HomeMy WebLinkAboutFile Documents.232 E Main St.0132.2018 (90).ACBK0132-2018-ARBK_BuildingComments_2 Subject: PlanCheck Page: 1 Page Index: 1 Author: nickt Color: File Name: Architectural Plan Set Nick.232 E Main.2019.08.pdf Previous comment not addressed: I have not received the line grade form. Please complete and provide it. Architectural Plan Set Nick.232 E Main.2019.08.pdf (23) Subject: PlanCheck Page: 6 Page Index: 6 Author: nickt Color: File Name: Architectural Plan Set Nick.232 E Main.2019.08.pdf Previous comment not addressed: The provided "Roofing Specifications" document is blank. Provide documentation that the roof assemblies are Class A. This is typically either an ESR or UL report. Revise you roof details to match the report(s). (Ordinance 40, 2016) Subject: PlanCheck Page: 6 Page Index: 6 Author: nickt Color: File Name: Architectural Plan Set Nick.232 E Main.2019.08.pdf Previous comment not addressed: I have not received a new thermal envelope COMcheck. Revise the old one to use the same naming labels as your wall, floor, and roof types. Subject: PlanCheck Page: 8 Page Index: 8 Author: nickt Color: File Name: Architectural Plan Set Nick.232 E Main.2019.08.pdf Maximum common path of travel distance for a single exit story for a B occupancy on the second story above grade plane is 75'. The 100' exception in footnote b only applies to the first story above or below grade plane. This is the second story above grade plane. 2015 IBC 1006.3.2(2) Subject: PlanCheck Page: 8 Page Index: 8 Author: nickt Color: File Name: Architectural Plan Set Nick.232 E Main.2019.08.pdf This wall enclosing the understair space must be 1 hour rated. 2015 IBC 1011.7.3 T Previous comment not addressed: I have not received the line grade form. Please complete and provide it. 1 Previous comment not addressed: The provided "Roofing Specifications" document is blank. Provide documentation that the roof assemblies are Class A. This is typically either an ESR or UL report. Revise you roof details to match the report(s). (Ordinance 40, 2016) SLAB ON GRADE 5" CAST IN PLACE CONCTRETE 6" GRAVEL SECOND LEVEL FLOOR 3/4" PLYWOOD 3/8" SOUND MAT 3/4" PLYWOOD TYPE 1A TYPE 2A Previous comment not addressed: I have not received a new thermal envelope COMcheck. Revise the old one to use the same naming labels as your wall, floor, and roof types. TRA EXI LEGEND : CEI WA EX I T SD SM HORIZONTAL REQ'D. SEPARATIO FLOOR OCC MAIN N = NO SEPARATION REQUIRED SECOND LEVEL 1 H FIRE SEPARATION PER TABLE 60 REQUIRED FIRE SEP 1 HR FIRE SEPAR DISTANCE X ≤ 5 5 ≤ X <10 X ≥ 30 10 ≤ X <30 1 HR FIRE SEPAR 0 HR FIRE SEPAR 0 HR FIRE SEPAR 2 H OUTDOOR TERRACE MECH. EQ. SECOND FLOOR TENANT SPACE- 'B' 200 71 ' -5'' T R A V E L D I S T A N C E EXIT 12" A.F.F. TWO-WAY COMMUNICATION SYSTEM 1 4 Maximum common path of travel distance for a single exit story for a B occupancy on the second story above grade plane is 75'. The 100' exception in footnote b only applies to the first story above or below grade plane. This is the second story above grade plane. 2015 IBC 1006.3.2(2) UP 1,380 1,380 TENANT SPACE 'B' 101 ELEV. 44' 0'' TRAVEL DISTANCE VEL E 5'- 3 " 5 6'-6 5/8 " C.2 C.4 E.8 F.8 6'- 0 " EX I T 12" A.F.F. EX I T EGRESS ACCESS STAIR 23 ' 0 ' ' T R A V E L D I S T A N C E 1 1 TRASH AREA (300 SF) 103 4 7 8 8.5 9 10 1 This wall enclosing the understair space must be 1 hour rated. 2015 IBC 1011.7.3 Subject: PlanCheck Page: 8 Page Index: 8 Author: nickt Color: File Name: Architectural Plan Set Nick.232 E Main.2019.08.pdf Why is this wall rated? Subject: PlanCheck Page: 8 Page Index: 8 Author: nickt Color: File Name: Architectural Plan Set Nick.232 E Main.2019.08.pdf The trash area may not egress through the mechanical room as it is an intervening space. 2015 IBC 1016.2 Subject: PlanCheck Page: 8 Page Index: 8 Author: nickt Color: File Name: Architectural Plan Set Nick.232 E Main.2019.08.pdf Previous comment not addressed: The exit access stair qualifies as designed as the vertical path for accessible means of egress (2015 IBC 1009.3). However, a two-way communication system complying with 2015 IBC 1009.8 is required at the elevator. Subject: PlanCheck Page: 8 Page Index: 8 Author: nickt Color: File Name: Architectural Plan Set Nick.232 E Main.2019.08.pdf The mechanical room contains a boiler greater than 400kbtu, requiring it to be an incidental occupancy per 2015 IBC 509. You may choose to either give it a 1 hour fire rating, which will require 1 hour fire barrier walls extending to the underside of the slab/deck above (extend past the ceiling) and 1 hour horizontal assembly above and 45 minute rated door; or you may sprinkler the trash enclosure and seal it from the passage of smoke. Clearly demonstrate compliance on the plans. Subject: PlanCheck Page: 8 Page Index: 8 Author: nickt Color: File Name: Architectural Plan Set Nick.232 E Main.2019.08.pdf The trash area is greater than 100 sqft, making it an incidental use area per 2015 IBC 509. You may choose to either give it a 1 hour fire rating, which will require 1 hour fire barrier walls extending to the underside of the slab/deck above (extend past the ceiling) and 1 hour horizontal assembly above and 45 minute rated door; or you may sprinkler the trash enclosure and seal it from the passage of smoke. Clearly demonstrate