Subject: PlanCheck
Page Label: A202-DEMOLITION FLOOR PLANS
Author: justinh
File Name: RUTH PERMIT SET 12.06.17.pdf
Identify demising walls to
provide unit building relationship
with neighboring units (I'm
assuming that there are no units
above or below this one, please
note if there are). If more than
32 SF of drywall (one 8'x4'
sheet) is being removed in any
location along the demising wall
during demo then a listed 1 hour
assembly with STC rating of at
least 50 will be required for
replacement of the dwelling
separation. Provide this listed
assembly or note that less than
32 SF of drywall will be removed
along the applicable demising
wall.
RUTH PERMIT SET 12.06.17.pdf (2)
Subject: PlanCheck
Page Label: A601-WALL ASSEMBLIES
Author: justinh
File Name: RUTH PERMIT SET 12.06.17.pdf
Please label this as an existing
exterior wood wall as it does not
meet IECC insulation req's for a
new wood wall. Also note that
any cavities exposed during
construction will be filled with
insulation per IECC R503.1.1.
Subject: PlanCheck
Page Label: 1
Author: justinh
File Name: structural engineer letter.pdf
Your structural letter speaks to
the new header for the egress
window but does not make any
mention of the other proposed
interior wall demo being non
structural. Provide verification
that all proposed demolition is
non-structural.
structural engineer letter.pdf (1)
Identify demising walls to provide unit building relationship with neighboring units (I'm assuming that
there are no units above or below this one, please note if there are). If more than 32 SF of drywall (one
8'x4' sheet) is being removed in any location along the demising wall during demo then a listed 1 hour
assembly with STC rating of at least 50 will be required for replacement of the dwelling separation.
Provide this listed assembly or note that less than 32 SF of drywall will be removed along the
applicable demising wall.
Please label this as an
existing exterior wood
wall as it does not
meet IECC insulation
req's for a new wood
wall. Also note that
any cavities exposed
during construction will
be filled with insulation
per IECC R503.1.1.
P.O. Box 2544 • Crested Butte CO 81224 USA • ph: 970.349.5922• f: 970.349.5926
Zone 4 Architects
P.O. Box 2508
Aspen, CO 81621
RE: 120 Spring St. New lower level Header
Tim,
You recently contacted us to design a new window headers at the lower level of the
residence located at 120 Spring Street in Aspen, Colorado. After reviewing the plans and
running the calcs the new header for the 24" opening it needs to be (3)-5 1/2" LVL
supported with (2)-2x6 one of which are trimmers if it is in a framed wall. The stone
veneer may be supported off a L4x4x1/4 lintel attached with 5/8” bolts @ 12”o.c. If the
wall is a concrete wall the new opening may be saw cut and the stone veneer may be
supported with a L4x4x1/4 steel lintel.
Please give me a call if you need anything else on this project.
Sincerely,
Mike Arbaney P.E.
Your structural letter speaks to the new
header for the egress window but does
not make any mention of the other
proposed interior wall demo being non
structural. Provide verification that all
proposed demolition is non-structural.
1 PLEASE SEE NOTE LOCATING EXISTING
DEMISING WALL TO REMAIN. 1,2 AND 3/A202.
PLEASE SEE DEMOLITION NOTE #1.
3/A202.
2 PLEASE SEE REVISED DETAIL LABELED AS
"EXISTING". 2/A601
PLEASE SEE DEMOLITION NOTE #2.
3/A202.
3 PLEASE SEE REVISED LETTER FROM THE
STRUCTURAL ENGINEER DATED 03.05.18.