HomeMy WebLinkAboutFile Documents.611 E Durant Ave.0048.2019 (37).ACBKTYPICAL HEALTH/HYGIENE-AUTHORITY FIT-OUT REQUIREMENTS
What follows are typical requirements from review authorities within food/beverage storage, preparation and service zones. These are offered for reference-only and do not necessarily constitute design or
construction direction from Ricca Design Studios.
•Flooring surfaces/systems should be smooth, non-slip with commercial-grade durability, made of non-absorbent material, and easily cleanable in all the following zones:
•where food is prepared, packaged or stored
•where utensils are washed
•where refuse is stored
•within janitor rooms
•within washroom and hand washing areas
•Flooring surfaces should be coved at the intersection of the floor and wall with 3/8” (10mm) minimum radius and should extend up the wall minimum of six inches (6” or 152mm) in all foodservice
rooms/zones. Mastic-applied vinyl is not acceptable.
•Floor drains should be installed in culinary zones for general area cleaning. Additional drains should be installed in floors that are more frequently sprayed-down in the cleaning process. Flooring should
be sloped to the drain 1/16” (2mm) per foot within a six-foot (6’ or 1.8 M) radius.
•Wall and ceiling finishes within all foodservice rooms/zones where food is stored in unopened containers, and in dining and sales areas should be durable, smooth, non-absorbent, impervious and
washable. Wall and ceiling finishes within food preparation and utensil washing areas should be light-colored with durability equal to demand. Wall finishes on interior surfaces of walk-in refrigeration
cavities should also be light-colored with durability equal to demand. Cement board with Fiberglass Reinforced Panel finish is typical minimum wall finish in all preparation/wash-up zones. Wall areas
adjacent to bar sinks should be smooth and easily cleanable. Conduits of all types should be installed within walls; when installed on surface of walls, they should be shrouded to facilitate ease of cleaning.
•Lighting in every zone where food is prepared, processed or packaged or where utensils are cleaned should be provided in an intensity of no less than 50 foot candles as measured 30” (762mm) above
the finished floor, except the working surfaces of bars and bar work-boards where at least 10 foot-candles of light are required. Required light source must be shrouded with shatter-proof covers.
•Exhaust ventilation should be provided at or above all electric or gas cooking equipment and dishwashers that utilize hot water or chemicals for sanitization per local, regional and national code. Exhaust
ventilation may be required above hot beverage equipment – confirm with local code. Washrooms, dressing rooms should be vented to the atmosphere by means of an openable, screened window, and
air shaft or switch-activated exhaust fan per local building codes.
•Foodservice facility should be constructed, and maintained and operated to prevent entrance of animals, birds and vermin including rodents and insects.
•Delivery Doors leading to the exterior should be self-closing and open outward. Vestibules are typically required where large double-doors may enter-into a food preparation area. All exterior doors should
be provided with an overhead air curtain, air curtain should produce a downward and outward airflow not less than three inches (3” of 75mm) thick at the nozzle with an air velocity no less than 1600FPM
across entire opening.
•Circulation- minimum of thirty-six inches (36” or 914mm) is required for all aisles and working areas within foodservice and beverage preparation zones.
•Hand Washing sinks with single-use towels and hand cleanser should be provided within, or adjacent to, washrooms and should be equipped with an adequate supply of hot/cold running water. A
dedicated hand washing station should be provided within each food preparation zone.
•Washrooms for use by foodservice employees should be provided and should be fit-out with self-closing doors.
•Ware Washing machines using hot water or chemical sanitizing rinse must conform to applicable National Sanitation Foundation (NSF) standards and shall be installed and operated in accordance with
those standards.
•Refrigeration cavities must be equipped with a thermometer that is easily-readable and in proper working condition.
•Equipment installation- all equipment must meet National Sanitation Foundation (NSF) design and installation requirements. All foodservice equipment should be easily moveable, light enough to be
easily-moved by one (1) person or installed on a raised minimum six inches (6” or 152mm) rounded stainless steel legs or sealed to a minimum four inches (4” or 101mm) stainless steel or galvanized
steel channel base filled with lightweight concrete with minimum 3/8” (10mm) coved radius. If on an island, equipment should overhang the base at least three inches (3” or 75mm), but not more than the
height of the base. Sealing to the finished floor is acceptable for equipment designed to be on level with floor such as roll-in refrigerator/freezers, large blast chiller/freezers, roll-in ovens and proofers.
Gaps between equipment base and top of channel base should be sealed with non-hardening silicone sealant. All equipment on counters, tables and shelves that are not easily moved are to be installed
on approved four inch (4” of 101mm) legs or sealed to table, shelf, etc. (Verify with local code). All fabricated equipment, flashing, and back splashes must be sealed to walls and abutting equipment or
moved away from adjacent fabricated equipment minimum of three inches (3” or 75 mm) or adjacent wall minimum of six inches (6” or 152mm). Dipper wells with running water should be provided for ice
cream/frozen dessert with scooping required.
ABBREVIATIONS
ADA
ADJ
AMP
AFF
ALT
BFD
BFF
BHP
BOH
BTC
BTU
BTUH
C
CFH
CFM
CHR
CHS
CLG
C02
CONN
CONV
CW
DCR
DCV
DEG
DFA
DIA
DIM
DISC
DWG
DW
EA
NOTE:REFER TO ARCHITECTURAL / MECHANICAL / ELECTRICAL / PLUMBING / INTERIOR DESIGN DRAWINGS FOR ADDITIONAL ABBREVIATIONS SHOWN ON FOODSERVICE DRAWINGS BUT NOT INCLUDED IN THIS LIST.
