Loading...
HomeMy WebLinkAboutFile Documents.232 E Main St.0132.2018 (86).ACBK0132-2018-ACBK_BuildingComments_1 Page: 1 File Name: 2015 IECC REMP Calculations.232 E. Main St.2018.09.pdf Subject: PlanCheck Author: nickt Color: Revise snowmelt plan to show the electric snowmelt. Note: roof and gutter deicing systems extending less than 6' from the exterior wall are exempt from REMP. Deicing extending more than 6' from the exterior wall are counted in REMP. Ordinance 11, 2011. 2015 IECC REMP Calculations.232 E. Main St.2018.09.pdf (1) Page: 1-COVER 1-COVER COVER SHEET COVER SHEET File Name: Architectural.232 E. Main St.2018.11.pdf Subject: PlanCheck Author: nickt Color: Provide a line grade form. Architectural.232 E. Main St.2018.11.pdf (36) Page: A-030 SNOWMELT PLANS File Name: Architectural.232 E. Main St.2018.11.pdf Subject: PlanCheck Author: nickt Color: Coordinate snowmelt square footages between architecturals and mechanicals (currently they are different). Round snowmelt areas to nearest whole number. Revise CREMP worksheet as necessary to match. Page: A-030 SNOWMELT PLANS File Name: Architectural.232 E. Main St.2018.11.pdf Subject: PlanCheck Author: nickt Color: Up to a 48" wide portion of accessible routes are exempt from REMP per Ordinance 40, 2016. Page: A-100 PROPOSED MAIN FLOOR PLAN File Name: Architectural.232 E. Main St.2018.11.pdf Subject: PlanCheck Author: nickt Color: Provide the scale of your drawings. PROJECT ADDRESS: Parcel ID #: Permit Number: CONTACT INFORMATION : Owner: Name:City: CHICAG Address:State: IL Email:Zip Code: 60614 Phone: Cell Phone: 312-850-1 Owner's Representative : Name:City: CHICAG Address:State: IL Email:Zip Code: 60607 Phone: Cell Phone: 312-714-8 A.COMMERCIAL RENEWABLE ENERGY MITIGATION PROGRAM Sheets showing snowmelt, pool, spa, and solar/GSHP information: Do you have snowmelt or a spa that has been exempted by the buiding official? Hydro Snowmelt Electric Snowmelt Pool Spa Existing 0.00 sqft 0.00 sqft 0.00 sqft 0.00 sqft To be Demoed 0.00 sqft 0.00 sqft 0.00 sqft 0.00 sqft Existing to Remain 0.00 sqft 0.00 sqft 0.00 sqft 0.00 sqft New (non-exempt)450.00 sqft 378.00 sqft New (exempt) Total New 450.00 sqft 378.00 sqft 0.00 sqft 0.00 sqft Total on site 450.00 sqft 378.00 sqft 0.00 sqft 0.00 sqft Total Snowmelt on site Boiler Efficiency 95.0%100%75.0% 75.0% Mitigation Payment -$ -$ Total Payment for Mitigation:$51,101.05 B.ON-SITE RENEWABLE CREDITS Supplemental System REMP Credit Use PV Worksheet Photovoltaic System -$ Use Thermal Worksheet Hot Water Panels -$ Use GSHP Cert Ground Source Heat Pump -$ Other Approved System -$ Total Mitigation Credits:-$ 2015 IECC COMMERCIAL RENEWABLE ENERGY MITIGATION PROGRAM CITY OF ASPEN VERSION 11.3 UPDATED DECEMBER 13, 2017 232 E. MAIN ST. 273707320008 1200 W. LAKE ST. SUITE 200 232 EAST MAIN STREET LLC 2001 N. HALSTED ST. SUITE 304 JRICHMAN@MDEVCO.COM 312-850-1680 BRAD HRIBAR - CENTAUR 312-714-8519 BHRIBAR@CENTAURCO.COM 828.00 sqft $51,101.05 A-030 Yes (enter sqft below on the exempt row)No Revise snowmelt plan to show the electric snowmelt. Note: roof and gutter deicing systems extending less than 6' from the exterior wall are exempt from REMP. Deicing extending more than 6' from the exterior wall are counted in REMP. Ordinance 11, 2011. T Provide a line grade form. 1,380 2,0001,380 2,000 ALLEY HIST O R I C C O R T I N A L O D G E PROPERTY LINE 418.17 SF SNOW MELT SYSTEM TO ALLEVIATE SNOW SHEDDING BOTH IN THE ROW AND ON ANY ADJACENT LOTS SNOW CLEAT 9" / 1'-0"9" / 1'-0" 9" / 1'-0"9" / 1'-0" TRANSFORMER 9" / 1'-0"4 1/2" / 1'-0" 9" / 1'-0"9" / 1'-0" ALLEY PROPOSED 2 STORY BUILDING MO N A R C H S T . MAIN ST. HIST O R I C C O R T I N A L O D G E NEW S T R E E T PAR K I N G NEW S T R E E T PAR K I N G NEW S T R E E T PAR K I N G PROPERTY LINE CORTINALODGE BALCONY BENCH DETECTABLEWARNING DETECTABLEWARNING HISTORIC CORTINA LODGE STONE CHIMNEY DRAIN ANY WATER THAT ACCUMULATES VIA NATURAL GRADE TO ALLEY NEW S T R E E T PAR K I N G CITY OF ASPEN APPROVEDBIKE RACK FENCED EXTERIOR TRASH AREA & UTILITY OVERHANG ABOVE SLIDING DOOR 10'-0 " 13'-0" 5'-3 " 4'-9" 5'-0" AWNING. TYP. TRANSFORMER 7'-2 5/8" 59.13SF SNOW MELT AT ENTRY DOOR 81.78SF SNOW MELT AT MAIN ENTRANCE 248.79SF SNOW MELT AT MECH. RM DOOR, AND TRASH AND UTILITY BACK DOOR 60.44SF SNOW MELT AT MAIN ENTRANCE 1/8" = 1'-0"1 PROPOSED SNOWMELT ROOF PLAN 1/8" = 1'-0"2 SNOWMELT SITE PLAN Coordinate snowmeltsquare footagesbetween architecturalsand mechanicals(currently they aredifferent). Roundsnowmelt areas tonearest wholenumber. ReviseCREMP worksheet asnecessary to match. ROPOSED 2 STORY BUILDING 81.78SF SNOW MELT AT MAIN ENTRANCE Up to a 48" wide portion of accessible routes are exempt from REMP per Ordinance 40, 2016. 11 ' - 4 " 17' - 9 1 / 2 " 5'-0" C ADA PUSHBUTTON Scale PROJECT NUMBER DATE DRAWN BY CHECKED BY modif. modif. As indicated 11 / 1 2 / 2 0 1 8 1 0 : 1 2 : 0 1 A M A−100 2016−005 11.12.18 PROPOSED MAIN FLOOR PLAN NO. DATE BY 1 05.09.18 MODIF. SCHEMATI 2 07.13.18 MODIF. DESIGN DE 3 09.6.18 MODIF. 90% PERM 4 9.25.18 MODIF. PERMIT SE Provide the scale of your drawings. Page: A-100 PROPOSED MAIN FLOOR PLAN File Name: Architectural.232 E. Main St.2018.11.pdf Subject: PlanCheck Author: nickt Color: Provide a minimum 36" wide pathway between trash containers and the gate to allow for both means of egress (2015 IBC 1020.2) and an accessible on property route to the trash (2015 IBC 1104.2). Page: A-100 PROPOSED MAIN FLOOR PLAN File Name: Architectural.232 E. Main St.2018.11.pdf Subject: PlanCheck Author: nickt Color: Route to trash must be accessible. Provide maneuvering clearance on both sides of the trash area gate. Show and dimension the clearances. ICC A117.1-2009 section 404.2.3.2. Page: A-100 PROPOSED MAIN FLOOR PLAN File Name: Architectural.232 E. Main St.2018.11.pdf Subject: PlanCheck Author: nickt Color: Identify what this is. Page: A-131 ROOF PLAN File Name: Architectural.232 E. Main St.2018.11.pdf Subject: PlanCheck Author: nickt Color: Provide guards at the mechanical roof decks (2015 IBC 1015.6) Page: A-300 BUILDING SECTIONS File Name: Architectural.232 E. Main St.2018.11.pdf Subject: PlanCheck Author: nickt Color: Provide a barrier where vertical clearance is less than 80" per 2015 IBC 1003.3.1. UP 7'-6 1/2"28'-7 1/2"7'-2 5/8" 59'-9" 5'-3 " 27 ' - 8 1 / 4 " SLIDING GATE FENCED EXTERIOR TRASH AND UTILITY AREA 103 26'-1 1/2" SLIDING GATE ELEV. /8" 8'-5 1/2" A-412 1 1 9'-6 3/4"8'-4"9'-2 1/2" C.2 C.4 E.8 F.8 4'- 9 " D.S. D.S. 16'-10 7/8"9'-7 1/4"8'-0 3/4" 7'-0 1 / 4 " 3'- 2 1 / 2 " 5x5x1/4 F E JANITOR CLOSET P GAS METERS 1. PROVIDE F.T. WOOD BLOC ACCESSORIES AND MILLWOR 2. FIRE RATED HORIZONTAL A AND UNINTERRUPTED. 3. ALL EXPOSED STEEL ON T PAINTED. 4. THESE DRAWINGS INDICAT THE ARCHITECTURAL DESIGN INDICATE OR DESCRIBE ALL PROJECT. 5. THE CONTRACTOR OR SUB VERIFICATION OF ALL DIMEN ANY WORK AND SHALL NOTIF DISCREPANCIES. 6. SUBCONTRACTOR SHALL V BEFORE PROCEEDING WITH 7. ALL WORK SHALL BE COOR AVOID INTERFERENCES, PRE 8. ALL DOORS USED IN CONN WITHOUT THE USE OF A KEY 9. DIMENSIONS MARKED 'HOL DIMENSIONS ARE FACE TO F 10. DIMENSIONS, TARGETS, E ONLY ONCE. 11. PROVIDE PRIME COAT ON FILE CABINETS, WALL COVER OTHERWISE. GENERAL NOTES: Provide a minimum 36" wide pathway between trash containers and the gate to allow for both means of egress (2015 IBC 1020.2) and an accessible on property route to the trash (2015 IBC 1104.2). 8'-7 1/2"7'-2 5/8" 5'- 3 " 4" FENCED EXTERIOR TRASH AND UTILITY AREA 103 6'-1 1/2" ATE ELEV. A-412 1 8'-4"9'-2 1/2" E.8 F.8 D.S. F E SET 1. PROVIDE F ACCESSORIE 2. FIRE RATE AND UNINTE 3. ALL EXPOS PAINTED. 4. THESE DR THE ARCHITE INDICATE OR PROJECT. 5. THE CONT VERIFICATIO ANY WORK A DISCREPANC 6. SUBCONTR BEFORE PRO 7. ALL WORK AVOID INTER 8. ALL DOOR WITHOUT TH 9. DIMENSIO DIMENSIONS 10. DIMENSIO GENERAL Route to trash must be accessible. Provide maneuvering clearance on both sides of the trash area gate. Show and dimension the clearances. ICC A117.1-2009 section 404.2.3.2. 13'-0 1/2"3'-4"7'-6 1/2" 59'-9 SLIDING GATETRANSFORMER 2 A-311 1 A-600 24'-4"9'-6 3/4" C.2 GAS METERS Identify what this is. 1,380 2,0001,380 2,000 CEDAR SHAKE SHINGLES OVER GABLED ROOF, ROOF 1 A-300 3 A-400 9" / 1'-0"9" / 1'-0"9" / 1'-0" 9" / 1'-0"9" / 1'-0" 9" / 1 ' - 0 " 9" / 1 ' - 0 " 3 4 5 6 7 8 8.5 9 10 C.2 C.4 E.8 9" / 1'-0" CONCEALED GUTTER, TYP.INTERNAL GUTTER, TYP. INTERNAL D.S., TYP. 3" V.T.R. 3" V.T.R. 1" / 1 ' -0" MECHANICAL EQUIPMENT SE 15'-0" PROPOSED SATELLITE LOCATION 12'-0" 12'-0" T/ 2ND FLOOR 12'-0" T/ 2ND FLOOR 12'-0"T/ 2ND FLOOR 9'-6 3/4" 9'-6 3/4" 9'-6 3/4" MECHANICAL SCREENING, TYP. D.S. ROOF ACCESS 24'-4"9'-6 3/4"8'-4"9'-2 1/2 12'- 6 3 / 4 " 4'-0 1 / 8 " 13 ' - 5 " 13'- 3 " 13' - 5 " 3'-1 0 3 / 8 " 4'-1 0 1 / 4 " 4'-9 " T/ 2ND FLOOR 9'-6 3/4" PROPOSED SNOW SYSTEM TO ALLE SNOW SHEDDING B THE ROW AND ON ADJACENT LO PROPOSED SNOW MELT SYSTEM TO ALLEVIATE SNOW SHEDDING BOTH IN THE ROW AND ON ANY ADJACENT LOTS Provide guards at themechanical roof decks (2015 IBC 1015.6) 9 12 9 12 GOOSENECK LIGHT FIXTURE WITH FROSTED LENS, TYP. ACM RAIN SCREEN PANELING W/ 1/2" REVEAL ACM WET SEAL SYSTEM W/ 1/2" REVEAL OVER ROOF AT (9/12) SLOPE CEDAR SHAKE SHINGLES OVER GABLED ROOF, ROOF AT (9/12) SLOPE SECOND FLOOR TENANT SPACE- 'B' 200 EGF.8 5'-5 3/8" MIN . H E A D C L E A R A N C E 7'- 0 " 1/4" = 1'-0"1 BUILDING SECTION Provide a barrier where vertical clearance is less than 80" per 2015 IBC 1003.3.1. Page: A-301 BUILDING SECTIONS File Name: Architectural.232 E. Main St.2018.11.pdf Subject: PlanCheck Author: nickt Color: Provide a parapet at the wall on gridline A or demonstrate how you comply with one of the exemptions. 2015 IBC 705.11. Page: A-311 WALL SECTIONS File Name: Architectural.232 E. Main St.2018.11.pdf Subject: PlanCheck Author: nickt Color: Parapet height must be 30" min. 2015 IBC 705.11.1 Page: A-400 STAIRS & ELEVATOR File Name: Architectural.232 E. Main St.2018.11.pdf Subject: PlanCheck Author: nickt Color: The walls and ceiling of the enclosure under the stairs must be protected by 1 hour fire rated construction. Detail and provide listed assemblies. 2015 IBC 1011.7.3 Page: A-400 STAIRS & ELEVATOR File Name: Architectural.232 E. Main St.2018.11.pdf Subject: PlanCheck Author: nickt Color: Handrail extensions must return to a wall, floor, or guard. 2015 IBC 1014.6. Page: A-400 STAIRS & ELEVATOR File Name: Architectural.232 E. Main St.2018.11.pdf Subject: PlanCheck Author: nickt Color: Provide access to attic spaces. 2015 IBC 1209.2. 1 A-300 9 12 A-503 1 A B Provide a parapet at the wall on gridline A or demonstrate how you comply with one of the exemptions. 2015 IBC 705.11. T/PARAPET14'-4" B/GABLE16'-1 1/2" 2ND LEVEL12'-0" 1 A-300 A PR O P E R T Y L I N E 3" A-502 6 3 A-400 PR O P E R T Y L I N E 1010 A-502 9 Sim Parapet height must be 30" min. 2015 IBC 705.11.1 FENCED EXTERIOR TRASH AND UTILITY AREA 103 TENANT SPACE 'B' LOBBY 101 A-501 2 Sim A-501 5 Sim 0" G SECTION The walls and ceiling of the enclosure under the stairs must be protected by 1 hour fire rated construction. Detail and provide listed assemblies. 