compliance on the plans. UP 1,380 2,0001,380 2,000 TENANT SPACE 'A' 100 TENANT SPACE 'B' 101MECH. RM. 102 ELEV. 88' 0'' TRAVEL DISTANCE 44' 0'' TRAVEL DISTANCE 34' 0'' TRAVEL DISTANCE 3" 10'- 0 " 5'-3 " 5'-0" 74'-9 1/2" 56'-6 5/8" 3 4 5 6 7 8 8.5 9 10 C.2 C.4 E.8 F.8 EX I T EX I T 6'-0 " 6'-0 " 12" A.F.F. EX I T 12" A.F.F. EX I T EGRESSACCESS STAIR 23 ' 0 ' ' T R A V E L D I S T A N C E 1 1 TWO-WAY COMMUNICATION SYSTEM1 1 1 TRASH AREA (300 SF) 103 4 4 OPEN OUTDOOR TERRACE MECH. EQ. ROOF LADDER 3 4 5 6 7 8 8.5 9 10 C.2 1 T C S Why is this wall rated? UP TENANT SPACE 'B' 101 MECH. RM. 102 ELEV. 44' 0'' TRAVEL DISTANCE 34' 0'' TRAVEL DISTANCE 10 ' - 0 " 5'- 3 " 5 6'-6 5/8 "8 8.5 9 10 C.2 C.4 E.8 F.8 6'- 0 " EX I T 12" A.F.F. EX I T EGRESS ACCESS STAIR 23 ' 0 ' ' T R A V E L D I S T A N C E 1 1 1 TRASH AREA (300 SF) 103 4 4 The trash area may not egress through the mechanical room as it is an intervening space. 2015 IBC 1016.2 SECOND FLOOR TENANT SPACE- 'B' 200DI S T A N C E EXIT 12" A.F.F. TWO-WAY COMMUNICATION SYSTEM 1 Previous comment not addressed: The exit access stair qualifies as designed as the vertical path for accessible means of egress (2015 IBC 1009.3). However, a two-way communication system complying with 2015 IBC 1009.8 is required at the elevator. UP 1,380 1,380 TENANT SPACE 'A' 100 TENANT SPACE 'B' 101 MECH. RM. 102 ELEV. 88' 0'' TRAVEL DISTANCE 44' 0'' TRAVEL DISTANCE 34' 0'' TRAVEL DISTANCE 3" 10'- 0 " 5'-3 " 5'-0" 74'-9 1/2" 56'-6 5/8" 4 5 6 7 8 8.5 9 10 C.2 C.4 E.8 F.8 EX I T 6'-0 " 12" A.F.F. EX I T 12" A.F.F. EX I T EGRESSACCESS STAIR 23 ' 0 ' ' T R A V E L D I S T A N C E 1 1 TWO-WAY COMMUNICATION SYSTEM1 1 1 TRASH AREA (300 SF) 103 4 4 4 5 6 7 8 8.5 9 10 The mechanical room contains a boiler greater than 400kbtu, requiring it to be an incidental occupancy per 2015 IBC 509. You may choose to either give it a 1hour fire rating, which will require 1 hour fire barrierwalls extending to the underside of the slab/deck above(extend past the ceiling) and 1 hour horizontal assembly above and 45 minute rated door; or you may sprinkler the trash enclosure and seal it from the passage of smoke. Clearly demonstrate compliance on the plans. UP TENANT SPACE 'B' 101 MECH. RM. 102 ELEV. 44' 0'' TRAVEL DISTANCE 34' 0'' TRAVEL DISTANCE 10 ' - 0 " 5'- 3 " 5 6'-6 5/8" 7 8 8.5 9 10 C.2 C.4 E.8 F.8 6'-0 " EX I T 12" A.F.F. EX I T EGRESSACCESS STAIR 23 ' 0 ' ' T R A V E L D I S T A N C E 1 1 TWO-WAY COMMUNICATION SYSTEM1 1 1 TRASH AREA (300 SF) 103 4 4 The trash area is greater than 100 sqft, making it an incidental use area per 2015 IBC 509. You may choose to either give it a 1 hour fire rating, which will require 1 hour fire barrier walls extending to the underside of the slab/deck above (extend past the ceiling) and 1 hour horizontal assembly above and 45 minute rated door; or you may sprinkler the trash enclosure and seal it from the passage of smoke. Clearly demonstrate compliance on the plans. Subject: PlanCheck Page: 11 Page Index: 11 Author: nickt Color: File Name: Architectural Plan Set Nick.232 E Main.2019.08.pdf Only accessible routes are exempt from snowmelt. These areas are not accessible routes. Subject: PlanCheck Page: 11 Page Index: 11 Author: nickt Color: File Name: Architectural Plan Set Nick.232 E Main.2019.08.pdf Provide a tally of the snowmelt square footages with totals for hydronic, electric, exempt, non-exempt, and total on the snowmelt plan. Must match the CREMP worksheet. Update the CREMP worksheet to match the snowmelt plans (I have not received an updated one). Subject: PlanCheck Page: 12 Page Index: 12 Author: nickt Color: File Name: Architectural Plan Set Nick.232 E Main.2019.08.pdf Provide wall type callouts for these walls. 1 hour fire rating required for enclosure under stairs- 2015 IBC 1011.7.3 Subject: PlanCheck Page: 13 Page Index: 13 Author: nickt Color: File Name: Architectural Plan Set Nick.232 E Main.2019.08.pdf Provide access to all attic spaces. 2015 IBC 1209.2 Subject: PlanCheck Page: 14 Page Index: 14 Author: nickt Color: File Name: Architectural Plan Set Nick.232 E Main.2019.08.pdf 42" guards required where equipment is less than 10' from roof edge. 2015 1015.6 PROPOSED 2 STORY BUILDING HIS T O R I C C O R T I N A L O D G E NE W S T R E E T PA R K I N G NE W S T R E E T PA R K I N G ONY DETECTABLE HISTORIC CORTINA LODGE STONE CHIMNEY WATER THAT ES VIA NATURAL LLEY OVERHANG ABOVE 5'- 0 " AWNING. TYP. 207 SF EXEMPT SNOWMELT EX E M P T 4'- 0 " 152 SF SNOWMELT 1 1 1544 SF SNOWMELT (R.O.W. TOTAL) 1 45 SF EXEMPT SNOWMELT1 828 SF EXEMPT SNOWMELT 1 EX E M P T 4'- 0 " EXEMPT 4'-0" EXEMPT 4'-0" EXEMPT 4'-0" Only accessible routes are exempt from snowmelt. These areas are not accessible routes. 44 SF EXEMPT SNOWMELT1 44 SF EXEMPT SNOWMELT 1EXEMPT 6'- 0 " EXE6 LINE OF WALL BELOW EXEMPT 6'-0" 1/8" = 1'-0"1 PROPOSED SNOWMELT ROOF PLAN Provide a tally of the snowmelt square footages with totals for hydronic, electric, exempt, non-exempt, and total on the snowmelt plan. Must match the CREMP worksheet. Update the CREMP worksheet to match the snowmelt plans (I have not received an updated one). UP 23'-10 7/8"28'-7 1/2"7'-2 5/8" 10' - 0 " 59'-9" 1 A-300 TENANT SPACE 'B' 101 3 -400 5'-3 " 2'-7 3 / 4 " R.O . 10 ' - 7 3 / 4 " 2'-7 5 / 8 " R.O . 