Americans with Disabilities Act
Adjustable
Amperage
Above Finished Floor
Alternate
Backflow Prevention Device
Below Finished Floor
Boiler Horsepower
Back of House
Branch to Connection
British Thermal Unit
British Thermal Unit Per Hour
Degree Centigrade (note, need “degree” symbol in front of C)
Cubic Feet Per Hour
Cubic Feet Per Minute
Chilled or Condenser Water Return
Chilled or Condenser Water Supply
Ceiling
Compressed Carbon Dioxide Gas
Connection
Convenience Receptacle
Cold Water
Duplex Convenience Receptacle
Demand Control Ventilation
Degree (or Degrees)
Down From Above
Diameter
Dimension
Disconnect
Drawing
Direct Waste
Each
EC
EE
EM
EQ
EQUIP
ETR
ETL
EXH
EXIST
°F
FAB
FD
FP
FPM
FR
FS
GA
GAL
GC
GFCI
GPH
GPM
HVAC
HW
HZ
IW
JB
KEC
KCAL
KW
Electrical Contractor/Division
Electrical Engineer
Emergency Power
Equal
Equipment
Existing to Remain
Listing Equal to UL (Intertek)
Exhaust
Existing
Degree Fahrenheit
Fabricated
Floor Drain
Fire Protection
Feet Per Minute
From
Floor Sink
Gauge
Gallon
General Contractor
Ground Fault Circuit Interrupter
Gallon(s) Per Hour
Gallon(s) Per Minute
Heating Ventilation & Air Conditioning
Hot Water
Hertz
Indirect Waste
Junction Box
Kitchen Equipment Contractor
Kilocalorie
Kilowatt
LEC
LC
LF
LPH
LPG
MBH
MC
ME
MFR
MIN
MISC
MUA
MTD
N2
NA
NIC
NIKEC
NSF
OC
OFI
OFCI
OFOI
PB
PC
PE
PH
POC
POS
PREP
PRV
PSI
Laundry Equipment Contractor
Load Center
Linear Foot (or Feet)
Liters per Hour
Liquid Propane Gas
Thousand British Thermal Units Per Hour
Mechanical Contractor/Mechanical Division
Mechanical Engineer
Manufacturer
Minimum
Miscellaneous
Make-Up Air
Mounted
Compressed Nitrogen Gas
Not Applicable
Not in Contract
Not in Kitchen Equipment Contract
National Sanitation Foundation
On-Center
Owner or Operator Furnished Item
Owner or Operator Furnished/Contractor Installed
Owner or Operator Furnished/Owner or Operator Installed
Pull Box
Plumbing Contractor/Plumbing Division
Plumbing Engineer
Phase
Point of Connection
Point of Sale
Preparation
Pressure Regulating/Reducing Valve
Pounds-Per-Square-Inch
QT
QTY
RAD
RCP
SC
SF
SP
SPEC
SST
STD
SW
SYS
TDO
TLS
TYP
UDS
UL
UV
V
VAV
VD
VFD
VIF
W
WC
Quart
Quantity
Radius
Receptacle
Self-Contained
Square Foot (or Feet)
Static Pressure
Specifications
Stainless Steel
Standard
Switch
System
Tangent Draw-Off
Table Limit Switch
Typical
Utility Distribution System
Underwriters Laboratory
Ultraviolet
Volt
Variable Air Volume
Volume Damper
Variable Frequency Drive
Verify in Field
Watts
Water Column
5325 South Valentia Way, Greenwood Village, CO 80111
Phone 303 221 0500 Fax 303 221 0600
www.ricca.com
Key Plan
It is the responsibility of the Construction
Manager/General Contractor and all
Sub-Contractors to verify all dimensions and
accept conditions of prior work by related
trades before proceeding with any work.
Date
Drawn By
Scale
Seal
Project Title
Project Address
Project Number
Drawing Title and Number
PROJECT
NORTH
Revisions
FO
R
R
E
F
E
R
E
N
C
E
O
N
L
Y
1" = 1'-0"
C:
\
U
s
e
r
s
\
j
j
u
r
g
e
n
s
\
D
o
c
u
m
e
n
t
s
\
1
9
2
0
1
_
A
s
p
e
n
M
o
u
n
t
a
i
n
C
l
ub
_
F
o
o
d
s
e
r
v
i
c
e
_
R
1
6
_
j
j
u
r
g
e
n
s
@
r
i
c
c
a
.
c
o
m
.
r
v
t
12
/
1
9
/
2
0
1
9
1
0
:
0
1
:
3
8
A
M
Issue Date
Author
Aspen Mountain Club
19201
675 E Durant Ave
Aspen, CO 81611
19201
Index Sheet
QF001-1
Rev.
No.Description Date
Construction Documents 11/22/19
Sheet Number Sheet Name CO
N
S
T
R
U
C
T
I
O
N
D
O
C
U
M
E
N
T
S
-
1
1
/
2
2
/
1
9
QF001-1 Index Sheet X
QF101-1 Foodservice Key Plan X
QF401-1 Foodservice Equipment Plan X
QF401-2 Foodservice Utility Schedule X
QF401-3 Foodservice Building Conditions & Ventilation Plan X
QF401-4 Foodservice Plumbing Plan X
QF401-5 Foodservice Electrical Plan X
1
A4.1
H.1
F.6
I
J
J.5
E
D
C
B1.W
TF
TE
TD
TC
TB
B.W
A1.W
A.W
4.WT5T4T3T2T11.W12108
2.W12108 3.W 4.W
TA
B1.W
1.W119
9 11
0,0,0 CONTROL POINT
QF401-1
1
A1.W
B.W
B1.W
B1W
C1
D1
E1
A.W
8 9 10W 11X 12Y 1.W 2.W 3.W 4.W
5325 South Valentia Way, Greenwood Village, CO 80111
Phone 303 221 0500 Fax 303 221 0600
www.ricca.com
Key Plan
It is the responsibility of the Construction
Manager/General Contractor and all
Sub-Contractors to verify all dimensions and
accept conditions of prior work by related
trades before proceeding with any work.
Date
Drawn By
Scale
Seal
Project Title
Project Address
Project Number
Drawing Title and Number
PROJECT
NORTH
Revisions
FO
R
R
E
F
E
R
E
N
C
E
O
N
L
Y
1/8" = 1'-0"
C:
\
U
s
e
r
s
\
j
j
u
r
g
e
n
s
\
D
o
c
u
m
e
n
t
s
\
1
9
2
0
1
_
A
s
p
e
n
M
o
u
n
t
a
i
n
C
l
ub
_
F
o
o
d
s
e
r
v
i
c
e
_
R
1
6
_
j
j
u
r
g
e
n
s
@
r
i
c
c
a
.
c
o
m
.
r
v
t
12
/
1
9
/
2
0
1
9
1
0
:
0
1
:
4
0
A
M
Issue Date
Author
Aspen Mountain Club
19201
675 E Durant Ave
Aspen, CO 81611
19201
Foodservice Key Plan
QF101-1
SCALE: 1/8" = 1'-0"1 Foodservice Key Plan - Locker Room
Rev.