2015 IBC 1011.7.3 UP DN 3 A-400 STAIR WIDTH 3'-1 " F.O. 3'-6" HOLD 5'-9 " 8.5 9 10 C.4 E.8 2500# CAPACITY6'-8" x 4'-3" CAB.8'-4" x 5'-9" HOISTWAY5'-0" PIT DEPTH 2'-8" R.O. 4'-3 3/8"2'-8" HOLD 8'-4" 5 A-400 JANITOR CLOSET P E 8'-0 " LAN D I N G 3'-11 5 / 8 " LANDING 3'-3" STAIR WIDTH 3'-1" ACCESS PANELSURFACE MOUNTEDTO CMU WALL FIN. FLR. TENANT 'A' 7903.200" T/GABLE 0226'-6 7/8" T/PARAPET14'-4" 2ND LEVEL12'-0" NORTHWEST GRADE-3'-3" 1 A-300 FENCED EXTERIORTRASH AND UTILITYAREA 103 CEDAR SHAKE SHINGLES OVER GABLED ROOF, ROOF AT (9/12) SLOPE RECLAIMED WOOD FACIA GUTTER 9 12 912 2 A-311 AC.2C.4E.8F.8 SECOND FLOORTENANT SPACE- 'B' 200 TENANT SPACE 'B'LOBBY 101 E A-5012 Sim A-5015 Sim FIN. FLR. TENANT 'B' 7902.20-1'-0"FIN. FLR. MECH. ROOM 7901.20-2'-0" T/ ELEVATOR PARAPET27'-0" 3 A-400 8.5 9 10 C.4 E.8 F.O. 3'-6" R.O. 4'-3 3/8" HOLD8'-4" HOLD 5'-9 " 2500# CAPACITY6'-8" x 4'-3" CAB.8'-4" x 5'-9" HOISTWAY5'-0" PIT DEPTH 1'-0 " 4'-0 " LANDING 3'-11 5 / 8 " LANDING 3'-10 1/4"8'-9 1/8" STAIR WIDTH 3'-1 " STAIR WIDTH 3'-1" E FIN. FLR. TENANT 'A' 7903.200" ROOF21'-0" 2ND LEVEL12'-0" 3A-4008.5 9 10 NOTE:ELEVATOR WALLS NOT SHOWN FOR CLARITY FIN. FLR. TENANT 'B' 7902.20-1'-0" FIN. FLR. MECH. ROOM 7901.20-2'-0" 2'-9 1 / 4 " 5'-4 1 / 4 " 4'-10 1 / 2 " 1'-0" HAN D R A I L H E I G H T 3'-0 " 1'-0" SECOND FLOORTENANT SPACE- 'B' 200 TENANT SPACE 'B'LOBBY 101 MIN . H E A D C L E A R A N C E 6'-10 " Scale PROJECT NU DATE DRAWN BY CHECKED BY A S EL CO R E & S H E L L B U I L D I N G 1/2" = 1'-0"1 MAIN FLOOR STAIR PLAN 1/4" = 1'-0"3 BUILDING SECTION 1/2" = 1'-0"2 SECOND FLOOR STAIR PLAN 1/2" = 1'-0"5 STAIR SECTION NO. DATE BY REVISION 1 05.09.18 MODIF.SCHEMATIC DESIGN 2 07.13.18 MODIF.DESIGN DEVELOPMENT 3 09.6.18 MODIF.90% PERMIT SET Handrail extensions must return to a wall,floor, or guard. 2015IBC 1014.6. CEDAR SHAKE SHINGLES OVER GABLED ROOF, ROOF AT (9/12) SLOPE RECLAIMED WOOD FACIA GUTTER 9 12 9 12 C.4E.8F.8 SECOND FLOOR TENANT SPACE- 'B' 200 TENANT SPACE 'B' LOBBY 101 Provide access to attic spaces. 2015 IBC 1209.2. Page: A-400 STAIRS & ELEVATOR File Name: Architectural.232 E. Main St.2018.11.pdf Subject: PlanCheck Author: nickt Color: Provide a section detailing the continuity of the top of the elevator shaft and demonstrate compliance with 2015 IBC 713.5 or 713.12. Page: A-410 WINDOW & DOOR ENLARGED PLAN & ELEVATION File Name: Architectural.232 E. Main St.2018.11.pdf Subject: safety Glazing windows Author: nickt Color: Indicate which windows require safety glazing per 2015 IBC 2406.4. Revise the window schedule or elevations. Page: A-411 WINDOW & DOOR ENLARGED PLAN & ELEVATION File Name: Architectural.232 E. Main St.2018.11.pdf Subject: skylight Author: nickt Color: The sloped glazing requires laminated glass with a min. 30 mil pvb interlayer, or a screen. Demonstrate compliance. 2015 IBC 2405.2 Page: A-502 WALL DETAILS AT SECOND LEVEL File Name: Architectural.232 E. Main St.2018.11.pdf Subject: PlanCheck Author: nickt Color: Revise detail 8/A-502 at the joint of the non-fire resistant floor assembly to comply with 2015 IBC 712.1.5.2. Page: A-502 WALL DETAILS AT SECOND LEVEL File Name: Architectural.232 E. Main St.2018.11.pdf Subject: PlanCheck Author: nickt Color: Insulate at this ledger to avoid a thermal break in the thermal envelope. E.8 F.O. 3'-6" R.O. 4'-3 3/8" HOLD 8'-4" HOLD 5'- 9 " 2500# CAPACITY 6'-8" x 4'-3" CAB. 8'-4" x 5'-9" HOISTWAY 5'-0" PIT DEPTH 8'-9 1/8" STAIR WIDTH 3'-1 " E 8.5 9 Provide a section detailing the continuity of the top of the elevator shaft and demonstrate compliance with 2015 IBC 713.5 or 713.12. A-410 A-500 10 B C BASIS OF DESIGN: Indicate which windows require safety glazing per 2015 IBC 2406.4. Revise the window schedule or elevations. 12 ' - 1 0 3 / 4 " 9 " / 1 '-0 "1 6'-1 1" EGF.8 106° ROOF OVERHANG The sloped glazing requires laminated glass with a min. 30 mil pvb interlayer, or a screen. Demonstrate compliance. 2015 IBC 2405.2 2ND LEVEL 12'-0" C R 03 40 00.A3 05 0 07 06 1 06 22 06 2 09 8 07 2 UP AND PARAP 04 22 04 2 04 2 2ND LEVEL12'-0" F.8 06 16 00.D11 07 21 00.E4 06 16 00.D11 06 17 00.B8 08 43 00.A13 05 12 00.M296 08 81 00.C8 1 1/2" = 1'-0" SECTION DETAIL - SLOPED GLAZING MULLION Revise detail 8/A-502 at the joint of the non-fire resistant floor assembly to comply with 2015 IBC 712.1.5.2. 09 29 00.D1 07 21 00.A10 3/4"3/4" 3"7 5/8"2 1/2" 5/8"1'-3 1/4" 04 22 00.C3 06 17 00.B8 Scale PROJECT NUMBER DATE DRAWN BY CHECKED BY modif. modif. 1 1/2" = 1’−0" A−502 2016−005 11.12.18 WALL DETAILS AT SECOND LEVEL 1 1/2" = 1'-0"9 SECTION DETAIL - NORTH PARAPET WALL NO. 1 2 3 4 Insulate at this ledger to avoid a thermal break in the thermal envelope. Page: A0.7 CODE ANALYSIS AND EGRESS PLAN File Name: Architectural.232 E. Main St.2018.11.pdf Subject: PlanCheck Author: nickt Color: Show accessible door maneuvering clearances at both sides of all office and conference room doors. ICC A117.1-2009 section 404.2.3.2. Page: A0.7 CODE ANALYSIS AND EGRESS PLAN File Name: Architectural.232 E. Main St.2018.11.pdf Subject: PlanCheck Author: nickt Color: The two exit doors are not spaced far enough apart (2015 IBC 1007.1.1) so this tenant space is considered to only have a single exit. Maximum common path travel distance is 75' (2015 IBC table 1006.3.2(2)) Page: A0.7 CODE ANALYSIS AND EGRESS PLAN File Name: Architectural.232 E. Main St.2018.11.pdf Subject: PlanCheck Author: nickt Color: The printer area has two doors in a series. Provide 48" between the door swings or swing one door in a different direction. 2015 IBC 1010.1.8. Page: A0.7 CODE ANALYSIS AND EGRESS PLAN File Name: Architectural.232 E. Main St.2018.11.pdf Subject: PlanCheck Author: nickt Color: Provide accessible seating at this table/work surface. 2015 IBC 1109.11. Page: A1.1 FLOOR PLAN File Name: Architectural.232 E. Main St.2018.11.pdf Subject: PlanCheck Author: nickt Color: The shell drawings show folding doors. The tenant finish drawings show differently. Coordinate the drawings. 102 LOBBY 113 PCS 5 109 CORRIDOR 36x56 42 36x56 42 36x72 36x72 >>>>>> > > > > > > > > > > >>>>>> 112 PCS 4 111 PCS 3 110 PCS 2 108 CMS 1 > > > > > > > >>>>>>>XIMUM TRAVEL DISTANCE = 57'-11" ALLOWED 300'-0" N. M O N A R C H S T . Show accessible door maneuvering clearances at both sides of all office and conference room doors. ICC A117.1-2009 section 404.2.3.2. DOOROCCS:REQD: 101A 3532" 102LOBBY 103DAB 115WOMENS 118JANITOR 106MANUAL TRANSACTION 105CAFE 104LIVING ROOM 113PCS 5 116MENS117LOUNGE 107PRINTERS 119DATA 109CORRIDOR 36x56 42 36x56 42 36x72 30" H. 34" H . 42" H . 34" H . 42 36x72 34 " H . 34 " H . 3" >> >>>>>> > > > > > > >>>>>>>>>>>>>>> > > > > > > > > > > >>>>>>>>> > > >>>>>>> 112PCS 4 111 PCS 3 110PCS 2 108CMS 1 >>> > > > > > > > >>>>>>>MAXIMUM TRAVEL DISTANCE = 57'-11" ALLOWED 300'-0" F.E.C. ACCESSIBLE COUNTERAT 34" A.F.F. MAX. MAXIMUM TRAVEL DISTANCE = 105'-10" ALLOWED 300'-0" N. M O N A R C H S T . AD J A C E N T T E N A N T NO T P A R T O F CH A S E UP 3 4 5 6 7 8 8.5 9 10 114CORRIDOR > > > > > > > > DESCRIPTION AREA /SF OCCUPANT LOAD FEMALE BUSINESS 1-25 OCC. =1 REQUIRED =1 PROVIDED =1 WATER CLOSETS URINALS LAVATORIES DRINKING FOUNTAINS 1-40 OCC =1 REQUIRED =1 PROVIDED =1 1-100 OCC. =1 REQUIRED =1 PROVIDED =2 SERVICE SINK REQUIRED =1 PROVIDED =12,600 SF 2,600/ 100 = 2613 MALE /13 FEMALE N/A PLUMBING FIXTURE ANALYSIS AS PER TABLE 403.1 IPC 2015 FLOOR MALE 1-25 OCC. =1 REQUIRED =1 PROVIDED =1 FEMALE 1-40 OCC =1 REQUIRED =1 PROVIDED =1 MALE N/A CODE ANALYSIS: (201 USE AND OCCUPANCY CLASSIFICATION TWO STORY BUILDING, MULTI TENANT CHASE TENANT: B-BUSINESS OTHER TENANTS: UNKNOW TYPE OF CONSTRUCTION (SECTION 60 TYPE V-B, SPRINKLERED BUILDING FIRE RESISTANCE RATING REQUIREMEN ALL INTERIOR NON-BEARING WALLS & DEMISING WALL: ADJACENT TENANT DEMISING CEILING: BUILDING HEIGHT & AREA (CHAPTER 5 EXISTING 22'-8 BY LL - IN LINE LEASE SP ALLOWABLE BUILDING AREA (TABLE 5 ALLOWABLE SQUARE FOOTAGE PER FL ACTUAL BUILDING AREA: 5,709 S CHASE:2,600 SQ. FT GROUND FLOOR RETAIL:4,339 S OFFICE SPACE ABOVE:1,370 S OCCUPANT LOAD (TABLE 1004.1.2): 2,600/100 = 26 OCCUPANTS INTERIOR FINISHES (CHAPTER 8 AND T EXIT PASSAGEWAYS - CLASS B CORRIDORS AND ENCLOSURE FOR EXIT ROOMS AND ENCLOSED SPACES - CLAS INTERIOR FLOOR FINISHES - CLASS II MINIMUM EGRESS SIZING (SECTION 1 DOORWAYS: .15” * 26 OCC. = 3.9” REQ PROVIDED: 68" EXIT ACCESS TRAVEL DISTANCE (TABLE MAXIMUM: 300'-0" ACTUAL: 105'-10" NUMBER OF EXITS (SECTION 1006): REQUIRED - 1 EXIT PROVIDED - 1 EXIT The two exit doors are not spaced far enoughapart (2015 IBC1007.1.1) so this tenant space isconsidered to onlyhave a single exit. Maximum commonpath travel distance is75' (2015 IBC table 1006.3.2(2)) 102 LOBB 103 DAB 115 WOMENS 118 JANITOR 106 MANUAL TRANSACTION 105 CAFE 104 LIVING ROOM 113 PCS 5 116 MENS 117 LOUNGE 107 PRINTERS 119 DATA 109 CORRIDOR 36x72 30" H. 34 " H . 42 " H . 34 " H . 34 " H . 34 " H . >> >>>>>> > > > > > > >>>>>>>>>>>>>>> > > > > > > > > > > >>>>>>>>> > > >>>>>>> 108 CMS 1 > > > > >MAXIMUM TRAVEL DISTANCE = 57'-11" ALLOWED 300'-0" F.E.C. ACCESSIBLE COUNTER AT 34" A.F.F. MAX. MAXIMUM TRAVEL DISTANCE = 105'-10" ALLOWED 300'-0" 3 4 5 6 114 CORRIDOR > > > > > > > > The printer area has two doors in a series. Provide 48" between the door swings or swing one door in a different direction. 2015 IBC 1010.1.8. DOOR OCCS:REQD:PRVD:68" 101A 35 32" 101 TRANSACTION VESTIBULE 102 LOBBY 103 DAB 104 LIVING ROOM 36x56 34 " H . > > > > > > > >>>>> > > >>>>>>> 110 PCS 2 >>>>>>> MAXIMUM TRAVEL DISTANCE = 57'-11" ALLOWED 300'-0" F.E.C. CESSIBLE COUNTER 34" A.F.F. MAX. E. MAIN ST. PATIO C D E F G > > > > > SCALE EGRESS PLAN 11/4"=1'-0" N Provide accessible seating at this table/work surface. 2015 IBC 1109.11. 109CORRIDOR 103DAB 106MANUAL TRANSACTION 105CAFE 104LIVING ROOM 117LOUNGE 107PRINTERS 119DATA 114CORRIDOR 101TRANSACTION VESTIBULE 118JANITOR 115WOMENS 116MENS 110PCS2 108CMS1 111PCS3 112PCS4 113PCS5 102LOBBY NICADJACENT TENANT NICMECHANICAL ROOM 10'- 2 3 / 8 " 5'-4 1 / 4 " HOL D 9 3 / 4 " 3'-0 " 3'-10 1 / 4 " 9'-0 " 1'-7 1 / 8 " 5'-5 " 1'-6 " 6 1/4 " 7'-7 5 / 8 " 1'-8 1 / 8 " 9'-0 1 / 4 " 1'-0 1 / 2 " 9'-1 0 3 / 4 " 1'-0 1 / 2 " 9'-10 3 / 4 " 1'-0 1 / 2 " 9'-5 1 / 2 " 9'-3 3 / 4 " 1'-0 1 / 2 " 3'-7 1 / 8 " 6'-5 3 / 8 " 4'-11 7 / 8 " 5'-4 5 / 8 " 3 5/ 8 " 3 5/8 " 10'- 2 1 / 4 " 5'-5 " 10'-1 3 / 4 " 9'-5 " 1'-7 1 / 8 " 8'-1 5 / 8 " 5" 5'-4 1 / 4 " 5'-4 1 / 4 " 4'-9 1 / 2 " 7'-1 1 / 2 " 1'-6" 3'-0 " 7'-2 " 3'-0 " 4'-3 1 / 2 " 7'-8 1 / 4 " 3'-0 " 6'-8" 2'-0 " 7'-0 1 / 2 " 6'-7 1 / 2 " 7'-1 0 3 / 8 " 14'-0 7 / 8 " 4'-0 " MIN . 