Subject: PlanCheck
Page: 1
Page Index: 1
Author: nickt
Color:
File Name: 30.Envelope ComCheck.20210209.pdf
Wall type D has R-11.4
continuous insulation per sheet
G-005. Revise COMcheck to
match.
30.Envelope ComCheck.20210209.pdf (3)
Subject: PlanCheck
Page: 1
Page Index: 1
Author: nickt
Color:
File Name: 30.Envelope ComCheck.20210209.pdf
Polyiso has an R-value of
approximately 5-5.6. Sheet
G-005 calls for 3" of polyiso at
Roof 1 (R 15-16.8) and 1.5" at
Roof 2 and 3 (R 7.5-8.4). Revise
COMcheck to match.
Subject: PlanCheck
Page: 2
Page Index: 2
Author: nickt
Color:
File Name: 30.Envelope ComCheck.20210209.pdf
Wall type C6 has R 17.1 of
continuous insulation per sheet
G-005. Revise Comcheck to
match.
Note: Please go through and
revise all assemblies in
Comcheck to match the plans. I
have stopped here but imagine
there are other inconsistencies.
Subject: PlanCheck
Page: 2
Page Index: 2
Author: nickt
Color:
File Name: 30.Mechanical ComCheck.20210209.pdf
There are 3 UH-2 unit heaters.
Revise mechanical comcheck.
30.Mechanical ComCheck.20210209.pdf (2)
Subject: PlanCheck
Page: 4
Page Index: 4
Author: nickt
Color:
File Name: 30.Mechanical ComCheck.20210209.pdf
The newly submitted exterior
lighting comcheck does not
match the electrical plans
submitted in the previous round
(have not received new electrical
lighting plans with this round).
Please coordinate.
Assembly Cavity
R-Value
Cont.
R-Value
Proposed
U-Factor
Budget U-
Factor(a)
Gross Area
or
Perimeter
1 wood shingle roof (type 1): Attic Roof with Wood Joists, [Bldg.
2 - Second Floor]
1492 0.0 23.5 0.040 0.021
2 gable roof (type 2): Insulation Entirely Above Deck, [Bldg. Use 1
und Floor]
1347 ---15.0 0.064 0.028
3 second level plaza deck floor (type 3): Insulation Entirely Above
, [Bldg. Use 1 - Ground Floor]
1200 ---16.4 0.058 0.028
(type 2A): Slab-On-Grade:Unheated, [Bldg. Use 1 - Ground
] (d)
275 ------0.730 0.520
TH
ior North Wall (type D): Steel-Framed, 16" o.c., [Bldg. Use 1 -
nd Floor]
603 0.0 17.8 0.048 0.064
(type U): Insulated Metal, Swinging, [Bldg. Use 1 - Ground Floor]21 ------0.660 0.370
(type T): Insulated Metal, Swinging, [Bldg. Use 1 - Ground Floor]21 ------0.660 0.370
ior North Wall (type D): Steel-Framed, 16" o.c., [Bldg. Use 2 -
nd Floor]
167 0.0 17.8 0.048 0.064
ior North Wall (type D): Concrete Block:8", Partially Grouted, Cells
y, Normal Density, Furring: Metal, [Bldg. Use 1 - Ground Floor]
35 0.0 11.4 0.069 0.071
ior North Wall (type D2): Concrete Block:8", Partially Grouted,
Empty, Normal Density, Furring: Metal, [Bldg. Use 1 - Ground
]
477 0.0 11.4 0.069 0.071
ct Title:
filename:
232 MAIN ST.
C:\Users\mwarnes\Modif Dropbox\Aspen\2016-005 232 E Main St\municipal\ComCheck\232 MAIN
ST 01-21-21_4.1.5.1.cck
02/09/21Report date:
101 ofPage
Wall type D has
R-11.4 continuous
insulation per sheet
G-005. Revise
COMcheck to match.
1/2018
29%
Owner/Agent:
232 East Main Street LLC
2001 N. Halsted St. Suite 304
Chicago, IL 60614
312-850-1680
Designer/Contractor:
Steve Coughlin
modif. architecture
1229 N North Branch St. Suite 206
Cihcgao, IL 60642
708-261-2611
steve.coughlin@modifarchitecture.c
om
equirements are implicitly enforced within interior lighting allowance calculations.
kage(s)
Floor Area
residential 4445
residential 1600
sembly Cavity
R-Value
Cont.
R-Value
Proposed
U-Factor
Budget U-
Factor(a)
Gross Area
or
Perimeter
Attic Roof with Wood Joists, [Bldg.1492 0.0 23.5 0.040 0.021
on Entirely Above Deck, [Bldg. Use 1 1347 ---15.0 0.064 0.028
oor (type 3): Insulation Entirely Above
]
1200 ---16.4 0.058 0.028
nheated, [Bldg. Use 1 - Ground 275 ------0.730 0.520
-Framed, 16" o.c., [Bldg. Use 1 -603 0.0 17.8 0.048 0.064
winging, [Bldg. Use 1 - Ground Floor]21 ------0.660 0.370
winging, [Bldg. Use 1 - Ground Floor]21 ------0.660 0.370
-Framed, 16" o.c., [Bldg. Use 2 -167 0.0 17.8 0.048 0.064
rete Block:8", Partially Grouted, Cells
Metal, [Bldg. Use 1 - Ground Floor]
35 0.0 11.4 0.069 0.071
ncrete Block:8", Partially Grouted,477 0.0 11.4 0.069 0.071
Polyiso has an R-value of
approximately 5-5.6. Sheet
G-005 calls for 3" of polyiso at
Roof 1 (R 15-16.8) and 1.5" at
Roof 2 and 3 (R 7.5-8.4).
Revise COMcheck to match.
Assembly Cavity
R-Value
Cont.
