HomeMy WebLinkAboutFile Documents.533 W Hallam St.0285.2018 (86).ARBK0285-2018-ARBK_BuildingComment1
Subject: PlanCheck
Page Label: A101
Author: justinh
File Name: Architectural Plans. 533 W HALLAM.pdf
Color:
I believe the site plan was
supposed to be revised so that
guards were not required around
the window wells set into walking
surfaces as is shown here.
Please revise, building will have
to require guards around any
light wells or emergency escape
egress wells that are surrounded
by a walking surface. If the patio
layout is changed please be sure
to also update the REMP plan,
etc. as applicable.
Architectural Plans. 533 W HALLAM.pdf (22)
Subject: PlanCheck
Page Label: A101
Author: justinh
File Name: Architectural Plans. 533 W HALLAM.pdf
Color:
Identify patio materials, there is
a detail for permeable pavers
and the site plan should clearly
show where this is proposed.
Subject: PlanCheck
Page Label: A203
Author: justinh
File Name: Architectural Plans. 533 W HALLAM.pdf
Color:
Show all electrical panel
locations on your architectural
floor plans.
Subject: PlanCheck
Page Label: A205
Author: justinh
File Name: Architectural Plans. 533 W HALLAM.pdf
Color:
Show your radon mitigation
system termination pipe on the
roof plan along with any other
venting that is not currently
shown.
Subject: PlanCheck
Page Label: A205
Author: justinh
File Name: Architectural Plans. 533 W HALLAM.pdf
Color:
Show compliant secondary roof
drainage per IRC 903.4.1, either
scuppers or secondary drains. If
secondary drains are used they
must discharge to a different
location than the primary drains
where they will be observed by
the building occupant per IPC
1108.2.
7914
7913
7915
14
14
14
13
14
13
15
10' SETBACK
PROPERTY LINE N14°50'49"E 100.00'
10'
S
E
T
B
A
C
K
5TH STREET
HAL
L
A
M
S
T
R
E
E
T
GR
A
V
E
L
A
L
L
E
Y
60'
-
0
"
60'
-
0
"
100' - 0"
100' - 0"
AA
1
1
LIGHT WELL LIGHT WELL LIGHT WELL LIGHT WELL BELOWBELOWBELOWBELOW LIGHT WELL LIGHT WELL LIGHT WELL LIGHT WELL BELOWBELOWBELOWBELOW
LIGHT WELL LIGHT WELL LIGHT WELL LIGHT WELL BELOWBELOWBELOWBELOW
LIGHT WELL LIGHT WELL LIGHT WELL LIGHT WELL BELOWBELOWBELOWBELOW
8' - 6" + V.I.F.
V.I.
F
.
SETBACK
10' - 0"
V.I.F.
SETBACK
5' - 0"
PROPOSED 36" FENCE
5' SETBACK
6' PRIVACY FENCE
3' WIDE GATE
SETBACK
10' - 0"
PRO
P
E
R
T
Y
L
I
N
E
S
7
5
°
0
9
'
1
1
"
E
6
0
.
0
0
'
12' - 2 1/4"
11' - 11 1/2"
PROPERTY LINE
PR
O
P
E
R
T
Y
L
I
N
E
DRIP LINE OF COTTONWOOD ESTABLISHED BY PARKS DEPT.VIA PHONE ON 9.12.2018
LINE OF NO FOUNDATION / DIGGING ESTABLISHED BY PARKS IN PERSON MEETING ON 06.19.2018
COTTONWOOD TREE LOCATED ON THE SURVEY
1' - 6"
1. BUILDING ELEVATION 100' - 0" = USGS ELEVATION 7915.7'
2. REFER TO CIVIL DRAWINGS FOR FINAL GRADING.
3. REFER TO CIVIL AND LANDSCAPE PLANS FOR ALL SITE RELATED WORK AND VEGETATION.
ARCHITECTURAL SITE PLAN NOTESARCHITECTURAL SITE PLAN NOTESARCHITECTURAL SITE PLAN NOTESARCHITECTURAL SITE PLAN NOTES
NOR
Consultant
ARCHITECTUREARCHITECTUREARCHITECTUREARCHITECTURE
(((( TTTT )))) 9999 7777 0000 //// 9999 2222 5555 4444 7777 5555 5555
6666 0000 5555 EEEE AAAA SSSS TTTT MMMM AAAA IIII NNNN SSSS TTTT RRRR EEEE EEEE TTTT AAAA
SHEET TITLE
BILL POSS AND ASSO ARCHITECTURE AND
THE INFORMATION AND DESIGN INTENT CON PROPERTY OF BILL POSS AND ASSOCIATES, OF THIS INFORMATION MAY BE USED WITHO POSS AND ASSOCIATES, ARCHITECTURE AN ARCHITECTURE AND PLANNING, P.C. SHALL OTHER RESERVED RIGHTS, INCLUDINGCOP
c 2018
PROJECT NO:
Issue:
11/
2
8
/
2
0
1
8
9
:
4
9
:
4
3
A
M
DDDDUUUUNNNNCCCCAAAANNNN RRRREEEESSSSIIIIDDDD
533 W HALLAM ST AS
A101A101A101A101
AAAARRRRCCCCHHHHIIIITTTTEEEECCCCTTTTUUUURRRRAAAA
21708.00
SCALE 1/4" = 1'-0"1 ARCHITECTURAL SITE PLAN
1 11.27.2018
I believe the site plan wassupposed to be revised so thatguards were not required aroundthe window wells set into walkingsurfaces as is shown here. Please revise, building will have torequire guards around any lightwells or emergency escapeegress wells that are surroundedby a walking surface. If the patio
layout is changed please be sureto also update the REMP plan,etc. as applicable.
1
4
10' SETBACK
N14°50'49"E 100.00'
100' - 0"
LIGHT WELL LIGHT WELL LIGHT WELL LIGHT WELL
BELOWBELOWBELOWBELOW
V.
I
.
F
.
SETBACK
10' - 0"
PROPOSED 36" FENCE
LINE OF NO FOUNDATION /
DIGGING ESTABLISHED BY
PARKS IN PERSON MEETING
ON 06.19.2018
Identify patio materials,
there is a detail for
permeable pavers and
the site plan should
clearly show where
this is proposed.
A
PR
O
P
E
R
T
Y
L
I
N
B
4'
-
6
"
6"
12
'
-
2
3
/
8
"
Show all electrical panel locations on
your architectural floor plans.
NE OF
OW
Show your radon mitigation
system termination pipe on the
roof plan along with any other
venting that is not currently shown.
Show compliant secondary roof drainage per
IRC 903.4.1, either scuppers or secondary
drains. If secondary drains are used they
must discharge to a different location than the
primary drains where they will be observed by
the building occupant per IPC 1108.2.
Subject: PlanCheck
Page Label: A404
Author: justinh
File Name: Architectural Plans. 533 W HALLAM.pdf
Color:
Please dimension the height and
opening size on your guard to
show compliance with IRC 312
Subject: PlanCheck
Page Label: A404
Author: justinh
File Name: Architectural Plans. 533 W HALLAM.pdf
Color:
Please show utility meters on
your elevations.
Subject: PlanCheck
Page Label: A702
Author: justinh
File Name: Architectural Plans. 533 W HALLAM.pdf
Color:
Show a compliant handrail and
guard on the lower level stairs.
Subject: PlanCheck
Page Label: A702
Author: justinh
File Name: Architectural Plans. 533 W HALLAM.pdf
Color:
Please add dimensions to show
that both the guard and open
risers meet the opening
limitation requirements of IRC
312.1.3.
Subject: PlanCheck
Page Label: A804
Author: justinh
File Name: Architectural Plans. 533 W HALLAM.pdf
Color:
Please verify that HPC will allow
you to spray foam the existing
wall cavities of the historic
building. How are you proposing
to waterproof behind the existing
historic siding as this detail
shows?
04
03
GUARDRAIL
PER CODE
LIGHTWELL
Please dimension the
height and opening
size on your guard to
show compliance with
IRC 312
04
DRYER VENT
UARDRAIL
PER CODE
LIGHTWELL Please show utility
meters on your
elevations.
T.O. F.F. @ MAIN
100' - 0"
T.O. F.F. @ UPPER
110' - 4 1/2"
T.O. PLY @ MAIN
99' - 9"
T.O. PLY @ UPPER
110' - 1 1/2"
6' - 8"MIN. HEAD
HEIG H T
MIN. HEA D
H EIGHT
10 3/4"
7"
T.O. PLY @ BASEMENT
86' - 4"
T.O. F.F. @ BASEMENT86' - 7"
T.O. CONC. @ CRAWL SPACE
79' - 6 3/8"
6' - 8"
6' - 8"
3' - 0"
001
FAMILY /FAMILY /FAMILY /FAMILY /
GAMEGAMEGAMEGAME
M01
MECHANICALMECHANICALMECHANICALMECHANICAL
CRAWLSPACECRAWLSPACECRAWLSPACECRAWLSPACE
106
LIVINGLIVINGLIVINGLIVING
STAIRSTAIRSTAIRSTAIR
MECHANICAL
ACCESS HATCH
6' - 8"
MIN. HEAD
HEIGHT
MIN. HEAD
HEIGHT
11 3/4"
7"
6' - 8"
M01
MECHANICALMECHANICALMECHANICALMECHANICAL
CRAWLSPACECRAWLSPACECRAWLSPACECRAWLSPACE
STAIRSSTAIRSSTAIRSSTAIRS
STAIRSSTAIRSSTAIRSSTAIRS
004
STO.STO.STO.STO.001
FAMILY /FAMILY /FAMILY /FAMILY /
GAMEGAMEGAMEGAME
ANICAL
S HATCH
SCALE 1/4" = 1'-0"1 STAIR SECTION - NORTHSOUTH
Show a compliant
handrail and guard on
the lower level stairs.