3'-0 1 / 2 " 7'-6 7 / 8 " 3'-0 " 4'-3 1 / 2 " 3'-4 1 / 2 " 16'-2 5 / 8 " 10'- 4 3 / 8 " 5'-4 1 / 4 " HOL D A5.1.2 4C4A 4D 4B A5.1.2 6A 6B A5.1.1 3B3D 3A 3C A5.1.1 2B2D 2A 2C A5.1.22A A5.1.2 1B1D 1C 1A A5.1.2 3C3A 3B A5.5- A5.31 A5.2.14 A5.2.14 ℄ ℄ ℄ ℄℄℄℄ ℄ ℄ ℄ ℄ ℄ A5.1.11 A5.37 A B A A3.22 A3.2 1 1'-0 1/2" 7'-4 1/4"9'-0"7'-4 7/8" 1'-0 1/2"7 5/8"1'-0 1/2"3 7/8" 1'-5 1/8" 1'-0 1/2" 1'-0 1/2" 1'-10 1/4" 1'-10 1/4" 1'-0"2'-0"10" 9'-1 7/8"6'-0"9"2'-8" 7" 3'-9 1/4" 1'-0 1/2"1'-0 1/2" 8'-6" 9'-0 3/4"9'-3 1/8"12'-0 3/8" 14'-1"5'-10 7/8"10'-4 3/8" 1'-7"5'-8 3/8" 9'-10 7/8" 7 1/2" 3'-0"3'-7 7/8"12'-3 1/2" 9'-8 3/8" 5" 3'-0" 1'-7"1'-8 5/8"5'-8 5/8" 7'-5 3/8" 6'-6" 2'-8 3/4"3'-0"9 1/4" 2'-8" 2'-9 3/8"3'-2" 7'-5 3/8" 7'-5 1/4"1'-7"3'-0"6'-0 1/8" 19'-3 1/4"9'-6 1/4" 3'-6 1/8" 2'-10 1/8"3'-2"4'-5 3/4" 3'-8 1/4" 9'-7 1/4" 13'-7 1/2" 2 5/8" ℄ ℄ ℄ ℄ ℄ ℄℄℄ ℄ ℄ ℄℄℄ 6" 8 1/4 " 112A 111A 110A 108A113A 115A 107B 107A 102A 101A 101B 6 1 / 4 " ℄ 116A 119A 117A 102B P10 P10 P10 P9 FE C P8 P6 P11 P21 P21 P5 P5 P3 P1 P1 P44 P41 ℄ ℄ P27 P1 P15 P24 P36 P15 P1 P1 P1 P1 P19 P19 P12 P2P2P2 P16 P26 P26 P26 P26 P22 P26 P2 P28 P28 P28 P28P28P28 P28 P28 P28 P28 P28 P28 P28 P32 P33 P37 P39 P40P40 P40 P40 P43 A3.11 A3.0 1 A3.12 P45TYP. P17 P17 P18 P18 P18 TYP. TYP. TYP. 114A 7 1/2" WJ1 WK1 WJ1 WJ1 WJ1 WJ1 WJ4 WN5 WJ7 WJ4 WN7 WJ WJ WJ WJ WJ WR1 WJ WJ WJ WJ8 WJ WJ WTTYP. WTTYP. WT TYP. WT TYP. WTTYP.WTTYP. WN WQ WQ WQ WT 9 3/8" P27 WN8 WN8WN8 WN8 WN8 WN8 WN8WN8WN8WN8 P32P32 WN8 WN WN 6'-4 1/4"12'-11"9'-0 1 / 2 " P11 P21 P37 P37 P46P46 A5.1.2 5A 5B A5.1.4 1B1D 1A 1C A5.1.3 1C1A 1B 1D A5.1.3 5C5A 5B 5D A5.1.3 2B2D 2A 2C A5.1.3 4B4D 4A 4C A5.1.3 3B3D 3A 3C 101C 103A 104B 104A 36x 5 6 42 36x 5 6 42 36 x 7 2 42 36x 7 2 E E E3" E. M A I N S T . N. MONARCH ST. PA T I O ADJACENT TENANT NOT PART OF CHASE UP 12345678.5 A B C D E F G PLATE FOR SINGLE DOOR INGRESS TO VESTIBULE - LOCATE PUSH PLATE: BOTTOM PLATE @ 7" MIN. & 8"MAX. AFF TO CENTER LINE OF PLATE - TOP PLATE @ 30"MIN. & 44" MAX. AFF TO CENTER LINEOF PLATE. PROVIDE WEATHER RING TO ENSURE WEATHER-TIGHT INSTALLATION". SEE EXTERIOR ELEVATIONSAND ELECTRICAL DRAWINGS. P7 ROLL-UP GRILLE CONTROL AND EMERGENCY RELEASE LEVEL MOUNTED AT 44" MAX. A.F.F.COORDINATE WITH MANUFACTURER AND ELECTRICAL DRAWINGS. P8 FIRE EXTINGUISHER IN RECESSED CABINET WITHIN 6" WALL. MOUNT 27" FROM FINISH FLOOR TOINSIDE BOTTOM OF CABINET. COORDINATE QUANTITY AND LOCATION WITH FIRE MARSHALL.CABINET SHALL NOT REQUIRE TIGHT GRASPING, PINCHING OR TWISTING OF WRIST TO OPEN.FIRE EXTINGUISHER MAX. HEIGHT 48" P9 MOP SINK WITH WATER HEATER ABOVE. SEE 8/A5.4 AND PLUMBING DRAWINGS. P10 FLOOR DRAIN. SEE PLUMBING DRAWINGS. P11 TACTILE "EXIT" SIGN. SEE DETAIL 3/A0.4. P12 STOREFRONT SYSTEM. SEE SHEET A2.1. EXTEND STUDS, GYP. BD., AND PLYWOOD TO UNDERSIDEOF STRUCTURE. P13 SEE STRUCTURAL FOR THE LOCATION/SIZE/SPACING OF THE STEEL POSTS @ LOW WALLS. P14 2'-2" X 4'-7" @ 1'-1" AF.F. FOR THE ATM OPENING. SEE DETAIL 2/A4.5 AT INTERIOR WALL ANDA2.1. G.C. TO FIELD VERIFY. P15 ALUMINUM STOREFRONT SYSTEM WITH CLEAR FIXED GLAZING. P16 RECESSED MOUNTED ELECTRICAL PANELS PER THE ELECTRICAL DRAWINGS P17 EXISTING EXTERIOR DOORS BY LL TO REMAIN, GC TO REVIEW THE DOOR HARDWAREPER CHASE STANDARDS P18 EXISTING EXTERIOR FACADE BY LL TO REMAIN. P19 POWER AND DATA CONDUIT STUB-UP POINT. GC TO INSTALL FLUSH MOUNTED POWER/DATAFLOOR BOX - SEE ELECTRICAL DRAWINGS. P20 POWER, DATA AND SECURITY CONDUIT STUB-UP POINT. SEE ELECTRICAL DRAWINGS FORFLOOR OUTLET INFORMATION P21 RECESSED HIGH/LOW SQUARE PUSH PLATE. SEE KEYNOTE P6 FOR ADDITIONAL INFO. P22 MOTORIZED TELLER SCRIM, SEE 3&4/A5.5. P23 VESTIBULE WALLS AND ROLL-UP GRILLE SOFFIT SHALL EXTEND TO ROOF STRUCTURE SECUREABOVE CEILING WITH 3/4" PLYWOOD, SEE 1/A5.2. P24 1'-11 1/2" (W) X 2'-1 1/2" (H) AT 1'-11" A.F.F. OPENING FOR AHD. P25 2'-2" (W) X 4'-7" (H) AT 1'-11" A.F.F. OPENING FOR ATM. SEE 3/A4.0 P26 PROVIDE BLOCKING AS REQUIRED FOR OPEN SHELVING. P27 EXISTING ALUMINUM STOREFRONT SYSTEM WITH CLEAR FIXED GLAZING. GC TO COORDINATEINSTALLATION OF ELECTRICAL CONDUIT FOR POWER OPERATED CARD READER/ PULLPADDLES AT BANK MAIN ENTRY. P28 (E) STRUCTURAL COLUMN WITHIN WALL CAVITY. P29 ROOF ACCESS LADDER. P30 (E) GAS METER P31 (E) ELECTRICAL TRANSFORMER. P32 ELECTRICAL TO PROVIDE A CONVENIENCE OUTLET AT +18" AFF P33 (E) EXTERIOR CANOPY ABOVE. SEE A1.4 AND STRUCTURAL DRAWINGS. P34 ALUMINUM STOREFRONT SYSTEM WITH FILM P35 RESTRICT DOOR TO SWING IN ONLY. P36 "KNOX BOX 3200 SERIES," OR APPROVED EQUAL, RECESSED, SECURE-ACCESS KEYVAULT. COLOR: ALUMINUM. COORDINATE FRAMING AND SEAL ALL SIDES OF BOX TIGHTTO FINISHED SURFACE. MOUNTING HEIGHT: +3'-6" AFF TO C.L., CENTERED IN WALL. P37 GC TO VIF IF RECESSED MOUNTING IS POSSIBLE W/ EXISTING MULLION. NOTIFY THE ARCHITECT IF RECESSEDWILL NOT BE POSSIBLE FOR SURFACE MOUNTING DETAIL.P38 BLOCKING REQUIRED BEHIND WALL FOR DOOR TRACK - TOP OF BLOCKING AT 9'-6" ANDBOTTOM AT 7'-6" P39 WING WALL TO INCLUDE EXISTING PIPE. GC TO NOTIFY ARCHITECT IF ANYDISCREPANCIES ARE UNCOVERED W/ FIELD CONDITIONS. P40 DEMOUNTABLE PARTITION SYSTEM WITH INTEGRAL DOORS AND POWER, DATA, ANDSECURITY CONDUIT SYSTEMS. ANCHORED TO BUILDING WALLS, SUBFLOOR, ANDBULKHEADS. P41 X-HR RATED DEMISING WALL. SEE A2.0 FOR CLARIFICATION P42 DASH LINE REPRESENTS EXTENT OF BALLISTICS PANEL. SEE WALL TYPE "WJ6" ON A2.0(TO BE CONFIRMED BY THE SECURITY TEAM). P43 GC TO CONFIRM DIMS OF CLOSET W/ AHD EQUIPMENT VENDOR PRIOR TO FRAMING. P44 SECURITY MESH INSTALLED ON DEMISING WALL TO 11'-0" AFF ON BANK SIDE, SEE A2.0 P45 EXISTING FOLDING DOORS BY LL TO REMAIN P46 EXISTING ROOF MELT 24"X24" ACCESS PANELS BY OTHERS. FLOOR PLAN LEGEND EXTERIOR WALL CONSTRUCTION - SEE WALL TYPES AND WALL SECTIONSFOR MORE INFORMATION INTERIOR NON-BEARING PARTITIONS, EXTEND STUDS 6" ABOVE CEILING.SEE STRUCTURAL FOR CONNECTIONS. INTERIOR NON-BEARING PARTITION FULL HEIGHT WALL. SEE STRUCTURALFOR CONNECTIONS. INTERIOR NON-BEARING PARTITIONS. OWNER'S EQUIPMENTCONTRACTOR WALL PARTITION TYPES - REFER TO SHEET A2.0 DOOR INDICATOR - SEE SHEET A2.1 AND A2.2FOR DOOR AND HARDWARE SCHEDULE KEYNOTE, SEE SCHEDULE X ###A P#SCALEFLOOR PLAN 11/4"=1'-0" N FLOOR PLAN A1.1 CH A S E #3 8 2 0 0 P 3 1 0 9 3 9 MA I N & M O N A R C H (S T A N D A R D P A L E T T E ) 11-02-2018222769128 PROJECT INFORMATION BLOCKJOB #DATE: DRAWN BY: CHECKED BY: MODEL SHEET TITLE SHEET NUMBER ISSUE DATE DESCRIPTION SEAL ARCHITECT OF RECORD JB/BR 23 2 E . M A I N S T R E E T , A S P E N , C O 8 1 6 1 1 18.3 10 S . D E A R B O R N S T R E CH I C A G O , I L Copyright Reserved The Contractor shall verify and be responsible for alldimensions. DO NOT scale the drawing - any errors oromissions shall be reported to Stantec without delay. TheCopyrights to all designs and drawings are the propertyof Stantec. Reproduction or use for any purpose otherthan that authorized by Stantec is forbidden. Architecture Inc. www.stantec.com TEL. 224 South Michigan Ave., Ste 1400Chicago, IL 60604312.554.1400 PERMIT SUBMITTAL11/2/18- 1.PROVIDE BLOCKING AND BACKING AS DEFINED IN SPECIFICATIONS AT 2'-0" AFF AND8'-0" AFF IN (E) WALLS AND NEW PARTITIONS FOR ALL CASEWORK AND ACCESSORIES.COORDINATE WITH FIXTURE SHOP DRAWINGS. 2.FOR GYP. BD. CEILING AND SOFFIT FINISHES SEE REFLECTED CEILING PLAN. 3.FOR RESTROOM ELEVATIONS SEE A5.1.1. 4.ALL WALLS TO RECEIVE PT-207 & WALL BASE UNLESS NOTED OTHERWISE ON FINISH PLAN. 5.PROVIDE WATER RESISTANT GYP. BD. AT ALL WET LOCATIONS. 6.ALL WALLS TO RECEIVE A LEVEL 4 FINISH U.O.N. 7.ALL DOORS TO BE LOCATED 4" FROM PERPENDICULAR WALL U.O.N. 8.ALL INTERIOR DIMENSIONS ARE FINISH SURFACE TO FINISH SURFACE UNLESS OTHERWISENOTED. 9.INTERIOR PARTITIONS ARE 5" WIDE (NOMINAL DIMENSION) - ACTUAL DIMENSION ISSLIGHTLY SMALLER. 10.FIRE EXTINGUISHER CABINET SHALL BE RECESSED WITHIN 6" MIN. WALL. 11.GC SHALL PROVIDE 15 MIL. VAPOR BARRIER (STEGOWRAP) AT ALL INFILLS SLAB. 12.REFER TO SHEET A0.3 FOR SINGLE TOILET ACCOMMODATION ACCESSIBILITY REQUIREMENTS. 13.REFER TO SHEET A0.3 FOR DOOR ACCESSIBILITY REQUIREMENTS. 14.WALL, FLOOR AND CEILING SHALL NOT EXCEED THE FLAME SPREAD CLASSIFICATION INIBC TABLE 803.11. FLOOR 804. 15.FOR ELECTRICAL RECEPTACLE MOUNTING HEIGHTS TO COMPLY WITH IBC SECTION11B-308.1.2 SEE DETAIL 12/A5.3. 16.WHERE SLAB PATCHING OCCURS SEE DETAIL 4/A5.4. 17.AT ANY CHANGE IN LEVEL SEE DETAIL 6/A0.2. 18.EXTERIOR DIMENSIONS ARE TO FACE OF MASONRY AND FOUNDATION BELOW FLOOR PLAN GENERAL NOTES The shell drawingsshow folding doors.The tenant finishdrawings showdifferently. Coordinatethe drawings. Page: A1.3 FURNITURE AND EQUIPMENT PLAN File Name: Architectural.232 E. Main St.2018.11.pdf Subject: PlanCheck Author: nickt Color: Detail 6/A5.5 has been crossed out. Reference another detail. Page: A2.2 HARDWARE SCHEDULE File Name: Architectural.232 E. Main St.2018.11.pdf Subject: PlanCheck Author: nickt Color: Provide documentation demonstrating that the proposed electronic locks comply with 2015 IBC 1010.1.9.9. Page: A5.1.2 NTERIOR ELEVATIONS File Name: Architectural.232 E. Main St.2018.11.pdf Subject: PlanCheck Author: nickt Color: Locker rooms require an accessible bench per ICC A117.1-2009 section 803.4. Page: G-005 WALL TYPES File Name: Architectural.232 E. Main St.2018.11.pdf Subject: PlanCheck Author: nickt Color: Provide callouts to each wall, floor, and roof type in the plans, sections, and/or wall sections. Revise thermal envelope Comcheck to use the same naming labels as these wall, floor, and roof types. Page: G-005 WALL TYPES File Name: Architectural.232 E. Main St.2018.11.pdf Subject: PlanCheck Author: nickt Color: You list all of your walls as having a fire rating but very few of your walls require it. This could cause confusion during construction and inspection for dealing with penetrations. I recommend you only note the walls that are required to be rated as rated (the West wall on the property line, possibly the roof on top of it, and the elevator shaft). DAMAGED AT THE TIME DELIVERY. DAMAGED FURNISHINGS SHALL BE REPLACED IMMEDIATELY. 3.ALL FURNITURE , BANKING AND OFFICE EQUIPMENT SHALL NOT ENCROACH INTO OR REDUCE WIDTH OF ADA CLEARANCE AND TURNING RADIUS REQUIREMENTS AS IDENTIFIED ON PLANS. GC SHALL REVIEW THE ADA STANDARDS AND NOTIFY THE ARCHITECT IF ANY ISSUES. 4.GC SHALL FURNISH THE ITEMS IDENTIFIED ON THE PLAN AND SCHEDULES TO BE DELIVERED TO THE BANKING CENTER AT THE TIME OF SUBSTANTIAL COMPLETION. 