated COMcheck. In particular, roofs appear to have minimal insulation. 90.Architectural Plans.20201106.pdf (14) Subject: PlanCheck Page: G-008 - FIRE RESISTANCE SITE PLAN Page Index: 9 Author: nickt Color: File Name: 90.Architectural Plans.20201106.pdf Dimension the extent of this roof fire rating. Subject: PlanCheck Page: A-100 - PROPOSED MAIN FLOOR PLAN Page Index: 12 Author: nickt Color: File Name: 90.Architectural Plans.20201106.pdf Only penetrations serving the exit enclosure may penetrate the exit enclosure. Remove all plumbing from the exit enclosure. 2015 IBC 1023.5 Subject: PlanCheck Page: A-100 - PROPOSED MAIN FLOOR PLAN Page Index: 12 Author: nickt Color: File Name: 90.Architectural Plans.20201106.pdf Only openings necessary for egress are allowed in exit enclosures. Window not permitted. 2015 IBC 1023.4 Subject: PlanCheck Page: A-101 - PROPOSED 2ND FLOOR PLAN Page Index: 13 Author: nickt Color: File Name: 90.Architectural Plans.20201106.pdf Door swings over a step according to detail 7/A-502. Landing elevations on each side of the door must be the same height. 2015 IBC 1010.1.5 BLIES: ROOF -CLASS A NGLE ED CAP SHEET ATION OVER BEAMS IBC 2015 7 2-4.1 TWO BRACKETS 1 5/8" DEE TO AND ON FLANGE. T CONSTRU BRACKETS THE BENT CUT OUT S Assemblies in the thermal envelope have changed. Provide an updated COMcheck. In particular, roofs appear to have minimal insulation. PROPOSED 2 STORY BUILDING LANDSCAPE AREA 414 SF HIS T O R I C C O R T I N A L O D G E CORTINA LODGE BALCONY LA N D S C A P E A R E A 1,1 3 6 S F HISTORIC CORTINA LODGE STONE CHIMNEY OVERHANG ABOVE 5'- 0 " AWNING. TYP. 2-HR RATED CONSTRUCTION (NO PARAPET) 2- H R R A T E D C O N S T R U C T I O N ( N O P A R A P E T ) 9 Dimension the extent of this roof fire rating. UP DN 5'- 3 1 / 2 " 2'- 7 1 / 4 " R. O . 10 ' - 7 3 / 4 " ENANT 'B' ELEV. A-412 1 E.8 F.8 4" D.S. D18'-2 1/8" R.O. 3'-4" TENANT 'B' STAIR 105 U -2'-1 1/8" 9.8 8'-4"9'-4 3/4" 9.1 3'- 4 " 11 " BH = -1'-0'' BH = -1'-7'' E4 9 2'-6 3/4" -1'-0" 10 1. P AC 2. F AN 3. A PA 4. T TH IND PR 5. T VE AN DIS 6. S BE 7. A AV 8. A WI 9. D GE Only penetrations serving the exit enclosure may penetrate the exit enclosure. Remove all plumbing from the exit enclosure. 2015 IBC 1023.5 UP DN 2 A-300 TENANT SPACE 'B' 101 2 A-310 5'- 3 1 / 2 " 2'- 7 1 / 4 " R.O . 10 ' - 7 3 / 4 " 2'- 7 5 / 8 " R.O . 10 ' - 7 3 / 4 " 2'- 7 3 / 4 " R.O . 10 ' - 7 3 / 4 " 5/8 " AIR CURTAIN BY TENANT TENANT 'B' ELEV. A-412 1 00 A-400 1 C-1 4" D.S. 4'-10"22'-10 3/8" ACCESS PANEL * ADA PUSH BUTTON GAS METERS D R.O. 3'-4"18'-2 1/8" R.O. 3'-4" H 1s T E1 TENANT 'B' STAIR 105 U Es O. -0" -2'-1 1/8" TWO-WAY COMMUNICATION SYSTEM WALL THIS ONLY DRYWALL THIS SIDE ONLY -1'-0" 9.8 1'-6" 9.1 3'- 4 " 11 " R.O. 6'-0" BH = +0-0" BH = +0-0" BH = -8" BH = -1'-4''BH = -1'-4'' BH = -1'-0'' 13'-3" BH = -1'-7'' BH = +0'-0'', TYP. E4 -1'-0" 9 2'-6 3/4" 11'-0" 5'-4 1/4" G2 B F C6 -2'-8" DN 1" / 2 5 ' ' ( 4 % ) 2'- 0 " 12 ' - 6 " 4'- 0 3 / 8 " -1'-0" -1'-1 11/16'' 1.7% 2.5 % 10 10 10 PAINTED. 