T.O. F.F. @ MAIN
100' - 0"
T.O. F.F. @ UPPER
110' - 4 1/2"
T.O. PLY @ MAIN
99' - 9"
T.O. PLY @ UPPER
110' - 1 1/2"
6' - 8"M IN. HEAD
H EIGH T
MIN. H E A D
H EIGHT
10 3/4"
7"
006
A
004
A
ELEV
B
ELEVC
T.O. PLY @ BASEMENT
86' - 4"
T.O. F.F. @ BASEMENT
86' - 7"
6' - 8"
6' - 8"
3' - 0"
004
STO.STO.STO.STO.
005
LAUNDRYLAUNDRYLAUNDRYLAUNDRY
001
FAMILY /FAMILY /FAMILY /FAMILY /
GAMEGAMEGAMEGAME
106
LIVINGLIVINGLIVINGLIVING
STAIRSTAIRSTAIRSTAIR
STAIRSSTAIRSSTAIRSSTAIRS
MECHANICAL
ACCESS HATCH
Please add
dimensions to show
that both the guard
and open risers meet
the opening limitation
requirements of IRC
312.1.3.
INTERIORINTERIORINTERIORINTERIOR PER P
PANEL MODULE
1/2"
PANEL MODULE
PER P 5/8"3/4"
1/4"3/4"
1 1/2"EXTERIOREXTERIOREXTERIOREXTERIORPER PLAN5/8"
INTERIOR FINISH
REF. FINISH SHCHED.
WATERPROOFING
SPRAYED FOAM INSULATION
(R-20 MIN.)
EXISTING WOOD FRAMING
REF. STRUCT. DWGS.
5/8" GYPSUM WALL BOARD
EXISTING WOOD SIDING
INTERIORINTERIORINTERIORINTERIOR
EXTERIOREXTERIOREXTERIOREXTERIOR
4"3/4"1/2"5/8"
3/4" PLYWOOD SHEATHING
SCALE 3
W-8 METAL
SCALE 3
W-9 WOOD C
SCALE 3" = 1'-0"W-11 EXISTING HISTORIC WOOD SIDING
SCALE 3" = 1'-0"W-12 NEW HISTORIC WOOD SIDING
Please verify that HPC will
allow you to spray foam
the existing wall cavities
of the historic building.
How are you proposing to
waterproof behind the
existing historic siding as
this detail shows?
Subject: PlanCheck
Page Label: A804
Author: justinh
File Name: Architectural Plans. 533 W HALLAM.pdf
Color:
All basement/foundation wall
details should be showing
waterproofing, please revise.
Subject: PlanCheck
Page Label: A805
Author: justinh
File Name: Architectural Plans. 533 W HALLAM.pdf
Color:
This wall assembly is not
required to be fire rated, we
measure fire separation distance
to the center of the alley on the
south side of the building.
Please revise.
Subject: PlanCheck
Page Label: A806
Author: justinh
File Name: Architectural Plans. 533 W HALLAM.pdf
Color:
I believe you may have a
layering issue here, the detail is
not actually shown. Please
revise.
Subject: PlanCheck
Page Label: A808
Author: justinh
File Name: Architectural Plans. 533 W HALLAM.pdf
Color:
Provide documentation of class
A assembly for these assemblies
similar to what you provided for
both the flat membrane roof and
sloped shingle roof.
Subject: PlanCheck
Page Label: A808
Author: justinh
File Name: Architectural Plans. 533 W HALLAM.pdf
Color:
Provide a detail showing your
proposed hole pattern in the rigid
insulation that will achieve a R10
weighted average while still
meeting engineering's 30% open
requirement to be permeable
(this detail only shows 20%, but
I believe engineering requires
30%). Attached is our pervious
snowmelt calculator that can
help to find the pattern that best
suits your situation.
EXTERIOR
R-15/19
HYDRODUCT COIL 600
5/8" TYPE X GWB
2X FURRING
RUCTURAL 1/2"3"
1/2" FURRING GAP
UNDATION WALL WEST
All basement/foundation wall details should be
showing waterproofing, please revise.
. PAINTED WOOD
G
IOR FINISH
INISH SHCHED.
HER RESISTIVE
ER
AGE MAT
YED FOAM INSULATION
MIN.)
FRAMING
STRUCT. DWGS.
YPSUM WALL BOARD
ATED SHEATHING
L (R-5 MIN.)
R WALL SHEATHING
STRUCT. DWGS.
INTERIOR FINISH
REF. FINISH SHCHED.
WEATHER RESISTIVE
BARRIER
DRAINAGE MAT
SPRAYED FOAM INSULATION
(R-20 MIN.)
WOOD FRAMING
REF. STRUCT. DWGS.
5/8" GWB TYPE X
INSULATED SHEATHING
PANEL (R-5 MIN.)
HORIZ. CHANNEL LAP
WOOD SIDING
3/4"
1/4"
2 1/8"
INTERIORINTERIORINTERIORINTERIOR
EXTERIOREXTERIOREXTERIOREXTERIOR
PER PLAN5/8"
8 5/8"
3/4"
1/2"
9 7/8"
1"
SHEET TITLE
BILL POSS AND ASSOCIATES,
ARCHITECTURE AND PLANNING, P.C.
THE INFORMATION AND DESIGN INTENT CONTAINED ON THIS DOCUMENT IS THE PROPERTY OF BILL POSS AND ASSOCIATES, ARCHITECTURE AND PLANNING, P.C.NO PART
OF THIS INFORMATION MAY BE USED WITHOUT THE PRIOR WRITTEN PERMISSION OF BILL
POSS AND ASSOCIATES, ARCHITECTURE AND PLANNING, P.C. BILL POSS AND ASSOCIATES,
ARCHITECTURE AND PLANNING, P.C. SHALL RETAIN ALL COMMON LAW STATUTORY AND
OTHER RESERVED RIGHTS, INCLUDINGCOPYRIGHT THERETO.
c 2018
PROJECT NO:
SCALE:
3" = 1'-0"
533 W HALLAM ST ASPEN, CO 81611
A805A805A805A805
ASSEMBLIES ASSEMBLIES ASSEMBLIES ASSEMBLIES ---- EEEEXXXXTTTTEEEERRRRIIIIOOOORRRR
WALLWALLWALLWALL
21708.00
WALL
SCALE 3" = 1'-0"W-13 WOOD CHANNEL LAP SIDING - 1HR RATED
This wall assembly is
not required to be fire
rated, we measure fire
separation distance to
the center of the alley
on the south side of
the building. Please
revise.
ON THINSET MORTAR
CEMENTITIOUS
KERBOARD W/ FLUID
LIED WATERPROOFING
ND-ATTENUATION
T INSULATION
GWB
FRAMING,
STRUCT.
6 WD. FRAMING
SHEET TITLE
BILL POSS AND ASSOCIATES,
ARCHITECTURE AND PLANNING, P.C.
THE INFORMATION AND DESIGN INTENT CONTAINED ON THIS DOCUMENT IS THE
PROPERTY OF BILL POSS AND ASSOCIATES, ARCHITECTURE AND PLANNING, P.C.NO PART
OF THIS INFORMATION MAY BE USED WITHOUT THE PRIOR WRITTEN PERMISSION OF BILL
POSS AND ASSOCIATES, ARCHITECTURE AND PLANNING, P.C. BILL POSS AND ASSOCIATES ARCHITECTURE AND PLANNING, P.C. SHALL RETAIN ALL COMMON LAW STATUTORY AND
OTHER RESERVED RIGHTS, INCLUDINGCOPYRIGHT THERETO.
c 2018
PROJECT NO:
SCALE:
3" = 1'-0"
533 W HALLAM ST ASPEN, CO 81611
A806A806A806A806
ASSEMBLIES ASSEMBLIES ASSEMBLIES ASSEMBLIES ---- IIIINNNNTTTTEEEERRRRIIIIOOOORRRR
WALLWALLWALLWALL
21708.00
EXISTING
INTERIOR
WALL
SCALE 3" = 1'-0"WI-2 INTERIOR WALL @ GWB/GWB
SCALE 3" = 1'-0"WI-1 INTERIOR WALL @ EXISTING WALL
I believe you may
have a layering issue
here, the detail is not
actually shown.
Please revise.
PER STRUCT.
5/8" SHEATHING,
REF. STRUCTURAL
SPRAY FOAM INSULATION
R-49 MIN.