5.ATMS MUST COMPLY WITH ACCESSIBILITY REQUIREMENTS SEE 2/A0.2. ACCESSIBLE TRANSACTION COUNTER CALCULATION ACCESSIBLE TRANSACTION COUNTER REQUIRED: 5% ACCESSIBLE TRANSACTION COUNTER PROVIDED: 1 1 ACCESSIBLE TRANSACTION COUNTER / 2 TELLERS = 50% 50% > 5%, THEREFORE WE COMPLY WITH MINIMUM REQUIRED. REFER TO DETAIL 6/A5.5 FOR WIDTH AND HEIGHTS OF ACCESSIBLE TRANSACTION COUNTER. CH A S E 38 2 0 0 P 3 1 0 9 3 9 MA I N & M O N A R C H AN D A R D P A L E T T E ) FURNITURE AND EQUIPMENT PLAN LEGEND Detail 6/A5.5 has beencrossed out.Reference another detail. EXTERIOR DOOR PUSH PLATE LCN 8310-853T SATIN S.S RECESSED IN HINGE JAMB MULLION INCLUDE LOW HT. AUTO. DOOR BUTT EXTERIOR DOOR PUSHBAR LCN 8310-836T SATIN S.S RECESSED IN HINGE JAMB MULLION INCLUDE LOW HT. AUTO. DOOR BUTT OPTIONAL: PUSHBAR BOLLARD LCN LCN 8310-3836T 8310-866FLA AL AL 36" VERTICAL ACTIVATION COLUMN W OMIT AT 01A CLOSER LCN 4111-3077CNS SP28 GRAY PAINT LEFT-HAND LEAF AS VIEWED FROM E OPENING FORCE REQUIRED TO MAIN SEALS PEMKO 297AS MILL-FIN. ALUMINUM SWEEP (2)PEMKO 318AV MILL-FIN. ALUMINUM THRESHOLD PEMKO 253X3AFG MILL-FIN. ALUMINUM 02 VESTIBULE BUTT HINGE (6)HAGER BB1191 ANSI A2112 NRP 4.5x4.5 630 SATIN STAINLESS STEEL REMOVABLE MULLION VON DUPRIN KR4954 SP28 GRAY PAINT PANIC BAR VON DUPRIN CD99EO 626 SATIN CHROMIUM PANIC BAR VON DUPRIN CD99NL-OP 626 SATIN CHROMIUM MORTISE CYLINDER SCHLAGE 20-001/C123 626 SATIN CHROMIUM MORTISE CYLINDER (2)SCHLAGE 20-001 XQ11-948/C123 626 SATIN CHROMIUM RIM CYLINDER SCHLAGE 20-022 626 SATIN CHROMIUM OFFSET DOOR PULL (2)IVES 8190-0-O 630 SATIN STAINLESS STEEL POWER OPERATOR LCN 4640CS POWDER COAT ALUMINUM RIGHT-HAND LEAF AS VIEWED FROM 5) INTERIOR DOOR PUSH PLATE LCN 8310-853T SATIN S.S RECESSED IN HINGE JAMB MULLION EXTERIOR DOOR PUSH PLATE LCN 8310-818T SATIN S.S RECESSED IN WALL OPPOSITE ATM/E KEY SWITCH LCN 8310-806K ---RECESSED IN HINGE JAMB MULLION SWEEP (2)PEMKO 318AV MILL-FIN. ALUMINUM CLOSER LCN 4111-3077CNS SP28 GRAY PAINT LEFT-HAND LEAF AS VIEWED FROM E 03 SECURED BUTT HINGE (3)HAGER BB1191 ANSI A2112 4.5x4.5 652 SATIN CHROMIUM ELECTRONIC LOCK SCHLAGE CO-100/C123/SPA 626 SATIN CHROMIUM CYPER LOCK STANDARD MOU CLOSER LCN 4011/4010-3077 SP28 GRAY PAINT DOOR-MOUNT ON ROOM SIDE- NOT V FLOOR STOP IVES FS13 / FS17 626 SATIN CHROMIUM AT DOORS OPENING AGAINST WALL; OVERHEAD STOP GLYNN-JOHNSON 410S 630 SATIN STAINLESS STEEL AT DOORS OPENING AGAINST FURNI KICK PLATE IVES 8400 630 SATIN STAINLESS STEEL PUSH SIDE ONLY; 8" x 2" LESS THAN D DOOR SCOPE IPI / DOOR SCOPE DS2000 SILVER PAINT ALUMINUM BODY, NOTE 1 SILENCERS IVES SR64 GRAY 04 PRIVACY BUTT HINGE (3)HAGER BB1191 ANSI A22112 4.5x4.5 652 SATIN CHROMIUM ELECTRONIC LOCK SCHLAGE CO-200/C123/SPA 626 SATIN CHROMIUM WITH PRIVACY FUNCTION - CYPER LO CLOSER LCN 4011/4010-3077 SP28 GRAY PAINT DOOR-MOUNT ON ROOM SIDE- NOT V FLOOR STOP IVES FS13 / FS17 626 SATIN CHROMIUM WITH R14 RISER AS REQUIRED KICK PLATE IVES 8400 630 SATIN STAINLESS STEEL PUSH SIDE ONLY; 8" x 2" LESS THAN D DOOR SCOPE IPI / DOOR SCOPE DS2000 SILVER PAINT ALUMINUM BODY- OMIT AT SDB VIEW SILENCERS IVES SR64 GRAY 04A STANDARD ATSDB VIEWING RM.---ALTERNATE AT RESTROOMS BY EXCEPTION BUTT HINGE (3)HAGER BB1191 ANSI A22112 4.5x4.5 652 SATIN CHROMIUM PRIVACY LOCK SCHLAGE ND50PD/C123/SPA 626 SATIN CHROMIUM PUSH-BUTTON PRIVACY INTERIOR / K CLOSER LCN 4011/4010-3077 SP28 GRAY PAINT OMIT AT SDB VIEWING ROOMS; DOOR FLOOR STOP IVES FS13 / FS17 626 SATIN CHROMIUM WITH R14 RISER AS REQUIRED KICK PLATE IVES 8400 630 SATIN STAINLESS STEEL PUSH SIDE ONLY; 8" x 2" LESS THAN D COAT HOOKS (2)IVES 581 626 SATIN CHROMIUM AT RESTROOMS ONLY, 1 AT 36" AFF, DOOR SCOPE IPI / DOOR SCOPE DS2000 SILVER PAINT ALUMINUM BODY- OMIT AT RESTROO SILENCERS IVES SR64 GRAY 04B RESTROOM BUTT HINGE (3)HAGER BB1191 ANSI A22112 4.5x4.5 652 SATIN CHROMIUM ELECTRONIC LOCK SCHLAGE CO-200/C123/SPA 626 SATIN CHROMIUM WITH PRIVACY FUNCTION - CYPER LO CLOSER LCN 4011/4010-3077 SP28 GRAY PAINT DOOR-MOUNT ON ROOM SIDE- NOT V FLOOR STOP IVES FS13 / FS17 626 SATIN CHROMIUM WITH R14 RISER AS REQUIRED KICK PLATE IVES 8400 630 SATIN STAINLESS STEEL PUSH SIDE ONLY; 8" x 2" LESS THAN D COAT HOOKS (2)IVES 581 626 SATIN CHROMIUM 36" AFF, 1 AT 60" AFF SILENCERS IVES SR64 GRAY 05PASSAGE BUTT HINGE (3)HAGER BB1191 ANSI A2112 4.5x4.5 652 SATIN CHROMIUM PASSAGE LATCH SET SCHLAGE ND10S/SPA 626 SATIN CHROMIUM INCLUDE MILLED GROOVES (/8SP) AT CLOSER LCN 4011/4010-3077 SP28 GRAY PAINT DOOR-MOUNT ON ROOM SIDE- NOT V FLOOR STOP IVES FS13 / FS17 626 SATIN CHROMIUM WITH R14 RISER AS REQUIRED KICK PLATE IVES 8400 630 SATIN STAINLESS STEEL PUSH SIDE ONLY; 8" x 2" LESS THAN D SILENCERS IVES SR64 GRAY 06UTILITY BUTT HINGE (3)HAGER BB1191 ANSI A2112 4.5x4.5 652 SATIN CHROMIUM STOREROOM LOCK SET SCHLAGE ND80PD/C123/SPA 626 SATIN CHROMIUM CLOSER LCN 4011/4010-3077 SP28 GRAY PAINT DOOR-MOUNT ON ROOM SIDE- NOT V CONCEALED OVERHEAD STOP/HOLDER GLYNN-JOHNSON 410H 630 SATIN STAINLESS STEEL OVERHEAD CONCEALED; OMIT AT LA KICK PLATE (2)IVES 8400 630 SATIN STAINLESS STEEL 8" x 2" LESS THAN DOOR WIDTH Provide documentationdemonstrating that the proposed electronic locks comply with 2015 IBC 1010.1.9.9. (35.5") 35.5" 35.5" S 8' - 0 " 3'-1 1/2" 5'- 6 " 3'- 5 " 2'- 1 " 1x4 EASED-EDGE S4S POPLAR WITH COUNTERSUNK SCREWS INTO WALL BLOCKING CONCEALED BEHIND HOOKS- PAINT TO MATCH WALL 4" TYP. WB-400 50% OF CABINET STORAGE FRONTAGE MUST BE WITHIN ACCESSIBLE REACH RANGE LVING FRONTAGE WITHIN REACH RANGE:140" FING FRONTAGE BEYOND REACH RANGE:(139")4C 1' - 0 " WB-400 " 1'- 0 " 3' - 0 " Locker rooms require an accessible bench per ICC A117.1-2009 section 803.4. TYPE A FIRE RATING -2 HR MINIMUMUL SYSTEM -U905CONCRETE MASONRY UNIT WALLSIDING -3/4" WOOD SIDINGFURRING -3/4" VERTICAL WOOD FURRINGAPPLIED WATERPROOF MEMBRANE7-5/8" CONCRETE MASONRY UNIT3'' RIGID INSULATION (R-15)STEEL STUD -2 1/2" 20 GA. STEEL STUD @ MAX 24" O.C.GYPSUM BOARD -(1) LAYER 5/8" GYPSUM BOARD TYPE B FIRE RATING -1 HRUL SYSTEM -U4231'-7 1/4" METAL RAINSCREEN OVER STEEL STUD (TOTAL WIDTH)METAL RAINSCREEN -2" METAL RAINSCREENAPPLIED WATERPROOF MEMBRANE3" RIGID INSULATION (R-15)DENS GLASS -(1) LAYER 5/8" DENS GLASS WITH LIQUIDFRAMING -6" STEEL STUDS @ MAX 16" O.C.AIR SPACE -2 1/2" AIR SPACEFRAMING -2 1/2" STEEL STUDS @ MAX 16" O.C.DENS GLASS -(1) LAYER 5/8" DENS GLASS WITH LIQUIDAPPLIED VAPOR BARRIERMETAL RAINSCREEN -2" METAL RAINSCREEN TYPE A1 FIRE RATING -2 HR MINIMUMUL SYSTEM -U905CONCRETE MASONRY UNIT WALL7-5/8" CONCRETE MASONRY UNITSTEEL STUD -21/2" 20 GA. STEEL STUD @ MAX 24" O.C.AIR SPACE -4" AIR SPACESTEEL STUD -2 1/2" 20 GA. STEEL STUD @ MAX 24" O.C.GYPSUM BOARD -(1) LAYER 5/8" GYPSUM BOARDMETAL RAINSCREEN -2" METAL RAINSCREEN WALL ASSEMBLIES:FLOOR & ROOF ASSEMBLIES: SLAB ON GRADE5" CAST IN PLACE CONCTRETE6" GRAVEL SECOND LEVEL FLOOR 3/4" PLYWOOD3/8" SOUND MAT3/4" PLYWOOD SECOND LEVEL PLAZA DECK FLOOR2" BRICK PAVERSAIRSPACE8"RIGID INSULATIONWATERPROOFING MEMBRANE3/4" DENS DECK GABLE ROOFACM WET SEAL SYSTEMEPDM MEMBRANE4" RIGID INSULATION1 1/2" 18 GA. METAL DECK WOOD SHINGLE ROOFWOOD SHAKE SHINGLEUNDERLAYMENT3/4" PLYWOOD4" RIGID INSULATION3/4" PLYWOOD TYPE A2 SHEAR WALL FIRE RATING -2 HR MINIMUMUL SYSTEM -U915CONCRETE MASONRY UNIT WALL 9 5/8" CONCRETE MASONRY UNIT TYPE A3 FIRE RATING -2 HR MINIMUMUL SYSTEM -U905SIDING -3/4" WOOD SIDINGFURRING -3/4" VERTICAL WOOD FURRINGAPPLIED WATERPROOF MEMBRANE3" RIGID INSULATION (R-15)7-5/8" CONCRETE MASONRY UNITSTEEL STUD -2 1/2" 20 GA. STEEL STUD @ MAX 24" O.C.GYPSUM BOARD -(1) LAYER 5/8" GYPSUM BOARD TYPE B1FIRE RATING -1 HRUL SYSTEM -U423 METAL RAINSCREEN -2" METAL RAINSCREENAPPLIED WATERPROOFMEMBRANE3" RIGID INSULATION (R-15)7 5/8" CONCRETE MASONRY UNITFRAMING -6" STEEL STUDS @ MAX 16" O.C.GYPSUM BOARD -(1) LAYER 5/8" GYPSUM BOARD TYPE C8FIRE RATING -1 HRUL SYSTEM -U423 SIDING -3/4" WOOD SIDINGFURRING -3/4" VERTICAL WOOD FURRINGAPPLIED WATERPROOF MEMBRANE3" RIGID INSULATION (R-15)DENS GLASS -(1) LAYER 5/8" DENS GLASS WITH LIQUIDFRAMING -8" STEEL STUDS @ MAX 16" O.C.7.5" BATT INSULATION (R-30)GYPSUM BOARD -(1) LAYER 5/8" GYPSUM BOARD TYPE E FIRE RATING -1 HR MINIMUMUL U419 or MEA 81-98-MGYPSUM BOARD -(1) LAYER 5/8" GYPSUM BOARDSTEEL STUD -3 5/8" 20 GA. STEEL STUD @ MAX 24" O.C.GYPSUM BOARD -(1) LAYER 5/8" GYPSUM BOARD SOUND INSULATION BETWEEN TENANTS TYPE FFIRE RATING -2 HR MINIMUMUL SYSTEM -U905STAIRS SHAFTCONCRETE MASONRY UNIT WALL SIDING -3/4" WOOD SIDING AT THE EXTERIOR OF THE WALLFURRING -3/4" VERTICAL WOOD FURRING7-5/8" CONCRETE MASONRY UNIT TYPE GFIRE RATING -0.5 HR MINIMUMUL U419 or MEA 81-98-M GYPSUM BOARD -(1) LAYER 5/8" GYPSUM BOARDSTEEL STUD -2 1/2" 20 GA. STEEL STUD @ MAX 24" O.C.GYPSUM BOARD -(1) LAYER 5/8" GYPSUM BOARD TYPE D FIRE RATING -1 HRUL SYSTEM -U423SIDING -3/4" WOOD SIDINGFURRING -3/4" VERICAL WOOD FURRINGAPPLIED WATERPROOF MEMBRANE3" RIGID INSULATION (R-15)7-5/8" CONCRETE MASONRY UNITSTEEL STUD -2 1/2" 20 GA. STEEL STUD @ MAX 24" O.C.GYPSUM BOARD -(1) LAYER 5/8" GYPSUM BOARD TYPE A4 FIRE RATING -2 HR MINIMUMUL SYSTEM -U905 7-5/8" CONCRETE MASONRY UNIT3" RIGID INSULATION (R-15)STEEL STUD -2 1/2" 20 GA. STEEL STUD @ MAX 24" O.C.GYPSUM BOARD -(1) LAYER 5/8" GYPSUM BOARD TYPE E1 FIRE RATING -1 HR MINIMUMUL U419 or MEA 81-98-MGYPSUM BOARD -(1) LAYER 5/8" GYPSUM BOARDSTEEL STUD -6" 20 GA. STEEL STUD @ MAX 24" O.C.GYPSUM BOARD -(1) LAYER 5/8" GYPSUM BOARD SOUND INSULATION BETWEEN TENANTS TYPE D1 FIRE RATING -1 HRUL SYSTEM -U423SIDING -3/4" WOOD SIDINGFURRING -3/4" VERICAL WOOD FURRINGAPPLIED WATERPROOF MEMBRANE3" RIGID INSULATION (R-15)7-5/8" CONCRETE MASONRY UNIT STC: 49DESIGN STC RATING STC: 49DESIGN STC RATING TYPE G1 FIRE RATING -0.5 HR MINIMUMUL U419 or MEA 81-98-M GYPSUM BOARD -(1) LAYER 5/8" GYPSUM BOARDSTEEL STUD -2 1/2" 20 GA. STEEL STUD @ MAX 24" O.C. TYPE C6FIRE RATING -1 HRUL SYSTEM -U423 SIDING -3/4" WOOD SIDINGFURRING -3/4" VERTICAL WOOD FURRINGAPPLIED WATERPROOF MEMBRANE3" RIGID INSULATION (R-15)DENS GLASS -(1) LAYER 5/8" DENS GLASS WITH LIQUIDFRAMING -6" STEEL STUDS @ MAX 16" O.C.5.25" BATT INSULATION (R-21)GYPSUM BOARD -(1) LAYER 5/8" GYPSUM BOARD FIREPROOF SEALANT DEEP LEG DEFLECTION TRACK STEEL STUD FRAMING, SEE PLAN FOR SIZE AND WALL TYPE (1) OR (2) LAYER OF TYPE 'X' GYP. BD., SEE PLAN FOR WALL TYPE ACOUSTICAL SEALANT 1/2" T 0 1 " G A P CLIP ANGLE MECHANICALLY FASTENED TO UNDERSIDE OF STRUCTURE, SEE STRUC. DWGS.FIREPROOF SEALANT MINERAL WOOL FIRESTOP INSULATION GROUT AND REINFORCEMENT AS REQUIRED SOLID CMU AT TOP COURSE FIREPROOF SEALANT Scale PROJECT NUMBER DATE DRAWN BY CHECKED BY modif. modif. As indicated 11/12 / 2 0 1 8 1 0 : 1 2 : 4 7 A M G−005 2016−005 11.12.18 WALL TYPES CO R E & S H E L L B U I L D I N G 232 E . M A I N S T . ASP E N , C O 1 1/2" = 1'-0"1 DEFLECTION TRACK DETAIL 1 1/2" = 1'-0"2CMU RATED WALL DETAIL NO. DATE BY REVISION 1 05.09.18 MODIF.SCHEMATIC DESIGN 2 07.13.18 MODIF.DESIGN DEVELOPMENT 3 09.6.18 MODIF.90% PERMIT SET 4 9.25.18 MODIF.PERMIT SET Provide callouts toeach wall, floor, androof type in the plans,sections, and/or wallsections. Revisethermal envelopeComcheck to use thesame naming labelsas these wall, floor,and roof types. TYPE AFIRE RATING -2 HR MINIMUMUL SYSTEM -U905CONCRETE MASONRY UNIT WALLSIDING -3/4" WOOD SIDINGFURRING -3/4" VERTICAL WOOD FURRINGAPPLIED WATERPROOF MEMBRANE7-5/8" CONCRETE MASONRY UNIT3'' RIGID INSULATION (R-15)STEEL STUD -2 1/2" 20 GA. STEEL STUD @ MAX 24" O.C.GYPSUM BOARD -(1) LAYER 5/8" GYPSUM BOARD TYPE BFIRE RATING -1 HRUL SYSTEM -U4231'-7 1/4" METAL RAINSCREEN OVER STEEL STUD (TOTAL WIDTH)METAL RAINSCREEN -2" METAL RAINSCREENAPPLIED WATERPROOF MEMBRANE3" RIGID INSULATION (R-15)DENS GLASS -(1) LAYER 5/8" DENS GLASS WITH LIQUIDFRAMING -6" STEEL STUDS @ MAX 16" O.C.AIR SPACE -2 1/2" AIR SPACEFRAMING -2 1/2" STEEL STUDS @ MAX 16" O.C.DENS GLASS -(1) LAYER 5/8" DENS GLASS WITH LIQUIDAPPLIED VAPOR BARRIERMETAL RAINSCREEN -2" METAL RAINSCREEN TYPE A1 FIRE RATING -2 HR MINIMUMUL SYSTEM -U905CONCRETE MASONRY UNIT WALL 7-5/8" CONCRETE MASONRY UNITSTEEL STUD -21/2" 20 GA. STEEL STUD @ MAX 24" O.C.AIR SPACE -4" AIR SPACESTEEL STUD -2 1/2" 20 GA. STEEL STUD @ MAX 24" O.C.GYPSUM BOARD -(1) LAYER 5/8" GYPSUM BOARDMETAL RAINSCREEN -2" METAL RAINSCREEN WALL ASSEMBLIES:FLOOR & ROOF ASSEMBLIES: SLAB ON GRADE 5" CAST IN PLACE CONCTRETE6" GRAVEL SECOND LEVEL FLOOR 3/4" PLYWOOD3/8" SOUND MAT3/4" PLYWOOD SECOND LEVEL PLAZA DECK FLOOR 2" BRICK PAVERSAIRSPACE8"RIGID INSULATIONWATERPROOFING MEMBRANE3/4" DENS DECK GABLE ROOF ACM WET SEAL SYSTEMEPDM MEMBRANE4" RIGID INSULATION1 1/2" 18 GA. METAL DECK WOOD SHINGLE ROOF WOOD SHAKE SHINGLEUNDERLAYMENT3/4" PLYWOOD4" RIGID INSULATION3/4" PLYWOOD TYPE A2 SHEAR WALLFIRE RATING -2 HR MINIMUMUL SYSTEM -U915CONCRETE MASONRY UNIT WALL9 5/8" CONCRETE MASONRY UNIT TYPE A3 FIRE RATING -2 HR MINIMUMUL SYSTEM -U905 SIDING -3/4" WOOD SIDINGFURRING -3/4" VERTICAL WOOD FURRINGAPPLIED WATERPROOF MEMBRANE3" RIGID INSULATION (R-15)7-5/8" CONCRETE MASONRY UNITSTEEL STUD -2 1/2" 20 GA. STEEL STUD @ MAX 24" O.C.GYPSUM BOARD -(1) LAYER 5/8" GYPSUM BOARD TYPE B1 FIRE RATING -1 HRUL SYSTEM -U423 METAL RAINSCREEN -2" METAL RAINSCREENAPPLIED WATERPROOFMEMBRANE3" RIGID INSULATION (R-15)7 5/8" CONCRETE MASONRY UNITFRAMING -6" STEEL STUDS @ MAX 16" O.C.GYPSUM BOARD -(1) LAYER 5/8" GYPSUM BOARD TYPE C8 FIRE RATING -1 HRUL SYSTEM -U423 SIDING -3/4" WOOD SIDINGFURRING -3/4" VERTICAL WOOD FURRINGAPPLIED WATERPROOF MEMBRANE3" RIGID INSULATION (R-15)DENS GLASS -(1) LAYER 5/8" DENS GLASS WITH LIQUIDFRAMING -8" STEEL STUDS @ MAX 16" O.C.7.5" BATT INSULATION (R-30)GYPSUM BOARD -(1) LAYER 5/8" GYPSUM BOARD TYPE E FIRE RATING -1 HR MINIMUMUL U419 or MEA 81-98-M GYPSUM BOARD -(1) LAYER 5/8" GYPSUM BOARDSTEEL STUD -3 5/8" 20 GA. STEEL STUD @ MAX 24" O.C.GYPSUM BOARD -(1) LAYER 5/8" GYPSUM BOARD SOUND INSULATION BETWEEN TENANTS TYPE F FIRE RATING -2 HR MINIMUMUL SYSTEM -U905STAIRS SHAFT CONCRETE MASONRY UNIT WALL SIDING -3/4" WOOD SIDING AT THE EXTERIOR OF THE WALLFURRING -3/4" VERTICAL WOOD FURRING7-5/8" CONCRETE MASONRY UNIT TYPE G FIRE RATING -0.5 HR MINIMUMUL U419 or MEA 81-98-MGYPSUM BOARD -(1) LAYER 5/8" GYPSUM BOARDSTEEL STUD -2 1/2" 20 GA. STEEL STUD @ MAX 24" O.C.GYPSUM BOARD -(1) LAYER 5/8" GYPSUM BOARD TYPE D FIRE RATING -1 HRUL SYSTEM -U423 SIDING -3/4" WOOD SIDINGFURRING -3/4" VERICAL WOOD FURRINGAPPLIED WATERPROOF MEMBRANE3" RIGID INSULATION (R-15)7-5/8" CONCRETE MASONRY UNITSTEEL STUD -2 1/2" 20 GA. STEEL STUD @ MAX 24" O.C.GYPSUM BOARD -(1) LAYER 5/8" GYPSUM BOARD TYPE A4 FIRE RATING -2 HR MINIMUMUL SYSTEM -U905 7-5/8" CONCRETE MASONRY UNIT3" RIGID INSULATION (R-15)STEEL STUD -2 1/2" 20 GA. STEEL STUD @ MAX 24" O.C.GYPSUM BOARD -(1) LAYER 5/8" GYPSUM BOARD TYPE E1 FIRE RATING -1 HR MINIMUMUL U419 or MEA 81-98-MGYPSUM BOARD -(1) LAYER 5/8" GYPSUM BOARDSTEEL STUD -6" 20 GA. STEEL STUD @ MAX 24" O.C.GYPSUM BOARD -(1) LAYER 5/8" GYPSUM BOARDSOUND INSULATION BETWEEN TENANTS TYPE D1FIRE RATING -1 HRUL SYSTEM -U423 SIDING -3/4" WOOD SIDINGFURRING -3/4" VERICAL WOOD FURRINGAPPLIED WATERPROOF MEMBRANE3" RIGID INSULATION (R-15)7-5/8" CONCRETE MASONRY UNIT STC: 49DESIGN STC RATING STC: 49DESIGN STC RATING TYPE G1 FIRE RATING -0.5 HR MINIMUMUL U419 or MEA 81-98-M GYPSUM BOARD -(1) LAYER 5/8" GYPSUM BOARDSTEEL STUD -2 1/2" 20 GA. STEEL STUD @ MAX 24" O.C. TYPE C6FIRE RATING -1 HRUL SYSTEM -U423 SIDING -3/4" WOOD SIDINGFURRING -3/4" VERTICAL WOOD FURRINGAPPLIED WATERPROOF MEMBRANE3" RIGID INSULATION (R-15)DENS GLASS -(1) LAYER 5/8" DENS GLASS WITH LIQUIDFRAMING -6" STEEL STUDS @ MAX 16" O.C.5.25" BATT INSULATION (R-21)GYPSUM BOARD -(1) LAYER 5/8" GYPSUM BOARD FIREPROOF SEALANT DEEP LEG DEFLECTION TRACK STEEL STUD FRAMING, SEE PLAN FOR SIZE AND WALL TYPE (1) OR (2) LAYER OF TYPE 'X' GYP. BD., SEE PLAN FOR WALL TYPE ACOUSTICAL SEALANT 1/2" T 0 1 " G A P CLIP ANGLE MECHANICALLY FASTENED TO UNDERSIDE OF STRUCTURE, SEE STRUC. DWGS.FIREPROOF SEALANT MINERAL WOOL FIRESTOP INSULATION GROUT AND REINFORCEMENT AS REQUIRED SOLID CMU AT TOP COURSE FIREPROOF SEALANT Scale PROJECT NUMBER DATE DRAWN BY CHECKED BY modif. modif. As indicated 11/1 2 / 2 0 1 8 1 0 : 1 2 : 4 7 A M G−005 2016−005 11.12.18 WALL TYPES CO R E & S H E L L B U I L D I N G 232 E . M A I N S T . ASP E N , C O 1 1/2" = 1'-0"1DEFLECTION TRACK DETAIL 1 1/2" = 1'-0"2 CMU RATED WALL DETAIL NO. DATE BY REVISION 1 05.09.18 MODIF.SCHEMATIC DESIGN 2 07.13.18 MODIF.DESIGN DEVELOPMENT 3 09.6.18 MODIF.90% PERMIT SET 4 9.25.18 MODIF.PERMIT SET You list all of yourwalls as having a firerating but very few ofyour walls require it.This could causeconfusion duringconstruction andinspection for dealingwith penetrations. Irecommend you onlynote the walls that arerequired to be rated asrated (the West wallon the property line,possibly the roof ontop of it, and theelevator shaft). Page: G-005 WALL TYPES File Name: Architectural.232 E. Main St.2018.11.pdf Subject: PlanCheck Author: nickt Color: This detail has no insulation. Page: G-005 WALL TYPES File Name: Architectural.232 E. Main St.2018.11.pdf Subject: PlanCheck Author: nickt Color: Provide documentation that the roof assemblies are Class A. This is typically either an ESR or UL report. Revise you roof details to match the report(s). (Ordinance 40, 2016) Page: G-007 OCCUPANCY & MEANS OF EGRESS PLANS File Name: Architectural.232 E. Main St.2018.11.pdf Subject: PlanCheck Author: nickt Color: The exit access stair qualifies as designed as the vertical path for accessible means of egress (2015 IBC 1009.3). However, a two-way communication system complying with 2015 IBC 1009.8 is required at the elevator. Page: G-007 OCCUPANCY & MEANS OF EGRESS PLANS File Name: Architectural.232 E. Main St.2018.11.pdf Subject: PlanCheck Author: nickt Color: Measure the common path travel distance from the most remote point 2' off the walls. Measure following the angle of the stairs. Total distance from most remote point to the exit stair on the main level (or other protected exit) may not exceed 75'. I measure 105'-10". 2015 IBC table 1006.3.2(2) Page: G-007 OCCUPANCY & MEANS OF EGRESS PLANS File Name: Architectural.232 E. Main St.2018.11.pdf Subject: PlanCheck Author: nickt Color: Measure fire separation distance to the center line of the alley. This should allow the back walls to be unrated. 2015 IBC 202. CONCRETE MASONRY UNIT WALL SIDING -3/4" WOOD SIDING FURRING -3/4" VERTICAL WOOD FURRING APPLIED WATERPROOF MEMBRANE 7-5/8" CONCRETE MASONRY UNIT 3'' RIGID INSULATION (R-15) STEEL STUD -2 1/2" 20 GA. STEEL STUD @ MAX 24" O.C. GYPSUM BOARD -(1) LAYER 5/8" GYPSUM BOARD TYPE A1 FIRE RATING -2 HR MINIMUM UL SYSTEM -U905 CONCRETE MASONRY UNIT WALL 7-5/8" CONCRETE MASONRY UNIT STEEL STUD -21/2" 20 GA. STEEL STUD @ MAX 24" O.C. AIR SPACE -4" AIR SPACE STEEL STUD -2 1/2" 20 GA. STEEL STUD @ MAX 24" O.C. GYPSUM BOARD -(1) LAYER 5/8" GYPSUM BOARD METAL RAINSCREEN -2" METAL RAINSCREEN TYPE A2 SHEAR WALL FIRE RATING -2 HR MINIMUM UL SYSTEM -U915 CONCRETE MASONRY UNIT WALL 9 5/8" CONCRETE MASONRY UNIT This detail has no insulation. FLOOR & ROOF ASSEMBLIES: SLAB ON GRADE 5" CAST IN PLACE CONCTRETE6" GRAVEL SECOND LEVEL FLOOR 3/4" PLYWOOD 3/8" SOUND MAT 3/4" PLYWOOD SECOND LEVEL PLAZA DECK FLOOR 2" BRICK PAVERS AIRSPACE 8"RIGID INSULATION WATERPROOFING MEMBRANE 3/4" DENS DECK GABLE ROOF ACM WET SEAL SYSTEM EPDM MEMBRANE 4" RIGID INSULATION 1 1/2" 18 GA. METAL DECK WOOD SHINGLE ROOF WOOD SHAKE SHINGLE UNDERLAYMENT 3/4" PLYWOOD 4" RIGID INSULATION 3/4" PLYWOODOOD FURRING MBRANE " DENS GLASS WITH LIQUID @ MAX 16" O.C. ) R 5/8" GYPSUM BOARD OD FURRINGMBRANE Y UNITSTEEL STUD @ MAX 24" O.C.R 5/8" GYPSUM BOARD OD FURRING MBRANE Y UNIT Provide documentation that the roof assemblies are Class A. This is typically either an ESR or UL report. Revise you roof details to match the report(s). (Ordinance 40, 2016) DN 1,380 2,0001,380 2,000 MECH. EQ. ELEV. ROOF LADDER 8 8.5 9 10 C.2 C.4 E.8 F.8 EXIT 12" A.F.F. The exit access stair qualifies as designed as the vertical path for accessible means of egress (2015 IBC 1009.3). However, a two-way communication system complying with 2015 IBC 1009.8 is required at the elevator. TRAVEL DISTANCE EXIT DISCHARGE LEGEND : CEILING MOUNTED EXIT SIGN WALL MOUNTED EXIT SIGN EX I T SD SMOKE DETECTOR 3 HR FIRE SEPA 1 HR FIRE SEPARATION FIRE SEPARATION PER TABLE 602 REQUIRED FIRE SEPARATION PROVIDED FIRE 1 HR FIRE SEPARATION DISTANCE X ≤5 5 ≤X <10 X ≥30 10 ≤X <30 1 HR FIRE SEPARATION 0 HR FIRE SEPARATION 0 HR FIRE SEPARATION 3 HR FIRE SEPA 0 HR FIRE S 0 HR FIRE S 2 HR FIRE SEPARATION SECOND FLOOR TENANT SPACE- 'B' 200 76 ' -0'' T R A V E L D I S T A N C E Measure the common path travel distance from the most remote point 2' off the walls. Measure following the angle of the stairs. Total distance from most remote point to the exit stair on the main level (or other protected exit) may not exceed 75'. I measure 105'-10". 2015 IBC table 1006.3.2(2) UP DN 1,380 2,0001,380 2,000 TRAVEL DISTANCE EXIT DISCHARGE LEGEND : CEILING MOUNTED EXIT SIGN WALL MOUNTED EXIT SIGN EXI T SD SMOKE DETECTOR CONSTRUCTION TYPE: TYPE V-B , NEW CONSTRUCTION , FULLY SPRINKLEREDTOTAL EXTIS : ONE EXIT PER SPACE PROVIDED.ONE EXIT REQUIRED PER TABLE 1006.2.1. OCCUPANCY CLASS: B FULLY SPRINKLERED BUILDING WITH FIRE ALARM STATIONTWO STORY BUILDING AREA : 6,111.6 S.F.BUILDING HEIGHT : 13' 0" ESTIMATED TOTAL OCCUPANTS : AREA/ 100 GROSS (PER TABLE 1004.1.2)61.2 = 62 OCCUPANT DOORWAY EXIT WIDTH REQUIRED FOR SPRINKELRED BUILDING 62X.15= 9.3", MIN REQ. = 36" ACTUAL DOORWAY WIDTHS:DOOR #1: (1) @ 36"W = 36" TOTAL DOORWAY WIDTH SUPPLIED = 36" (COMPLIES) STAIRWAY EXIT WIDTH REQUIRED FOR A SPRINKLERED BUILDING:62 x .2 INCHES PER PERSON =12.4 INCHES REQUIRED. (44" MIN.)ACTUAL WIDTHS:STAIR #1: (1) @ 44"W = 44"TOTAL STAIRWAY WIDTH SUPPLIED = 44" (COMPLIES) MAX LENGTH REQUIRED (EXIT ACCESS TRAVEL W/ SPRINKLERS): 250'-0"MAX LENGTH PROVIDED: 84' 6'' (COMPLIES) HORIZONTAL REQ'D. SEPARATION OF OCCUPANCIES FLOOR OCCUPANCY MAIN SEPARATION N = NO SEPARATION REQUIRED NSECOND LEVEL B B 3 HR FIRE SEPARATION 1 HR FIRE SEPARATION FIRE SEPARATION PER TABLE 602 REQUIRED FIRE SEPARATION PROVIDED FIRE SEPARATION 1 HR FIRE SEPARATION DISTANCE X ≤5 5 ≤X <10 X ≥30 10 ≤X <30 1 HR FIRE SEPARATION 0 HR FIRE SEPARATION 0 HR FIRE SEPARATION 3 HR FIRE SEPARATION 0 HR FIRE SEPARATION 0 HR FIRE SEPARATION 2 HR FIRE SEPARATION OUTDOOR DECK TENANT SPACE 'A'100 TENANT SPACE 'B'LOBBY101 FENCED EXTERIORTRASH AND UTILITYAREA103 MECH. RM.102 ELEV. 94' 6'' TRAVEL DISTANCE 57' 6'' TRAVEL DISTANCE 31' 7'' TRAVEL DISTANCE 3" 10'- 0 " 5'-3" 5'-0" 74'-9 1/2" 56'-6 5/8" 2 3 4 5 6 7 8 8.5 9 10 C.2 C.4 E.8 F.8 3'-0" EX I T EX I T 6'-0 " 5'-1 1 7 / 8 " 12" A.F.F. EXI T 12" A.F.F. EX I T EGRESSACCESS STAIR 31' 0 ' ' T R A V E L D I S T A N C E OPEN TO BELOW OUTDOOR TERRACE MECH. EQ. SECOND FLOORTENANT SPACE- 'B'200 ELEV. 76'-0'' T R A V E L D I S T A N C E ROOF LADDER 2 3 4 5 6 7 8 8.5 9 10 C.2 C.4 E.8 F.8 EXIT12" A.F.F. PROJECT NUMBER DATE DRAWN BY CHECKED BY modif. modif. 2016−005 11.12.18 CO R E & S H E L L B U I L D I N G 23 2 E . M A I N S T . AS P E N , C O NO. DATE BY REVISION 1 05.09.18 MODIF.SCHEMATIC DESIGN 2 07.13.18 MODIF.DESIGN DEVELOPMENT 3 09.6.18 MODIF.90% PERMIT SET 4 9.25.18 MODIF.PERMIT SET Measure fire separation distance tothe center line of thealley. This should allowthe back walls to beunrated. 