10 ' - 7 3 / 4 " 3/4 " TRASH AREA (300 SF) 103 AIR CURTAIN BY TENANT 12 ' - 1 1 " TRANSFORMER MECH. RM. 102 ELEV. -2'-0" 4 7 / 8 " 8'-1 3 / 4 " A-412 1 2 A-311 1 A-600A-500 1 A-400 1 24'-4"9'-6 3/4"8'-4"9'-2 1/4" 13 ' - 5 " 3'- 1 0 3 / 8 " 4'- 1 0 1 / 4 " 4'- 9 " 1'-0 5 / 8 " 7 8 8.5 9 10 C.2 C.4 E.8 F.8 D.S. FOUNDATIONDRYWELL STORM DRYWELL C-1 E 4'- 7 7 / 8 " D.S. D.S. 23'-7 7/8" 23'-3 3/8" 4 7/8" 4'-5 1/4" 4 7/8" 21'-4 1/2" 5x5x1/4 ACCESS PANEL -1'-0" * ADA PUSH BUTTON EJANITOR CLOSET P GAS METERS 1 F D1 DRAIN TILE, TYP.1 14'-0" M.O. 9'-0" 7 7/8" E BOLLARD, TYP. 4 7 / 8 " 9'-3 3 / 4 " R.O . 3'-0 " 7 1 / 4 " 1'-4" M.O. 3'-4" ACCESS PANEL -2'-0" D24 R K Provide wall type callouts for these walls. 1 hour fire rating required for enclosure under stairs- 2015 IBC 1011.7.3 DN2,000 2,000 OUTDOOR TERRACE 2 A-300 2 A-310 MECH. EQUIP., TYP. SECOND FLOOR TENANT SPACE-'B' 200 1/8 " 13 ' - 6 " 19 ' - 6 3 / 4 " 5'-7 7 / 8 " A-413 1 A-400 2 24'-4"9'-6 3/4"8'-4"9'-2 1/4" C.2 C.4 E.8 F.8 E F CHANICAL SCREENING, TYP. D.S.D.S. D 8" R.O. 13 ' - 6 " 23 ' - 1 1 3 / 8 " ELEV. 4'-10 3/4" 3 A-311 1 A-504 C6 1 C6 1 C8 1 D 1 1 1 E2 ACCESS PANEL 1 CK T ROOF 1/4'' : 1'-0'' 1/4'' : 1'-0'' 7'' MAX. THICK INSULATION 1 1 1 1/4'' : 1'-0'' VC ROOF MEMBRANE 4 4 1. PROVIDE F.T. WOOD BLOCK ACCESSORIES AND MILLWOR 2. FIRE RATED HORIZONTAL A AND UNINTERRUPTED. 3. ALL EXPOSED STEEL ON TH PAINTED. 4. THESE DRAWINGS INDICATE THE ARCHITECTURAL DESIGN INDICATE OR DESCRIBE ALL W PROJECT. 5. THE CONTRACTOR OR SUB VERIFICATION OF ALL DIMENS ANY WORK AND SHALL NOTIF DISCREPANCIES. 6. SUBCONTRACTOR SHALL V BEFORE PROCEEDING WITH F 7. ALL WORK SHALL BE COOR AVOID INTERFERENCES, PRES 8. ALL DOORS USED IN CONNE WITHOUT THE USE OF A KEY F 9. DIMENSIONS MARKED 'HOLD DIMENSIONS ARE FACE TO FA 10. DIMENSIONS, TARGETS, ET ONLY ONCE. 11. PROVIDE PRIME COAT ONL FILE CABINETS, WALL COVERI OTHERWISE. 12. PROVIDE MOISTURE RESIS WET AREAS (IE., SINKS, TOILE 13. PROVIDE TILE BACKER CE AREA APPLICATION (IE.,SINKS 14. INTERSECTION BETWEEN PAINTABLE CAULK U.N.O. 15. UPON INSTALLATION OF D HOLES, VOIDS, ETC. BETWEEN TO BE PAINTABLE. 16. THRESHOLDS BE CONTINU 17. THRESHOLD END CONDITI SHAPE/PROFILE OF JAMB/WAL 18. DO NOT SCALE DRAWINGS ARCHITECT'S WRITTEN APPRO 19. ALL INTERIOR FINISHES TO 22. EXPOSED CONCRETE WOR SEALER IF NOT INTENDED TO 23. G.C. TO CONFIRM/ COORD COMENCING CONSTRUCTION 1 1 1 Provide access to all attic spaces. 2015 IBC 1209.2 1,380 2,0001,380 2,000 FIBER-REINFORCED CEMENT PANELS WITH OPEN JOINTS OVER ROOF AT (9/12) SLOPE.1798 SF SLOPED GLAZING 90 SF CEDAR SHAKE SHINGLES OVER GABLED ROOF, ROOF PROPOSED SNOW MELT SYSTEM TO ALLEVIATE SNOW SHEDDING BOTH IN THE ROW AND ON ANY ADJACENT LOTS SNOW CLEAT 1 A-300 2 A-30 1 A-30 3 A-400 9" / 1'-0"9" / 1'-0"9" / 1'-0" GUTTER 9" / 1'-0"9" / 1'-0" 9" / 1 ' - 0 " 9" / 1 ' - 0 " AWNING, TYP. 2 3 4 5 6 7 8 8.5 9 10 C.2 C.4 E.8 F.8 9" / 1'-0" INTERNAL GUTTERS, TYP.INTERNAL GUTTER, TYP. INTERNAL D.S., TYP. 3" V.T.R. 3" V.T.R. 1" / 1 ' -0" MECHANICAL EQUIPMENT SETBACK 15'-0 " LINE OF BUILDINGBELOW LINE OF BUILDING BELOW MECHANICAL EQUIPMENT SETBACK 15'-0" PROPOSED SATELLITE LOCATION D.S. D.S.ROOFACCESS 24'-4"9'-6 3/4"8'-4"9'-2 1/4" 12'- 6 3 / 4 " 4'-0 1 / 8 " 13' - 5 " 13' - 3 " 13'- 5 " 3'-1 0 3 / 8 " 4'-1 0 1 / 4 " 4'-9 " 6'-7" 11'- 1 1 3 / 4 " PROPOSED SNOW MELT SYSTEM TO ALLEVIATE SNOW SHEDDING BOTH IN THE ROW AND ON ANY ADJACENT LOTS PROPOSED SNOW MELT SYSTEM TO ALLEVIATE SNOW SHEDDING BOTH IN THE ROW AND ON ANY ADJACENT LOTS PROPOSED SNOW MELT SYSTEM TO ALLEVIATE SNOW SHEDDING BOTH IN THE ROW AND ON ANY ADJACENT LOTS 88'- 8 3 / 8 " 42'' HIGH GUARDRAIL1 1 A-504 1 1 ROOF OVERHANG OF CORTINA LODGE INTEGRAL FORMED COPPER GUTTER AND D.S., TYP. INTEGRAL FORMED COPPER GUTTER AND D.S., TYP. INTEGRAL FORMED COPPER GUTTER AND D.S., TYP. 4 4 4 42" guards required where equipment isless than 10' from roofedge. 2015 1015.6 Subject: PlanCheck Page: 18 Page Index: 18 Author: nickt Color: File Name: Architectural Plan Set Nick.232 E Main.2019.08.pdf Indicate the floor type separating the two units. Subject: PlanCheck Page: 20 Page Index: 20 Author: nickt Color: File Name: Architectural Plan Set Nick.232 E Main.2019.08.pdf Dimension the depth of the slab edge insulation. Must match comcheck. Subject: PlanCheck Page: 21 Page Index: 21 Author: nickt Color: File Name: Architectural Plan Set Nick.232 E Main.2019.08.pdf Dimension the depth of the slab edge insulation. Must match comcheck. Subject: PlanCheck Page: 22 Page Index: 22 Author: nickt Color: File Name: Architectural Plan Set Nick.232 E Main.2019.08.pdf Provide a listed assembly for the ceiling of the stair enclosure. Subject: PlanCheck Page: 22 Page Index: 22 Author: nickt Color: File Name: Architectural Plan Set Nick.232 E Main.2019.08.pdf UL U415 is a wall assembly. Per the gypsum manual general explanatory notes a wall assembly may not be arbitrarily used as a ceiling assembly. Choose a ceiling assembly and print the full UL instructions on the plans as you have done with the other UL assemblies. MECH. EQUIP. SCREENING GOOSENECK LIGHT FIXTURE WITH FROSTED LENS, TYP. CM RAIN SCREEN PANELING W/ 1/2" REVEAL CEDAR SHAKE SHINGLES OVER GABLED ROOF, ROOF AT (9/12) SLOPE ALUM. INSULATED STOREFRONT WITH DIVIDED LITES MULLIONS SECOND FLOOR TENANT SPACE- 'B' 200 A-502 7 4'-11 7/8" MIN . H E A D C L E A R A N C E 6'-8 " A-501 2 Sim A-510 1 A1 1A1 