TJI RAFTER, REF. STRUCTURAL
5/8" GYPSUM WALL BOARD, REF. INTERIOR FINISH SCHED.
R-49 MIN.
SELF ADHERED WATERPROOF MEMBRANE
MINERAL SURFACED CAP
SHEET, CLASS A
EXPOSURE
5"
CEDAR BREATHER, CLASS A
CLASS A ROOF ASSEMBLY
20% PERMEABLE RATIO CAN
BE ACHIEVED AT 4"
3" THICK PAVERS
COMPACTED SAND
RADIANT TUBING
FILTER FABRIC -HYDRODRAIN AL
3" RIGID INSULATION
R-15 MIN.
DRAINAGE MAT -
HYDRODRAIN 990
CONCRETE, REF. STRUCTURAL
SPRAY FOAM INSULATION R-35 MIN.
STEEL, REF. STRUCTURAL
5/8" GYPSUM CEILING,
REF. INTERIOR FINISH SCHED.
WATERPROOF MEMBRANE - MM6125 EV
3"
2"1/4
"
3"
1/2
"
4"
PE
R
S
T
R
U
C
T
.
R-49 MIN.
COMPACTED SAND
FILTER FABRIC -HYDRODRAIN AL
3" RIGID INSULATIONR-15 MIN.
DRAINAGE MAT -
HYDRODRAIN 990
CONCRETE, REF. STRUCTURAL
SPRAY FOAM INSULATIONR-35 MIN.
STEEL, REF. STRUCTURAL
5/8" GYPSUM CEILING,REF. INTERIOR FINISH SCHED.
WATERPROOF MEMBRANE - MM6125 EV
VA
R
I
E
S
2"1/4
"
3"
1/2
"
PE
R
S
T
R
U
C
T
.
SOD
R-49 MIN.
SHEET TITLE
BILL POSS AND ASSOCIATES,ARCHITECTURE AND PLANNING, P.C.
THE INFORMATION AND DESIGN INTENT CONTAINED ON THIS DOCUME PROPERTY OF BILL POSS AND ASSOCIATES, ARCHITECTURE AND PLAN OF THIS INFORMATION MAY BE USED WITHOUT THE PRIOR WRITTEN PE POSS AND ASSOCIATES, ARCHITECTURE AND PLANNING, P.C. BILL POS ARCHITECTURE AND PLANNING, P.C. SHALL RETAIN ALL COMMON LAW OTHER RESERVED RIGHTS, INCLUDINGCOPYRIGHT THERETO.
c 2018
PROJECT NO:
SCALE: 1 1/2" = 1'-0"
DDDDUUUUNNNNCCCCAAAANNNN RRRREEEESSSSIIIIDDDDEEEENNNNCCCCEEEE
533 W HALLAM ST ASPEN, CO 8161
A808A808A808A808
ASSEMBLIES ASSEMBLIES ASSEMBLIES ASSEMBLIES ---- RRRROOOOOOOOFFFF
21708.00
SCALE 1 1/2" = 1'-0"R-2 CEDAR SHINGLE ROOF 12:12
SCALE 1 1/2" = 1'-0"R-1 PERMEABLE PAVERS @ PATIO GREEN ROOF
SCALE 1 1/2" = 1'-0"R-4 SOD @ GREEN ROOF
Provide documentation of class A
assembly for these assemblies similar to
what you provided for both the flatmembrane roof and sloped shingle roof.
P ER STR
5/8" SHEATHING,
REF. STRUCTURAL
SPRAY FOAM INSULATION
R-49 MIN.
TJI RAFTER, REF. STRUCTURAL
5/8" GYPSUM WALL BOARD,
REF. INTERIOR FINISH SCHED.
R-49 MIN.
SELF ADHERED WATERPROOF
MEMBRANE
MINERAL SURFACED CAP
SHEET, CLASS A
CLASS A ROOF ASSEMBLY
20% PERMEABLE RATIO CAN
BE ACHIEVED AT 4"
3" THICK PAVERS
COMPACTED SAND
RADIANT TUBING
FILTER FABRIC -
HYDRODRAIN AL
3" RIGID INSULATION
R-15 MIN.
DRAINAGE MAT -HYDRODRAIN 990
CONCRETE, REF. STRUCTURAL
SPRAY FOAM INSULATION
R-35 MIN.
STEEL, REF. STRUCTURAL
5/8" GYPSUM CEILING,REF. INTERIOR FINISH SCHED.
WATERPROOF
MEMBRANE - MM6125 EV
3"
2"1/
4
"
3"
1/2
"
4"
PE
R
S
T
R
U
C
T
.
R-49 MIN.
COMPACTED SAND
FILTER FABRIC -
HYDRODRAIN AL
3" RIGID INSULATION
R-15 MIN.
DRAINAGE MAT -
HYDRODRAIN 990
CONCRETE, REF. STRUCTURAL
SPRAY FOAM INSULATION
R-35 MIN.
STEEL, REF. STRUCTURAL
5/8" GYPSUM CEILING,
REF. INTERIOR FINISH SCHED.
WATERPROOF
MEMBRANE - MM6125 EV
VA
R
I
E
S
2"1/4
"
3"
1/2
"
PE
R
S
T
R
U
C
T
.
SOD
R-49 MIN.
SHEET TITLE
BILL POSS AND ASSOCIATES,ARCHITECTURE AND PLANNING, P.C.
THE INFORMATION AND DESIGN INTENT CONTAINED ON THIS DOCUMENT IS THE
PROPERTY OF BILL POSS AND ASSOCIATES, ARCHITECTURE AND PLANNING, P.C.NO PAR OF THIS INFORMATION MAY BE USED WITHOUT THE PRIOR WRITTEN PERMISSION OF BIL POSS AND ASSOCIATES, ARCHITECTURE AND PLANNING, P.C. BILL POSS AND ASSOCIATE
ARCHITECTURE AND PLANNING, P.C. SHALL RETAIN ALL COMMON LAW STATUTORY AND OTHER RESERVED RIGHTS, INCLUDINGCOPYRIGHT THERETO.
c 2018
PROJECT NO:
SCALE:
1 1/2" = 1'-0"
DDDDUUUUNNNNCCCCAAAANNNN RRRREEEESSSSIIIIDDDDEEEENNNNCCCCEEEE
533 W HALLAM ST ASPEN, CO 81611
A808A808A808A808
ASSEMBLIES ASSEMBLIES ASSEMBLIES ASSEMBLIES ---- RRRROOOOOOOOFFFF
21708.00
SCALE 1 1/2" = 1'-0"R-2 CEDAR SHINGLE ROOF 12:12
SCALE 1 1/2" = 1'-0"R-1 PERMEABLE PAVERS @ PATIO GREEN ROOF
SCALE 1 1/2" = 1'-0"R-4 SOD @ GREEN ROOF
Provide a detail showing your proposed
hole pattern in the rigid insulation that
will achieve a R10 weighted average
while still meeting engineering's 30%
open requirement to be permeable (this
detail only shows 20%, but I believe
engineering requires 30%). Attached is
our pervious snowmelt calculator that
can help to find the pattern that best
suits your situation.
Subject: PlanCheck
Page Label: A812
Author: justinh
File Name: Architectural Plans. 533 W HALLAM.pdf
Color:
Revise all drawings
(architecturals, structurals, civils)
so grade is 6” or more below the
top of each foundation wall per
2015 IRC R404.1.6 (clearly
dimensioned in the architectural
details). Alternatively, the City
will accept a lesser distance if all
of the following are provided.
Note this requirement at all
applicable wall sections and
details:
1.All wood materials within 6” of
grade to be protected from
decay per R317.1 5.
2.Waterproof membrane
extending up wall a minimum of
6” above grade.
3.Capillary break separating
concrete from wood materials.
If you go that route you will also
need to have the structural plan
revised to show treated lumber
as a specified material and have
them list the proper fasteners for
treated wood as the chemicals
used to treat lumber can
degrade typical fasteners.
Subject: PlanCheck
Page Label: A815
Author: justinh
File Name: Architectural Plans. 533 W HALLAM.pdf
Color:
Indicate how you will accomplish
the air sealing requirements of
2015 IECC table R402.4.1.1
using notes and details. Indicate
the continuity of the air barrier
and where it is located
throughout the building. Note
locations that require caulking,
sealing, taping, etc. Note which
components are included in the
air barrier such as spray foam,
gypsum, housewrap, and/or
exterior insulation. You may
have all of the above but you
need to pick one continuous
barrier and stick to it. It needs to
follow the thermal barrier. The
better detail you provide, the
easier it will be for the contractor
and inspector to be successful.
This is a new 2015 code
requirement in lieu of a blower
door test. I've attached our
standard air sealing detail sheets
to this comment letter as an
example of the type of detailing
we're looking for.
W-1
T.O. CONC. @ CRAWL SPACE79' - 6 3/8"
F-1
WATERPROOFING
HYDRODUCT COIL 600
WRAP HYDRODUCT 220 PERMANUFACTURER'S RECOMMENDATIONS.
PER STRUCT.
PER STRUCT.
T.O. CONC. @ BASEMENT83' - 2"
F-1
W-2
SIM
MECHANICAL VOID SPACE
PER STRUCT.
