Page: [1] 1-Cover Cover Sheet
File Name: Civil - Comment Response Drawings.pdf An updated drainage report was
not included in the resubmittal.
Please provide.
Civil - Comment Response Drawings.pdf (18)
Page: [5] C2 Site Plan
File Name: Civil - Comment Response Drawings.pdf Will the snowmelted concrete
end at the property line? If
snowmelt is placed int he ROW
it needs to be on a separate
zone and will require a
permanent encroachment
license.
Page: [5] C2 Site Plan
File Name: Civil - Comment Response Drawings.pdf Verify the proposed C&G detail
matches the neighbors C&G.
Page: [5] C2 Site Plan
File Name: Civil - Comment Response Drawings.pdf Provide snowmelted pervious
paver detail. Clarify on the plans
the extents of the snowmelted
pervious pavers.
Page: [6] C3 Utility Plan
File Name: Civil - Comment Response Drawings.pdf Show asphalt patch for
abandonment of the existing
water service. Show abandoned
water service line.
LLC
.
An updated drainage report was not included in the resubmittal. Please provide.
Will the snowmelted concrete
end at the property line? Ifsnowmelt is placed int he ROW
it needs to be on a separate
zone and will require a
permanent encroachment
license.
Verify the proposed C&G detail
matches the neighbors C&G.
Provide snowmelted pervious
paver detail. Clarify on the plans
the extents of the snowmelted
pervious pavers.
Show asphalt patch for
abandonment of the existing
water service. Show abandoned
water service line.
Page: [6] C3 Utility Plan
File Name: Civil - Comment Response Drawings.pdf The demo plan and response to
comments states the existing
sanitary service line will be
reused. This utility sheet is
showing a new service line.
Please verify and show what is
planned.
Page: [6] C3 Utility Plan
File Name: Civil - Comment Response Drawings.pdf Show or call out what
transformer the property is tying
in to. Reach out the the Electric
Department to ensure the
existing transformer has capacity
to feed the new house.
Page: [6] C3 Utility Plan
File Name: Civil - Comment Response Drawings.pdf Provide fire flow calcs or a
memo from the fire suppression
company that verifies a 2" line is
needed and a smaller service
line will not provide adequate fire
suppression flows.
Page: [7] C4 Grading & Drainage Plan
File Name: Civil - Comment Response Drawings.pdf Has HPC approved the
placement of the lid in front of
the historical house? Typically
manhole lids are not permitted. If
the lid is covered the
maintenance and inspections of
the pump needs to be
addressed.
Page: [7] C4 Grading & Drainage Plan
File Name: Civil - Comment Response Drawings.pdf The drainage report does not
mention a sump pump. Is the 4"
drain routed to the sump pump
where it is then pumped up to
the reverse trench drain? With a
no infiltration paver section the
pump will turn on after every
storm. Verify runoff will be
evenly spread and will not point
discharge into the ROW or erode
a path.
The demo plan and response to
comments states the existing
sanitary service line will be
reused. This utility sheet is
showing a new service line.
Please verify and show what is
planned.
Show or call out what
transformer the property is tying
in to. Reach out the the Electric
Department to ensure the
existing transformer has
capacity to feed the new house.
Provide fire flow calcs or a
memo from the fire suppression
company that verifies a 2" line is
needed and a smaller service
line will not provide adequate
fire suppression flows.
Has HPC approved the
placement of the lid in front of
the historical house? Typically
manhole lids are not permitted.
If the lid is covered themaintenance and inspections ofthe pump needs to be
addressed.
The drainage report does not
mention a sump pump. Is the 4"
drain routed to the sump pump
where it is then pumped up to
the reverse trench drain? With
a no infiltration paver section the
pump will turn on after every
storm. Verify runoff will be
evenly spread and will not point
discharge into the ROW or
erode a path.
Page: [7] C4 Grading & Drainage Plan
File Name: Civil - Comment Response Drawings.pdf The drainage report says runoff
from basin 4 and 5 will sheet
flow to 5th St. This plan shows
runoff routed to the pump and
reverse trench drain. Please
update report.
Page: [7] C4 Grading & Drainage Plan
File Name: Civil - Comment Response Drawings.pdf No plumbing plans are provided.
Show downspouts and how
structure drains.
Page: [7] C4 Grading & Drainage Plan
File Name: Civil - Comment Response Drawings.pdf How does the patio drain? The
civil plans call out a flat patio.
The mechanical plans do not
show any drains. There are no
plumbing plans provided in the
submittal. Is the design to have
4" of grass in between the
pavers and a standard green
roof drainage? Where is
drainage routed?
Page: [7] C4 Grading & Drainage Plan
File Name: Civil - Comment Response Drawings.pdf No infiltration pervious pavers
require an underdrain. Please
show underdrain routing. This
strip of pavers appears to be
outside the extents of the
subgrade building.
Page: [7] C4 Grading & Drainage Plan
File Name: Civil - Comment Response Drawings.pdf Provide a detail of snowmelted
no infiltration pervious pavers
above subgrade structure.
The drainage report says runofffrom basin 4 and 5 will sheetflow to 5th St. This plan showsrunoff routed to the pump andreverse trench drain. Pleaseupdate report.
No plumbing plans are provided.
Show downspouts and how
structure drains.
How does the patio drain? Thecivil plans call out a flat patio.
The mechanical plans do notshow any drains. There are no
plumbing plans provided in the
submittal. Is the design to have4" of grass in between the
pavers and a standard greenroof drainage? Where is
drainage routed?
No infiltration pervious pavers
require an underdrain. Please
show underdrain routing. This
strip of pavers appears to be
outside the extents of thesubgrade building.
Provide a detail of snowmelted
no infiltration pervious pavers
above subgrade structure.
Page: [7] C4 Grading & Drainage Plan
File Name: Civil - Comment Response Drawings.pdf The landscape plan sheet L1.01
calls out concrete pavers set in
sand on existing grade within
driplines. Show the extents of
the sand set pavers and the
extents of the true pervious
paver detail with gravel
subgrade. WQCV can only be
accounted for in areas with a
section that matches the URMP
detail.
Provide a detail of the pavers set
in sand in the dripline. The area
of these pavers is considered
impervious.
Page: [10] C7 Detail (1)
File Name: Civil - Comment Response Drawings.pdf On the plan view show the
extents of the floating sidewalk.
The property is in a sidewalk
deffered zone and thus a public
sidewalk is not needed. Where is
this floating sidewalk detail
utilized?
Page: [11] C8 Detail (2)
File Name: Civil - Comment Response Drawings.pdf This detail is for full full
infiltration pavers. The plan calls
out no infiltration pavers. Clarify
where infiltration pavers are
utilized.
The landscape plan sheet L1.01
calls out concrete pavers set insand on existing grade within
driplines. Show the extents ofthe sand set pavers and theextents of the true perviouspaver detail with gravelsubgrade. WQCV can only beaccounted for in areas with asection that matches the URMPdetail.
Provide a detail of the paversset in sand in the dripline. The
area of these pavers isconsidered impervious.
On the plan view show the
extents of the floating sidewalk.
The property is in a sidewalkdeffered zone and thus a publicsidewalk is not needed. Whereis this floating sidewalk detailutilized?
This detail is for full fullinfiltration pavers. The plan callsout no infiltration pavers. Clarifywhere infiltration pavers are
utilized.