3 1 K 1 1/4" = 1'-0"2 BUILDING SECTION Indicate the floor type separating the two units. SUB FLR. TENANT 'A' 7903.200" B/GABLE16'-1 1/2" 2ND LEVEL12'-0" TENANT SPACE 'A' 100 COMPACTED GRAVEL FILL 4'' DIA. DRAIN TILE FOUNDATION DAMPPROOFING RAINSCREEN COMPOSITE MATERIAL XPS INSULATION A-5033 CMU 6" METAL STUDS 5/8" GYP. BD. A-5024 A-5011 SUB FLR. TENANT 'B' 7902.20-1'-0" SUB FLR. MECH. ROOM 7901.20-2'-0" SIDEWALK VAPOR BARRIER 1 SUB FLR. TENANT 'A' 7903.200" T/ LOWER GLAZING10'-0" B/FACIA13'-0" 2ND LEVEL12'-0" SNOW GUARD TENANT SPACE 'A' 100 COMPACTED GRAVEL FILL 4'' DIA. DRAIN TILE FOUNDATION DAMPPROOFING SIDEWALK A-5012 A-5023 Sim SUB FLR. TENANT 'B' 7902.20-1'-0" SUB FLR. MECH. ROOM 7901.20-2'-0" A-50312 RECLAIMED WOOD SIDING WOOD FURRING XPS INSULATION 5/8" DENSLGASS 8" METAL STUDS 5/8" GYP. BD. VAPOR BARRIER 1 SUB FLR. TENANT 'A' 7903.200" WET SEALED ACM PANEL SURROUNDAT MAIN ST. ENTRY WALL SCONCE INSULATED STOREFRONT ENTRANCE FIRE TREATED RECLAIMED WOOD SIDING TENANT SPACE 'A' 100 4" DIA. DRAIN TILE A-5022 A-5013 A-5039 SUB FLR. TENANT 'B' 7902.20-1'-0" SUB FLR. MECH. ROOM 7901.20-2'-0" 9 1/2" SIDEWALK CAST STONE BASE FOUNDATION DAMPPROOFING COMPACTED GRAVEL FILL 1 4 3/4" = 1'-0"1 WALL SECTION - EAST ENTRANCE 3/4" = 1'-0"2 WALL SECTION - EAST PILASTER 3/4" = 1'-0"3 WALL SECTION - SOUTH ENTRANCE Dimension the depth of the slab edgeinsulation. Must matchcomcheck. SUB FLR. TENANT 'A' 7903.200" T/PARAPET14'-8" B/GABLE16'-1 1/2" 2ND LEVEL12'-0" 1 A-300 A TENANT SPACE 'A' 100 PRO P E R T Y L I N E 3" COMPACTED GRAVEL FILL 4" DIA. DRAINAGE TILE A-5026 A-5014 SUB FLR. TENANT 'B' 7902.20-1'-0" SUB FLR. MECH. ROOM 7901.20-2'-0" ADJA C E N T B U I L D I N G ( N . I . C . ) FOUNDATION DAMPPROOFING 5/8" GYP. BD. 2 1/2" METAL STUD XPS INSULATION 8" CMU 1 1 SUB FLR. TENANT 'A' 7903.200" T/PARAPET14'-8" 2ND LEVEL12'-0" 3A-400 TRANSFORMER PRO P E R T Y L I N E MIN. CLEARENCE10'-0" MECH. EQUIP. 910 4" DIA. DRAINAGE TILE A-5017 A-5029 Sim SUB FLR. TENANT 'B' 7902.20-1'-0" SUB FLR. MECH. ROOM 7901.20-2'-0" 5/8" GYP. BD.2 1/2" METAL STUD 8" CMU XPS INSULATION VAPOR BARRIER WOOD FURRING RECLAIMED WOOD SIDING COMPACTED GRAVEL FILL FOUNDATION DAMPPROOFING 1 1 SUB FLR. TENANT 'A' 7903.200" T/ LOWER GLAZING10'-0" T/BLOCK WALL/LINE OF CORTINA EAVE15'-0"ROOF -SPRING POINT15'-0" B/FACIA13'-0" T/PARAPET14'-8" B/GABLE16'-1 1/2" 2ND LEVEL12'-0" 1/3 GABLE 0119'-0 1/4" F.8 A-5023 SUB FLR. TENANT 'B' 7902.20-1'-0" SUB FLR. MECH. ROOM 7901.20-2'-0" 4" DIA. DRAINAGE TILE TENANT SPACE 'A' 100 COMPACTED GRAVEL FILL FOUNDATION DAMPPROOFING 1 Scale PROJECT NUMBER DATE DRAWN BY CHECKED BY modif. modif. 3/4" = 1’−0"8/7/2 0 1 9 2 : 4 6 : 3 9 P M A−311 2016−005 11.13.18 WALL SECTIONS CO M M E R C I A L DE V E L O P M E N T 232 E . M A I N S T . AS P E N , C O 3/4" = 1'-0"1 WALL SECTION - WEST WALL 3/4" = 1'-0"2 WALL SECTION - NORTH WALL 3/4" = 1'-0"3 WALL SECTION - EAST GLAZING NO. DATE BY REVISION 1 05.24.19 MODIF. PERMIT DOCUMENT REVISIONS 2 09.25.18 MODIF. PERMIT SET 3 11.28.18 MODIF. ISSUED FOR BID 4 08.2.19 MODIF. PERMIT DOCUMENT REVISION #1 Dimension the depth ofthe slab edgeinsulation. Must matchcomcheck. ROOF 21'-0" 8.5 9 4 1 / 8 " 3" = 1'-0"5 1 HOUR CEILING - STAIR ENCLOSURE Provide a listed assembly for the ceiling of the stair enclosure. 1 A-300 9 12 9 12 2 A-311 C.2C.4E.8F.8 SECOND FLOOR TENANT SPACE- 'B' 200 TENANT SPACE 'B' 101 " 5'- 5 " 2'- 8 1 / 2 " 1 A-504 1 1 JANITOR CLOSET 5/8" FIRECODE C GYPSUM PANEL, 2 1/2" METAL STUD @ 24" O.C., 1" GYP. BD. LINER PANEL. UL U415 1 UL U415 is a wall assembly. Per the gypsum manual general explanatory notes a wall assembly may not be arbitrarily used as a ceiling assembly. Choose a ceiling assembly and print the full UL instructions on the plans as you have done with the other UL assemblies. Subject: PlanCheck Page: 24 Page Index: 24 Author: nickt Color: File Name: Architectural Plan Set Nick.232 E Main.2019.08.pdf Indicate the threshold height of all nanawall and similar liftslide or folding doors. 1/2" max per 2015 IBC 1010.1.7 Subject: PlanCheck Page: 30 Page Index: 30 Author: nickt Color: File Name: Architectural Plan Set Nick.232 E Main.2019.08.pdf The trusses supporting the roof deck are wood per the structural plans. Please choose a different exception to the parapet requirement (your response stated that you would use exception 3, non-combustible construction). 2015 IBC 705.11 Subject: PlanCheck Page: 30 Page Index: 30 Author: nickt Color: File Name: Architectural Plan Set Nick.232 E Main.2019.08.pdf The insulation on the exterior of the wall does not connect with the insulation of the roof deck, this creates a gap in the envelope. You could insulate at the interior ledger to connect the insulation on the interior of the wall with the roof deck insulation, or you could find another method, or account for the gap in COMcheck with a portion of roof with 0 insulation. Subject: PlanCheck Page: [4] 18029 - M2(D-64)-M2.0 Page Index: 4 Author: nickt Color: File Name: Mechanical Plan Set.232 E Main.2019.08.pdf Now that the trash area is here and it is an incidental use per 2015 IBC 509, it is required to be either protected with 1 hour fire barriers (which would require fire dampers) or be sealed from the passage of smoke and fire sprinklered. Coordinate with architecturals. Mechanical Plan Set.232 E Main.2019.08.pdf (1) Subject: PlanCheck Page: 1 Page Index: 1 Author: nickt Color: File Name: Original Energy Code Compliance Comcheck interior lighting.232 E. Main St.2018.10.pdf I've included my comments from the originally submitted comcheck as I did not receive a new lighting comcheck. Provide interior and exterior lighting comchecks for the core and shell. Original Energy Code Compliance Comcheck interior lighting.232 E. Main St.2018.10.pdf (6) A FOLDING DOOR FOLDING DOOR FOLDING DOOR FOLDING DOOR 3'-7 5/8"3'-7 5/8"3'-7 5/8" BASIS OF DESIGN: NANAWALL HSW60 1 T T T T T T T 1 1'-0" NG ELEVATION Indicate the threshold height of all nanawall and similar liftslide or folding doors. 