EXPANSION JOINT
HYDRODUCT 220
HYDRODUCT COIL 600
PER STRUCT.
REFERENCE SOIL RETENSION PLANS FOR SYSTEM TO USE
A
T.O. PLY @ MAIN99' - 9"
B
T.O.F.F. @ PATIO & GARAGE99' - 11"
R-1 R-4
WOOD CLAD STEEL COLUMN.PAINT TO MATCH SIDING.
KEEP WOOD 1" UP FROM FIN. GRADE
1"
COLUMN BASE PER STRUCTURAL
WATERPROOFING PER WJE
CONCRETE DECKING PER STRUCTURAL
MICROPILE WALL DEMO CAP AS NECESSARY. VERIFY LOCATIONS WITH ENGINEER.
STEEL PER STRUCTURAL
PER STRUCTURAL
T.O. F.F. @ MAIN100' - 0"
A
T.O. PLY @ MAIN99' - 9"
B
W-2
EXISTING HISTORIC STUDS AND SIDING VIF LOCATION AND CONNECTION TO NEW STRUCTURAL FOOTING WITH ARCHITECT AND STRUCTURAL ENGINEER DURING DEMO PHASE.
W-11 1/2" DENSGLASS BACKER OVER WATERPROOFING.
CONCRETE SCRACTH COAT TO MATCH EXISTING CONDITION. VIF COLOR WITH ARCHITECT.
PROPOSED GRADE TO MATCH RELATIONSHIP OF EXISTING GRADE TO HISTORIC HOUSE. REF CIVIL AND GRADING PLAN
RIGID INSULATION
3"
DRAINAGE MAT
CONTINUE SPRAY INSULATION UP TO THE BOTTOM OF SHEATHING (TYP)
T.O. F.F. @ MAIN100' - 0"
LK
T.O. PLY @ MAIN99' - 9"
METAL FLASHING CONTINUOUSUNDER WINDOW
1/2" DENSGLASS OVER ZIP PANELFOR PROTECTION.
WATERPROOFING PER WJE
CONCRETE TOPPING SLOPED 1/4" PER FOOT
CONTINUE SPRAY FOAM INSULUP TO UNDERSIDE OF SHEATHING(TYP)
CONCRETE PER STRUCTURAL
W-3
PER STRUCT.
PER STRUCT.
10
T.O. PLY @ MAIN99' - 9"
T.O.F.F. @ PATIO & GARAGE99' - 11"
F-2
EXPANSION JOINT
CONC FILL AS NECESSARY VIF WITH STRUCTURAL
ALLEY GRAVEL
CONCRETE DRIVE UP FROM PROPERTY LINE TO GARAGE ENTRY.
GARAGE DOOR
MICROPILE WALL
PER STRUCT.
STEEL PER STRUCTURAL
STEEL DECKING AND GARAGE CONC PERSTRUCTURAL
LK
T.O. PLY @ MAIN99' - 9"
T.O.F.F. @ PATIO & GARAGE99' - 11"
F-2
W-1
W-7 METAL FLASHING CONTINUOUSUNDER DRAINAGE MAT AND OVER FOUNDATION INSULATION
METAL FLASHING WITH DRIP EDGE COLOR TO MATCHSIDING
CONTINUOUS METALFOUNDATION FLASHING. POWEDER COAT TO MATCHMETAL PANNEL SYSTEM.
SELF ADHERED FLASHINGTO OVERLAP ALL METAL FLASHING
PER STRUCT.
PER STRUCT.
STEEL PER STRUCTURAL
T.O. F.F. @ MAIN100' - 0"
C
T.O. PLY @ MAIN99' - 9"
T.O.F.F. @ PATIO & GARAGE99' - 11"
R-1
SELF ADHERED FLASHINGTO OVERLAP ALL METAL FLASHING
METAL FLASHING CONTINUOUSUNDER DRAINAGE MAT AND OVER FOUNDATION INSULATION
METAL FLASHING WITH DRIP EDGE COLOR TO MATCH SIDING.
W-7
WATERPROOFING PER WJE
3" RIGID INSULATION
1/2" DENSGLASS
CONC PER STRUCTURAL
STEEL PER STRUCTURAL
T.O. F.F. @ MAIN100' - 0"
T.O. PLY @ MAIN99' - 9"
W-7SIM
W-1
SELF ADHERED FLASHINGTO OVERLAP ALL METAL FLASHING
METAL FLASHING CONTINUOUSUNDER DRAINAGE MAT AND OVER FOUNDATION INSULATION
METAL FLASHING WITH DRIP EDGE COLOR TO MATCHSIDING
FLOOR FRAMING. REF STRUCT.
CONTINUOUS METALFOUNDATION FLASHING. POWEDER COAT TO MATCHMETAL PANNEL SYSTEM.
A
T.O. F.F. @ UPPER110' - 4 1/2"
T.O. PLY @ UPPER110' - 1 1/2"
F-3
W-7
METAL FLASHING W/ DRIP EDGE,COLOR TO MATCH SIDING
WOOD FASCIA TO MATCH SIDING
CONTINUOUS SPRAY FOAM INSULATION
STEEL BEAM, REF. STRUCT.
SAW-CUT DRIP EDGE
WOOD WRAPPED COLUMN
SELF-ADHERED FLASHING TO OVERLAP METAL FLASHING
WEATHER RESISTANT BARRIER
SCALE 1 1/2" = 1'-0"A812
4 DTL_Foundation @ Office West
SCALE 1 1/2" = 1'-0"A8126 FOUNDATION WALL @ STAIR HALL
SCALE 1 1/2" = 1'-0"A812
7 DTL_Foundation Wall @ Garage DoorSCALE 1 1/2" = 1'-0"A812
8 FOUNDATION WALL @ GARAGE SLAB - EAST
SCALE 1 1/2" = 1'-0"A8129 PATIO @ EXTERIOR WALLSCALE 1 1/2" = 1'-0"A81210 TYPICAL FOUNDATION WALL @ WOOD JOIST SCALE 1 1/2" = 1'-0"A8125 COLUMN @ MASTER BATH
Revise all drawings (architecturals, structurals, civils) sograde is 6” or more below the top of each foundation wall
per 2015 IRC R404.1.6 (clearly dimensioned in the
architectural details). Alternatively, the City will accept a
lesser distance if all of the following are provided. Note this
requirement at all applicable wall sections and details:
1.All wood materials within 6” of grade to be protected from
decay per R317.1 5.
2.Waterproof membrane extending up wall a minimum of 6”
above grade.
3.Capillary break separating concrete from wood materials.
If you go that route you will also need to have the structural
plan revised to show treated lumber as a specified material
and have them list the proper fasteners for treated wood as
the chemicals used to treat lumber can degrade typicalfasteners.
Indicate how you will accomplish the air sealing
requirements of 2015 IECC table R402.4.1.1 using
notes and details. Indicate the continuity of the air
barrier and where it is located throughout the building.
Note locations that require caulking, sealing, taping, etc.
Note which components are included in the air barrier
such as spray foam, gypsum, housewrap, and/or
exterior insulation. You may have all of the above but
you need to pick one continuous barrier and stick to it. It
needs to follow the thermal barrier. The better detail you
provide, the easier it will be for the contractor and
inspector to be successful. This is a new 2015 code
requirement in lieu of a blower door test. I've attached
our standard air sealing detail sheets to this comment
letter as an example of the type of detailing we're
looking for.
Subject: PlanCheck
Page Label: A901
Author: justinh
File Name: Architectural Plans. 533 W HALLAM.pdf
Color:
One of these windows should be
marked egress as you have
done for the bedrooms in the
basement. The master bedroom
requires emergency escape
egress as well.
Subject: PlanCheck
Page Label: A901
Author: justinh
File Name: Architectural Plans. 533 W HALLAM.pdf
Color:
All windows and exterior doors
are required to have a U value of
.28 or better. Note this
requirement on the window and
door schedules. If you are
unable to accomplish this with
the historic replicas you will need
to submit a formal request,
addressed to the Chief Building
Official, to be exempted from this
requirement per IECC R501.6
due to the fact that compliance
would degrade the historic form
of the building.
Subject: PlanCheck
Page Label: G001
Author: justinh
File Name: Architectural Plans. 533 W HALLAM.pdf
Color:
Provide a copy of the state demo
license for the demolition of the
non-historic addition. You may
submit other responses without
this piece, but the building
department will not be able to
fully sign off on this permit until
that has been submitted.
Subject: PlanCheck
Page Label: G010
Author: justinh
File Name: Architectural Plans. 533 W HALLAM.pdf
Color:
Fire area/gross building area is
measured from the interior face
of the exterior walls rather than
the exterior face. You also do
not need to include areas under
the standard 1' eave overhang,
just areas under larger roof
projections such as your covered
exterior doors and front porch.
Please revise, and note on the
plan that fire sprinklers will be
required.
Subject: PlanCheck
Page Label: G011
Author: justinh
File Name: Architectural Plans. 533 W HALLAM.pdf
Color:
Show the property line on the
REMP plan, snowmelt in the
ROW needs to be on a separate
zone from snowmelt on your
property. This should be noted
on the plan and shown as
separate zones in the
mechanical plans.