R-Value
Proposed
U-Factor
Budget U-
Factor(a)
Gross Area
or
Perimeter
Door (type R): Insulated Metal, Non-Swinging, [Bldg. Use 1 - Ground
Floor]
90 ------0.140 0.179
Exterior North Wall (type A5): Steel-Framed, 16" o.c., [Bldg. Use 1 -
Ground Floor]
26 0.0 11.4 0.070 0.064
EAST
Exterior East Wall (type C6): Steel-Framed, 16" o.c., [Bldg. Use 1 -
Ground Floor]
807 0.0 23.5 0.038 0.064
Window 4 around door C-1: Metal Frame with Thermal Break:Fixed,
Perf. Specs.: Product ID KAWNEER, SHGC 0.25, PF 0.14, [Bldg. Use 1
- Ground Floor] (c)
51 ------0.350 0.290
Window 5: Metal Frame with Thermal Break:Fixed, Perf. Specs.:
Product ID KAWNEER, SHGC 0.25, PF 0.14, [Bldg. Use 1 - Ground
Floor] (c)
102 ------0.350 0.290
Window 6: Metal Frame with Thermal Break:Fixed, Perf. Specs.:
Product ID KAWNEER, SHGC 0.25, PF 0.14, [Bldg. Use 1 - Ground
Floor] (c)
102 ------0.350 0.290
Window 7: Metal Frame with Thermal Break:Fixed, Perf. Specs.:
Product ID KAWNEER, SHGC 0.25, PF 0.14, [Bldg. Use 1 - Ground
Floor] (c)
113 ------0.350 0.290
Window 11: Metal Frame with Thermal Break:Fixed, Perf. Specs.:
Product ID KAWNEER, SHGC 0.22, [Bldg. Use 1 - Ground Floor] (c)
14 ------0.480 0.290
Door 4 (type C-1): Glass (> 50% glazing):Metal Frame, Entrance Door,
Perf. Specs.: Product ID KAWNEER, SHGC 0.22, PF 0.14, [Bldg. Use 1
61 ------0.290 0.770
Wall type C6 has R
17.1 of continuous
insulation per sheet
G-005. Revise
Comcheck to match.
Note: Please go
through and revise all
assemblies in
Comcheck to match
the plans. I have
stopped here but
imagine there are
other inconsistencies.
Quantity System Type & Description
Heating: 1 each - Central Furnace, Gas, Capacity = 72 kBtu/h
Proposed Efficiency = 82.00% Et, Required Efficiency: 80.00 % Et or 78% AFUE
Cooling: 1 each - Single Package DX Unit, Capacity = 41 kBtu/h, Air-Cooled Condenser, Air Economizer
Proposed Efficiency = 16.40 SEER, Required Efficiency: 14.00 SEER
Fan System: RTU-4 FAN -- Compliance (Brake HP method) : Passes
Fans:
RTU 4 FAN Supply, Multi-Zone VAV, 2000 CFM, 3.0 motor nameplate hp, 1.8 design brake hp (1.8 max. BHP), 80.0 fan efficiency
grade
1 RTU-4 (Multiple-Zone):
Heating: 1 each - Unit Heater (UH-1), Electric, Capacity = 3 kBtu/h
No minimum efficiency requirement applies
Fan System: None
3 UH-1 (Single Zone):
Heating: 1 each - Unit Heater (UH-2), Electric, Capacity = 5 kBtu/h
No minimum efficiency requirement applies
Fan System: None
1 UH-2 (Single Zone):
Electric Storage Water Heater, Capacity: 7 gallons
Proposed Efficiency: 2.00 SL, %/h (if > 12 kW), Required Efficiency: 4.16 SL, %/h (if > 12 kW)
1 WH-1:
Mechanical Compliance Statement
Compliance Statement: The proposed mechanical design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed mechanical systems have been
designed to meet the 2015 IECC requirements in COMcheck Version 4.1.5.1 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist.
Name - Title Signature Date
Bryan Urban 01/27/21
There are 3 UH-2 unit
heaters. Revise
mechanical comcheck.
Main entry 90 ft of door 30 Yes 2700
Total Tradable Watts (a) =
Total Allowed Watts =
Total Allowed Supplemental Watts (b) =
2700
2700
1300
(a) Wattage tradeoffs are only allowed between tradable areas/surfaces.
(b) A supplemental allowance equal to 1300 watts may be applied toward compliance of both non-tradable and tradable areas/surfaces.
Proposed Exterior Lighting Power
E
(C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
Main entry (90 ft of door width): Tradable Wattage
LED 1: FIXTURE A: Other:1 11 17 187
LED 2: FIXTURE B: Other:1 2 10 21
LED 3: FIXTURE H: Other:1 1 25 25
233Total Tradable Proposed Watts =
Exterior Lighting Compliance Statement
Compliance Statement: The proposed exterior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed exterior lighting systems have been
designed to meet the 2015 IECC requirements in COMcheck Version 4.1.5.1 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist.
Name - Title Signature Date
Exterior Lighting PASSES: Design 94% better than code
Project Title:
Data filename:
232 East Main Street
P:\Current Projects\18029.00 - 232 East Main Street\Calculations\COMcheck\Electrical
COMcheck.cck
01/27/21Report date:
72 ofPage
Bryan Urban 01/27/21
The newly submitted
exterior lighting
comcheck does not
match the electrical
plans submitted in the
previous round (have
not received new
electrical lighting plans
with this round).
Please coordinate.
Subject: PlanCheck
Page: 6
Page Index: 6
Author: nickt
Color:
File Name: 90.Architectural Plans.20210209.pdf
Provide a listed assembly for this
shaft wall. Print the full listing
instructions on the plans.
90.Architectural Plans.20210209.pdf (9)
Subject: PlanCheck
Page: 6
Page Index: 6
Author: nickt
Color:
File Name: 90.Architectural Plans.20210209.pdf
Wall type E4 appears to still be
in use as shown on A-100 for the
exit enclosure. It must be 1 hour
fire rated (2015 IBC 1023).
Provide a listed assembly and
print the full listing instructions
on the plans.
Subject: PlanCheck
Page: 13
Page Index: 13
Author: nickt
Color:
File Name: 90.Architectural Plans.20210209.pdf
Provide an accessible route to
the rooftop deck. 2015 IBC
1104.3.