1/2" max per 2015 IBC 1010.1.7 09 29 00.D1 07 21 00.A10 07 26 00.A4 07 21 00.B10 3/8 " 1 07 44 50 1 BLIND RIVET 1 T/PARAPET14'-8" 2ND LEVEL12'-0" 07 61 00 05 05 23.E1 04 22 00.C3 04 22 00.A16 07 21 00.A10 07 21 00.B10 07 26 00.A4 06 11 00.A9 5/8"2 1/2"3"7 5/8" 1'-1 3/4" 09 29 00.D1 07 19 00.A2 32 31 13.A3 05 12 00.A129 (2) TYP. 3'- 1 0 1 / 2 " 2 1 / 4 " A-503 8 C.2 EXTERIOR A-503 4 Sim INTERIOR 06 16 00.D11 07 21 00.E4 06 16 00.D11 06 17 00.B8 08 71 00.A19 05 41 00.A6 07 21 00.A10 05 12 00.M296 1 1/2" = 1'-0"4 SECTION DETAIL - METAL RAINSCREEN The trusses supporting the roof deck are wood per the structural plans. Please choose a different exception to the parapet requirement (your response stated that you would use exception 3, non-combustible construction). 2015 IBC 705.11 T/ LOWER GLAZING10'-0" 2ND LEVEL12'-0" C T/PARAPET14'-8" 2ND LEVEL12'-0" 905 05 23.E1 07 61 00 06 11 00.A9 07 46 25 09 81 00.B2 07 26 00.A4UP AND OVER PARAPET WALL 04 22 00.A16 A-503 8 Sim 09 29 00.D1 3/8" 3"7 5/8"2 1/2" 5/8"1'-2 1/8" 07 19 00.A2 04 22 00.C3 04 22 00.C3 06 17 00.B8 42" HIGH GUARDRAIL 1 4 4 09 22 16.13.L2 4 T/ LOWER GLAZING10'-0" 2ND LEVEL12'-0" F.8 06 16 00.D11 07 21 00.E4 06 16 00.D11 06 17 00.B8 08 43 00.A13 05 12 00.M296 08 81 00.C8 FUTURE CEILING 1 T/PARAPET14'-8" F.8 Scale PROJECT NUMBER DATE DRAWN BY CHECKED BY modif. modif. 1 1/2" = 1’−0" 8/7 / 2 0 1 9 2 : 4 7 : 0 4 P M A−502 2016−005 11.13.18 WALL DETAILS AT SECOND LEVEL CO M M E R C I A L DE V E L O P M E N T 23 2 E . M A I N S T . AS P E N , C O 1 1/2" = 1'-0"9 SECTION DETAIL - NORTH PARAPET WALL 1 1/2" = 1'-0"8 SECTION DETAIL - INSULATED STOREFRONT - EAST AIL - SLOPED GLAZING MULLION 1 1/2" = 1'-0"3 SECTION DETAIL - WINDOW HEAD AT EAST GLAZING 09 29 00.D1 5/8" GYPSUM WALLBOARD 09 29 00.D15 5/8" DENSGLASS 09 81 00.B2 XPS INSULATION 10 73 13.A3 FORMED SHEET METAL 32 31 13.A3 MECHANICAL SCREENING NO. DATE BY REVISION 1 05.24.19 MODIF. PERMIT DOCUMENT REVISIONS 2 09.25.18 MODIF. PERMIT SET 3 11.28.18 MODIF. ISSUED FOR BID 4 08.2.19 MODIF. PERMIT DOCUMENT REVISION #1 The insulation on the exterior of the wall does not connect withthe insulation of the roof deck, this creates a gap in the envelope. You could insulate at the interior ledger to connect the insulation on the interior of the wall with the roof deck insulation, or you could find anothermethod, or account for the gap in COMcheck with a portion of roof with 0 insulation. UP TENANT SPACE 'A' 100 TENANT SPACE 'B' 101 TRASH AREA (300 SF) 103 MECH. RM. 102 ELEV. 5 6 7 8 8.5 9 10 C.2 C.4 E.8 F.8 JANITOR CLOSET 5 6 7 8 8.5 9 10 C.2 1''  1'-0'' 1''  1'-0'' 1''  1'-0'' SHEET DETAIL NOTES: THERMOSTATS SHALL BE PROVIDED WITH ADDITIONAL WIRING TO ACCOMMODATE FUTURE RELOCATION. TERMINATE 8"Ø BOILER FLUE AND 8"Ø COMBUSTION AIR DUCTWITH WIRE MESH AND A GOOSE NECK DOWN ON THE INTAKE. ENSURE A 36" MIN SEPARATION FROM INTAKE AND VENT.TERMINATION SHALL BE AT LEAST 7'-0" ABOVE ANY PUBLIC WALKWAY AND 3'-0" ABOVE ANY FORCED AIR INTAKE WITHIN 10'-0". DUCT CAPPED FOR FUTURE USE. ROUTE BOILER FLUES FROM BOILERS TO TERMINATION PER MANUFACTURER'S INSTRUCTIONS. SLOPE VENT PIPES AT 14"/FOOTBACK TO THE BOILER FOR ALL HORIZONTAL RUNS. MAINTAIN 1" CLEARANCE TO COMBUSTIBLES. DO NOT EXCEED 100' MAXIMUMDEVELOPED LENGTH FOR ANY RUN. ESTIMATED LENGTHS AND ELBOWS FOR LONGEST RUN BOILER ARE SHOWN BELOW: B-1 VENT (CPVC):HORIZONTAL DISTANCE:25'VERTICAL DISTANCE: 10'90 DEGREE ELBOWS:(5')(2) = 10'45 DEGREE ELBOWS:(3')(0) = 0'TERMINATION:5'MAX DEVELOPED LENGTH:50' B-1 CA (PVC):HORIZONTAL DISTANCE:25'VERTICAL DISTANCE: 10' 90 DEGREE ELBOWS:(5')(2) = 10'45 DEGREE ELBOWS:(3')(X) = 0' TERMINATION:5'MAX DEVELOPED LENGTH:50' FOLLOW ALL MANUFACTURER'S INSTRUCTIONS FOR BOILERVENTING MATERIALS. PROVIDE CPVC ROUTING FOR THE BOILER FLUES (PVC IS ACCEPTABLE FOR THE COMBUSTION AIR). PVC ISNOT ALLOWED FOR ANY BOILER FLUE ROUTINGS. INSTALL ROOFTOP UNITS PER MANUFACTURER'S INSTALLATION INSTRUCTIONS. UNIT SHALL BE PLACED ON 14" ROOF CURB. AECIS NOT ABLE TO PROVIDE ACOUSTICAL MODELING OF EXTERIOR EQUIPMENT, NOR PROVIDE DOCUMENTATION SUPPORTINGCOMPLIANCE WITH THE CITY OF ASPEN NOISE ORDINANCE. AN ACOUSTICAL CONSULTANT IS RECOMMENDED TO VERIFYCOMPLIANCE. NOISE MITIGATION MEASURES (BY OTHERS) MAY BE REQUIRED. INSTALL LOUVER L-2 SUCH THAT IT TERMINATES 3'-0" AWAY FROMNATURAL AIR INTAKES, 10'-0" FROM PROPERTY LINE, 7'-0" ABOVE WALKWAYS, 3'-0" ABOVE GROUND OR 12" ABOVE SNOW LEVEL(WHICHEVER IS HIGHER). ALL EXTERIOR DUCTWORK SHALL BE WRAPPED WITH 2" THICK GENERAL NOTES: 1.ALL DUCTWORK DIMENSIONS ARE SHOWN INSIDE TO INSIDE. 