No.Description Date
Construction Documents 11/22/19
Does not include new background with structural
information - N/A for equipment
Walk-In Cooler
Chiller to be Mounted
Above
08/17/2020
nickt
C2.1
C3.1
C3.3
C3
C3.2
C2
B1.W
B1W
3.W 4.W
C1
5325 South Valentia Way, Greenwood Village, CO 80111
Phone 303 221 0500 Fax 303 221 0600
www.ricca.com
Key Plan
It is the responsibility of the Construction
Manager/General Contractor and all
Sub-Contractors to verify all dimensions and
accept conditions of prior work by related
trades before proceeding with any work.
Date
Drawn By
Scale
Seal
Project Title
Project Address
Project Number
Drawing Title and Number
PROJECT
NORTH
Revisions
FO
R
R
E
F
E
R
E
N
C
E
O
N
L
Y
1/4" = 1'-0"
C:
\
U
s
e
r
s
\
j
j
u
r
g
e
n
s
\
D
o
c
u
m
e
n
t
s
\
1
9
2
0
1
_
A
s
p
e
n
M
o
u
n
t
a
i
n
C
l
ub
_
F
o
o
d
s
e
r
v
i
c
e
_
R
1
6
_
j
j
u
r
g
e
n
s
@
r
i
c
c
a
.
c
o
m
.
r
v
t
12
/
1
9
/
2
0
1
9
1
0
:
0
1
:
4
1
A
M
Issue Date
Author
Aspen Mountain Club
19201
675 E Durant Ave
Aspen, CO 81611
19201
Foodservice Equipment
Plan
QF401-1
SCALE: 1/4" = 1'-0"1 Foodservice Equipment Plan - Lock Room - Area C
Foodservice Equipment Schedule - (C)
Item Number Qty Description Remarks
C1 1 Refrigerator, Undercounter
C2 1 Espresso Machine By Purveyor
C2.1 1 Water Filtration System
C3 1 Sparkling Water Dispenser
C3.1 1 Water Carbonator/Chiller
C3.2 1 Water Filtration System
C3.3 1 Drip Tray
Rev.
No.Description Date
Construction Documents 11/22/19
Clouded equipment will be
remote, located above walk-in
cooler in BOH corridor
08/17/2020
nickt
5325 South Valentia Way, Greenwood Village, CO 80111
Phone 303 221 0500 Fax 303 221 0600
www.ricca.com
Key Plan
It is the responsibility of the Construction
Manager/General Contractor and all
Sub-Contractors to verify all dimensions and
accept conditions of prior work by related
trades before proceeding with any work.
Date
Drawn By
Scale
Seal
Project Title
Project Address
Project Number
Drawing Title and Number
PROJECT
NORTH
Revisions
FO
R
R
E
F
E
R
E
N
C
E
O
N
L
Y
C:
\
U
s
e
r
s
\
j
j
u
r
g
e
n
s
\
D
o
c
u
m
e
n
t
s
\
1
9
2
0
1
_
A
s
p
e
n
M
o
u
n
t
a
i
n
C
l
ub
_
F
o
o
d
s
e
r
v
i
c
e
_
R
1
6
_
j
j
u
r
g
e
n
s
@
r
i
c
c
a
.
c
o
m
.
r
v
t
12
/
1
9
/
2
0
1
9
1
0
:
0
1
:
4
2
A
M
Issue Date
Author
Aspen Mountain Club
19201
675 E Durant Ave
Aspen, CO 81611
19201
Foodservice Utility
Schedule
QF401-2
Foodservice Utility Schedule - (C)
Item
Number QTY Description Remarks
Electrical Plumbing Ventilation
Item
Number
Emer.
Power
Req'd Volts PH Amps KW HZ
Elec.
Conn.
Type
Elec.
Rough-In
AFF Electrical Remarks
Cold
Water
Conn.
Size
Cold
Water
Rough-In
AFF
Hot
Water
Conn.
Size
Hot
Water
Flow
GPH
Hot
Water
Rough-In
AFF
Direct
Drain
Conn.
Size
Direct
Drain
Rough-In
AFF
Indirect
Drain
Conn.
Size
Gas
Conn.
Size
Gas
MBH
Gas
Rough-In
AFF
Cooling
Water
Supply
Conn.
Size
Cooling
Water
Return
Conn.
Size
Cooling
Water
Rough-In
AFF Plumbing Remarks
Exhaust Collar Size
Exhaust
Volume
Exhaust
Static
Pressure
Supply Collar
Size
Supply
Volume
Supply
Static
Pressure Mechcanical RemarksWidth Depth DIA Width Depth
C1 1 Refrigerator, Undercounter 120 1 2.3 0.28 60 PLUG 24"C1
C2 1 Espresso Machine By Purveyor 240 1 15.4 3.7 60 DIRECT 48" 208V/240V Service Required 3/8" 48"3/4"PC To Inter-Connect Water Filter With Equipment; IW To
Floor Sink
C2
C2.1 1 Water Filtration System 1/2" 24"PC To Inter-Connect Water Filter To Equipment C2.1
C3 1 Sparkling Water Dispenser 1/2" 18"PC To Inter-Connect Dispenser to Chiller C3
C3.1 1 Water Carbonator/Chiller 120 1 5 0.6 60 PLUG 24" 110-120V Service Required 3/8" 18"PC To Inter-Connect Water Filter To Chiller and from
Chiller to Dispenser; CO2 Required
C3.1
C3.2 1 Water Filtration System 3/8" 18"PC To Inter-Connect Water Filter To Equipment in Wall C3.2
C3.3 1 Drip Tray 1"IW To Floor Sink C3.3
Rev.