Subject: PlanCheck
Page: 21
Page Index: 21
Author: nickt
Color:
File Name: 90.Architectural Plans.20210209.pdf
This section of roof must be 2
hour fire rated per G-008 and
2015 IBC 705.11 ex 4.2. Detail
this fire rating and reference a
listed assembly. Print the listed
assembly instructions in full on
the plans.
Subject: PlanCheck
Page: 24
Page Index: 24
Author: nickt
Color:
File Name: 90.Architectural Plans.20210209.pdf
This floor ceiling assembly must
be a 1 hour rated horizontal
assembly as it separates the exit
enclosure from the upstairs
tenant space/closet. Detail this
fire rating to show all continuity
as required by 2015 IBC 1023.2
and 711.2.3. All construction
supporting this horizontal
assembly must also be 1 hour
fire rated. Provide listed
assemblies on the plans as
necessary. The supplied
structural verification letter
provides 2 hour fire rating to CLT
panel in a vertical configuration
but not a horizontal one.
OVER CLT
OUS PANEL
R-17.1)
EL STUD @ MAX 16" O.C.
D
SIDING
IT
ULATION (R-37.5)
EL STUD @ MAX 16" O.C.
" GYPSUM BOARD
BT TENANT, SEE PLANS.
FIRE RATING -N/A
UL SYSTEM -N/A
2" POLYISO RIGID INSULATION (R-11.4)
STEEL STUD -1-1/2" 20 GA. STEEL STUD @ MAX 16" O.C.
GYPSUM BOARD -(1) LAYER 5/8" GYPSUM BOARD
NOTE: PORTIONS OF DRYWALL BT TENANT, SEE PLANS.
TYPE A6 -SHAFT WALL
FIRE RATING -1 HOUR
UL SYSTEM -N/A
GYPSUM BOARD -(1) LAYER 5/8'' TYPE X GYPSUM BOARD
STEEL STUD -2-1/2" 20 GA. STEEL STUD @ MAX 16" O.C.
GYPSUM BOARD -(1) LAYER 1" GYPSUM BOARD LINER PANEL
9
11
11
11
Provide a listed
assembly for this shaft
wall. Print the full
listing instructions on
the plans.
FLOOR & ROOF ASSEMBLIES:
SLAB ON GRADE
5" CAST IN PLACE CONCTRETE6" GRAVEL
SECOND LEVEL FLOOR SUBFLOOR -2 HOUR (ASTM E119)
CLT PANEL
SECOND FLOOR MEMBRANE ROOF -CLASS A
PVC ROOF MEMBRANE1/4" DENS DECK COVER BD.POLYISO INSUATION 1.5" MIN. (TAPERED)
VAPOR BARRIER OVER
CLT ROOF PANEL
GABLE ROOF -CLASS A
FIBER-REINFORCED CEMENTITIOUS PANELALUM. FURRING CHANNELS ATTACHED WITH S-5! CLIPSSTANDING SEAM METAL ROOF
UNDERLAYMENT3/4" PLYWOOD1.5" MIN. POLYISO INSULATON (THICKNESS VARIES AT
VALLEY) OVER CLT ROOF PANEL
WOOD SHINGLE ROOF -CLASS A
WOOD SHAKE SHINGLEUNDERLAYMENTMINERAL SURFACED CAP SHEET
3/4" PLYWOOD3" POLYISO INSULATION OVERCLT ROOF PANEL
TYPE C8
SIDING -3/4" RELCAIMED WOOD SIDING
FURRING -3/4" VERTICAL WOOD FURRING
APPLIED WATERPROOF MEMBRANE3" XPS RIGID INSULATION (R-15)CLT -6 3/4" CLT COLUMN
STEEL STUD -3 5/8" STEEL STUD @ MAX 16" O.C.GYPSUM BOARD -(1) LAYER 5/8" GYPSUM BOARD
NOTE: PART OF THIS WALL TYPE WILL NOT HAVE
FURRING AND DRYWALL. SEE PLANS.
TYPE F -INTERIOR WALL
FIRE RATING -2 HR MINIMUMUL SYSTEM -U905ELEVATOR SHAFT INFILL
7-5/8" CONCRETE MASONRY UNIT WALL
TYPE D -EXT. FURRING OVER CLT OR CMU
SIDING -3/4" RECLAIMED WOOD SIDING
FURRING -3/4" VERTICAL WOOD FURRING2" POLYISO RIGID INSULATION (R-11.4)APPLIED VAPOR BARRIER
CLT PANEL OR CMU
TYPE C6 -EXT. FURRING WALL OVER WOOD SUBSTRATE
SIDING -3/4" RELCAIMED WOOD SIDINGFURRING -3/4" VERTICAL WOOD FURRING3" POLYISO RIGID INSULATION (R-17.1)VAPOR BARRIER
TYPE 1
TYPE 2
TYPE 3
TYPE 1A
TYPE 2A
EE SHEET G-007 FOR REQUIRED FIRE RATED WALLS
TYPE G
FIRE RATING -0.5 HR MINIMUM
UL U419 or MEA 81-98-M
GYPSUM BOARD -(1) LAYER 5/8" GYPSUM BOARD
STEEL STUD -2 1/2" 20 GA. STEEL STUD @ MAX 24" O.C.
GYPSUM BOARD -(1) LAYER 5/8" GYPSUM BOARD
TYPE G2 -INT. FURRING
STEEL STUD -3 5/8" 20 GA. STEEL
STUD @ MAX 16" O.C.OVER WOOD STRUCTURE
5/8" GYP. BD. BY TENANT.
TYPE E3
FIRE RATING -1 HR MINIMUM
UL U419 or MEA 81-98-M
GYPSUM BOARD -(1) LAYER 5/8" GYPSUM BOARD
STEEL STUD -8" 20 GA. STEEL STUD @ MAX 16" O.C.GYPSUM BOARD -(1) LAYER 5/8" GYPSUM BOARD
SOUND INSULATION BETWEEN TENANTS
BEAMS AND GIRDERS
TYPE F1
FIRE RATING -1 HR MINIMUMUL SYSTEM -U305, 314
STAIR WALLS
LOAD BEARING WOOD STUD WALL
GYPSUM BOARD -(1) LAYER 5/8'' TYPE X GYPSUM BOARDWOOD STUD -6'' WOOD STUD @
MAX 24'' O.C.