HARDWARE FINISHES WITH OWNER PRIOR TO ORDERING.
PROVIDED IN ALL HAZARDOUS AREAS PER SECTION R308 2015 IRC.
TH 2015 IECC CHAPTER 4, CLIMATE ZONE 7 & 8, FENESTRATION U-
UFACTORER TO PROVIDE DOCUMENTATION FOR THE WINDOW
A WEIGHTED AVERAGE OF U-VALUE 0.28 AND STICKER MARKING OF
HE CITY OF ASPEN BUILDING DEPARTMENT.
SS.
ERALL FRAME DIMENSIONS.
ENSIONS BEFORE ORDERING.
RABLE WINDOWS. COORDINATE WITH ARCHITECT.
ANS FOR REFERENCED SHADE POCKET DETAILS & DESCRIPTION.
B 01 8' - 0" 2' - 0" 6' - 0" FIXED-FIXED
B 02 3' - 0" 2' - 0" 6' - 0" FIXED
B 03 2' - 0" 2' - 0" 6' - 0" AWNING
B 04 7' - 5 1/2" 9' - 0" 0" FIXED-FIXED TEMPERED GLASS
B 05 2' - 6" 4' - 8" 3' - 6" CASEMENT
B 06 2' - 6" 4' - 8" 3' - 6" CASEMENT
B 08 1' - 11 1/4" 5' - 9 1/2" 1' - 4 1/4" DOUBLE HUNG EXISTING HISTORIC DOUBLE HUNG
B 09 2' - 3 3/8" 5' - 9 1/2" 1' - 4 1/4" DOUBLE HUNG EXISTING HISTORIC DOUBLE HUNG
B 10 2' - 3 3/8" 5' - 9 1/2" 1' - 4 1/4" DOUBLE HUNG EXISTING HISTORIC DOUBLE HUNG
B 11 1' - 11 1/4" 5' - 9 1/2" 1' - 4 1/4" DOUBLE HUNG EXISTING HISTORIC DOUBLE HUNG
B 12 2' - 2 3/4" 5' - 10" 1' - 4 1/2" DOUBLE HUNG HISTORIC REPLICA TO MATCH B 19 & B 20
B 13 2' - 9" 3' - 11" 3' - 0" FIXED HISTORIC STAINED GLASS, RELOCATED
B 14 1' - 11 1/4" 5' - 9 1/2" 1' - 5" DOUBLE HUNG EXISTING HISTORIC DOUBLE HUNG
B 15 2' - 3 1/4" 5' - 9 1/2" 1' - 5" DOUBLE HUNG EXISTING HISTORIC DOUBLE HUNG
B 16 2' - 3 1/4" 5' - 9 1/2" 1' - 5" DOUBLE HUNG EXISTING HISTORIC DOUBLE HUNG
B 17 1' - 11 1/4" 5' - 9 1/2" 1' - 5" DOUBLE HUNG EXISTING HISTORIC DOUBLE HUNG
B 18 1' - 10" 1' - 4" 1' - 2 1/2" FIXED EXISTING HISTORIC STAINED GLASS
B 18.2 1' - 10" 1' - 4" 1' - 2 1/2" FIXED HISTORIC REPLICA TO MATCH B 18
B 19 2' - 2 3/4" 5' - 10" 1' - 4 1/2" DOUBLE HUNG EXISTING HISTORIC DOUBLE HUNG
B 20 2' - 2 3/4" 5' - 10" 1' - 4 1/2" DOUBLE HUNG EXISTING HISTORIC DOUBLE HUNG
B 21 2' - 2 3/4" 5' - 10" 1' - 4 1/2" DOUBLE HUNG EXISTING HISTORIC DOUBLE HUNG
B 22 2' - 2 3/4" 5' - 10" 1' - 4 1/2" DOUBLE HUNG HISTORIC REPLICA TO MATCH B 19 & B 20
B 23 2' - 2 3/4" 5' - 10" 1' - 4 1/2" DOUBLE HUNG HISTORIC REPLICA TO MATCH B 19 & B 20
B 24 5' - 0" 5' - 6" 3' - 0" DOUBLE HUNG-DOUBLE HUNG
B 25 2' - 0" 3' - 0" 11' - 4" AWNING
C 01 4' - 8" 5' - 6" 3' - 0" DOUBLE HUNG-DOUBLE HUNG TEMPERED GLASS
C 02 2' - 0" 3' - 0" 9' - 11 1/2" AWNING
C 03 2' - 6" 5' - 6" 3' - 0" DOUBLE HUNG
C 04 2' - 6" 5' - 6" 3' - 0" DOUBLE HUNG
C 05 8' - 10" 5' - 6" 3' - 0" CASEMENT-FIXED-CASEMENT
C 06 4' - 8" 5' - 6" 3' - 0" DOUBLE HUNG-DOUBLE HUNG
C 07 2' - 0" 3' - 0" 9' - 11 1/2" AWNING
C 08 7' - 5 1/2" 9' - 0" 0" FIXED-FIXED TEMPERED GLASS
C 09 2' - 6" 5' - 0" 3' - 6" DOUBLE HUNG
C 10 2' - 6" 5' - 6" 3' - 0" DOUBLE HUNG
EXTERIOR DOOR SCHEDULE
DOOR
MARK DOOR TYPE
FRAME
NOTESWIDTH HEIGHT
101 A SINGLE SWING 3' - 4" 8' - 2" TEMPERED GLASS
103 A SINGLE SWING 3' - 4" 8' - 2" TEMPERED GLASS
106 A DOUBLE SWING 7' - 5" 9' - 0" TEMPERED GLASS
107 A SINGLE SWING 3' - 4" 8' - 2" TEMPERED GLASS
109 A 4-PANEL FOLDING 11' - 10 1/8" 9' - 0" TEMPERED GLASS
110 A 4-PANEL FOLDING 10' - 8 7/8" 9' - 0" TEMPERED GLASS
111 A SINGLE SWING 3' - 4" 7' - 2" NEW ENTRY DOOR.
LOWER PROFILE
AND PROPORTIONS
TO MATCH 113 B.
SINGLE WINDOW TO
FOLLOW HISTORIC
STYLING OF 113 B.
113 A HISTORIC SINGLE SWING 2' - 8" 6' - 8" HISTORIC REPLICA
TO MIRROR 113 B
113 B HISTORIC SINGLE SWING 2' - 8" 6' - 8" EXISTING HISTORIC
DOOR
One of these windows
should be marked
egress as you have
done for the bedrooms
in the basement. The
master bedroom
requires emergency
escape egress as well.
OVERALL FRAME DIMENSIONS.
DIMENSIONS BEFORE ORDERING.
OPERABLE WINDOWS. COORDINATE WITH ARCHITECT.
G PLANS FOR REFERENCED SHADE POCKET DETAILS & DESCRIPTION.
B 12
B 13
B 14
B 15
B 16
B 17
B 18
B 18.2
B 19
B 20
B 21
B 22
B 23
B 24
B 25
C 01
C 02
C 03
C 04
C 05
C 06
C 07
C 08
C 09
C 10
All windows and exterior doors are required to have a U
value of .28 or better. Note this requirement on the
window and door schedules. If you are unable to
accomplish this with the historic replicas you will need to
submit a formal request, addressed to the Chief Building
Official, to be exempted from this requirement per IECC
R501.6 due to the fact that compliance would degrade the
historic form of the building.
G00
G00
G00
G00
G00
G01
G01
G01
G01
D10
D10
D10
D10
D10
D10
SU SU SU SU
1 O
EXC EXC EXC EXC
Provide a copy of the state demo license for the demolition of the
non-historic addition. You may submit other responses without this piece,
but the building department will not be able to fully sign off on this permit
until that has been submitted.
FIRE AREA CALCULATIONS
LOWER LEVEL AREA TOTAL
MAIN LEVEL AREA TOTAL
MAIN LEVEL EXTERIOR COVERED AREA
UPPER LEVEL AREA TOTAL
3,571sf
2,682sf
130sf
1,027sf
381sfMAIN LEVEL OVERHANGS TOTAL
UPPER LEVEL OVERHANGS TOTAL 105sf
TOTAL AREA 7,896sf
Fire area/gross building area is measured from the interior face of the exterior walls rather
than the exterior face. You also do not need to include areas under the standard 1' eave
overhang, just areas under larger roof projections such as your covered exterior doors and
front porch. Please revise, and note on the plan that fire sprinklers will be required.
14
14
13
83.60 SQ FT
DDDDUUUUNNNNCCCCAAAANNNN RRRREEEESSSSIIIIDDDD
533 W HALLAM ST AS
Show the property line
on the REMP plan,
snowmelt in the ROW
needs to be on a
separate zone from
snowmelt on your
property. This should
be noted on the plan
and shown as
separate zones in the
mechanical plans.
Subject: PlanCheck
Page Label: 2
Author: justinh
File Name: Energy Code Compliance - Mech'l. 533 W
Hallam.pdf
Color:
Our summer design temperature
is 82°F, please revise.