No.Description Date
Construction Documents 11/22/19
B.W
B1.W
B1W
2.W 3.W 4.W
M-A. GENERAL NOTES
1. THE ASSIGNED KITCHEN EQUIPMENT CONTRACTOR SHALL PERFORM A THOROUGH
PROJECT REVIEW OF ALL CURRENT CONTRACT DOCUMENTS THAT APPLY TO
FOODSERVICE ZONES AND EQUIPMENT. KITCHEN EQUIPMENT CONTRACTOR
SHALL GENERATE ENGINEERING INDEPENDENT OF THIS SHEET CONFORMING TO
FIELD CONDITIONS WHERE REQUIRED AND MANUFACTURER’S REQUIREMENTS
FOR EQUIPMENT SPECIFIED AND THUS INTENDED TO BE PURCHASED AND
SET-IN-PLACE.
2. ALL CONSTRUCTION AND MECHANICAL WORK SHOWN ON THIS PLAN MUST
COMPLY WITH ALL APPLICABLE CODES AND REGULATIONS, INCLUDING CURRENT
INTERNATIONAL MECHANICAL CODE, AS THEY APPLY TO FOODSERVICE
EQUIPMENT AND ZONES.
3. ALL WORK SERVICES, INTERCONNECTIONS, FIELD CONNECTIONS, AND FINAL
CONNECTIONS INDICATED ON THIS PLAN SHALL BE COMPLETED BY CONTRACTORS
OTHER THAN THE KITCHEN EQUIPMENT CONTRACTOR UNLESS SPECIFICALLY
ASSIGNED TO THE KITCHEN EQUIPMENT CONTRACTOR.
4. THIS PLAN IS INTENDED TO SHOW SPECIAL BUILDING AND VENTILATION
REQUIREMENTS FOR FOODSERVICE EQUIPMENT ONLY. REFER TO
ARCHITECTURAL AND ENGINEERING PLANS FOR SCOPE OUTSIDE OF
FOODSERVICE EQUIPMENT.
5. THIS DRAWING IS ISSUED FOR DESIGN INTENT PURPOSES ONLY. REFER TO THE
KITCHEN EQUIPMENT CONTRACTOR’S DIMENSIONED ROUGH-IN DRAWINGS AND
APPROVED SHOP DRAWINGS FOR SUPPLEMENTAL COORDINATION AND
INSTALLATION REQUIREMENTS FOR FOODSERVICE EQUIPMENT ON THIS PLAN.
6. ALL EQUIPMENT PROVIDED BY OTHERS -INCLUDING BY
OWNER/OPERATOR/PURVEYOR- SHOWN ON THIS PLAN ARE MINIMUM GUIDELINES
ONLY. KITCHEN EQUIPMENT CONTRACTOR TO VERIFY INFORMATION, TECHNICAL
DATA, AND SPECIFICATIONS FOR THIS EQUIPMENT. GENERAL CONTRACTOR TO
VERIFY AND MAKE FINAL ROUGH-IN CONNECTIONS AS REQUIRED.
7. EXISTING, TO-REMAIN-IN-PLACE, OR TO-BE-RELOCATED EQUIPMENT SHOWN ON
THIS PLAN ARE MINIMUM GUIDELINES ONLY AND MUST BE VERIFIED. CONTACT
OWNER/OPERATOR FOR INFORMATION, TECHNICAL DATA, AND SPECIFICATIONS
FOR THIS EQUIPMENT. GENERAL CONTRACTOR AND KITCHEN EQUIPMENT
CONTRACTOR TO VERIFY, DISCONNECT, AND MAKE FINAL ROUGH-IN CONNECTIONS
AS REQUIRED.
8. RECOMMEND TO PROVIDE MINIMUM LIVE LOADS OF 150 LBS. PER SQUARE FOOT
(68KG PER.09 SQUARE METERS). PROVIDE REINFORCED SLAB FOR ANY
FOODSERVICE EQUIPMENT THAT MAY EXCEED 150 LBS. PER SQUARE FOOT, SUCH
AS A LARGE COMPRESSOR RACK, LARGE DISH MACHINE, LARGE OVENS, ETC.
BUILDING CONDITIONS & VENTILATION NOTES
THE NOTES BELOW MAY APPLY TO ONE OR ALL DESIGN,
CONSTRUCTION, OR CLOSE-OUT PHASES OF THIS PROJECT
9. RECOMMENDED MINIMUM FINISHED CEILING HEIGHTS IN KITCHEN AREAS AND FOR
SPECIFIC FOODSERVICE EQUIPMENT ARE AS FOLLOWS:
A. KITCHEN AREAS WITH EXHAUST HOODS 9’-0” (2.75M)
B. WALK-IN COOLER/FREEZER AREAS 9’-0” (2.75M)
C. GENERAL AREAS 9’-0” (2.75M)
D. ICE MACHINE AREAS 10’-6” (3.2M)
10. ADEQUATE SPACE IS NEEDED ABOVE THE FINISHED CEILINGS FOR MECHANICAL
AND ELECTRICAL WORK, ESPECIALLY ABOVE EXHAUST HOODS AND WALK-IN
COOLER/FREEZERS. NOTIFY RICCA DESIGN STUDIOS IF HEIGHTS ARE LESS THAN
RECOMMENDED MINIMUMS.
A. WALK-IN COOLER/FREEZER CEILING PANELS REQUIRE ADDITIONAL 18” (457MM)
CLEARANCE ABOVE FOR INSTALLATION
B. ICE MACHINES REQUIRE 24” (609 MM) CLEARANCE ABOVE FOR INSTALLATION
11. ALL FLOOR SINKS AND FLOOR TROUGHS TO BE SET FLUSH WITH FINISHED FLOOR -
UNLESS OTHERWISE DIRECTED BY LOCAL CODE. ALL FLOOR TROUGHS SERVING
FOODSERVICE EQUIPMENT WITH LIQUID VOLUME IN TILTING OR IN VALVED
DUMPING MANNER SHALL BE PLACED IN A LOCATION DIRECTLY RELATED TO
MANUFACTURER’S REQUIRED POUR-PATH FOR EQUIPMENT TO BE SET IN PLACE.
KITCHEN EQUIPMENT CONTRACTOR AND GENERAL CONTRACTOR TO FIELD-VERIFY
LOCATION IN RELATION TO REQUIRED POUR PATH, AND IN HEIGHT PER PITCH-TO-
DRAIN REQUIRED.