4. THESE DRAWINGS INDIC THE ARCHITECTURAL DESI INDICATE OR DESCRIBE AL PROJECT. 5. THE CONTRACTOR OR S VERIFICATION OF ALL DIME ANY WORK AND SHALL NOT DISCREPANCIES. 6. SUBCONTRACTOR SHALL BEFORE PROCEEDING WIT 7. ALL WORK SHALL BE COO AVOID INTERFERENCES, PR 8. ALL DOORS USED IN CON WITHOUT THE USE OF A KE 9. DIMENSIONS MARKED 'H DIMENSIONS ARE FACE TO 10. DIMENSIONS, TARGETS ONLY ONCE. 11. PROVIDE PRIME COAT O FILE CABINETS, WALL COVE OTHERWISE. 12. PROVIDE MOISTURE RE WET AREAS (IE., SINKS, TO 13. PROVIDE TILE BACKER AREA APPLICATION (IE.,SIN 14. INTERSECTION BETWEE PAINTABLE CAULK U.N.O. 15. UPON INSTALLATION OF HOLES, VOIDS, ETC. BETWE TO BE PAINTABLE. 16. THRESHOLDS BE CONT 17. THRESHOLD END COND SHAPE/PROFILE OF JAMB/W 18. DO NOT SCALE DRAWIN ARCHITECT'S WRITTEN APP 19. ALL INTERIOR FINISHES 20. G.C. TO CONFIRM/ COO COMENCING CONSTRUCTIO 21. ELEV. 0'-0" = 7903.70'10 Only openings necessary for egress are allowed in exit enclosures. Window not permitted. 2015 IBC 1023.4 SECOND FLOOR TENANT SPACE-'B' 200 19 ' - 0 5 / 8 " 13 ' - 9 " 27'-7 3/4" A-413 1 D C6 C6 D.S. AND SPLASH BLOCK E2 ACCESS PANEL " MIN. THICK LATION AT ROOF NS 1/4'' : 1'-0'' 1/4'' : 1'-0'' 7'' MAX. THICK INSULATION PVC ROOF MEMBRANE F M 6'-6 3/4"3'-0"6'-6 3/4" ACCESS PANEL ACCESS PANEL ACCESS PANEL BY TENANT, TYP. ACCESS PANEL COMMUNICATION SYSTEM WALLS BY TENANT, TYP. DOOR BY TENANT, TYP. N 6'- 2 1 / 2 " CKET PER MANUF. OMMENDATIONS, TYP. RTU 2 925 LBS. ROOF WALKWAY PADS, TYP. F DRAIN, TYP. A-502 C4C4 Door swings over a step according to detail 7/A-502. Landing elevations on each side of the door must be the same height. 2015 IBC 1010.1.5 Subject: PlanCheck Page: A-240 - PROPOSED OUTDOOR LIGHTING Page Index: 19 Author: nickt Color: File Name: 90.Architectural Plans.20201106.pdf Provide an updated exterior lighting COMcheck. Subject: PlanCheck Page: A-400 - STAIRS & ELEVATOR Page Index: 24 Author: nickt Color: File Name: 90.Architectural Plans.20201106.pdf Detail the fire resistance of this portion of the exit enclosure and reference listed fire rated assemblies. 2015 IBC 1023 Subject: PlanCheck Page: A-500 - PLAN DETAILS Page Index: 30 Author: nickt Color: File Name: 90.Architectural Plans.20201106.pdf This plumbing may not be in the exit enclosure. 2015 IBC 1023.5 Subject: PlanCheck Page: A-501 - WALL DETAILS AT GROUND LEVEL Page Index: 31 Author: nickt Color: File Name: 90.Architectural Plans.20201106.pdf Account for these thermal bridges in COMcheck or eliminate them with a different insulation design. Subject: PlanCheck Page: A-502 - WALL DETAILS AT SECOND LEVEL Page Index: 32 Author: nickt Color: File Name: 90.Architectural Plans.20201106.pdf Account for this bridge in the thermal envelope in COMcheck or reduce it (perhaps with insulation on the interior of the cmu wall. (3) PROPOSED 10" FRENCH FARMHOUSE SCONCE -TYPE 'A' (4) WALL SCONCE -TYPE 'B' 1 2 3 A B C D E F G EQ . 