GYPSUM BOARD -(1) LAYER 5/8'' TYPE X GYPSUM BOARD ROOF STUCTURE FIRE PROTECTION
IBC 2015 721.1(3)
21. BASE LAYER: -5/8" TYPE X GYPSUM WALLBOARD A
JOIST OR TRUSS 24" o.c. WITH 1 1/4" TYPE S OR TYPE W
FACE LAYER: -5/8" TYPE X GYPSUM WALLBOARD OR V ANGLES TO JOIST OR TRUSS THROUGH BASE LAYER W
DRYWALL SCREWS 12" o.c. AT JOINTS AND INTERMEDIA TYPE G DRYWALL SCREWS PLACED 2" BACK ON EITHER 12" o.c.
IBC 2015 721.1(1)
2-4.1 TWO LAYERS OF 5/8" TYPE X GYPSUM WALLBOAR
BRACKETS SPACED 24" ON CENTER. 0.018" THICK (NO.
1 5/8" DEEP BY 1" GALVANIZED STEEL RUNNER CHANNE TO AND ON EACH SIDE OF THE TOP BEAM FLANGE TO P FLANGE. THE CHANNEL RUNNERS ARE ATTACHED TO S
CONSTRUCTION WITH APPROVED FASTENERS SPACED BRACKETS ARE FORMED FROM MEMBERS IDENTICAL T THE BENT PORTION OF THE U-SHAPED BRACKET, THE F CUT OUT SO THAT 1 5/8" DEEP CORNER CHANNELS CAN
ATTACHMENT PARALLEL TO EACH SIDE OF THE LOWER
AS AN ALTERNATIVE, 0.021" THICK (NO. 24 CARBON SHE
AND CORNER ANGLES SHALL BE USED IN LIEU OF CHAN THE U-SHAPED BRACKETS SHALL NOT BE REQUIRED. E BRACKET WITH 1/2" - LONG NO. 8 SELF-DRILLING SCREW SHAPED BRACKET ARE ATTACHED TO THE RUNNERS W
DRILLING SCREW. THE COMPLETED STEEL FRAMING P BETWEEN THE INNER LAYER OF THE WALLBOARD AND STEEL BEAM, RESPECTIVELY. THE INNER LAYER OF WA
TOP RUNNERS AND BOTTOM CORNER CHANNELS OR C
NO. 6 SELF-DRILLING SCREWS SPACED 16" ON CENTER WALLBOARD IS APPLIED WITH 1 3/4" - LONG NO. 6 SELF- CENTER. THE BOTTOM CORNERS ARE REINFORCED W
TYPE F2
FIRE RATING -2 HR MINIMUMUL SYSTEM -U906STAIR WALLS
CONCRETE MASONRY UNIT WALL
5-5/8" CONCRETE MASONRY UNIT
STC: 49
DESIGN STC RATING
TYPE E4
GYPSUM BOARD -(1) LAYER
5/8" GYPSUM BOARDWOOD STUD -6" WOOD STUD @ MAX 16" O.C.
GYPSUM BOARD -(1) LAYER 5/8" GYPSUM BOARD
TYPE D2 -EXT. FURRING WALL OVER CMU
SIDING -5/16'' CEMENT BOARD SIDINGFURRING -3/4" VERTICAL WOOD FURRING
2" POLYISO RIGID INSULATION (R-11.4)
APPLIED VAPOR BARRIER OVERCMU WALL
11
11
11
AP
SMOKE SEALANT
2X WOOD BLOCKING
PLYWOOD DECK
9
9
9
9
9
9
9
11
Wall type E4 appears
to still be in use as
shown on A-100 for
the exit enclosure. It
must be 1 hour fire
rated (2015 IBC
1023). Provide a listed
assembly and print the
full listing instructions
on the plans.
DN
3
A-400
MECH. EQUIP., TYP.
SECOND FLOOR
TENANT SPACE-'B'
200
19'
-
0
5
/
8
"
13
'
-
9
"
25
'
-
0
5
/
8
"
27'-7 3/4"
A-413
1
1
A-311
A-4002
72
'
-
0
5
/
8
"
4
5
6
7
8
8.5
9
10
D.S.
D
24
'
-
9
1
/
8
"
TENANT 'B' ELEV.
1
1
A-504
E
C6
D.S. AND SPLASH BLOCK
E2
ACCESS PANEL
1 1/2" MIN. THICK
INSULATION AT ROOF
DRAINS
1/4'' : 1'-0''
1/4'' : 1'-0''
7'' MAX. THICK
INSULATION
1/4'' : 1'-0''
ROOF OVERHANG
ABOVE
PVC ROOF MEMBRANE
ROOF OVERHANG
OF CORTINA LODGE
FUTURE CLOSET
202
F
M
6'-6 3/4"3'-0"6'-6 3/4"
ACCESS
PANEL
ACCESS
PANEL
42" HIGH
GUARDRAIL
42" HIGH
GUARDRAIL
ACCESSPANEL BY
TENANT, TYP.
ACCESS
PANEL
E
4'-0"
TENANT 'B' STAIR
201
FUTURE ELEV. LOBBY
203 TWO-WAY
COMMUNICATIONSYSTEM
WALLS BY
TENANT, TYP.
DOOR BY TENANT,
TYP.
"
4'-
2
3
/
4
"
11
'
-
1
1
/
8
"
2'-
2
1
/
8
"
9'-
2
3
/
8
"
4'-
0
7
/
8
"
7'-
3
3
/
4
"
5'-
1
1
3
/
4
"
3'-
9
3
/
4
"
5'-
0
7
/
8
"
4'-
1
1
1
/
8
"
5.8
7.5
R.O.