Energy Code Compliance - Mech'l. 533 W Hallam.pdf (1)
Subject: PlanCheck
Page Label: 1
Author: justinh
File Name: Line Grade Verification Form.533 W Hallam.pdf
Color:
An elevation benchmark is
required, please fill this portion
of the form.
Line Grade Verification Form.533 W Hallam.pdf (1)
Subject: PlanCheck
Page Label: [1] 18032-M1(D-48)-M-001
Author: justinh
File Name: Mechanical Plans. 533 W HALLAM.pdf
Color:
There are 5 bedrooms in the
new SFR and I measure over
6000 SF of occupiable floor area
on the floor plans. ERV-1 is
shown in your equipment
schedule as being 110 CFM
rather than 126 CFM shown
here and it is noted as servicing
only crawlspace ventilation.
In the sequence of operations
you note that the ERV shall run
30 minutes per hour, that will
also increase your required CFM
(what you show here is using the
assumption the system will run
continuously). Please revise this
calculation and equipment
schedule as needed to
accurately depict the home size,
number of bedrooms and ERV
unit proposed that will meet the
ventilation requirements.
Mechanical Plans. 533 W HALLAM.pdf (3)
Subject: PlanCheck
Page Label: 6
Author: justinh
File Name: Mechanical Plans. 533 W HALLAM.pdf
Color:
Civil plans reference a sump
pump per MEP in the
crawlspace, revise to show this
in your plans.
OUTDOOR TEMPERATURE -15 °F OUTDOOR TEMPERATURE 88 °F
INDOOR TEMPERATURE 72 °F INDOOR TEMPERATURE 75 °F
TOTAL HEAT LOSS 89,782 BTU/HR SENSIBLE HEAT GAIN 85,380 BTU/HR
LATENT HEAT GAIN 4,938 BTU/HR
TOTAL HEAT GAIN 90,318 BTU/HR
MANUAL J DESIGN CONDITIONS
WINTER DESIGN CONDITIONS SUMMER DESIGN CONDITIONS
Our summer design
temperature is 82°F,
please revise.
ASPEN LINE GRADE VERIFICATION FORMASPEN LINE GRADE VERIFICATION FORM
Verification of Building Location by Building Contractor
For Building and Permit Information, please refer to our website at:
http://www.aspenpitkin.com/depts/41/
Exemption
A City verification of building location is not needed when the project creates less the 200 square feet of new floor area.
PART A: Complete and Submit as part of the Building Permit Application
o Building / Job Address or Location: _____________________________________________
o Your Name (Person Completing Part A): ____________________________________________
o Your Company: ________________________________________________________________
o Plans must show horizontal dimensions that ‘tie’ the building to the property boundary.
Are building ties shown? (circle one) ‘Yes’ ‘No’
o An elevation benchmark needs to be established on the site by a licensed surveyor and shown on the plans. What is the
elevation of this benchmark? _________________________________
o If the garage is located within 10 feet of the roadway or sidewalk, provide spot elevation on the on the roadway or sidewalk.
Is a spot elevation shown? ‘Yes’ ‘No’ ‘N/A’
o Provide the equation comparing site (surveyed) elevation to structure/ architectural plan elevation:
(i.e., 100’ first floor elev = 7962.50’) _______________________________
----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
PART B: Complete prior to first Foundation Inspection, by a licensed surveyor or an individual prequalified by the City
o Do field measured building ties to property match building ties shown on the plan? (circle one): ‘Yes’ ‘No’
o Surveyor needs to confirm that one spot on the top of the foundation wall is at the same elevation shown on the approved
building plans.
o What is the field measured elevation of top of foundation wall relative to the site bench mark? ____________
o According to the building plans, what was the design elevation for the same place on the foundation wall?
______________________________
o Was the elevation of the building adjusted in field? (circle one): ‘Yes’ ‘No’
An elevation
benchmark is
required, please fill
this portion of the
form.
A
B
(A) SECTION CUT LINE
(B) SHEET SHOWN ON
THERMOMETER
BE PER THE
REMENTS (UPON
F THE REQUIRED
ACCESS TO THE
ERVICE
A MAXIMUM OF 20
NUFACTURER'S
MMENDATIONS
RE.
RTERS, THERMAL
YS, CONTROL
ED BY THE
SHALL BE LOW
E PROVIDED BY THE
ENT
SYSTEM PER THE
ER, REGARDLESS OF
COMPLETE AND
E LOSS PROTECTION.
CONNECTS
E ELECTRICAL
Drawn By:
DATE
11-23-1
AEC P
DU
N
C
A
N
S
K
I
H
B
There are 5 bedrooms in the new SFR and I
measure over 6000 SF of occupiable floor
area on the floor plans. ERV-1 is shown in
your equipment schedule as being 110 CFM
rather than 126 CFM shown here and it is
noted as servicing only crawlspace
ventilation.
In the sequence of operations you note that
the ERV shall run 30 minutes per hour, that
will also increase your required CFM (what
you show here is using the assumption the
system will run continuously). Please revise
this calculation and equipment schedule as
needed to accurately depict the home size,
number of bedrooms and ERV unit proposed
that will meet the ventilation requirements.
1
3
FC
MECHANICAL
CRAWLSPACE
M01
RM
1 1/4"ø HWR
1 1/4"ø HWS 1/2"ø HWR
1/2"ø HWS 1"ø HWR
1"ø HWS
3/4"ø HWR
3/4"ø HWS
3/4"ø HWR
3/4"ø HWS
3/4"ø HWS3/4"ø HWR
3/4"ø HWS UP3/4"ø HWR UP
10
9
Civil plans reference a
sump pump per MEP
in the crawlspace,
revise to show this in
your plans.
Subject: PlanCheck
Page Label: 8
Author: justinh
File Name: Mechanical Plans. 533 W HALLAM.pdf
Color:
Snowmelt square footages
shown here and on the
snowmelt schedule do not match
what is shown on the
architectural REMP sheet.
Revise one or the other so that
the snowmelt quantities and
locations are consistent. You
may exempt 9 SF of snowmelt
for each window well (minimum
size required for an emergency
escape egress well) but you
must include any additional
square footage for each window
well in your REMP calculation.
Subject: PlanCheck
Page Label: 1
Author: justinh
File Name: RREMP Documents.533 W Hallam.pdf
Color:
Please fill out the contact info
portion of this form. If the site
plan/REMP plan are revised per
discussions with HPC and
building regarding the light well
guards, please be sure to update
the square footages on this
sheet accordingly.
RREMP Documents.533 W Hallam.pdf (1)
Subject: PlanCheck
Page Label: 3
Author: justinh
File Name: Special Inspection Agreement.533 W Hallam.pdf
Color:
You need an approved
fabricator's signature for the
shop welds shown in the
structural plans. Please
resubmit the agreement. You
may resubmit responses without
this if you have yet to decide on
your welder/steel fabricator but
building will not be able to sign
off on your permit until this
agreement has been fully
executed.
Special Inspection Agreement.533 W Hallam.pdf (1)
Subject: PlanCheck
Page Label: 1
Author: justinh
File Name: Structural Plans. 533 W HALLAM.pdf
Color:
Our wind speed design criteria is
89 MPH, please revise.
Structural Plans. 533 W HALLAM.pdf (3)
Subject: PlanCheck
Page Label: 1
Author: justinh
File Name: Structural Plans. 533 W HALLAM.pdf
Color:
We are seismic design category
C, please revise.
S
T
T
T
T
T
T
2
2
5
5
6
6
7
7
8
8
9
9
10
10
LL
K
K
JJ
FF
GG
DD
CC
AA
3
3
4
4
EE
HH
1
1
BB
5BRZ
30 SQFT
7ARZ
435 SQFT
7BRZ
125 SQFT
6BRZ
35 SQFT
6ARZ
1050 SQFT5ARZ
495 SQFT
8RM
9RM
7RM
GARAGE
103
MUD ROOM
102 ENTRY101
LIVING
106
STAIR
73
STAIRS
49
PDR105
KITCHEN
107
CASUAL DINING
109
ENTRY HALL
110
ENTRY
111
DINING
113
OFFICE
114
BIKES104
1/2"ø HWS1/2"ø HWR
3/4"ø HWR UP3/4"ø HWS UP
3/4"ø HWS1"ø HWR
3/4"ø HWS3/4"ø HWR1"ø HWS DN1"ø HWR DN
1SZ
635 SQFT2SZ
235 SQFT
3SZ
185 SQFT5SZ
10 SQFT
4SZ
30 SQFT
3SM
2
3
1
4
5
TO FC-4 &RZ-6A
TO FC-5,MD-5B &RZ-7A
TO FC-5,MD-5A &RZ-7B
TO RZ-5B
TO RZ-5A
TO RZ-6B
ww
w
.
a
e
c
-
v
a
i
l
.