2'- 9 " 2'- 9 " EQ . A.1 F.9 10 3/16" = 1'-0"1 PROPOSED LIGHTING PLAN Provide an updated exterior lighting COMcheck. CEDAR SHAKE SHINGLES OVER GABLED ROOF, ROOF AT (9/12) SLOPE RECLAIMED WOOD FACIA GUTTER 9 12 9 12 C.4E.8F.8 Sim 1 A-504 7'- 4 " L MIN . H E A D C L E A R A N C E 6'- 8 " A-400 6 5 A-400 6 Sim HANDRAIL BY TENANT -2'-1 1/8" B Detail the fire resistance of this portion of the exit enclosure and reference listed fire rated assemblies. 2015 IBC 1023 P. 2"3/4 " 3/4 " 10 F.8 3 1 / 2 " 07 95 13.E1 08 71 00.B14 10 73 13.A3 06 11 00.A9 09 81 00.B2 06 22 00.A4 07 26 00.A4 07 71 23.J1 07 26 00.A4 5" 3"3/4" 3/4" A-500 11 U 06 11 00.A9 9.8 CLT PANEL GLU-LAM COL. DRYWELL DISCHARGE PRESSURE BREAK BOTH SIDES 6 3 / 4 " 5 3 / 4 " 6 3/4"11 1/4" 6" 1 3/4" 1'-0 1/2" +/- 07 44 50 09 81 00.B2 3 13.A3 3" 0 00.B2 4"4" 05 40 00.B6 10 73 13.A3 06 11 00.A2 06 22 00.A407 26 00.A4 5 1/2" 1" 07 51 13.A5 9 PLAN DETAIL " = 1'-0" RGED PLAN - EAST ENTRANCE JAMB DETAIL 1 1/2" = 1'-0"6 ENLARGED PLAN - EAST ENTRANCE JAMB DETAIL 2 3" = 1'-0"11 TYP. ALUMIN This plumbing may not be in the exit enclosure. 2015 IBC 1023.5 SUB FLR. TENANT 'A' 7903.700" G 05 40 00.B6 07 26 00.A4 09 29 00.D1 05 41 00.A5 32 13 00.B9 03 31 00.M7 03 21 00.A12 07 51 13.A3 03 31 00.J1 07 13 00.A3 07 11 00 1'-5" 5/8"4 7/8"5 1/2"3"1 3/4"1"1/4" 07 44 50 05 40 00.B3 0'-8" BY TENANT ALIGN 6"1'-6" 7" 07 62 00.A9 10 SUB FLR. TENANT 'A' 7903.700" F.8 05 41 00.A5 03 21 00.A1203 21 00.A12 03 31 00.M7 03 31 00.J1 07 13 00.A3 07 11 00 3 1/2"3"3/4"3/4" 07 26 00.A4 06 22 00.A4 06 22 00.A11 07 51 13.A4 07 62 00.A9 10 SUB FLR. TENANT 'A' 7903.700" 2 07 95 13.B8 32 13 00.B903 31 00.J1 03 21 00.A12 07 13 00.A3 ADA COMPLIANT THRESHOLD 10 SUB FLR. TENANT 'A' 7903.700" A 07 13 00.A3 03 31 00.J1 07 21 00.E3 ADJA C E N T B U I L D I N G ( N . I . C . ) 6 TO 14 INCHESVARIES NON-COMPRESSIBLE RIGID INSULATION LAYERS FOR ONE-SIDED DAMPROOFING SUPPORT AND INFILL BETWEEN NEW AND EXISTING FOUNDATION WALLS FOUNDATION DAMPROOFING SHEET METAL GUTTER SLOPED TO ALLEY 10 SUB FLR. TENANT 'A' 7903.700" 9 SUB FLR. TENANT 'B' 7902.70-1'-0" SUB FLR. MECH. ROOM 7901.53-2'-2" 07 26 00.A4 03 31 00.J1 07 13 00.A3 32 13 00.B9 07 95 13.B8 -2'-0" -2'-8" 07 62 00.A9 07 62 00.A0 10 10 SUB FLR. TENANT 'A' 7903.700" A 07 95 13.B4 06 22 00.A11 06 16 00.D10 07 26 00.A6 04 22 00.A16 05 41 00.A8 HOLD1'-5" 1'-2" 2"+/-7 5/8"6"3/4"3/4" ADJA C E N T B U I L D I N G ( N . I . C . ) 6" 07 62 00.A9 10 SUB FLR. TENANT 'A' 7903.700" G 07 11 00 03 31 00.M7 07 62 00.A9 07 26 00.A4 06 22 00.A11 32 13 00.B9 07 95 13.B8 07 21 00.B10 07 26 00.A4 5 1/2"5 1/2"3"1 3/4"1"3/8"HOLD1'-5" 07 51 13.A3 05 40 00.B3 07 44 50 CLT PANEL 07 62 00.A9 10 Scale PROJECT NUMBER DATE DRAWN BY CHECKED BY modif. modif. 