8'-4"
6.7
N
D.S. AND SPLASH BLOCK
D.S. AND
SPLASH BLOCK
9
14'-2 3/8"14'-2 3/8"
6'-2
1
/
2
"
CRICKET PER MANUF.
RECOMMENDATIONS, TYP.
RTU 1600 LBS.
RTU 2
925 LBS.
RTU 3
468 LBS.RTU 4510 LBS.
ROOF
WALKWAY
PADS, TYP.
ROOF DRAIN, TYP.
ALIGN
DRYWALL THIS SIDE ONLY
1
A-502
C4
F
D
10
2'x2' PAVERS
11
6'-0"
6'-0
"
Provide an accessible
route to the rooftop
deck. 2015 IBC
1104.3.
1
A-300
9
12
9
12
9
12
9
12
A-503
2
A-503
1
A B C EC.2
A-501
4 Sim
1
A-510
7
A-503
23
'
-
8
5
/
1
6
"
23
'
-
8
5
/
1
6
"
This section of roof
must be 2 hour fire
rated per G-008 and
2015 IBC 705.11 ex
4.2. Detail this fire
rating and reference a
listed assembly. Print
the listed assembly
instructions in full on
the plans.
CEDAR SHAKE SHINGLES
OVER GABLED ROOF, ROOF
AT (9/12) SLOPE
RECLAIMED WOOD
FACIA
GUTTER
A-501
2 Sim
A-501
7
6 7
/
8
"
7'-
4
"
HA
N
D
R
A
I
L
3'-
6
"
MIN
.
H
E
A
D
C
L
E
A
R
A
N
C
E
6'-
8
"
A-400
6
A-400
5
HANDRAIL
BY TENANT
-2'-1 1/8"
A-502
V
1/4" = 1'-0"3 BUILDING SECTION
9
This floor ceiling assembly must
be a 1 hour rated horizontal
assembly as it separates the exit
enclosure from the upstairs
tenant space/closet. Detail this
fire rating to show all continuity
as required by 2015 IBC 1023.2
and 711.2.3. All construction
supporting this horizontal
assembly must also be 1 hour
fire rated. Provide listed
assemblies on the plans as
necessary. The supplied
structural verification letter
provides 2 hour fire rating to
CLT panel in a vertical
configuration but not a
horizontal one.
Subject: PlanCheck
Page: 31
Page Index: 31
Author: nickt
Color:
File Name: 90.Architectural Plans.20210209.pdf
Previous comment not
addressed:
Account for these thermal
bridges in COMcheck or
eliminate them with a different
insulation design.
You have entered the slab on
grade as having no insulation in
COMcheck, which is correct,
however there are portions of
the wall above the slab that have
zero insulation as shown in
these details. Please revise
comcheck.
Subject: PlanCheck
Page: 32
Page Index: 32
Author: nickt
Color:
File Name: 90.Architectural Plans.20210209.pdf
This detail shows the fire barrier
of the exit enclosure extending
through the CLT roof panels.
This does not appear to be
coordinated with the structural
plans. Please coordinate and
ensure fire barrier continuity as
required by 2015 IBC 707.5.
Subject: PlanCheck
Page: 32
Page Index: 32
Author: nickt
Color:
File Name: 90.Architectural Plans.20210209.pdf
Provide a thermal barrier over
the exposed foam plastic
insulation. 2015 IBC 2603.4
Subject: PlanCheck
Page: 33
Page Index: 33
Author: nickt
Color:
File Name: 90.Architectural Plans.20210209.pdf
Provide a thermal barrier over
exposed polyiso foam plastic.
2015 IBC 2603.4
Subject: PlanCheck
Page: 1
Page Index: 1
Author: nickt
Color:
File Name: 90.Electrical Plans.20210209.pdf
Submit complete sets of each
planset. We will not swap
sheets.
90.Electrical Plans.20210209.pdf (1)
SUB FLR. TENANT 'A' 7903.700"
G
05 40 00.B6
07 26 00.A4
09 29 00.D1
05 41 00.A5
32 13 00.B9
03 31 00.M7
03 21 00.A12
07 51 13.A3
03 31 00.J1
07 13 00.A3
07 11 00
1'-5"
5/8"4 7/8"5 1/2"3"1 3/4"1"1/4"
07 44 50
05 40 00.B3
0'-8"
BY TENANT
ALIGN
6"1'-6"
7"
07 62 00.A9
1007 22 00.A4 11
SUB FLR. TENANT 'A' 7903.700"
F.8
05 41 00.A5
03 21 00.A1203 21 00.A12
03 31 00.M7
03 31 00.J1
07 13 00.A3
07 11 00
3 1/2"3"3/4"3/4"
07 26 00.A4
06 22 00.A4
06 22 00.A11
07 51 13.A4
07 62 00.A9
10
07 22 00.A4 11
SUB FLR. TENANT 'A' 7903.700"
2
07 95 13.B8
32 13 00.B903 31 00.J1
03 21 00.A12
07 13 00.A3
ADA COMPLIANT THRESHOLD
10
SUB FLR. TENANT 'A' 7903.700"
A
07 13 00.A3
03 31 00.J1
07 21 00.E3
ADJ
A
C
E
N
T
B
U
I
L
D
I
N
G
(
N
.
I
.
C
.
)
6 TO 14 INCHESVARIES
NON-COMPRESSIBLE RIGID INSULATION LAYERS FOR ONE-SIDED DAMPROOFING SUPPORT AND INFILL BETWEEN NEW AND EXISTING FOUNDATION WALLS
FOUNDATION DAMPROOFING
SHEET METAL GUTTER SLOPED TO ALLEY
10
11
SUB FLR. TENANT 'A' 7903.700"
9
SUB FLR. TENANT 'B' 7902.70-1'-0"
SUB FLR. MECH. ROOM 7901.53-2'-2"
07 26 00.A4
03 31 00.J1
07 13 00.A3
32 13 00.B9 07 95 13.B8
-2'-0"
-2'-8"
07 62 00.A9
07 62 00.A0
10
10
2'-0"
11
07 22 00.A411
09 29 00.D1
05 41 00.A0
07 22 00.A4
SUB FLR. TENANT 'A' 7903.700"
A
07 95 13.B4
06 22 00.A11
06 16 00.D1007 26 00.A6
04 22 00.A16
05 41 00.A8
HOLD1'-5"
1'-2"
2"+/-7 5/8"6"3/4"3/4"
ADJ
A
C
E
N
T
B
U
I
L
D
I
N
G
(
N
.