2.ALL INTERIOR SUPPLY AND RETURN DUCTWORK SHALL INCLUDE 1" LINER UNLESS OTHERWISE NOTED. ALL OUTSIDE AIR INTAKE ANDROUND DUCTWORK SHALL BE WRAPPED WITH 1.5" THICK INSULATION UNLESS OTHERWISE NOTED. 3.ALL SQUARE 90 DEGREE ELBOWS SHALL HAVE TURNING VANES. 4.ALL DUCTWORK SHALL BE RUN TIGHT TO UNDERSIDE OFSTRUCTURE WHERE IT EXISTS UNLESS OTHERWISE NOTED. 5.ALL DUCTWORK PASSING THROUGH FIRE-RATED ASSEMBLIES SHALL INCLUDE FIRE DAMPERS RATED TO MATCH THAT OF THEASSEMBLY. 6.COORDINATE ALL ACCESS PANEL LOCATIONS WITH THE ARCHITECT. RTU 3 RTU2 RTU 1 RTU 4 UH 1 UH2 38x16-SA (40x18)46x14-RA(48x16) 20x12-SA UP(22x14) 20x12-RA(22x14) 20x12-SA(22x14) T 1 2 T RTU-3 1 T RTU-2 1 12x8-EA (MAX 425 CFM) 3 4 2 5 3 3 3 3 6 5 5 5 5 20x12-RA UP(22x14) EF1 9"Ø-EA T EF-1 7 7 7 L-1680-EX 30x12 6 18x8-EA(MAX 680 CFM) B 1 4 20x12-RA(22x14) EF 2 6"Ø-EA 8 Now that the trash area is here and it is an incidental use per2015 IBC 509, it is required to be either protected with 1 hourfire barriers (whichwould require fire dampers) or be sealed from the passage ofsmoke and fire sprinklered. Coordinate with architecturals. I've included my comments from the originally submitted comcheck as I did not receive a new lighting comcheck. Provide interior and exterior lighting comchecks for the core and shell. Subject: PlanCheck Page: 1 Page Index: 1 Author: nickt Color: File Name: Original Energy Code Compliance Comcheck interior lighting.232 E. Main St.2018.10.pdf The architectural sheets show the occupancies as being B (business), not retail. Revise. Subject: PlanCheck Page: 1 Page Index: 1 Author: nickt Color: File Name: Original Energy Code Compliance Comcheck interior lighting.232 E. Main St.2018.10.pdf Choose the same additional efficiency package as the other COMchecks so they are all coordinated. 2015 IECC C406. Subject: PlanCheck Page: 1 Page Index: 1 Author: nickt Color: File Name: Original Energy Code Compliance Comcheck interior lighting.232 E. Main St.2018.10.pdf Fill out the site, agent, and designer fields. Subject: PlanCheck Page: 1 Page Index: 1 Author: nickt Color: File Name: Original Energy Code Compliance Comcheck interior lighting.232 E. Main St.2018.10.pdf All COMchecks should be on the same version. Current version is 4.1.1.0. Subject: PlanCheck Page: 1 Page Index: 1 Author: nickt Color: File Name: Original Energy Code Compliance Comcheck interior lighting.232 E. Main St.2018.10.pdf Label this interior lighting COMcheck as being the core and shell one. The architectural sheets show the occupancies as being B (business), not retail. Revise. Choose the same additional efficiency package as the other COMchecks so they are all coordinated. 2015 IECC C406. Fill out the site, agent, and designer fields. All COMchecks should be on the same version. Current version is 4.1.1.0. Label this interior lighting COMcheck as being the core and shell one. Subject: PlanCheck Page: 1 Page Index: 1 Author: nickt Color: File Name: Original Energy Code Mechanical Compliance For.232 E. Main St.2018.10.pdf Fill out the owner/agent portion of the comcheck. Original Energy Code Mechanical Compliance For.232 E. Main St.2018.10.pdf (4) Subject: PlanCheck Page: 1 Page Index: 1 Author: nickt Color: File Name: Original Energy Code Mechanical Compliance For.232 E. Main St.2018.10.pdf All COMchecks should be on the same version. Current version is 4.1.1.0. Subject: PlanCheck Page: 1 Page Index: 1 Author: nickt Color: File Name: Original Energy Code Mechanical Compliance For.232 E. Main St.2018.10.pdf The thermal envelope COMcheck calls out higher efficiency mechanical equipment as the chosen additional efficiency package (2015 IECC C406). Coordinate the COMchecks to choose the same additional efficiency package and demonstrate compliance. Subject: PlanCheck Page: 1 Page Index: 1 Author: nickt Color: File Name: Original Energy Code Mechanical Compliance For.232 E. Main St.2018.10.pdf I've included my comments from the originally submitted comcheck as I did not receive a new mechanical comcheck. Subject: PlanCheck Page: 1 Page Index: 1 Author: nickt Color: File Name: Original Submission Energy Code Compliance Comcheck.232 E. Main St.2018.10.pdf I've included my comments from the originally submitted comcheck as I did not receive a new envelope comcheck. Original Submission Energy Code Compliance Comcheck.232 E. Main St.2018.10.pdf (6) COMcheck Software Version 4.0.8.1 Mechanical Compliance Certificate e: 2015 IECC pe:New Construction Aspen, Colorado ne:7 on Site: ain St CO 81611 Owner/Agent:Designer/Contractor: Alex Timberlake AEC 40801 US Hwy 6 Ste 214 Avon, CO 81620 970-748-8520 alex@aec-vail.com Information de: 232 E Main Core and Shell nterior lighting power. Requirements are implicitly enforced within interior lighting allowance calculations. nal Efficiency Package(s) Fill out the owner/agent portion of the comcheck. Software Version 4.0.8.1 ical Compliance Certificate 2015 IECC New Construction Aspen, Colorado 7 232 E Main Core and Shell All COMchecks should be on the same version. Current version is 4.1.1.0. COMcheck Software Version 4.0.8.1 Mechanical Compliance Certificate Project Title: 2015 IECC Project Type:New Construction Location:Aspen, Colorado Climate Zone:7 Construction Site: 232 E Main StAspen, CO 81611 Owner/Agent:Designer/Contractor: Alex TimberlakeAEC 40801 US Hwy 6Ste 214 Avon, CO 81620970-748-8520 alex@aec-vail.com Project