2015 IBC202. Page: G-007 OCCUPANCY & MEANS OF EGRESS PLANS File Name: Architectural.232 E. Main St.2018.11.pdf Subject: PlanCheck Author: nickt Color: The elevator shaft connects only 2 stories, requiring only 1 hour fire separation. 2015 IBC 713.4. Page: G-008 FIRE RESISTANCE SITE PLAN File Name: Architectural.232 E. Main St.2018.11.pdf Subject: Transformer Author: nickt Color: City of Aspen Transformer / Building Separation Requirements. Indicate the quantity of oil in the transformer and if the oil is FM approved fluid or mineral oil. Indicate the construction of the adjacent building and the distance from the transformer. Demonstrate compliance with the table below: Page: [1] E1.0 File Name: Electrical.232 E. Main St.2018.11.pdf Subject: PlanCheck Author: nickt Color: Provide time-switch controls and daylight responsive controls as required by 2015 IECC C405.2.2 and C405.2.3. Electrical.232 E. Main St.2018.11.pdf (3) Page: [3] 18029-E1 (D-64)-E2.0 File Name: Electrical.232 E. Main St.2018.11.pdf Subject: Electrical Code Author: mitchm Color: MDP location behind enclosure to be verified by COA Electric Dept if applicable & COA Fire Dept Page: [5] 18029-E1 (D-64)-E2.2 File Name: Electrical.232 E. Main St.2018.11.pdf Subject: PlanCheck Author: nickt Color: Provide automatic controls including timer and temperature sensor for the ice melt system per Ordinance 11, 2011. DN2,000 2,000 TRAVEL DISTANCE EXIT DISCHARGE LEGEND : CEILING MOUNTED EXIT SIGN T ESTIMATED TOTAL OCCUPANTS : AREA/ 100 GROSS (PER TABLE 1004.1.2) 61.2 = 62 OCCUPANT DOORWAY EXIT WIDTH REQUIRED FOR SPRINKELRED BUILDING 62X.15= 9.3", MIN REQ. = 36" ACTUAL DOORWAY WIDTHS: DOOR #1: (1) @ 36"W = 36" TOTAL DOORWAY WIDTH SUPPLIED = 36" (COMPLIES) STAIRWAY EXIT WIDTH REQUIRED FOR A SPRINKLERED BUILDING: 62 x .2 INCHES PER PERSON = 12.4 INCHES REQUIRED. (44" MIN.) ACTUAL WIDTHS: STAIR #1: (1) @ 44"W = 44" TOTAL STAIRWAY WIDTH SUPPLIED = 44" (COMPLIES) MAX LENGTH REQUIRED (EXIT ACCESS TRAVEL W/ SPRINKLERS): 250'-0" MAX LENGTH PROVIDED: 84' 6'' (COMPLIES) HORIZONTAL REQ'D. SEPARATION OF OCCUPANCIES FLOOR OCCUPANCY MAIN SEPARATION N = NO SEPARATION REQUIRED N SECOND LEVEL B B 1 HR FIRE SEPARATION 2 HR FIRE SEPARATION Q. SECOND FLOOR TENANT SPACE- 'B' 200 ELEV. 76 ' -0'' T R A V E L D I S T A N C E EXIT 12" A.F.F. The elevator shaft connects only 2 stories, requiring only 1 hour fire separation. 2015 IBC 713.4. T A PROP 2 ST BUIL HIS T O R I C C O R T I N A L O D G E 10 ' - 0 " 13'-0" 5'-3 " 4'-9 " TRANSFORMER 3" 10' - 2 3 / 8 " 10. 1 9 5 ' C/L R.O.W. City of Aspen Transformer / Building Separation Requirements. Indicate the quantity of oil in the transformer and if the oil is FM approved fluid or mineral oil. Indicate the construction of the adjacent building and the distance from the transformer. Demonstrate compliance with the table below: E. M A I N S T . PA T I O ADJACENT TENANT NOT PART OF CHASE INSULATED STOREFRONT INSULATED STOREFRONT UP 123456788.5910 A B C D E F G C.2 C.4 E.8 F.8 E C-1 L B-3 A C K UP E C-1 B-3 A E K F E. M A I N S T . PA T I O ADJACENT TENANT NOT PART OF CHASE INSULATED STOREFRONT INSULATED STOREFRONT UP 123456788.5910 A B C D E F G C.2 C.4 E.8 F.8 E C-1 L B-3 A C K L-11L11 L-11 L-11L-11 L-11 L-11 L-11 L-11 L-11L-11 L-11 L-11 L-11 L-11L-11 L-11 L-11 L-11 L-11 L-11 L-11 L-11 L-11 L-11 L-11 L-11 L-11 L-11 L-11 L-11 L-11 L-11 L-11 L-11 L-11 L-11 L-11 L-11 L-11 L-11 L-11 L-11 L-11 E E E L-57 0 L-570 L-40 2 NL L-40 2 NL L-40 2 NLL-40 2 NL L-2L-2L-2 L-2 L-2 L-2 L-2 L-2 L-2 L-2 L-2 L-2 L-2 L-2 109 COR R I D O R 103DAB 106 MAN U A L T R A N S A C T I O N 10 5 CA F E 104 LIV I N G R O O M 117 LO U N G E 107 PRIN T E R S 119DAT A 114 COR R I D O R 101 TRA N S A C T I O N V E S T I B U L E 118 JAN I T O R 115 WOM E N S 116MEN S 11 0 PCS 2 108 CM S 1 111 PC S 3 112 PC S 4 113 PC S 5 102 LO B B Y L-3 L-3 L-3 L-20 L-20 L-20 L-20 L-20 NIC ADJ A C E N T T E N A N T NIC MEC H A N I C A L R O O M L-580 L-580 L-580 L-580 L-560 L-560 L-560 L-560L-560 L-560 L-550L-550L-550L-550 L-530 L-2 L-11 L-11 L-11 L-11 L-11 L-11 L-11 L-11 WAPM OS WAPM OS WAPM OS $ WAPM OS WAPM OS OS WAPM OS $ $ WAPM OS WAPMOS WAPM OS $$ $ $ $ WAPMz14A z14A z14B z14B z14C z14C WAPM WAPM WAPM z15A z14D z21A z21A z21B z21B z21B z18 $ Z17A Z15B Z15B z16 z16 z16 z19 z19 z11A z11B z8NL L-2 z14A z14A z14B z14B z14C Z14D z14D z14E z14E z21A z21B WAPM z18 z18 Z9D Z9D z9D z9D z24 z24 z16 z19 $z19 z8NL z8NL-EM z8NL z8NL z8NL z8NL-EM z8NL z8NL z8NL z11A z11A z11A z11A z11A z11A z11A z11Az11A z11B z11B z11B z11B z11B z11B z11B z11B z11B z11C z11C z11C z11C z11C z11C z11C z11C z11C z11C z11D z11D z11D z11D z11D z11D z11D z11D z11D z11D z11E z11A, B, C, D,E z15A,BLOBBY LIGHTINGMANUAL DIMMERS z19 SE SE SE SE SE SE SE SE SE SE SE SE SE SE z21A z24 z15A WAPM (TYP) $z24 z24 CH70-1 CH70-1 CH70-1 CH70-1 CH70-1 z14CCH70-1 CH70-1 z14DCH70-1 z14ECH70-1 z14ECH70-1 CH70-9 z18CH70-9 z18CH70-9 CH70-9 SE CH70-9 CH70-9 CH70-9 CH70-9 CH70-9 CH70-9 CH70-9 CH70-9 CH70-9 CH400-9 CH70-9 CH70-9 CH70-3 CH70-3 CH70-3 CH70-3 CH70-3 CH70-3 CH70-3 z15ACH70-3 z15ACH70-3 z15ACH70-3 SE CH400-3 CH70-3 CH70-5 CH70-5 CH70-5 CH70-5 CH70-5 CH70-5 CH70-5 CH70-5 CH70-5 CH70-5 CH70-5 CH70-5 CH70-5 CH70-5 CH70-5 CH70-5 CH70-5 CH70-5 CH70-5 CH70-5 CH70-5 CH70-5 CH70-5 CH70-5 CH70-5 CH70-7 CH70-7 CH70-7 CH70-7 CH70-7 CH70-7 CH70-7 CH70-7 CH70-7 CH70-7 CH70-7 CH70-7 CH70-7 CH70-7 CH70-7 CH70-7 CH70-7 CH70-7 CH70-7 CH70-7 CH70-7 CH70-7 CH70-7 CH70-7 CH70-7 CH70-7 L-308 L-408BCH70-7 L-408CCH70-7 L-408ACH70-7 z11E z11E z11E $$$ CH70-5 CH70-5 WGA OS OSz24WGA WGA z8NLCH70-5 I.6 REFER TO SIGNAGEPACKAGE FORADDITIONALREQUIREMENTS. REFER TO SIGNAGEPACKAGE FORADDITIONALREQUIREMENTS. I.7CH70-2 CH70-4 Z5 Z5 CH70-6Z4 CH70-8Z4 CH70-230A-1PNEMA-1 30A-1PNEMA-1 30A-1PNEMA-1 30A-1PNEMA-1 3.ALL EXIT SIGNS SHALL BE PROVIDED WITH A 90 MINUTE EMERGENCY BATTERY PACK ANDCONNECTED TO LOCAL LIGHTING CIRCUIT, AHEAD OF ANY LOCAL SWITCHING. ALL FIXTURESWITH EMERGENCY BATTERY PACKS ARE NOTED WITH EM AND CONNECTED TO BECONTROLLED AS INDICATED UNLESS OTHERWISE NOTED. PROVIDE SEPARATED IDENTIFIEDNEUTRALS FOR EMERGENCY LIGHTS AND EXIT SIGNS. 4.INSTALL JUNCTION BOXES FOR SIGNAGE AS CLOSE TO CENTER OF SIGNAGE AS POSSIBLE. 5.COORDINATE LOCATIONS OF ALL LUMINARIES WITH ARCHITECTURAL DRAWINGS. NOTIFYARCHITECT OF ANY DISCREPANCIES. 6.ELECTRICAL CONTRACTOR SHALL PROVIDE ALL LOW VOLTAGE WIRING FOR LIGHTINGCONTROL SYSTEM AS REQUIRED. VERIFY QUANTITY AND REQUIREMENTS WITHMANUFACTURER PRIOR TO WORK 7.CONTRACTOR TO PROVIDE A FULLY OPERATIONAL LIGHTING CONTROL SYSTEM. 8.SECURELY FASTEN EACH RECESSED LIGHT FIXTURE TO THE CEILING SYSTEM WITH APPROPRIATESUPPORT BRACKETS AND CLIPS PER INDUSTRY STANDARDS. 9.DAINTREE WIRELESS DEVICE CONTROLS REPLACE TYPICAL HARDWIRED SWITCHING ANDWIRING REQUIREMENTS, THE CONDUIT SYSTEM IS NOT REQUIRED FOR THE CONTROL DEVICESASSOCIATED WITH THE BMS SYSTEM UNLESS OTHERWISE NOTED. SCALEELECTRICAL REFLECTED CEILING PLAN 11/4"=1'-0" 1.LUMINAIRES INDIACTED AS 'SE' SHALL BE CONTROLLED WITH OTHER FIXTURES WITHIN THESPECIFIED ZONE. THEY SHALL BE PROVIDED WITH ALL REQUIRED CONTROL DEVICES TOSYNCHRONIZE WITHIN THE ZONE LUMINAIRES. 2.ALL LUMINAIRES CONTAINED IN A DEFINED ZONE MUST BE DAISY CHAINED WITH 0-10VDIMMING WIRE TO THE RESPECTIVE ZONE WA100-PM 3.ALL LUMINAIRES SHALL BE 0-10V DIMMING FOR DAINTREE TO PROVIDE DIMMING CONTROL. 4.ALL WA100-PM WIRELESS ADAPTERS SHALL BE PROVIDED WITH UNINTERRUPTED POWER ANDSWITCH THE RESPECTIVE LUMINAIRES IN SPECIFIED ZONE. ZONES ARE LABELED BY LETTER. 5.ELECTRICAL CONTRACTOR SHALL PERFORM WIRELESS ADAPTER TEST DURING/POST INSTALL.SEE WA100-PM INSTALLATION GUIDE FOR INSTRUCTIONS. 6.REFER TO ELECTRICAL DETAILS FOR ADDITIONAL REQUIREMENTS AND WIRING DIAGRAMS. DAINTREE CONTROL NOTES 4 EXTERIOR BUILDING SIGNAGE PHOTOCELL TIMER SOFTWARE CONTROL WIRELESS5EXTERIOR-FACING INTERIOR SIGNAGE AND/OR WALL-WASH CANS TIMER TIMER SOFTWARE CONTROL WIRELESS 6 NOT USED 7 NOT USED 8 VESTIBULE (ALWAYS ON)------------1 9 DESK PENDANTS (ALWAYS ON)------------3 10A, 10B…NOT USED ------11A, 11B..LOBBY RECESSED CANS ------WALL DIMMER AT PRINTERS 2 12A, 12B NOT USED ------2 13 NOT USED ------2 14A, 14B…OFFICE AND CONFERENCE GRID STRIP TROFFERS OCC. SENSOR OCC. SENSOR WALL DIMMER ROOM WALL 5 15 SERVICE HALLWAYS WITH EMPLOYEE-ONLY ACCESS OCC. SENSOR OCC. SENSOR WALL DIMMER ROOM WALL 16 FILE / PRINT ROOM OCC. SENSOR OCC. SENSOR ------17A, 17B…JANITOR CLOSET, OTHER NON-DATA UTILITY ROOM OCC. SENSOR OCC. SENSOR ------6 18 LOUNGE OCC. SENSOR OCC. SENSOR WALL DIMMER ROOM WALL 19 TELLER LINE OCC. SENSOR OCC. SENSOR WALL DIMMER ROOM WALL 20 NOT USED ------------ 21A, 21B…RESTROOMS OCC. SENSOR OCC. SENSOR WALL DIMMER ROOM WALL22A, 22B…NOT USED ------ 23 NOT USED ------ 24 ROOF CENTRIFUGAL EXHAUST FAN SEE NOTES SEE NOTES ------4 25A, 25B…NOT USED ------4 NOTES: 1 PROVIDE DAYLIGHT-HARVEST DIMMING WITH PHOTOCELL CONTROL ONLY WHERE REQD. BY CODE 2 PROVIDE PILOT LIGHT SWITCH WHERE FIXTURES ARE NOT VISIBLE FROM SWITCH LOCATION 3 INCLUDE WITH BMS CONTROL FOR FUTURE PROGRAM ASSIGNMENT 4 ROOF CENTRIFUGAL EXHAUST FAN SHALL BE 4-WAY CONTROLLED ON/OFF BY FOUR DEVICES: ONE OCCUPANCY SENSOR EACH IN THE TWO RESTROOMS AND JANITOR CLOSET, AND THE TIMER SWITCH IN THELOUNGE. 5 UTILITY ROOM LIGHTING FIXTURES ARE PROVIDED WITH INTEGRAL OCCUPANCY SENSOR. ELECTRICAL REFLECTEDCEILING PLAN E1.2 CH A S E #3 8 2 0 0 P 3 1 0 9 3 9 MA I N & M O N A R C H (S T A N D A R D P A L E T T E ) 10-19-2018222769128PROJECT INFORMATION BLOCKJOB #DATE:DRAWN BY: CHECKED BY: MODEL SHEET TITLE SHEET NUMBER ISSUE DATE DESCRIPTION SEAL ARCHITECT OF RECORD RJ 23 2 E . M A I N S T R E E T , A S P E N , C O 8 1 6 1 1 18.2 _STANDARD (HYBRID) 10 S . D E A R B O R N S T R E E T , 1 5 T CH I C A G O , I L 6 0 6 0 3 Copyright ReservedThe Contractor shall verify and be responsible for alldimensions. DO NOT scale the drawing - any errors oromissions shall be reported to Stantec without delay. Th Copyrights to all designs and drawings are the propertyof Stantec. Reproduction or use for any purpose otherthan that authorized by Stantec is forbidden. Architecture Inc. www.stantec.comTEL. 