12. THE MOUNTED HEIGHT FOR THE BOTTOM EDGE OF EXHAUST HOODS TO BE SET
AT 6’-8” MINIMUM (2032MM) ABOVE THE FINISHED FLOOR UNLESS OTHERWISE
INDICATED. THE BOTTOM EDGE OF EXHAUST HOODS SHALL BE NO HIGHER THAN
7’-0” (2134MM) ABOVE FINISHED FLOOR.
13. MANUAL-PULL EXHAUST HOOD FIRE EVENT PULL STATION AND CONDUIT TO BE
MOUNTED WITHIN WALL CAVITY AND SET TO 48” ABOVE FINISHED FLOOR (1220MM)
AT CENTER. CONDUIT TO TERMINATE PER MANUFACTURER’S DRAWINGS. KITCHEN
EQUIPMENT CONTRACTOR AND MECHANICAL CONTRACTOR TO VERIFY LOCATION
WITH APPLICABLE FIRE CODE OFFICIALS PRIOR TO INSTALLATION.
14. GENERAL CONTRACTOR TO CONFIRM FOLLOWING IS COMPLETED PRIOR TO THE
FOODSERVICE EQUIPMENT DELIVERY AND SET-IN-PLACE:
A. THE WALLS AND CEILINGS ARE INSTALLED AND FINISHED. WALLS AND CEILINGS
MUST BE SMOOTH, EASILY CLEANABLE, NON-ABSORBENT, DURABLE, WITH
FINISHES APPROVED BY LOCAL HEALTH CODE OFFICIALS.
B. THE FLOORING IS INSTALLED AND WASHED CLEAN. FLOORS MUST BE NON-
SLIP, EASILY CLEANABLE, NON-POROUS, NON-ABSORBENT, AND DURABLE
WITH FINISHES APPROVED BY LOCAL HEALTH CODE OFFICIALS. ALL VERTICAL
INTERSECTIONS OF FLOORS-TO-WALLS SHALL HAVE COVED BASES
INSTALLED.
C. CONFIRM IF A LOADING DOCK IS AVAILABLE.
D. COORDINATION WITH APPLICABLE TRADESPEOPLE FOR ANY DOOR/WINDOW
OPENINGS AND/OR PASSAGEWAYS REQUIRED FOR THE DELIVERY OF
FOODSERVICE EQUIPMENT.
M-B. MECHANICAL NOTES
MECHANICAL ENGINEER IS RESPONSIBLE FOR SPECIFYING THE FOLLOWING APPLICABLE
EQUIPMENT AND PROVIDING THE FOLLOWING CONDITIONS. MECHANICAL CONTRACTOR IS
RESPONSIBLE FOR PROVIDING, INSTALLING, AND MAKING FINAL CONNECTIONS TO
FOODSERVICE EQUIPMENT PER BELOW INSTRUCTIONS.
1. ALL COOKING EXHAUST HOOD ASSEMBLIES, DUCTING, COMPONENTS, ETC. SHALL
BE TYPE I; ALL WARE WASHING ASSEMBLIES, DUCTING, COMPONENTS, ETC. SHALL
BE TYPE II AS REQUIRED PER N.F.P.A.-96.
2. EXHAUST HOOD DUCT TRANSITIONS TO HOODS, FANS, MAKE-UP AIR UNITS,
POLLUTION CONTROL UNITS, FIRE-RATED MATERIALS, COMPONENTS, ETC. MAKE
ALL FINAL CONNECTIONS ON ALL HOODS.
3. BALANCED TEMPERED SUPPLY AIR AND EXHAUST AIR IN KITCHEN AREAS TO
CONTAIN COOKING ODORS AND EFFLUENT AND PROVIDE A COMFORTABLE
WORKING ENVIRONMENT. THESE ZONES SHALL BE DESIGNED FOR SLIGHTLY
NEGATIVE PRESSURE PER CODE.
4. INDEPENDENT OF EXHAUST HOOD MAKE-UP AIR PLENUM DIFFUSERS AT A
LOCATION MINIMUM 8’-0” (2.4M) (CASTING NO GREATER THAN 150 FPM VELOCITY) TO
15’-0” (4.6M) (CASTING NO GREATER THAN 300 FPM VELOCITY) AWAY FROM THE
EXHAUST HOOD IN PLAN. 4-WAY CEILING DIFFUSERS SHALL NOT BE UTILIZED IN
ANY COOKING ZONE WITHIN KITCHENS.
5. ALL EXHAUST DUCTWORK SEAMS AND JOINTS MUST BE FULLY-WELDED AND
WATER/GREASE-TIGHT. ALL EXHAUST DUCTS MUST BE PITCHED PER CODES.
ALUMINUM EXHAUST DUCTWORK SHALL NOT BE USED AS DUCTING MATERIAL.
6. ALL FIRE-RATED MATERIALS FOR EXHAUST HOODS, VENT DUCTS, VENT STACKS,
AND HEAT-PRODUCING FOODSERVICE EQUIPMENT.
7. SWITCHES, CONTROLS FOR SUPPLY FANS AND EXHAUST FANS, DEMAND CONTROL
VENTILATION SYSTEMS, AND HVAC COMPONENTS.
8. AUTOMATIC ACTIVATION OF THE EXHAUST HOOD(S) WHENEVER COOKING OCCURS
PER CURRENT INTERNATIONAL MECHANICAL CODE IS THE RESPONSIBILITY OF THE
MECHANICAL ENGINEER OF RECORD. VERIFY SPECIFIC REQUIREMENTS WITH
LOCAL CODE AUTHORITIES.
9. ENSURE THAT ENTIRE KITCHEN EXHAUST SYSTEM FROM EXHAUST HOOD CANOPY
TO FAN IS ASHRAE 90.1 SECTION 5,6,7-COMPLIANT PRIOR TO COMMENCEMENT OF
CONSTRUCTION WHEN AND WHERE APPLICABLE. WHERE DEMAND CONTROL
VENTILATION IS PLANNED, MECHANICAL ENGINEER TO VERIFY THAT VOLUME
DAMPERS AND PEAK-DEMAND LIMITERS IN SIZE AND IN LOCATION ARE PLANNED
AND CONTROLLED TO PROVIDE A FULLY-FUNCTIONAL SYSTEM AT TIME OF
COMMISSIONING AND TURN-OVER.