Information Energy Code: 232 E Main Core and Shell Reduced interior lighting power. Requirements are implicitly enforced within interior lighting allowance calculations. Additional Efficiency Package(s) Mechanical Systems List Quantity System Type & Description Heating: 1 each - Central Furnace, Gas, Capacity = 150 kBtu/h Proposed Efficiency = 80.00% Et, Required Efficiency = 80.00% Et Cooling: 1 each - Single Package DX Unit, Capacity = 73 kBtu/h, Evaporatively Cooled Condenser, Air Economizer Proposed Efficiency = 12.80 EER, Required Efficiency: 11.90 EER + 12.1 IEER Fan System: RTU-1 FAN -- Compliance (Brake HP method) : Passes Fans: RTU 1 FAN Supply, Multi-Zone VAV, 3000 CFM, 5.0 motor nameplate hp, 2.4 design brake hp (2.4 max. BHP), 80.0 fan efficiency grade 1 RTU-1 (Multiple-Zone): Heating: 1 each - Central Furnace, Gas, Capacity = 150 kBtu/h Proposed Efficiency = 80.00% Et, Required Efficiency = 80.00% Et Cooling: 1 each - Single Package DX Unit, Capacity = 87 kBtu/h, Air-Cooled Condenser, Air Economizer Proposed Efficiency = 13.50 EER, Required Efficiency: 11.00 EER + 12.6 IEER Fan System: RTU-1 FAN -- Compliance (Brake HP method) : Passes Fans: RTU 1 FAN Supply, Multi-Zone VAV, 3000 CFM, 5.0 motor nameplate hp, 2.4 design brake hp (2.4 max. BHP), 80.0 fan efficiency grade 1 RTU-2 (Multiple-Zone): Heating: 1 each - Central Furnace, Gas, Capacity = 72 kBtu/h Proposed Efficiency = 82.00% Et, Required Efficiency = 80.00% Et Cooling: 1 each - Single Package DX Unit, Capacity = 30 kBtu/h, Air-Cooled Condenser, Air Economizer Proposed Efficiency = 15.50 SEER, Required Efficiency: 14.00 SEER Fan System: RTU-3 FAN -- Compliance (Brake HP method) : Passes 1 RTU-3 (Multiple-Zone): The thermal envelope COMcheck calls out higher efficiency mechanical equipment as the chosen additional efficiency package (2015 IECC C406). Coordinate the COMchecks to choose the same additional efficiency package and demonstrate compliance. COMcheck Software Mechanical Co Project Title: 2015 IECC Project Type:New Construc Location:Aspen, Colora Climate Zone:7 Project Information Energy Code: 232 E Main Co I've included my comments from the originally submitted comcheck as I did not receive a new mechanical comcheck. oftware Version 4.1.0.0 Compliance Certificate 15 IECC ew Construction 2018 % spen, Colorado Owner/Agent:Designer/Contractor: 2 MAIN ST. I've included my comments from the originally submitted comcheck as I did not receive a new envelope comcheck. Subject: PlanCheck Page: 1 Page Index: 1 Author: nickt Color: File Name: Original Submission Energy Code Compliance Comcheck.232 E. Main St.2018.10.pdf None of the wall assemblies match any of the COMcheck walls. Coordinate COMcheck with architectural wall assemblies. Subject: PlanCheck Page: 1 Page Index: 1 Author: nickt Color: File Name: Original Submission Energy Code Compliance Comcheck.232 E. Main St.2018.10.pdf Include the sloped glazing/skylight in the comcheck. Subject: PlanCheck Page: 1 Page Index: 1 Author: nickt Color: File Name: Original Submission Energy Code Compliance Comcheck.232 E. Main St.2018.10.pdf All COMchecks should be on the same version. Current version is 4.1.1.0. Subject: PlanCheck Page: 1 Page Index: 1 Author: nickt Color: File Name: Original Submission Energy Code Compliance Comcheck.232 E. Main St.2018.10.pdf None of the CMU wall assemblies have R19.5 continuous insulation. Some of them have R-15. Coordinate COMcheck with the plans. Use the same nomenclature as G-005 to label each element. Subject: Group Page: 3 Page Index: 3 Author: nickt Color: File Name: Original Submission Energy Code Compliance Comcheck.232 E. Main St.2018.10.pdf Your details lack slab edge insulation. Slab-on-grade floors with a floor surface less than 24" below grade must have insulation extending downward from the top of the slab on the outside or inside of the foundation wall.The insulation must be extended for by any combination of vertical insulation, insulation extending under the slab or insulation extending out from the building. See the details below for examples. As currently drawn, revise COMcheck to show 0 for slab edge insulation. 2015 IECC C402.2.5 2-Second Floor (Office) : Nonresidential 1686 Envelope Assemblies Assembly Cavity R-Value Cont. R-Value Proposed U-Factor Budget U- Factor(a) Gross Area or Perimeter Roof 1 wood shigles: Attic Roof with Wood Joists, [Bldg. Use 2 - Second Floor] 2322 0.0 24.0 0.039 0.021 Roof 2 gable structure: Insulation Entirely Above Deck, [Bldg. Use 1 - Ground Floor] 2195 ---24.0 0.040 0.028 Roof 2 flat: Insulation Entirely Above Deck, [Bldg. Use 1 - Ground Floor]1224 ---42.0 0.023 0.028 Floor 1: Slab-On-Grade:Unheated, Vertical 4 ft., [Bldg. Use 1 - Ground Floor] (d) 275 ---15.0 0.450 0.520 NORTH Exterior North Wall: Concrete Block:8", Partially Grouted, Cells Empty, Normal Density, Furring: Metal, [Bldg. Use 1 - Ground Floor] 1180 0.0 19.5 0.044 0.071 Door 1: Insulated Metal, Swinging, [Bldg. Use 1 - Ground Floor]21 ------0.660 0.370 EAST Exterior East Wall: Steel-Framed, 16" o.c., [Bldg. Use 1 - Ground Floor]1281 19.0 18.0 0.037 0.064 Window 3 around door: Metal Frame with Thermal Break:Fixed, Perf. Specs.: Product ID PORTELLA, SHGC 0.18, PF 0.14, VT 0.43, [Bldg. Use 1 - Ground Floor] (c) 60 ------0.290 0.290 Window 4 around door: Metal Frame with Thermal Break:Fixed, Perf. Specs.: Product ID PORTELLA, SHGC 0.18, PF 0.14, VT 0.34, [Bldg. Use 1 - Ground Floor] (c) 61 ------0.290 0.290 Project Title: Data filename: 232 MAIN ST. X:\Aspen\2016-005 232 E Main St\municipal\232 MAIN ST 9-05.cck 09/05/18Report date: 151 ofPage None of the wall assemblies match any of the COMcheck walls. Coordinate COMcheck with architectural wall assemblies. 