1 1/2" = 1’−0" 11/ 6 / 2 0 2 0 1 1 : 2 7 : 2 6 A M A−501 2016−005 11.05.20 WALL DETAILS AT GROUND LEVEL CO M M E R C I A L DE V E L O P M E N T 23 2 E . M A I N S T . A S P E N , C O 1 1/2" = 1'-0"1 ` 1 1/2" = 1'-0"2 SECTION DETAIL - EAST PILASTER 1 1/2" = 1'-0"3 SECTION DETAIL - SOUTH ENTRANCE 1 1/2" = 1'-0"4 SECTION DETAIL - WEST WALL 1 1/2" = 1'-0"7 SECTION DETAIL - NORTH WALL KEYNOTE LEGEND 03 21 00.A12 STEEL REINFORCEMENT, SEESTRUC. DWGS.03 31 00.J1 5" SLAB-ON-GRADE OVERENGINEERED FILL, SEESTRUC. DWGS.03 31 00.M7 CONC. FOUNDATION WALL,SEE STRUC. DWGS.04 22 00.A16 8" X 8" X 16" CMU - 2 CORE05 40 00.B3 VERTICAL HAT PROFILE 05 40 00.B6 HORIZ. FURRING05 41 00.A5 3-5/8" METAL FRAMING05 41 00.A8 6" METAL FRAMING06 16 00.D10 3/4" EXTERIOR GRADEPLYWOOD06 22 00.A4 1X4 VERTICAL FURRING STRIP06 22 00.A11 FIRE TREATED RECLAIMEDWOOD SIDING07 11 00 BITUMINOUS DAMPPROOFING07 13 00.A3 6 MIL. POLYETHYLENE07 21 00.B10 RIGID INSULATION07 21 00.E3 CLOSED CELL SPRAY FOAMINSULATION07 26 00.A4 VAPOR BARRIER07 26 00.A6 WEATHER BARRIER07 44 50 FIBER-REINFORCEDCEMENTITIOUS PANEL07 51 13.A3 FULLY ADHERED CONTINUOUSASPHALT FLASHING07 51 13.A4 FLASHING TAPE07 62 00.A0 METAL FLASHING07 62 00.A9 FLASHING07 95 13.B4 1/2" EXPANSION JOINT07 95 13.B8 FIBER EXPANSION JOINT WITHBACKER ROD ANDELASTOMERIC SEALANT09 29 00.D1 5/8" GYPSUM WALLBOARD32 13 00.B9 EXTERIOR SIDEWALK, SEECIVIL DWGS. 1 1/2" = 1'-0"5 SECTION DETAIL - WEST WING WALL 1 1/2" = 1'-0"6 SECTION DETAIL - EAST WING WALL NO. DATE BY REVISION 1 09.25.18 MODIF.PERMIT SET 2 11.28.18 MODIF.ISSUED FOR BID 3 05.24.19 MODIF.PERMIT DOCUMENT REVISIONS #1 4 08.2.19 MODIF.PERMIT DOCUMENT REVISION #2 5 11.12.19 MODIF.PERMIT DOCUMENT REVISION #3 6 12.18.19 MODIF.PERMIT DOCUMENT REVISION #4 7 3.27.20 MODIF.ISSUE FOR CONSTRUCTION 8 3.27.20 MODIF.CONSTRUCTION DOCUMENT REVISION #5 9 10.02.20 MODIF.CONSTRUCTION DOCUMENT REVISION #6 10 11.05.20 MODIF.CONSTRUCTION DOCUMENT REVISION #7 9 Account for thesethermal bridges inCOMcheck oreliminate them with adifferent insulationdesign. A-503 8 Sim 07 19 00.A2 11'-0" SEE STRUCTURAL DWGS. FOR ATTACHMENT DETAIL Account for this bridge in the thermal envelope in COMcheck or reduce it (perhaps with insulation on the interior of the cmu wall. Subject: PlanCheck Page: A-502 - WALL DETAILS AT SECOND LEVEL Page Index: 32 Author: nickt Color: File Name: 90.Architectural Plans.20201106.pdf Landing elevations on each side of the door must be the same height. 2015 IBC 1010.1.5 Subject: PlanCheck Page: A-503 - ROOF DETAILS Page Index: 33 Author: nickt Color: File Name: 90.Architectural Plans.20201106.pdf Account for this bridge in the thermal envelope in COMcheck or reduce it. Subject: PlanCheck Page: A-503 - ROOF DETAILS Page Index: 33 Author: nickt Color: File Name: 90.Architectural Plans.20201106.pdf Account for this bridge in the thermal envelope in COMcheck or reduce it. Subject: PlanCheck Page: A-510 - DETAILS Page Index: 36 Author: nickt Color: File Name: 90.Architectural Plans.20201106.pdf If the continuous insulation above the CLT roof panel is what's counted for the thermal envelope insulation, you must revise COMcheck to note the roof areas with no insulation at the equipment platforms as depicted in this drawing. Subject: PlanCheck Page: E1.1 - ELECTICAL ONE-LINE DIAGRAM & SCHEDULES Page Index: 2 Author: nickt Color: File Name: 90.Electrical Plans.20201109.pdf 250.52 Grounding Electrodes. (B) Not Permitted for Use as Grounding electrodes. The following systems and materials shall not be used as grounding electrodes: (1)Metal underground gas piping systems 90.Electrical Plans.20201109.pdf (2) 2ND LEVEL 12'-0" C.2 EXTERIORINTERIOR 08 71 00.A19 05 41 00.A2 07 50 00 07 62 00 07 50 00 07 26 00.A4 07 21 00.B10 1 1/2" = 1'-0"4 SECTION DETAIL - RAINSCREEN Landing elevations on each side of the door must be the same height. 2015 IBC 1010.1.5 A 3" PR O P E R T Y L I N E 04 22 00.C3 07 62 00.A9 06 16 00.D11 03 21 00.A12 16'-0" 07 44 50 07 71 23.H4 07 61 13 07 84 00.A5 06 18 00.A8 05 40 00.B7 07 21 00.B10 5"4" 06 11 00.A9 9" / 1'-0" 9" / 1'-0" HOL D 1'- 5" EDGE OF EXT. SOFFIT FINISH 6 3 /4 " 3 3 /8 "07 62 00.A13 9" / 1'-0" 3" = 1'-0"1 WEST EDGE GUTTER DETAIL Account for this bridge in the thermal envelope in COMcheck or reduce it. 07 31 29.16.A6 07 13 00.A8 06 16 00.D10 07 21 00.B10 07 62 00.E5 07 71 23.H1 07 24 00.B6 07 13 00.A9 07 13 00.A10 06 18 00.A705 41 00.A14 06 11 00.A9 S P D D C 1 1/2" = 1'-0"2 ROOF SOFFIT DETAIL Account for this bridge in the thermal envelope in COMcheck or reduce it. T/ LOWER GLAZING10'-0" 2ND LEVEL 12'-0" CU R B Scale PROJECT DATE DRAWN B CHECKED A /2" = 1'-0" CT PENETRATION THRU NON-RATED WALL NO. DATE BY 1 09.25.18 MODIF. 2 11.28.18 MODIF. If the continuous insulation above the CLT roof panel is what's counted for the thermal envelope insulation, you must revise COMcheck to note the roof areas with no insulation at the equipment platforms as depicted in this drawing. T ELECTRICAL ONE-LINE DIAGRAM 400/3 100/3400/3 UTILITY TRANSFORMER PAD MOUNTED MAINS 800A, 120/208V, 3P, 4W 42kAlC NO SCALE NOTE: PROVIDE SHORT CIRCUIT BRACING TO MEET FAULT CURRENT LEVELS NOTED ON ONE-LINE AS "X AFC", WHERE X IS IN AMPS. SERIES RATED CIRCUIT BREAKER COMBINATIONS ACCEPTABLE; SUBMIT MANUFACTURER'S SERIES RATINGS WITH SHOP DRAWING REVIEW. 3[(4 #500 MCM AL) 4"C] (4#1/0 AL, #6 AL G)1-1/2"C SERVICE GROUNDING DETAIL NO SCALE N G INCOMING WATER SERVICE PIPE (3) 3/4"x10' DRIVEN GROUND RODS IF REQUIRED BY LOCAL AHJ BONDING JUMPER #6 TO TELEPHONE/TV CONCRETE- ENCASED ELECTRODE REQUIRED IN FOOTING/FOUNDATION PER NEC 250-50. MINIMUM 20' #4 REBAR ORMINIMUM 20' #4 BARE COPPER. MUST BE INSTALLED AT FOOTING INSPECTION. WATER METER BUILDING STEEL INCOMING GAS SERVICE PIPE (#3/0 CU G)3/4"C #6 CU M M M PROVIDE AMP OR EQUAL MAINS WITHINTEGRATED SWITCHES AND CTS TO FIT DIMENSIONS