224 South Michigan Ave., Ste 1400Chicago, IL 60604312.554.1400 PERMIT SUBMITTAL11/02/2018- AB Provide time-switchcontrols and daylightresponsive controls asrequired by 2015IECC C405.2.2 andC405.2.3. FENCED EXTERIOR TRASH AND UTILITY AREA 103 ELEV. C.2 C.4 E.8 D.S. M ELEVATOR J ELEV LTS ELEV FANJ B-2,4,6 B-8 PANEL UH 1 M TO B-10 B-12 HOUSE-1 OUSE-9 SUB P/C +90" AFF TENANT TV & PHONE BACKBOARD PANEL B PANEL HOUSE MAINS B-15 B-17 10'-1118" 6' - 2 78" MDP location behind enclosure to be verified by COA Electric Dept if applicable & COA Fire Dept BY TYCO THERMAL CONTROLS. EQUAL MANUFACTURERS ACCEPTED. PROVIDE ONE RUN OF HEAT TRACE CABLE IN ALL GUTTERS. Provide automatic controls including timer and temperature sensor for the ice melt system per Ordinance 11, 2011. Page: 1 File Name: Energy Code Compliance Comcheck interior lighting TI.232 E. Main St.2018.11.pdf Subject: PlanCheck Author: nickt Color: All COMchecks should be on the same version. Current version is 4.1.1.0. Energy Code Compliance Comcheck interior lighting TI.232 E. Main St.2018.11.pdf (4) Page: 1 File Name: Energy Code Compliance Comcheck interior lighting TI.232 E. Main St.2018.11.pdf Subject: PlanCheck Author: nickt Color: Provide a mechanical COMcheck for the tenant finish equipment. The already submitted mechanical COMcheck pertains to the core and shell, not the tenant finish. Page: 2 File Name: Energy Code Compliance Comcheck interior lighting TI.232 E. Main St.2018.11.pdf Subject: PlanCheck Author: nickt Color: Include the two L-2 fixtures from Corridor 114 in the COMcheck. Page: 2 File Name: Energy Code Compliance Comcheck interior lighting TI.232 E. Main St.2018.11.pdf Subject: PlanCheck Author: nickt Color: There is only 1 light fixture in the janitor room Page: 1 File Name: Energy Code Compliance Comcheck interior lighting.232 E. Main St.2018.10.pdf Subject: PlanCheck Author: nickt Color: The architectural sheets show the occupancies as being B (business), not retail. Revise. Energy Code Compliance Comcheck interior lighting.232 E. Main St.2018.10.pdf (5) All COMchecks should be on the same version. Current version is 4.1.1.0. Provide a mechanical COMcheck for the tenant finish equipment. The already submitted mechanical COMcheck pertains to the core and shell, not the tenant finish. Include the two L-2 fixtures from Corridor 114 in the COMcheck. There is only 1 light fixture in the janitor room The architectural sheets show the occupancies as being B (business), not retail. Revise. Page: 1 File Name: Energy Code Compliance Comcheck interior lighting.232 E. Main St.2018.10.pdf Subject: PlanCheck Author: nickt Color: Choose the same additional efficiency package as the other COMchecks so they are all coordinated. 2015 IECC C406. Page: 1 File Name: Energy Code Compliance Comcheck interior lighting.232 E. Main St.2018.10.pdf Subject: PlanCheck Author: nickt Color: Fill out the site, agent, and designer fields. Page: 1 File Name: Energy Code Compliance Comcheck interior lighting.232 E. Main St.2018.10.pdf Subject: PlanCheck Author: nickt Color: All COMchecks should be on the same version. Current version is 4.1.1.0. Page: 1 File Name: Energy Code Compliance Comcheck interior lighting.232 E. Main St.2018.10.pdf Subject: PlanCheck Author: nickt Color: Label this interior lighting COMcheck as being the core and shell one. Page: 1 File Name: Energy Code Compliance Comcheck.232 E. Main St.2018.10.pdf Subject: PlanCheck Author: nickt Color: None of the wall assemblies match any of the COMcheck walls. Coordinate COMcheck with architectural wall assemblies. Energy Code Compliance Comcheck.232 E. Main St.2018.10.pdf (5) Choose the same additional efficiency package as the other COMchecks so they are all coordinated. 2015 IECC C406. Fill out the site, agent, and designer fields. All COMchecks should be on the same version. Current version is 4.1.1.0. Label this interior lighting COMcheck as being the core and shell one. 2-Second Floor (Office) : Nonresidential 1686 Envelope Assemblies Assembly Cavity R-Value Cont. R-Value Proposed U-Factor Budget U- Factor(a) Gross Area or Perimeter Roof 1 wood shigles: Attic Roof with Wood Joists, [Bldg. Use 2 - Second Floor] 2322 0.0 24.0 0.039 0.021 Roof 2 gable structure: Insulation Entirely Above Deck, [Bldg. Use 1 - Ground Floor] 2195 ---24.0 0.040 0.028 Roof 2 flat: Insulation Entirely Above Deck, [Bldg. Use 1 - Ground Floor]1224 ---42.0 0.023 0.028 Floor 1: Slab-On-Grade:Unheated, Vertical 4 ft., [Bldg. Use 1 - Ground Floor] (d) 275 ---15.0 0.450 0.520 NORTH Exterior North Wall: Concrete Block:8", Partially Grouted, Cells Empty, Normal Density, Furring: Metal, [Bldg. Use 1 - Ground Floor] 1180 0.0 19.5 0.044 0.071 Door 1: Insulated Metal, Swinging, [Bldg. Use 1 - Ground Floor]21 ------0.660 0.370 EAST Exterior East Wall: Steel-Framed, 16" o.c., [Bldg. Use 1 - Ground Floor]1281 19.0 18.0 0.037 0.064 Window 3 around door: Metal Frame with Thermal Break:Fixed, Perf. Specs.: Product ID PORTELLA, SHGC 0.18, PF 0.14, VT 0.43, [Bldg. Use 1 - Ground Floor] (c) 60 ------0.290 0.290 Window 4 around door: Metal Frame with Thermal Break:Fixed, Perf. Specs.: Product ID PORTELLA, SHGC 0.18, PF 0.14, VT 0.34, [Bldg. Use 1 - Ground Floor] (c) 61 ------0.290 0.290 Project Title: Data filename: 232 MAIN ST. X:\Aspen\2016-005 232 E Main St\municipal\232 MAIN ST 9-05.cck 09/05/18Report date: 151 ofPage None of the wall assemblies match any of the COMcheck walls. Coordinate COMcheck with architectural wall assemblies. Page: 1 File Name: Energy Code Compliance Comcheck.232 E. Main St.2018.10.pdf Subject: PlanCheck Author: nickt Color: Include the sloped glazing/skylight in the comcheck. Page: 1 File Name: Energy Code Compliance Comcheck.232 E. Main St.2018.10.pdf Subject: PlanCheck Author: nickt Color: All COMchecks should be on the same version. Current version is 4.1.1.0. Page: 1 File Name: Energy Code Compliance Comcheck.232 E. Main St.2018.10.pdf Subject: PlanCheck Author: nickt Color: None of the CMU wall assemblies have R19.5 continuous insulation. Some of them have R-15. Coordinate COMcheck with the plans. Use the same nomenclature as G-005 to label each element. Page: 3 File Name: Energy Code Compliance Comcheck.232 E. Main St.2018.10.pdf Subject: Group Author: nickt Color: Your details lack slab edge insulation. Slab-on-grade floors with a floor surface less than 24" below grade must have insulation extending downward from the top of the slab on the outside or inside of the foundation wall.The insulation must be extended for by any combination of vertical insulation, insulation extending under the slab or insulation extending out from the building. See the details below for examples. As currently drawn, revise COMcheck to show 0 for slab edge insulation. 2015 IECC C402.2.5 Page: 1 File Name: Energy Code Mechanical Compliance For.232 E. Main St.2018.10.pdf Subject: PlanCheck Author: nickt Color: Fill out the owner/agent portion of the comcheck. Energy Code Mechanical Compliance For.232 E. Main St.2018.10.pdf (3) 1200 W Lake St Suite 200 Chicago, IL 60607 312-714-8519 bhribar@centaurco.com High efficiency HVAC. Systems that do not meet the performance requirement will be identified in th report. Additional Efficiency Package(s) Building Area Floor Area 1-Ground Floor (Office) : Nonresidential 4341 2-Second Floor (Office) : Nonresidential 1686 Envelope Assemblies Assembly Cavit R-Valu Gross Area or Perimeter Roof 1 wood shigles: Attic Roof with Wood Joists, [Bldg. Use 2 - Second Floor] 2322 0.0 Roof 2 gable structure: Insulation Entirely Above Deck, [Bldg. Use 1 - Ground Floor] 2195 --- Roof 2 flat: Insulation Entirely Above Deck, [Bldg. Use 1 - Ground Floor]1224 --- Floor 1: Slab-On-Grade:Unheated, Vertical 4 ft., [Bldg. Use 1 - Ground Floor] (d) 275 --- NORTH Exterior North Wall: Concrete Block:8", Partially Grouted, Cells Empty, Normal Density, Furring: Metal, [Bldg. Use 1 - Ground Floor] 1180 0.0 Door 1: Insulated Metal, Swinging, [Bldg. Use 1 - Ground Floor]21 --- EAST Exterior East Wall: Steel-Framed, 16" o.c., [Bldg. Use 1 - Ground Floor]1281 19.0 Include the sloped glazing/skylight in the comcheck. Software Version 4.1.0.0 e Compliance Certificate 2015 IECC New Construction 1/2018 33% Aspen, Colorado 7 232 MAIN ST. All COMchecks should be on the same version. Current version is 4.1.1.0. COMcheck Software Version 4.1.0.0 Envelope Compliance Certificate Project Title: 2015 IECC Project Type:New Construction Permit Date:1/2018 Vertical Glazing / Wall Area:33% Location:Aspen, Colorado Climate Zone:7 Construction Site: 232 E. MAIN ST. Aspen, CO 81611 Owner/Agent: Brad Hribar Centaur Construction1200 W Lake St Suite 200 Chicago, IL 60607312-714-8519 bhribar@centaurco.com Designer/Contractor: Steve Coughlin modif. architecture1200 W Lake St Suite 200 Chicago, IL 60607708-261-2611 steve.coughlin@modifarchitecture.c om Project Information Energy Code: 232 MAIN ST. High efficiency HVAC. Systems that do not meet the performance requirement will be identified in the mechanical requirements checklist report. Additional Efficiency Package(s) Building Area Floor Area 1-Ground Floor (Office) : Nonresidential 4341 2-Second Floor (Office) : Nonresidential 1686 Envelope Assemblies Assembly Cavity R-Value Cont. R-Value Proposed U-Factor Budget U- Factor(a) Gross Area or Perimeter Roof 1 wood shigles: Attic Roof with Wood Joists, [Bldg. Use 2 - Second Floor] 2322 0.0 24.0 0.039 0.021 Roof 2 gable structure: Insulation Entirely Above Deck, [Bldg. Use 1 - Ground Floor] 2195 ---24.0 0.040 0.028 Roof 2 flat: Insulation Entirely Above Deck, [Bldg. Use 1 - Ground Floor]1224 ---42.0 0.023 0.028 Floor 1: Slab-On-Grade:Unheated, Vertical 4 ft., [Bldg. Use 1 - Ground Floor] (d) 275 ---15.0 0.450 0.520 NORTH Exterior North Wall: Concrete Block:8", Partially Grouted, Cells Empty, Normal Density, Furring: Metal, [Bldg. Use 1 - Ground Floor]1180 0.0 19.5 0.044 0.071 Door 1: Insulated Metal, Swinging, [Bldg. Use 1 - Ground Floor]21 ------0.660 0.370 EAST Exterior East Wall: Steel-Framed, 16" o.c., [Bldg. Use 1 - Ground Floor]1281 19.0 18.0 0.037 0.064 Window 3 around door: Metal Frame with Thermal Break:Fixed, Perf. Specs.: Product ID PORTELLA, SHGC 0.18, PF 0.14, VT 0.43, [Bldg. Use 1 - Ground Floor] (c) 60 ------0.290 0.290 Window 4 around door: Metal Frame with Thermal Break:Fixed, Perf. Specs.: Product ID PORTELLA, SHGC 0.18, PF 0.14, VT 0.34, [Bldg. Use 1 - Ground Floor] (c) 61 ------0.290 0.290 Project Title: Data filename: 232 MAIN ST. X:\Aspen\2016-005 232 E Main St\municipal\232 MAIN ST 9-05.cck 09/05/18Report date: 151 ofPage None of the CMU wall assemblies have R19.5 continuous insulation. Some of them have R-15. Coordinate COMcheck with the plans. Use the same nomenclature as G-005 to label each element. Envelope Compliance Statement Compliance Statement: The proposed envelope design represented in this document is consistent with the building plans, specifications, and other calculations submitted with this permit application. The proposed envelope systems have been designed to meet the 2015 IECC requirements in COMcheck Version 4.1.0.0 and to comply with any applicable mandatoryrequirements listed in the Inspection Checklist. Name - Title Signature Date Envelope PASSES: Design 1% better than code Project Title: Data filename: 232 MAIN ST. X:\Aspen\2016-005 232 E Main St\municipal\232 MAIN ST 9-05.cck 09/05/18Report date: 153 ofPage Your details lack slab edge insulation. Slab-on-grade floors with a floor surface less than 24" below grade must have insulation extending downward from the top of the slab on the outside or inside of the foundation wall.The insulation must be extended for by any combination of vertical insulation, insulation extending under the slab or insulation extending out from the building. See the details below for examples. As currently drawn, revise COMcheck to show 0 for slab edge insulation. 