I
.
C
.
)
6"
07 62 00.A9 10
SUB FLR. TENANT 'A' 7903.700"
G
07 11 00
03 31 00.M7
07 62 00.A9
07 26 00.A4
06 22 00.A11
32 13 00.B9
07 95 13.B8
07 22 00.A4
07 26 00.A4
5 1/2"5 1/2"3"1 3/4"1"3/8"
HOLD
1'-5"
07 51 13.A3
05 40 00.B307 44 50
CLT PANEL
07 62 00.A9
10
11
Scale
PROJECT NUMBER
DATE
DRAWN BY
CHECKED BY
modif.
modif.
1 1/2" = 1’−0"
2/1
0
/
2
0
2
1
1
:
3
3
:
3
0
P
M
A−501
2016−005
02.09.21
WALL DETAILSAT GROUNDLEVEL
CO
M
M
E
R
C
I
A
L
DE
V
E
L
O
P
M
E
N
T
23
2
E
.
M
A
I
N
S
T
.
A
S
P
E
N
,
C
O
1 1/2" = 1'-0"1 SECTION DETAIL - EAST ENTRANCE
1 1/2" = 1'-0"2 SECTION DETAIL - EAST PILASTER 1 1/2" = 1'-0"3 SECTION DETAIL - SOUTH ENTRANCE
1 1/2" = 1'-0"4 SECTION DETAIL - WEST WALL
1 1/2" = 1'-0"7 SECTION DETAIL - NORTH WALL
KEYNOTE LEGEND
03 21 00.A12 STEEL REINFORCEMENT, SEESTRUC. DWGS.
03 31 00.J1 5" SLAB-ON-GRADE OVERENGINEERED FILL, SEESTRUC. DWGS.03 31 00.M7 CONC. FOUNDATION WALL,SEE STRUC. DWGS.04 22 00.A16 8" X 8" X 16" CMU - 2 CORE05 40 00.B3 VERTICAL HAT PROFILE05 40 00.B6 HORIZ. FURRING05 41 00.A0 1-1/2" METAL STUD05 41 00.A5 3-5/8" METAL FRAMING05 41 00.A8 6" METAL FRAMING06 16 00.D10 3/4" EXTERIOR GRADEPLYWOOD06 22 00.A4 1X4 VERTICAL FURRING STRIP06 22 00.A11 FIRE TREATED RECLAIMEDWOOD SIDING07 11 00 BITUMINOUS DAMPPROOFING07 13 00.A3 6 MIL. POLYETHYLENE07 21 00.B10 RIGID INSULATION07 21 00.E3 CLOSED CELL SPRAY FOAMINSULATION
07 22 00.A4 POLYISOCYANURATEINSULATION BOARD07 26 00.A4 VAPOR BARRIER07 26 00.A6 WEATHER BARRIER07 44 50 FIBER-REINFORCEDCEMENTITIOUS PANEL07 51 13.A3 FULLY ADHERED CONTINUOUSASPHALT FLASHING07 51 13.A4 FLASHING TAPE07 62 00.A0 METAL FLASHING07 62 00.A9 FLASHING07 95 13.B4 1/2" EXPANSION JOINT07 95 13.B8 FIBER EXPANSION JOINT WITHBACKER ROD ANDELASTOMERIC SEALANT09 29 00.D1 5/8" GYPSUM WALLBOARD32 13 00.B9 EXTERIOR SIDEWALK, SEECIVIL DWGS.
1 1/2" = 1'-0"5 SECTION DETAIL - WEST WING WALL
1 1/2" = 1'-0"6 SECTION DETAIL - EAST WING WALL
9
NO.
DATE
BY
REVISION
3
05.24.19
MODIF.
PERMIT DOCUMENT REVISIONS #1
4
08.2.19
MODIF.
PERMIT DOCUMENT REVISION #2
5
11.12.19
MODIF.
PERMIT DOCUMENT REVISION #3
6
12.18.19
MODIF.
PERMIT DOCUMENT REVISION #4
7
3.27.20
MODIF.
ISSUE FOR CONSTRUCTION
8
3.27.20
MODIF.
CONSTRUCTION DOCUMENT
REVISION #5
9
10.02.20
MODIF.
CONSTRUCTION DOCUMENT
REVISION #6
10
11.05.20
MODIF.
CONSTRUCTION DOCUMENT
REVISION #7
11
02.09.21
MODIF.
PERMIT DOCUMENT REVISION #8
Previous comment not addressed:
Account for these thermalbridges in COMcheck oreliminate them with a differentinsulation design.
You have entered the slab ongrade as having no insulation inCOMcheck, which is correct,however there are portions of thewall above the slab that have zeroinsulation as shown in thesedetails. Please revise comcheck.
G
5/8"
4 7/8"5 1/2"3"1 3/4"
1"
1
09 29 00.D1
1'-5"
BY TENANT
CLT PANEL
1/2
"
08 71 00.B14
05 41 00.A2
07 62 00
07 84 00.A2
11
9
05 05 23.E2
07 61 00
06 11 00.A9
07 62 00.A0
07 22 00.A4
07 26 00.A4
04 22 00.A16
04 22 00.C3
11
F.8
6"
T/ LOWER GLAZING10'-0"
07 95 13.E1
06 11 00.A9
6"
5"
1 1/2"
E.8
CLT ROOF PANEL
1 HOUR FIRE RATED
WALL UL 419
FIREPROOF SEALANT
DEEP LEG
DEFLECTION TRACK
5/8" GYP. BD.3 5/8" METAL STUD 11
STOREFRONT AND FOLDING
DOOR SUPPORT
07 46 26
1 1/2" = 1'-0"4 SECTION DETAIL - RAINSCREEN
FIXED WINDOW
1 1/2" = 1'-0"3 SECTION DETAIL - WINDOW HEAD AT EAST GLAZING
1 1/2" = 1'-0"5 SOUTH ENTRANCE SEALED ACM ENCLOSURE
1 1/2" = 1'-0"10 FIRE RATED WALL HEAD DETAIL
11
FOLDING DOORS
This detail shows the
fire barrier of the exit
enclosure extending
through the CLT roof
panels. This does not
appear to be
coordinated with the
structural plans.