c
o
m
of
Drawn By:Checked By:
AEC PROJECT #:
COPYRIGHT 2018 ARCHITECTURAL ENGINEERING CONSULTANTS, INC.c
c
ae
PO
B
o
x
8
4
8
9
,
4
0
8
0
1
U
S
H
w
y
6
&
2
4
,
S
t
e
2
1
4
,
A
v
o
n
,
C
o
lo
r
a
d
o
,
8
1
6
2
0
Mec
h
a
n
i
c
a
l
,
E
l
e
c
t
r
i
c
a
l
&
L
i
g
h
t
i
n
g
D
e
s
i
g
n
S
e
r
v
i
c
e
s
Arc
h
i
t
e
c
t
u
r
a
l
E
n
g
i
n
e
e
r
i
n
g
C
o
n
s
u
l
t
a
n
t
s
Tel
e
p
h
o
n
e
:
9
7
0
-
7
4
8
-
8
5
2
0
F
a
x
:
9
7
0
-
7
4
8
-
8
5
2
1
An
O
f
f
i
c
e
w
i
t
h
L
E
E
D
™
A
c
c
r
e
d
i
t
e
d
P
r
o
f
e
s
s
i
o
n
a
l
s
DATE: ISSUE:
SCALE 1/4" = 1'-0"
18032.00
DU
N
C
A
N
S
K
I
H
A
U
S
53
3
W
E
S
T
H
A
L
L
A
M
AS
P
E
N
,
C
O
L
O
R
A
D
O
,
8
1
6
1
1
M-122
FIRST FLOOR
MECHANICALPIPING
10 14
BLU TOC
11/23/18PERMIT/PRICING
1/4" = 1'-0"1 MECHANICAL PIPING - 1ST FLOOR
SHEET NOTES:
1 CONNECT 1/2" SMS/R TO SM-3.2 CONNECT 1/2" HWS/R TO RM-9.3 CONNECT 3/4" HWS/R TO RM-8.4 CONNECT 3/4" HWS/R TO RM-7.5 INSTALL SNOW & ICE SENSOR IN THE SNOWMELT ZONE AS SHOWN.COORDINATE EXACT LOCATION WITH G.C. ENSURE THE SENSOR ISEQUIDISTANT BETWEEN TUBING & NOT UNDER OVERHANGS OR INWIND EDDIES.6 SEE ARCH SITE PLAN FOR CONTINUATION
1. OFFSET PIPING AS REQUIRED TO AVOID ALL DUCTWORK, LIGHTS, AND STRUCTURE. COORDINATE ALL STRUCTURAL PENETRATIONS WITH THE STRUCTURAL ENGINEER.
2. ALL PIPING PASSING THROUGH FIRE-RATED ASSEMBLIES SHALL INCLUDE A FIRE-RATED PIPE SEALANT RATED TO MATCH THAT OF THE ASSEMBLY.
3. VERIFY FINAL LOCATIONS OF ALL MANIFOLDS WITH THE G.C. CONTACT ENGINEER IF MANIFOLDS MOVE MORE THAN 10' FROM LOCATIONS SHOWN ON PLANS.
4. LOCATION OF ALL THERMOSTATS AND FLOOR SENSORS ARE APPROXIMATE, COORDINATE EXACT LOCATIONS WITH THE ARCHITECT. LOCATE FLOOR SENSORS EQUIDISTANT BETWEEN RADIANT LOOPS, AND DO NOT LOCATE WHERE THEY MAY LIKELY BE COVERED BY FUTURE RUGS OR FURNITURE.
5. ALL PIPING SIZED FOR TYPE L COPPER. CONTACT ENGINEER FOR ANY CHANGE TO PEX FOR NECESSARY PIPE SIZING AND/OR PUMP CHANGES.
6. INSULATE ALL PIPE LEADERS PASSING THROUGH ADJACENT ZONES.
GENERAL NOTES:
Snowmelt square footages shown here andon the snowmelt schedule do not matchwhat is shown on the architectural REMPsheet. Revise one or the other so that thesnowmelt quantities and locations areconsistent. You may exempt 9 SF ofsnowmelt for each window well (minimumsize required for an emergency escapeegress well) but you must include anyadditional square footage for each windowwell in your REMP calculation.
PROJECT ADDRESS:
Parcel ID #: Permit Number:
CONTACT INFORMATION :
Owner:
Name:City:
Address:State:
Email:Zip Code:
Phone: Cell Phone:
Owner's Representative :
Name:City:Aspen
Address:State:Colorado
Email:Zip Code:81611
Phone: Cell Phone:
`
A.RESIDENTIAL RENEWABLE ENERGY MITIGATION PROGRAMSheets showing snowmelt, pool, spa, and solar/GSHP information:
Do you have snowmelt or a spa that has been exempted by the buiding official?
Hydro Snowmelt Electric Snowmelt Pool SpaExisting0.00 sqft 0.00 sqft 0.00 sqft 0.00 sqftTo be Demoed 0.00 sqft 0.00 sqft 0.00 sqft 0.00 sqftExisting to Remain 0.00 sqft 0.00 sqft 0.00 sqft 0.00 sqftNew (non-exempt)1128.63 sqft 0.00 sqft 0.00 sqft 0.00 sqftNew (exempt)0.00 sqft 0.00 sqft 0.00 sqftTotal New 1128.63 sqft 0.00 sqft 0.00 sqft 0.00 sqftTotal on site 1128.63 sqft 0.00 sqft 0.00 sqft 0.00 sqftTotal Snowmelt on siteBoiler Efficiency 95.0%100%95.0%95.0%Mitigation Payment -$ -$ Total Payment for Mitigation:40,393.07$ B.ON-SITE RENEWABLE CREDITS Supplemental System REMP CreditUse PV Worksheet Photovoltaic System -$ Use Thermal Worksheet Hot Water Panels -$
2015 IECC RESIDENTIAL RENEWABLE ENERGY MITIGATION PROGRAM
City of Aspen Version 11.3 UpdAted deCember 13, 2017
533 West Hallam Aspen CO 81611
Wlewis@BillPoss.com
William Lewis
1128.63 sqft
605 East Main Street
G007
(970) 925-4755
$40,393.07
Yes (enter sqft below on the exempt row)No
Please fill out the contact info
portion of this form. If the site
plan/REMP plan are revised per
discussions with HPC and
building regarding the light well
guards, please be sure to
update the square footages on
this sheet accordingly.
You need an approved fabricator's
signature for the shop welds
shown in the structural plans.
Please resubmit the agreement.
You may resubmit responses
without this if you have yet to
decide on your welder/steel
fabricator but building will not be
able to sign off on your permit until
this agreement has been fully
executed.
Wind Loading
Basic Wind Speed Vult = 115 MPH Vasd = 90 MPH
Exposure Category B
GCpi 0.18
Wind Base Shear - Ultimate
21.9 K
Wind Design Pressure
Components & Cladding - Ultimate
50ft2
East/West
North/South
Seismic Loading
1.0
Mapped Spectral Response Acceleration
Seismic Importance Factor, Ie
0.315SS
0.082S1
DSite Class
Spectral Response Coefficients
Local Jurisdiction: City of Aspen
Building Code: 2015 International Building Code
-34.4 PSFInterior Roof Zone (Zone 1)
-47.0 PSFRoof End Zone (Zone 2)
-47.7 PSFCorner Roof Zone (Zone 3)
-25.6 PSFInterior Wall Zone (Zone 4)
-29.6 PSFWall End Zone (Zone 5)
STRUCTURAL DESIGN CRITERIA
Risk Category: II
20ft2
-42.3 PSF
-54.1 PSF
-55.6 PSF
-27.2 PSF
-32.7 PSF
100ft2
-28.4 PSF
-41.7 PSF
-41.7 PSF
-24.5 PSF
-27.2 PSF
(Note 1)
19.8 K
SURANCE
actor is responsible for quality assurance, including
ship and materials furnished by subcontractors and suppliers.
n or testing by the Owner does not relieve the Contractor of his
ility to perform the work in accordance with the Contract
ts.
nship: The Contractor is responsible and shall bear the cost of
g work which does not conform to the specified requirements.
eficient work by means acceptable to the Architect. The cost of
k incurred by the Architect to approve corrective work shall be
the Contractor.
NTROL
er's Testing Agency shall perform testing and special inspections
by the structural documents, building code and the local
The Testing Agency shall comply with ASTM E329 and upon
on of work, the Testing Agency shall furnish a certificate of
ce, signed by the professional engineer overseeing special
ns and testing. The professional engineer must be registered and
n the state where the project is located.
dual employed by the Testing Agency, responsible for
g testing and inspection of soils and foundations shall be a
nal engineer practicing the discipline of geotechnical
ng, referred to as the Geotechnical Engineer in the structural
f the construction documents. The Geotechnical Engineer is
le for testing and inspections of soils, earthwork and foundations
rmance to the foundation design and the geotechnical report.
dation section of the general notes.
al inspections section of the general notes for required testing
ction.
ABBRE
AB anchor
ADDNL addition
AFF above f
ALT alternat
ARCH architec
BLDG building
BM beam
BOT, B/, BOx bottom
BRG bearing
BS both si
BTWN between
CIP cast-in
CJ constru
CJP complet
CLR clear
CMU concret
COL column
CONC concret
CONN connect
CONST constru
CONT continu
D depth
DIA, D diamete
DIM dimensi
DK deck
DTL detail
DWGS drawing
DWL dowel
(E) existing
Our wind speed
design criteria is 89
MPH, please revise.