2015 IECC C402.2.5 COMcheck Software Version 4.0.8.1 Mechanical Compliance Certificate e: 2015 IECC pe:New Construction Aspen, Colorado ne:7 on Site: ain St CO 81611 Owner/Agent:Designer/Contractor: Alex Timberlake AEC 40801 US Hwy 6 Ste 214 Avon, CO 81620 970-748-8520 alex@aec-vail.com Information de: 232 E Main Core and Shell nterior lighting power. Requirements are implicitly enforced within interior lighting allowance calculations. nal Efficiency Package(s) Fill out the owner/agent portion of the comcheck. Page: 1 File Name: Energy Code Mechanical Compliance For.232 E. Main St.2018.10.pdf Subject: PlanCheck Author: nickt Color: All COMchecks should be on the same version. Current version is 4.1.1.0. Page: 1 File Name: Energy Code Mechanical Compliance For.232 E. Main St.2018.10.pdf Subject: PlanCheck Author: nickt Color: The thermal envelope COMcheck calls out higher efficiency mechanical equipment as the chosen additional efficiency package (2015 IECC C406). Coordinate the COMchecks to choose the same additional efficiency package and demonstrate compliance. Software Version 4.0.8.1 ical Compliance Certificate 2015 IECC New Construction Aspen, Colorado 7 232 E Main Core and Shell All COMchecks should be on the same version. Current version is 4.1.1.0. COMcheck Software Version 4.0.8.1 Mechanical Compliance Certificate Project Title: 2015 IECC Project Type:New Construction Location:Aspen, Colorado Climate Zone:7 Construction Site: 232 E Main St Aspen, CO 81611 Owner/Agent:Designer/Contractor: Alex Timberlake AEC40801 US Hwy 6 Ste 214Avon, CO 81620 970-748-8520alex@aec-vail.com Project Information Energy Code: 232 E Main Core and Shell Reduced interior lighting power. Requirements are implicitly enforced within interior lighting allowance calculations. Additional Efficiency Package(s) Mechanical Systems List Quantity System Type & Description Heating: 1 each - Central Furnace, Gas, Capacity = 150 kBtu/h Proposed Efficiency = 80.00% Et, Required Efficiency = 80.00% Et Cooling: 1 each - Single Package DX Unit, Capacity = 73 kBtu/h, Evaporatively Cooled Condenser, Air Economizer Proposed Efficiency = 12.80 EER, Required Efficiency: 11.90 EER + 12.1 IEER Fan System: RTU-1 FAN -- Compliance (Brake HP method) : Passes Fans: RTU 1 FAN Supply, Multi-Zone VAV, 3000 CFM, 5.0 motor nameplate hp, 2.4 design brake hp (2.4 max. BHP), 80.0 fan efficiency grade 1 RTU-1 (Multiple-Zone): Heating: 1 each - Central Furnace, Gas, Capacity = 150 kBtu/h Proposed Efficiency = 80.00% Et, Required Efficiency = 80.00% Et Cooling: 1 each - Single Package DX Unit, Capacity = 87 kBtu/h, Air-Cooled Condenser, Air Economizer Proposed Efficiency = 13.50 EER, Required Efficiency: 11.00 EER + 12.6 IEER Fan System: RTU-1 FAN -- Compliance (Brake HP method) : Passes Fans: RTU 1 FAN Supply, Multi-Zone VAV, 3000 CFM, 5.0 motor nameplate hp, 2.4 design brake hp (2.4 max. BHP), 80.0 fan efficiency grade 1 RTU-2 (Multiple-Zone): Heating: 1 each - Central Furnace, Gas, Capacity = 72 kBtu/h Proposed Efficiency = 82.00% Et, Required Efficiency = 80.00% Et Cooling: 1 each - Single Package DX Unit, Capacity = 30 kBtu/h, Air-Cooled Condenser, Air Economizer Proposed Efficiency = 15.50 SEER, Required Efficiency: 14.00 SEER Fan System: RTU-3 FAN -- Compliance (Brake HP method) : Passes 1 RTU-3 (Multiple-Zone): The thermal envelope COMcheck calls out higher efficiency mechanical equipment as the chosen additional efficiency package (2015 IECC C406). Coordinate the COMchecks to choose the same additional efficiency package and demonstrate compliance. Page: 1 File Name: Glazing Specification.232 E. Main St.2018.09.pdf Subject: PlanCheck Author: nickt Color: Some of your skylights, windows, and exterior doors appear to be site built storefront types. Either verify that all of your windows and doors will be factory assembled with NFRC certification (which requires a label applied to the window/door assembly and verified at field inspection) or verify U-factors using one of the following options per City policy: -Default values from 2015 IECC tables C303.1.3(1) C303.1.3(2), R303.1.3(1), or R303.1.3(2). -Default values from Table 4 U-Factors for Various Fenestration Products in 2013 ASHRAE Fundamentals Handbook chapter 15, pg. 15.3. To document the chain of custody, a certificate, affidavit or other evidence from the manufacturer confirming compliance with the above method is required. -Calculation methods in 2013 ASHRAE Fundamentals Handbook chapter 15, pg. 15.3: “U-Factor (Overall Coefficient of Heat Transfer)”. A calculation is required for the standard NFRC window size of 47.2” x 47.2”. To document the chain of custody, a certificate, affidavit or other evidence from the manufacturer confirming compliance with the above calculation is required. -U-ratings by an NFRC–accredited lab in accordance with NFRC-100. To document the chain of custody, verification labels affixed to the units by an accredited independent inspection agency or a certificate, affidavit or other evidence from the manufacturer confirming compliance with the above simulation or testing. Glazing Specification.232 E. Main St.2018.09.pdf (1) Page: [1] 18029 - M1(D-48)-M1.0 File Name: Mechanical.232 E. Main St.2018.11.pdf Subject: PlanCheck Author: nickt Color: Windows are 0.29 and 0.27 U factor per the COMcheck. Coordinate. Mechanical.232 E. Main St.2018.11.pdf (4) 232 E. Main St. Aspen, Colorado Glazing Specification 09.05.2018 modif. architecture 1200 west lake street suite 200 chicago, il 60607 312.288.2009 So m e o f y o u r s k y l i g h t s , w i n d o w s , a n d e x t e r i o r d o o r s a p p e a r t o b e s i t e b u i l t st o r e f r o n t t y p e s . E i t h e r v e r i f y t h a t a l l o f y o u r w i n d o w s a n d d o o r s w i l l b e f a c t o r y as s e m b l e d w i t h N F R C c e r t i f i c a t i o n ( w h i c h r e q u i r e s a l a b e l a p p l i e d t o t h e win d o w / d o o r a s s e m b l y a n d v e r i f i e d a t f i e l d i n s p e c t i o n ) o r v e r i f y U - f a c t o r s u s i n g on e o f t h e f o l l o w i n g o p t i o n s p e r C i t y p o l i c y : -D e f a u l t v a l u e s f r o m 2 0 1 5 I E C C t a b l e s C 3 0 3 . 1 . 3 ( 1 ) C 3 0 3 . 1 . 3 ( 2 ) , R 3 0 3 . 1 . 3 ( 1 ) , or R 3 0 3 . 1 . 3 ( 2 ) . -D e f a u l t v a l u e s f r o m T a b l e 4 U - F a c t o r s f o r V a r i o u s F e n e s t r a t i o n P r o d u c t s i n 20 1 3 A S H R A E F u n d a m e n t a l s H a n d b o o k c h a p t e r 1 5 , p g . 1 5 . 3 . T o d o c u m e n t t h e ch a i n o f c u s t o d y , a c e r t i f i c a t e , a f f i d a v i t o r o t h e r e v i d e n c e f r o m t h e m a n u f a c t u r e r co n f i r m i n g c o m p l i a n c e w i t h t h e a b o v e m e t h o d i s r e q u i r e d . -C a l c u l a t i o n m e t h o d s i n 2 0 1 3 A S H R A E F u n d a m e n t a l s H a n d b o o k c h a p t e r 1 5 , pg . 1 5 . 3 : “ U - F a c t o r ( O v e r a l l C o e f f i c i e n t o f H e a t T r a n s f e r ) ” . A c a l c u l a t i o n i s re q u i r e d f o r t h e s t a n d a r d N F R C w i n d o w s i z e o f 4 7 . 2 ” x 4 7 . 2 ” . T o d o c u m e n t t h e ch a i n o f c u s t o d y , a c e r t i f i c a t e , a f f i d a v i t o r o t h e r e v i d e n c e f r o m t h e m a n u f a c t u r e r co n f i r m i n g c o m p l i a n c e w i t h t h e a b o v e c a l c u l a t i o n i s r e q u i r e d . -U - r a t i n g s b y a n N F R C – a c c r e d i t e d l a b i n a c c o r d a n c e w i t h N F R C - 1 0 0 . T o do c u m e n t t h e c h a i n o f c u s t o d y , v e r i f i c a t i o n l a b e l s a f f i x e d t o t h e u n i t s b y a n ac c r e d i t e d i n d e p e n d e n t i n s p e c t i o n a g e n c y o r a c e r t i f i c a t e , a f f i d a v i t o r o t h e r ev i d e n c e f r o m t h e m a n u f a c t u r e r c o n f i r m i n g c o m p l i a n c e w i t h t h e a b o v e si m u l a t i o n o r t e s t i n g . Windows are 0.29 and 0.27 U factor per the COMcheck. Coordinate. Page: M1.1 File Name: Mechanical.232 E. Main St.2018.11.pdf Subject: PlanCheck Author: nickt Color: Indicate if returns are ducted from each location or if using the above ceiling space as a plenum. If plenum, indicate plenum rated wiring requirement on electrical sheets. Page: M1.1 File Name: Mechanical.232 E. Main St.2018.11.pdf Subject: PlanCheck Author: nickt Color: This wall is not fire rated, therefore dampers are not required. 2015 IBC 508. Page: M1.1 File Name: Mechanical.232 E. Main St.2018.11.pdf Subject: PlanCheck Author: nickt Color: Provide ventilation out door air CFM calculations per 2015 IMC 403. Page: 3 File Name: Special Inspections and Testing Agreement.232 E. Main St.2018.10.pdf Subject: PlanCheck Author: nickt Color: Fabricator will need to sign the special inspection agreement prior to permit approval. Special Inspections and Testing Agreement.232 E. Main St.2018.10.pdf (1) Page: 5 File Name: Special Inspections Statement.232 E. Main St.2018.09.pdf Subject: PlanCheck Author: nickt Color: Please stamp the special inspection program. Special Inspections Statement.232 E. Main St.2018.09.pdf (1) Indicate if returns are ducted from each location or if using the above ceiling space as a plenum. If plenum, indicate plenum rated wiring requirement on electrical sheets. This wall is not fire rated, therefore dampers are not required. 2015 IBC 508. Provide ventilation out door air CFM calculations per 2015 IMC 403. (PROJECT NOT BID YET) (PROJECT NOT BID YET) Fabricator will need to sign the special inspection agreement prior to permit approval. Inspections of penetration firestop systems that are tested and listed <in accordance with Sections 714.3.1.2 and 714.4.2 shall be conducted by an approved agency in accordance with ASTM E2174. Inspection of fire-resistant joint systems that are tested and listed in accordance with Sections 715.3 and 715.4 shall be conducted by an approved agency <in accordance with ASTM E2393. End of list. ************* Please contact me with any questions. Best regards, Stephen Coughlin, RA Owner/Architect Modif. Architecture Please stamp the special inspection program. Page: S1.1 SPECIAL INSPECTIONS File Name: Structural.232 E. Main St.2018.11.pdf Subject: PlanCheck Author: nickt Color: Sign the structural stamp on all sheets. Structural.232 E. Main St.2018.11.pdf (1) CK PROHIBITION, , WELD PROFILES, WELD ED JOINT OR MEMBER FASTENER MATERIALS REQUIREMENTS ETAIL L RIATE FAYING SURFACED, MEET APPLICABLE ALLATION PERSONNELEMBLIES AND METHODS WASHERS, AND OTHER PLACED IN ALL HOLES REQUIRED. RIOR TO THE NCH PREVENTED E WITH THE RCSC FROM THE MOST ED CONNECTIONS. X X X X X X X X X X X X X X X X X X X SEAL: No. Description Date 1 PERMIT 9-25-2018 Sign the structural stamp on all sheets.