10. ADDITIONAL AIR CHANGES/HEAT REMOVAL FOR AIR-COOLED AND FOR WATER-
COOLED CONDENSING UNITS AND ICE MACHINES SHALL BE SUPPLIED PER
MANUFACTURER’S RECOMMENDATIONS.
11. AT LEAST 1.5 TIMES ADDITIONAL VS STANDARD ROOM AIR CHANGES SHALL BE
PLANNED WITHIN WARE WASHING ROOMS/ZONES.
12. WHERE DIRECT EXHAUST VENTING IS PERMITTED, PROVIDE A DOUBLE-WALLED
GAS CHIMNEY TO THE ATMOSPHERE AS ALLOWED/REQUIRED BY LOCAL CODE.
ANY FLUE OF EXCESSIVE LENGTH WITH BENDS OR OTHER RESTRICTIONS SHALL
BE PROVIDED WITH A BOOSTER EXHAUST FAN INTERWIRED TO OPERATE WITH
THE EQUIPMENT SERVED. BOOSTER FAN SHALL PROVIDE 0” S.P. AT CONNECTION
TO EQUIPMENT.
M-C.GENERAL CONTRACTOR NOTES
THE ARCHITECT IS RESPONSIBLE FOR SPECIFYING THE FOLLOWING. THE GENERAL
CONTRACTOR IS RESPONSIBLE FOR PROVIDING AND INSTALLING THE FOLLOWING.
1. THE IN-WALL REINFORCING OR WALL BACKING FOR ALL WALL-MOUNTED AND
RECESSED FOODSERVICE EQUIPMENT AND CONTROL PANELS.
2. TROUGH DIMENSIONS AND LOCATIONS ON THIS PLAN ARE FOR USE IN SLAB BLOCK-
OUT PLANNING IF REQUIRED BY CONSTRUCTION SCHEDULE. FINAL SIZE AND
LOCATION TO BE PROVIDED BY KEC WITHIN ISSUED SUBMITTALS.
3. REFER TO MANUFACTURER'S DRAWINGS IN QF701 WALK-IN BOX DETAILS SHEET
SERIES FOR NECESSARY FLOOR CONDITIONS - INCLUDING DEPTHS, FLOOR
CONSTRUCTION, AND FINISHES. ALL SUB-SLAB, SLAB, OR DEPRESSIONS SHALL BE
PROVIDED WITH A SMOOTH AND TRANSIT-LEVEL FINISH. ONCE EQUIPMENT IS SET
IN PLACE, REMAINING DEPRESSION TO BE INFILLED WITH GROUT.
4. MANDATORY FOR ALL WALK-IN FREEZER COMPARTMENTS OVER 600 SQUARE FOOT
AREA(56SM): PROVIDE FREEZE PREVENTION BELOW THE INSULATED FLOOR SLAB
ON GRADE. SUGGESTIONS ARE DRAINAGE/VENTING SYSTEM, HEAT TRACE
SYSTEM, AND/OR REFRIGERATION HEAT GAIN GLYCOL SYSTEM.
5. ALL OPENINGS IN WALLS AS INDICATED ON THIS PLAN.
6. ALL PADS OR CURBS FOR FOODSERVICE EQUIPMENT AND/OR ROOF-MOUNTED
COMPRESSOR RACKS PER MANUFACTURER’S INSTRUCTIONS AND/OR DETAILS
SHOWN IN THIS DOCUMENT SET.
7. ALL HOLES OR SLEEVES THROUGH ROOFS, FLOORS, WALLS, AND CEILINGS AS
REQUIRED FOR THE INSTALLATION OF REFRIGERATION, DRINK, ELECTRICAL, OR
PLUMBING LINES. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR
SEALING HOLES AND SLEEVES AFTER INSTALLATION OF THE LINES TO ENSURE A
VERMIN-PROOF INSTALLATION.
8. WALL(S) AND CEILING, BEHIND, BELOW, AND AROUND TYPE 1 EXHAUST HOOD(S)
SHALL CONFORM TO CURRENT N.F.P.A.- 96 AND ANY OTHER APPLICABLE CODE
DEFINITION IN REGARD TO REQUIRED CLEARANCES TO COMBUSTIBLE, LIMITED, OR
NON-COMBUSTIBLE MATERIALS. ARCHITECT, MECHANICAL ENGINEER, AND KEC TO
VERIFY THAT PLANNED CLEARANCES CONFORM TO CODE PRIOR TO INSTALLATION
OF EXHAUST CANOPY.
9. PROVIDE A TRANSIT-LEVEL FINISH BELOW THIS EQUIPMENT TO THE OUTER EDGE
AS INDICATED IN PLAN.
10. ALL CONDUITS AND ROUTING OF CONDUITS FOR REMOTE REFRIGERATION LINES
AS REQUIRED. ARCHITECT TO ASSIGN SCOPE AND SHOW ROUTING OF CONDUITS
THROUGH BUILDING. CONDUITS SHALL HAVE A SMOOTH INTERIOR FINISH. VERIFY
SIZES WITH KITCHEN EQUIPMENT CONTRACTOR.