Please coordinate and
ensure fire barrier
continuity as required
by 2015 IBC 707.5.
2"
3 1/8"
SEE STRUCTURAL
DWGS. FOR ATTACHMENT
DETAIL
11
2'-
0
"
07 22 00.A4
PARAPET WALL
Provide a thermal
barrier over the
exposed foam plastic
insulation. 2015 IBC
2603.4
A
3"
PR
O
P
E
R
T
Y
L
I
N
E
04 22 00.C3
07 62 00.A9
06 16 00.D11
03 21 00.A12
16'-0"
07 44 50
07 71 23.H4
07 61 13
07 84 00.A5
06 18 00.A8
05 40 00.B7
07 21 00.B10
5"4"06 11 00.A9
9" / 1'-0"
9" / 1'-0"
HOLD
1'-5 3/8"
EDGE OF EXT.SOFFIT FINISH
7 1/8"
3 3/8"07 62 00.A13
2'-0"
2"
1'-4 3/4"
1'-4 7/8"
11
07 22 00.A4
C
07 22 00.A4
06 16 00.D8
07 44 50
05 40 00.B8 07 84 00.A5
07 61 13
06 18 00.A7
07 62 00.A15
3'' D.S., BEYOND
8 5/8" / 1'-0"
8 1/2" / 1'-0"
LINE OF BOTTOM OF FASCIA
4 1/2"
2 5/8"
5 1/2"
3"3/4"
5/8"
1'-5"
06 16 00.D8
09 29 00.D17
06 22 00.A13
07 53 00.A7
06 11 00.A10
RIGID INSULATION INFILL BELOW CRICKET
TAPERED CRIKET DECKING @ LOW POINT
1'-2"
3 1/2"8"8"
G
09 29 00.D1
05 41 00.A12
07 22 00.A4
07 26 00.A4
05 40 00.B3
07 44 50
07 61 13
06 18 00.A7
07 84 00.A5
05 40 00.B7
06 16 00.D8
07 71 23.H4
07 62 00.A9
BY TENANT
05 40 00.B6
4"
5"
1'-0 5/8"
9" / 1'-0"
9" / 1'-0"
HOLD1'-5 3/8"
EDGE OF EXT.SOFFIT FINISH
7 1/8"
4 3/4"
11
F.8
07 31 29.16.A6
07 13 00.A8
06 16 00.D10
07 21 00.B10
07 62 00.E5
07 71 23.H1
07 24 00.B6
07 13 00.A9
07 13 00.A10
06 18 00.A705 41 00.A14
06 11 00.A9
2'-0"
2"
11
07 22 00.A4
T/GABLE 0328'-6 3/4"
T/GABLE 0226'-6 7/8"
1
07 44 50
05 40 00.B3
07 51 13.A4
06 11 00.A9
07 46 23.A1
06 18 00.A7
GLU-LAM BEAM
06 16 00.D11
05 41 00.A5
05 41 00.A8
1/4"07 62 00.A14
07 84 00.A5 05 40 00.B7
05 05 23.A11
07 21 00.B10
05 05 23.A12
HOT AIR WELD, 1 1/2"
07 92 00.A6
09 29 00.D17
06 18 00.A7
RTU
SUPPLY/ RETURN DUCT
07 21 00.B10
07 92 00.A4
07 53 00.A4
SHEET METAL CURB
11
07 95 13.A6
USE ONE CONTINUOUS SHEET OF REINFORCED THERMOPLASTIC MEMBRANE TO WRAP AROUND CURB
INSTALL OUTSIDE CORNERS PER DETAIL 7/ A-503
05 05 23.A12
PRE-MOLDED OUTSIDE CORNER
07 53 00.A4
PRE-MOLDED OUTSIDE CORNER BEFORE INSTALLATION
2ND LEVEL12'-0"
A
HOT AIR WELD, 1 1/2"
05 05 23.A12
07 40 00.B1
07 92 00.A10
CONTINUOUS WATERBLOCK
05 05 23.A11
07 84 00.A3
05 05 23.A11CONTINUOUS WATERBLOCK
09 29 00.D17
4
06 11 00.A2
07 44 50
07 31 29.16.A6
07 13 00.A8
07 13 00.A10
07 13 00.A9
06 16 00.D10
07 21 00.B10
06 18 00.A7
06 16 00.D8
07 61 13
07 62 00.A14
1/4"
07 21 00.B10
07 92 00.A6
HOT AIR WELD, 1 1/2" MIN. ALONG ENTIRE MEMBRANE EDGE
06 18 00.A7
MIN.
1 1/
2
"
B/GABLE16'-1 1/2"
1
1/4"
07 46 23.A1
06 16 00.D11
06 18 00.A7
07 44 50
05 40 00.B3
07 51 13.A4
06 11 00.A9
GLU-LAM BEAM
07 62 00.A14
07 84 00.A5 05 40 00.B7
Scale
PROJE
DATE
DRAW
CHECK
R
3" = 1'-0"1 WEST EDGE GUTTER DETAIL
1 1/2" = 1'-0"2 VALLEY GUTTER DETAIL - GABLE ROOF 1 1/2" = 1'-0"3 EAST EDGE GUTTER DETAIL
KEYNOTE LEGEND
03 21 00.A12 STEEL REINFORCEMENT, SEESTRUC. DWGS.
04 22 00.C3 8" X 8" BOND BEAM
05 05 23.A11 FASTENER @ 12" MAX O.C.