SHOWN ON PLANS. X20,300 AIC (3) 400A LPN FUSES (3) 400A LPN FUSES (3) 100A LPN FUSESX18,245 AIC REFERENCE CIVIL PLANS FOR TRANSFORMER LOCATION AND PRIMARY ROUTING. ELEVATOR RECALL DIAGRAM THE ELEVATOR SYSTEM INTO RECALL MODESHALL COMPLY WITH NFPA NO SCALE 250.52 Grounding Electrodes. (B) Not Permitted for Use as Grounding electrodes. The following systems and materials shall not be used as grounding electrodes: (1)Metal underground gas piping systems Subject: PlanCheck Page: E2.1 - LIGHTING SYSTEM PLAN Page Index: 4 Author: nickt Color: File Name: 90.Electrical Plans.20201109.pdf Provide an updated exterior lighting comcheck. Subject: PlanCheck Page: M2.0 - MAIN FLOOR & 2ND LEVEL HVAC PLAN SCALE 3/16" = 1'-0" Page Index: 3 Author: nickt Color: File Name: 90.Mechanical Plans.20201110.pdf Update mechanical comcheck. 90.Mechanical Plans.20201110.pdf (2) Subject: PlanCheck Page: M2.0 - MAIN FLOOR & 2ND LEVEL HVAC PLAN SCALE 3/16" = 1'-0" Page Index: 3 Author: nickt Color: File Name: 90.Mechanical Plans.20201110.pdf Intake air must be at least 10' from property lines. 2015 IMC 401.4 Subject: PlanCheck Page: P2.0 - MAIN FLOOR UNDERSLAB WASTE & VENT PLAN SCALE 3/16" = 1'-0" Page Index: 3 Author: nickt Color: File Name: 90.Plumbing Plans.20201110.pdf Only penetrations serving the exit enclosure may penetrate the exit enclosure. Remove all plumbing from the exit enclosure. 2015 IBC 1023.5 90.Plumbing Plans.20201110.pdf (2) Subject: PlanCheck Page: P2.1 - MAIN FLOOR & 2ND LEVEL WASTE & VENT PLAN SCALE 3/16" = 1'-0" Page Index: 4 Author: nickt Color: File Name: 90.Plumbing Plans.20201110.pdf Only penetrations serving the exit enclosure may penetrate the exit enclosure. Remove all plumbing from the exit enclosure. 2015 IBC 1023.5 1 2 3 4 5 6 A B 5.8 A.1 TENANT SPACE 'A' 100 1 2 3 4 5 6 A B C D E F G L C 5.8 A.1 F.9 E K FF F F A-36 B B A A A A A B B NORTH 2ND FLOOR LIG SCALE: 3/16" = 1'0" 1ST FLOOR LIGHTING SYSTEMS PLAN SCALE: 3/16" = 1'0" Provide an updated exterior lighting comcheck. SECOND FLOOR TENANT SPACE- 'B' 200 T RTU-4 1 H 2 9 Update mechanical comcheck. 3 5 5 2 (2 7 SD CO 11 RTU 4 Intake air must be at least 10' from property lines. 2015 IMC 401.4 UP DN EV. E.8 F.8 TENANT 'B' STAIR 105 9.1 ZED) 3" SD (PRESSURIZED) UP 3 a ca l , E l e c t r i c a l & L i g h t i n g D e s i g n S e r v i c e s tu r a l E n g i n e e r i n g C o n s u l t a n t s ce e w i t h L E E D ™ A c c r e d i t e d P r o f e s s i o n a l s Only penetrations serving the exit enclosure may penetrate the exit enclosure. Remove all plumbing from the exit enclosure. 2015 IBC 1023.5 9 10 A A.5 UP DN . E.8 F.8 TENANT 'B' STAIR 105 9.8 9.1 3" SD GUTTER UP & PVC DN 7 NZ 9 3" SD (PRESSURIZED) DN 3" SD DN TO NZ (POINT OF GRAVITY) 5" SD TO NZ 17 Only penetrations serving the exit enclosure may penetrate the exit enclosure. Remove all plumbing from the exit enclosure. 2015 IBC 1023.5