1200 W Lake St Suite 200 Chicago, IL 60607 312-714-8519 bhribar@centaurco.com High efficiency HVAC. Systems that do not meet the performance requirement will be identified in th report. Additional Efficiency Package(s) Building Area Floor Area 1-Ground Floor (Office) : Nonresidential 4341 2-Second Floor (Office) : Nonresidential 1686 Envelope Assemblies Assembly Cavit R-Valu Gross Area or Perimeter Roof 1 wood shigles: Attic Roof with Wood Joists, [Bldg. Use 2 - Second Floor] 2322 0.0 Roof 2 gable structure: Insulation Entirely Above Deck, [Bldg. Use 1 - Ground Floor] 2195 --- Roof 2 flat: Insulation Entirely Above Deck, [Bldg. Use 1 - Ground Floor]1224 --- Floor 1: Slab-On-Grade:Unheated, Vertical 4 ft., [Bldg. Use 1 - Ground Floor] (d) 275 --- NORTH Exterior North Wall: Concrete Block:8", Partially Grouted, Cells Empty, Normal Density, Furring: Metal, [Bldg. Use 1 - Ground Floor] 1180 0.0 Door 1: Insulated Metal, Swinging, [Bldg. Use 1 - Ground Floor]21 --- EAST Exterior East Wall: Steel-Framed, 16" o.c., [Bldg. Use 1 - Ground Floor]1281 19.0 Include the sloped glazing/skylight in the comcheck. Software Version 4.1.0.0 e Compliance Certificate 2015 IECC New Construction 1/2018 33% Aspen, Colorado 7 232 MAIN ST. All COMchecks should be on the same version. Current version is 4.1.1.0. COMcheck Software Version 4.1.0.0 Envelope Compliance Certificate Project Title: 2015 IECC Project Type:New Construction Permit Date:1/2018 Vertical Glazing / Wall Area:33% Location:Aspen, Colorado Climate Zone:7 Construction Site: 232 E. MAIN ST. Aspen, CO 81611 Owner/Agent: Brad Hribar Centaur Construction1200 W Lake St Suite 200 Chicago, IL 60607 312-714-8519bhribar@centaurco.com Designer/Contractor: Steve Coughlin modif. architecture1200 W Lake St Suite 200 Chicago, IL 60607 708-261-2611steve.coughlin@modifarchitecture.c om Project Information Energy Code: 232 MAIN ST. High efficiency HVAC. Systems that do not meet the performance requirement will be identified in the mechanical requirements checklist report. Additional Efficiency Package(s) Building Area Floor Area 1-Ground Floor (Office) : Nonresidential 4341 2-Second Floor (Office) : Nonresidential 1686 Envelope Assemblies Assembly Cavity R-Value Cont. R-Value Proposed U-Factor Budget U- Factor(a) Gross Area or Perimeter Roof 1 wood shigles: Attic Roof with Wood Joists, [Bldg. Use 2 - Second Floor] 2322 0.0 24.0 0.039 0.021 Roof 2 gable structure: Insulation Entirely Above Deck, [Bldg. Use 1 - Ground Floor] 2195 ---24.0 0.040 0.028 Roof 2 flat: Insulation Entirely Above Deck, [Bldg. Use 1 - Ground Floor]1224 ---42.0 0.023 0.028 Floor 1: Slab-On-Grade:Unheated, Vertical 4 ft., [Bldg. Use 1 - Ground Floor] (d) 275 ---15.0 0.450 0.520 NORTH Exterior North Wall: Concrete Block:8", Partially Grouted, Cells Empty, Normal Density, Furring: Metal, [Bldg. Use 1 - Ground Floor] 1180 0.0 19.5 0.044 0.071 Door 1: Insulated Metal, Swinging, [Bldg. Use 1 - Ground Floor]21 ------0.660 0.370 EAST Exterior East Wall: Steel-Framed, 16" o.c., [Bldg. Use 1 - Ground Floor]1281 19.0 18.0 0.037 0.064 Window 3 around door: Metal Frame with Thermal Break:Fixed, Perf. Specs.: Product ID PORTELLA, SHGC 0.18, PF 0.14, VT 0.43, [Bldg. Use 1 - Ground Floor] (c) 60 ------0.290 0.290 Window 4 around door: Metal Frame with Thermal Break:Fixed, Perf. Specs.: Product ID PORTELLA, SHGC 0.18, PF 0.14, VT 0.34, [Bldg. Use 1 - Ground Floor] (c) 61 ------0.290 0.290 Project Title: Data filename: 232 MAIN ST. X:\Aspen\2016-005 232 E Main St\municipal\232 MAIN ST 9-05.cck 09/05/18Report date: 151 ofPage None of the CMU wall assemblies have R19.5 continuous insulation. Some of them have R-15. Coordinate COMcheck with the plans. Use the same nomenclature as G-005 to label each element. Envelope Compliance Statement Compliance Statement: The proposed envelope design represented in this document is consistent with the building plans, specifications, and other calculations submitted with this permit application. The proposed envelope systems have beendesigned to meet the 2015 IECC requirements in COMcheck Version 4.1.0.0 and to comply with any applicable mandatory requirements listed in the Inspection Checklist. Name - Title Signature Date Envelope PASSES: Design 1% better than code Project Title: Data filename: 232 MAIN ST. X:\Aspen\2016-005 232 E Main St\municipal\232 MAIN ST 9-05.cck 09/05/18Report date: 153 ofPage Your details lack slab edge insulation. Slab-on-grade floors with a floor surface less than 24" below grade must have insulation extending downward from the top of the slab on the outside or inside of the foundation wall.The insulation must be extended for by any combination of vertical insulation, insulation extending under the slab or insulation extending out from the building. See the details below for examples. As currently drawn, revise COMcheck to show 0 for slab edge insulation. 2015 IECC C402.2.5