05 05 23.A12 FASTENER AND SEAM FASTENINGPLATE @ 12" MAX O.C.05 40 00.B3 VERTICAL HAT PROFILE05 40 00.B6 HORIZ. FURRING05 40 00.B7 HORIZ. Z CHANNEL05 40 00.B8 (2) LAYERS 1" EXTRUDEDCHANNELS (Z AND HAT)
05 41 00.A5 3-5/8" METAL FRAMING
05 41 00.A8 6" METAL FRAMING
05 41 00.A12 SLOTTED TRACK
05 41 00.A14 METAL FRAMING
06 11 00.A2 WOOD BLOCKING AS REQUIRED
06 11 00.A9 F.T. WOOD BLOCKING
06 11 00.A10 3" TREATED BLOCKING
06 16 00.D8 F.R. 5/8" PLYWOOD
06 16 00.D10 3/4" EXTERIOR GRADE PLYWOOD
06 16 00.D11 F.R. 3/4" PLYWOOD
06 18 00.A7 5 1/2" CLT
06 18 00.A8 6 7/8" CLT
06 22 00.A13 3/4" RECLAIMED WOOD SOFFIT WITHMESH VENTS @ TOP AND BOTTOMBETWEEN SIDING JOINTS
07 13 00.A8 UNDERLAYMENT
07 13 00.A9 ICE AND WATER SHIELD
07 13 00.A10 MINERAL-SURFACED CAP SHEET
07 21 00.B10 RIGID INSULATION
07 22 00.A4 POLYISOCYANURATE INSULATIONBOARD07 24 00.B6 1" ROOF SOFFIT07 26 00.A4 VAPOR BARRIER07 31 29.16.A6 FIRE-RETARDANT-TREATED CEDARROOF SHINGLES
07 40 00.B1 COUNTERFLASHING
07 44 50 FIBER-REINFORCED CEMENTITIOUSPANEL07 46 23.A1 RECLAIMED WOOD SOFFIT07 51 13.A4 FLASHING TAPE07 53 00.A4 THERMOPLASTIC REINFORCEDMEMBRANE07 53 00.A7 TPO MEMBRANE, EXTEND UP EACHSIDE MIN. 18" VERTICALLY FROMCRICKET
07 61 13 STANDING SEAM METAL ROOF
07 62 00.A9 FLASHING
07 62 00.A13 COPING FLASHING
07 62 00.A14 SHEET METAL FLASHING
07 62 00.A15 COUNTERFLASHING07 62 00.E5 FASCIA BOARD
07 71 23.H1 GUTTER07 71 23.H4 SHEET METAL RECTANGULARGUTTER07 84 00.A3 TERMINATION BAR07 84 00.A5 S-5! CLIP ATTACHED TO METALROOF
07 92 00.A4 BONDING ADHESIVE07 92 00.A6 CUT EDGE SEALANT07 92 00.A10 CONTINUOUS BEAD OF AP SEALANT07 95 13.A6 T-JOINT COVER09 29 00.D1 5/8" GYPSUM WALLBOARD09 29 00.D17 1/4" DENSDECK
1 1/2" = 1'-0"12 ROOF SOFFIT DETAIL
1 1/2" = 1'-0"9 SECTION THRU MAIN ST. ENTRY
N.T.S4ROOF CURB DETAIL
N.T.S.10 ROOF CURB CORNER DETAIL 1
N.T.S.11 ROOF CURB CORNER DETAIL 2
3" = 1'-0"8 PARAPET WALL AT PAVERS DETAIL
1 1/2" = 1'-0"7 STANDING SEAM DETAIL AT ROOF
N.T.S.5 DRAIN DETAIL AT ROOF
1 1/2" = 1'-0"6 SECTION THRU VALLEY
NO.
DATE
BY
REVISION
3
05.24.19
MODIF.
PERMIT DOCUMENT REVISIONS #1
Provide a thermalbarrier over exposedpolyiso foam plastic.2015 IBC 2603.4
Submit complete sets of each planset.
We will not swap sheets.
Subject: PlanCheck
Page: [2] 18029 - M1(D-48)-M1.1
Page Index: 2
Author: nickt
Color:
File Name: 90.Mechanical Plans.20210209.pdf
Where is supply fan 1? It
appears to have been removed
from the plans. Provide outside
air to all spaces including
mechanical room as required by
2015 IMC ch 4.
90.Mechanical Plans.20210209.pdf (1)
ww
w
.
a
e
c
-
v
a
i
l
.
c
o
m
a
PO
B
o
x
8
4
8
9
,
4
0
8
0
1
U
S
H
w
y
6
&
2
4
,
S
t
e
2
1
4
,
A
v
o
n
,
C
o
l
o
r
a
d
o
,
8
1
6
2
0
Me
c
h
a
n
i
c
a
l
,
E
l
e
c
t
r
i
c
a
l
&
L
i
g
h
t
i
n
g
D
e
s
i
g
n
S
e
r
v
i
c
e
s
Arc
h
i
t
e
c
t
u
r
a
l
E
n
g
i
n
e
e
r
i
n
g
C
o
n
s
u
l
t
a
n
t
s
Te
l
e
p
h
o
n
e
:
9
7
0
-
7
4
8
-
8
5
2
0
ce
Drawn By:Checked By:
DATE:ISSUE:
AEC PROJECT #:
23
2
E
.
M
A
I
N
S
T
.
CO
R
E
&
S
H
E
L
L
AS
P
E
N
,
C
O
8
1
6
1
1
18029.00
An
O
f
f
i
c
e
w
i
t
h
L
E
E
D
™
A
c
c
r
e
d
i
t
e
d
P
r
o
f
e
s
s
i
o
n
a
l
s
12-13-19 PERMIT COMMENTS R2
01-09-20 PERMIT COMMENTS R4
03-27-20 ISSU FOR CONST.
CD REVISION09-29-20
PLUMBING UPDATES10-08-20
PERMIT COMMENTS02-03-21
BLU TOC
MECHANICAL
SCHEDULES
Where is supply fan1? It appears to have
been removed fromthe plans. Provideoutside air to all
spaces includingmechanical room asrequired by 2015 IMC
ch 4.