11. ALL CONDUITS/CHASES AND ROUTING OF CONDUITS/CHASES FOR BEVERAGE
LINES AS REQUIRED. ARCHITECT TO ASSIGN SCOPE AND SHOW ROUTING OF
CHASES THROUGH BUILDING. CONDUITS/CHASES SHALL HAVE A SMOOTH
INTERIOR FINISH AND MUST BE SEALED WATER-TIGHT. A MINIMUM RADIUS OF 30”
(762 MM) AT ALL BENDS WITH SWEEPS WIDENING AS DIAMETER WIDENS (45-DEGREE
JOINTS ARE NOT ALLOWED). AN ACCESSIBLE PULL BOX/PULL SLEEVE MAY BE
REQUIRED IF OVER 75’-0” (23M) (VERIFY WITH OWNER/OPERATOR’S PURVEYOR) OR
WHERE LOCATED IN FLOORS OR CONCEALED SPACES. THE TOTAL OF ALL BENDS
BETWEEN PULL BOXES NOT TO EXCEED 180 DEGREES. STUB CONDUIT ENDS OUT 4”
(100MM) FROM WALLS, CEILING, OR FINISHED FLOORS. RECOMMENDED CONDUIT
SIZE IS 8” (200MM) DIAMETER FOR BEER, 6” (152MM) DIAMETER MINIMUM FOR
OTHER BEVERAGES. SCHEDULE 40 PVC IS STANDARD FOR UNDER-SLAB
APPLICATIONS, BUT METAL MAY BE REQUIRED ABOVE GRADE AND WITHIN CEILING
PLENUMS. GENERAL CONTRACTOR TO VERIFY MATERIAL TYPE WITH LOCAL CODES
AND REGULATIONS. CONDUIT CHASEWAYS SHALL BE SEALED WITH EXPANDING
FOAM INSULATION AFTER INSTALLATION IS COMPLETE AND COVER TO A SMOOTH
AND CLEANABLE CONDITION. WHERE BEVERAGE CONDUITS ARE REQUIRED TO
RUN EXTERIOR OR OUTSIDE OF A TEMPERATURE-CONTROLLED SPACE, THEY
SHALL BE INSTALLED IN A WEATHER-PROOF AND TEMPERATURE-RESISTANT
MANNER.
12. ALL CONDUITS/CHASES AND ROUTING OF CONDUITS/CHASES FOR BULK CO2 TANK
LINES AS REQUIRED. ARCHITECT TO ASSIGN SCOPE AND SHOW ROUTING OF
CHASE THROUGH BUILDING. CONDUITS SHALL HAVE A SMOOTH INTERIOR FINISH.
VERIFY SIZES WITH OWNER/OPERATOR’S LOCAL GAS (CO2) COMPANY. EXTERIOR
FILL BOX CANNOT BE MORE THAN 50’-0” (15M) FROM DELIVERY TRUCK. TOTAL LINE
RUN FROM BULK CO2 TANK TO EXTERIOR FILL BOX CANNOT BE MORE THAN 50’-0”
(15M). PROVIDE CO2 DETECTOR AT THE BULK CO2. CONDUIT CHASEWAYS SHALL
BE SEALED WITH EXPANDING FOAM INSULATION AFTER INSTALLATION IS
COMPLETE AND COVER TO A SMOOTH AND CLEANABLE CONDITION.
M-D.ADDITIONAL NOTES
FLOOR DEPRESSION
MASONRY PAD
NON-COMBUSTIBLE WALL MATERIAL
(VERIFY REQUIREMENTS with LOCAL CODES)
FINISHED WALL OPENING
WALL BACKING
SUPPLY DUCT
EXHAUST DUCT
DIRECT CONNECT FLUE
AIR MOVEMENT / HEAT REMOVAL
REFER TO INDICATED NOTE
ABOVE FINISHED FLOORAFF
BFF
DOWN FROM ABOVEDFA
BELOW FINISHED FLOOR
BEVERAGE CONDUIT
BC&V Symbol Legend
REFRIGERATION LINE CONNECTION
TAG INDICATING REMOTE
REFRIGERATION LINE
R
ITEM#
TRANSIT - LEVEL FINISH
5325 South Valentia Way, Greenwood Village, CO 80111
Phone 303 221 0500 Fax 303 221 0600
www.ricca.com
Key Plan
It is the responsibility of the Construction
Manager/General Contractor and all
Sub-Contractors to verify all dimensions and
accept conditions of prior work by related
trades before proceeding with any work.
Date
Drawn By
Scale
Seal
Project Title
Project Address
Project Number
Drawing Title and Number
PROJECT
NORTH
Revisions
FO
R
R
E
F
E
R
E
N
C
E
O
N
L
Y
As indicated
C:
\
U
s
e
r
s
\
j
j
u
r
g
e
n
s
\
D
o
c
u
m
e
n
t
s
\
1
9
2
0
1
_
A
s
p
e
n
M
o
u
n
t
a
i
n
C
l
ub
_
F
o
o
d
s
e
r
v
i
c
e
_
R
1
6
_
j
j
u
r
g
e
n
s
@
r
i
c
c
a
.
c
o
m
.
r
v
t
12
/
1
9
/
2
0
1
9
1
0
:
0
1
:
4
5
A
M
Issue Date
Author
Aspen Mountain Club
19201
675 E Durant Ave
Aspen, CO 81611
19201
Foodservice Building
Conditions &
Ventilation Plan
QF401-3
SCALE: 1/4" = 1'-0"1 Foodservice BC&V Plan - Lock Room - Area C
Rev.
No.Description Date
Construction Documents 11/22/19
C2
C2.1
PLUMBING CONTRACTOR
TO INTER-CONNECT WATER
FILTER AND EQUIPMENT
C3
C3.1C3.1 C3.2 PLUMBING CONTRACTOR
TO INTER-CONNECT WATER
FILTER AND EQUIPMENT
C3.3
B.W
B1.W
B1W
3.W 4.W
PLUMBING NOTES
THE NOTES BELOW MAY APPLY TO ONE OR ALL DESIGN, CONSTRUCTION, OR
CLOSE-OUT PHASES OF THIS PROJECT
P-A. GENERAL NOTES
1. THE ASSIGNED KITCHEN EQUIPMENT CONTRACTOR SHALL PERFORM A
THOROUGH PROJECT REVIEW OF ALL CURRENT CONTRACT DOCUMENTS THAT
APPLY TO FOODSERVICE ZONES AND EQUIPMENT. KITCHEN EQUIPMENT
CONTRACTOR SHALL GENERATE ENGINEERING INDEPENDENT OF THIS SHEET
CONFORMING TO FIELD CONDITIONS WHERE REQUIRED AND MANUFACTURER’S
REQUIREMENTS FOR EQUIPMENT SPECIFIED AND THUS INTENDED TO BE
PURCHASED AND SET-IN-PLACE.
2. ALL PLUMBING WORK SHOWN ON THIS PLAN MUST COMPLY WITH ALL APPLICABLE
CODES AND REGULATIONS AS THEY APPLY TO FOODSERVICE EQUIPMENT AND
ZONES.