GCpi 0.18
Wind Base Shear - Ultimate
21.9 K
Wind Design Pressure
Components & Cladding - Ultimate
50ft2
East/West
North/South
Seismic Loading
1.0
Mapped Spectral Response Acceleration
Seismic Importance Factor, Ie
0.315SS
0.082S1
DSite Class
Spectral Response Coefficients
0.325SDS
0.131SD1
BSeismic Design Category
Wood Shear WallsBasic Seismic Force Resisting System
6.5Response Modification Factor, R
0.050Seismic Response Coefficient, Cs
Equivalent Lateral Force MethodAnalysis Procedure Used
Seismic Base Shear - Ultimate
11.5 KEast/West
11.5 KNorth/South
Snow Loading
100 PSFGround Snow Load, Pg
70 PSFMinimum Flat Roof Snow Load, Pf
1.0Importance Factor, Is
BTerrain Category
1.0Exposure Factor, Ce
1.0Thermal Factor, Ct
See Load KeysSlope Factor, Cs
Live Loads and Superimposed Dead Loads
(Notes 2,3,5)
(Notes 4,5)
-34.4 PSFInterior Roof Zone (Zone 1)
-47.0 PSFRoof End Zone (Zone 2)
-47.7 PSFCorner Roof Zone (Zone 3)
-25.6 PSFInterior Wall Zone (Zone 4)
-29.6 PSFWall End Zone (Zone 5)
20ft2
-42.3 PSF
-54.1 PSF
-55.6 PSF
-27.2 PSF
-32.7 PSF
100ft2
-28.4 PSF
-41.7 PSF
-41.7 PSF
-24.5 PSF
-27.2 PSF
19.8 K
2.5Over-Strength Factor, Ωo
4Deflection Amplification Factor, Cd
4. Correct deficient work by means acceptable to the Architect. The cost of
extra work incurred by the Architect to approve corrective work shall be
borne by the Contractor.
QUALITY CONTROL
1. The Owner's Testing Agency shall perform testing and special inspections
required by the structural documents, building code and the local
authority. The Testing Agency shall comply with ASTM E329 and upon
completion of work, the Testing Agency shall furnish a certificate of
compliance, signed by the professional engineer overseeing special
inspections and testing. The professional engineer must be registered and
licensed in the state where the project is located.
2. The individual employed by the Testing Agency, responsible for
overseeing testing and inspection of soils and foundations shall be a
professional engineer practicing the discipline of geotechnical
engineering, referred to as the Geotechnical Engineer in the structural
portion of the construction documents. The Geotechnical Engineer is
responsible for testing and inspections of soils, earthwork and foundations
for conformance to the foundation design and the geotechnical report.
See foundation section of the general notes.
3. See special inspections section of the general notes for required testing
and inspection.
SPECIAL INSPECTION
1. Special inspection and testing shall be performed as required by the local
jurisdiction, the building code and the construction documents. See
quality assurance section of the general notes.
2. Coordinate and schedule inspection and testing prior to the start of work
requiring inspection and testing while providing special inspector
reasonable notice.
3. All deficiencies shall be corrected for acceptance by the testing agency.
4. Inspections performed by the local jurisdiction do not replace inspection
or testing required by the owners testing agency.
5. Special inspection and testing is required for the items shown in the
special inspections and testing table.
SPECIAL INSPECTIONS AND TESTING
ClassCategory/Material
X
54321
Component/Work
Footing Soil Bearing Material
So
i
l
s
a
n
d
Fo
u
n
d
a
t
i
o
n
s
XSlab-on-Grade Subgrade Material
XXXCompaction
X
XX
Formwork Installation
Reinforcing Placement
BM beam
BOT, B/, BOx bottom of (
BRG bearing
BS both sides
BTWN between
CIP cast-in-pla
CJ construction
CJP complete jo
CLR clear
CMU concrete ma
COL column
CONC concrete
CONN connection
CONST construction
CONT continuous
D depth
DIA, D diameter
DIM dimension
DK deck
DTL detail
DWGS drawings
DWL dowel
(E) existing con
EA each
EF each face
EJ expansion jo
ELEV elevation
EOx edge of (S=
EW each way
EXP expansion
EXT exterior
FDN foundation
FLR floor
FOx face of (S=
FS far side
FTG footing
GA gage
GC general con
GEN general
HDG hot dip galv
HDR header
HK hook
HORIZ horizontal
HSA headed stud
I.F. inside face
INT interior
JST joist
We are seismic design
category C, please
revise.
Subject: PlanCheck
Page Label: 13
Author: justinh
File Name: Structural Plans. 533 W HALLAM.pdf
Color:
Per discussion with HPC the
existing roof framing was to
remain in the historic structure
and be added to as needed.
This appears to be a new roof
framing package entirely.
Please coordinate with HPC and
revise the structural plan to
clearly show existing historic
framing to remain everywhere
that is applicable.
HD1 HD1ZIP9'-3"
HD1 HD1ZIP5'-3"HD1 HD1ZIP5'-3"
HD1
ZIP
12
'
-9"
HD
1
HSS
A
6'-6"
2567
L
K
J
F
G
D
C
A
34
E
H
1
B
86'-0 1/2"
15'-11"11'-9"2'-0 1/2"9'-0 7/8"11'-11 1/8"4'-5 1/2"
15'-11"11'-9"2'-0 1/2"9'-0 7/8"11'-11 1/8"4'-5 1/2"
42'-5 1/2"
1'-8"
4'-2 1/2"
12'-5 3/4"
9'-0"
1'-4 1/4"
1'-8"
3'-7 1/2"
3'-5 1/2"
4'-6"
6"
11
7
/
8
"
T
J
I
2
1
0
@
1
6
"
O
C
11
7
/
8
"
T
J
I
2
1
0
@
1
6
"
O
C
(1
)
1
3
/
4
"
x
9
1
/
2
"
L
V
L
@
1
6
"
O
C
(1)
1
3
/
4
"
x
9
1
/
2
"
L
V
L
@
1
6
"
O
C
(1)1 3/4"x11 7/8" LVL@24"OC
(1)1 3/4"x11 7/8" LVL@24"OC
(1)
1
3
/
4
"
x
1
1
7
/
8
"
L
V
L
@
2
4
"
O
C
(1)
1
3
/
4
"
x
1
1
7
/
8
"
L
V
L
@
2
4
"
O
C
(1)1 3/4"x11 7/8" LVL@24"OC
(1)1 3/4"x11 7/8" LVL@24"OC
(1
)
1
3
/
4
"
x
1
1
7
/
8
"
L
V
L
@
2
4
"
O
C
(1
)
1
3
/
4
"
x
1
1
7
/
8
"
L
V
L
@
2
4
"
O
C
W10x22 (BENT)
W10x22 (BENT)(2)1 3/4"x14" LVL(2)1 3/4"x14" LVL(2)1 3/4"x14" LVL(2)1 3/4"x14" LVL(2
)
1
3
/
4
"
x
1
4
"
L
V
L(2)1 3/4"x14" LVL(2)1 3/4"x14" LVL
(2
)
1
3
/
4
"
x
1
4
"
L
V
L
(2)
1
3
/
4
"
x
1
4
"
L
V
L
W8x67
109'-10 1/4"
W1
8
x
4
6
110'-7 1/4"
W14
x
2
6
110'-3 1/4"
W10x22
109'-11 1/4"
2S402
3S402
4S402
(2)1 3/4"x9 1/2" LVL
(2)
1
3
/
4
"
x
9
1
/
2
"
L
V
L
(3)
1
3
/
4
"
x
9
1
/
2
"
L
V
L
1S301
1S301
T/SHEATHING
110'-1 1/2"
T/SHEATHING
109'-11"
No2
(3
)
1
3
/
4
"
x
1
1
7
/
8
"
L
V
L
(2)1 3/4"x11 7/8" LVL
(2)1 3/4"x11 7/8" LVL
2x6 DFL No2@24"OC
2x6
D
F
L
N
o
2
@
2
4
"
O
C
2x
6
D
F
L
N
o
2
@
2
4
"
O
C
2x
6
D
F
L
N
o
2
@
2
4
"
O
C
KL A&Engineers Builders215 North 12th Street, Unit ECarbondale, Colorado 81623P: (970) 927 5174 F: (970) 927 5194
Buffalo, WY ○ Carbondale, CO ○ Golden, CO ○ Loveland, CO
&
NORTH
Consultant
ARCHITECTURE PLANNING+
( T ) 9 7 0 / 9 2 5 4 7 5 5 ( F ) 9 7 0 / 9 2 0 2 9 5 0
6 0 5 E A S T M A I N S T R E E T A S P E N, C O L O R A D O 8 1 6 1 1
PROJECT NO:
Issue:
DUNCAN RESIDENCE
533 W. HALLAM
1 UPPER LEVEL / LOW ROOF FRAMING PLAN
10/31/18 PERMIT
10/25/2018
Per discussion with HPC the existing
roof framing was to remain in the historic
structure and be added to as needed.
This appears to be a new roof framingpackage entirely. Please coordinate
with HPC and revise the structural planto clearly show existing historic framing
to remain everywhere that is applicable.