3. ALL WORK SERVICES, INTERCONNECTIONS, FIELD CONNECTIONS, AND FINAL
CONNECTIONS INDICATED ON THIS PLAN SHALL BE COMPLETED BY
CONTRACTORS OTHER THAN THE KITCHEN EQUIPMENT CONTRACTOR UNLESS
SPECIFICALLY ASSIGNED TO THE KITCHEN EQUIPMENT CONTRACTOR.
4. THIS PLAN IS INTENDED TO SHOW PLUMBING REQUIREMENTS FOR FOODSERVICE
EQUIPMENT ONLY. REFER TO ARCHITECTURAL/ENGINEERING PLANS FOR SCOPE
OUTSIDE OF FOODSERVICE EQUIPMENT.
5. THIS DRAWING IS ISSUED FOR DESIGN INTENT PURPOSES ONLY. REFER TO THE
KITCHEN EQUIPMENT CONTRACTOR’S DIMENSIONED ROUGH-IN DRAWINGS AND
APPROVED SHOP DRAWINGS FOR SUPPLEMENTAL COORDINATION AND
INSTALLATION REQUIREMENTS FOR FOODSERVICE EQUIPMENT ON THIS PLAN.
6. ALL EQUIPMENT PROVIDED BY OTHERS -INCLUDING BY
OWNER/OPERATOR/PURVEYOR- SHOWN ON THIS PLAN ARE MINIMUM GUIDELINES
ONLY. VERIFY INFORMATION, TECHNICAL DATA, AND SPECIFICATIONS FOR THIS
EQUIPMENT. GENERAL CONTRACTOR TO VERIFY AND MAKE FINAL ROUGH-IN
CONNECTIONS AS REQUIRED.
7. EXISTING, TO-REMAIN-IN-PLACE, OR TO-BE-RELOCATED EQUIPMENT SHOWN ON
THIS PLAN ARE MINIMUM GUIDELINES ONLY AND MUST BE VERIFIED. CONTACT
OWNER/OPERATOR FOR INFORMATION, TECHNICAL DATA, AND SPECIFICATIONS
FOR THIS EQUIPMENT. GENERAL CONTRACTOR TO VERIFY, DISCONNECT, AND
MAKE FINAL ROUGH-IN CONNECTIONS AS REQUIRED.
8. GENERAL CONTRACTOR TO VERIFY, DISCONNECT, AND MAKE FINAL ROUGH-IN
CONNECTIONS AS REQUIRED.
P-B. PLUMBING NOTES
PLUMBING ENGINEER IS RESPONSIBLE FOR SPECIFYING THE FOLLOWING. PLUMBING
CONTRACTOR IS RESPONSIBLE FOR PROVIDING, INSTALLING, AND MAKING FINAL
CONNECTIONS TO FOODSERVICE EQUIPMENT AND SHALL PROVIDE THE FOLLOWING.
1. DRAIN-LINES, FITTINGS, VALVES, AND ALL PLUMBING COMPONENTS SERVICING
FOODSERVICE EQUIPMENT SHALL BE CAPABLE TO WITHSTAND HOT WATER
TEMPERATURES MORE THAN 140-200 DEGREES FAHRENHEIT, DRAIN
TEMPERATURES OF 130 DEGREES FAHRENHEIT TO BOILING (SOMETIMES UNDER
PRESSURE), AND STEAM (IF APPLICABLE) TEMPERATURES AS PER DESIGN
PRESSURES. PROVIDE MINIMUM 6’-0” (1.8M) LENGTH CAST IRON PIPING FROM
FLOOR SINKS TO WITHSTAND HOT WATER TEMPERATURES.
2. PRESSURE-REDUCING OR REGULATING VALVES, FAUCETS AND WATER INLETS,
IN-LINE WATER FILTERS, VACUUM BREAKERS, BACKFLOW PREVENTERS,
ANTI-SCALD VALVES, STAINLESS STEEL DOUBLE CHECK VALVES FOR SODA SYSTEM,
ETC. NOT OTHERWISE SUPPLIED TO FOODSERVICE EQUIPMENT AS REQUIRED BY
LOCAL CODES AND MANUFACTURER’S SPECIFICATIONS.
3. WASTE LINES, DIRECT AND INDIRECT, TO BE PITCHED DOWNWARD AND TO HAVE
ADEQUATE CLEAN-OUT PROVISIONS PER CODE.
4. FLOOR SINKS SHOULD BE SPECIFIED AND INSTALLED WITH TOP GRATES AND
REMOVABLE SEDIMENT BUCKET INCLUDED. FLOOR SINK TOP TO BE SET FLUSH
WITH FINISHED FLOOR UNLESS DIRECTED OTHERWISE BY LOCAL CODE. PROVIDE
ACID-RESISTANT FLOOR SINKS FOR EQUIPMENT THAT DISCHARGES CO2 (I.E.
SODA AND WATER DISPENSERS). VERIFY COMPLIANCE WITH LOCAL CODES AND
REGULATIONS.
5. AREA FLOOR DRAINS IN QUANTITY AND PROPOSED LOCATION AS COORDINATED
WITH OWNER/OPERATOR. SLOPE FLOORS TO AREA DRAINS AT MINIMUM OF 1/16”
(.40MM) PER FOOT (304MM) WITHIN A 6’ (1.8M) RADIUS OR PER LOCAL CODE.
6. GREASE TRAPS, INCLUDING SIZING, AS REQUIRED. INSTALL GREASE TRAPS
OUTSIDE OF BUILDING WHENEVER POSSIBLE. INSTALLATION WITHIN THE BUILDING
MUST COMPLY WITH LOCAL CODES AND REGULATIONS. NOTIFY RICCA DESIGN
STUDIOS WHEN INSTALLATION MUST BE WITHIN ANY KITCHEN AREAS OR
FOODSERVICE ZONES.
7. PROVIDE AND INSTALL INDIRECT DRAIN LINE FROM WALK-IN OR ROOM COOLING
EVAPORATOR COILS TO ASSIGNED FLOOR SINK. DRAIN LINES TO BE P-TRAPPED AT
EJECTION POINT OUTSIDE OF COLD ZONE. DRAIN LINES WITHIN FREEZER CAVITIES
TO BE INSULATED AND WRAPPED WITH HEAT TAPE PROVIDED BY E.C.
8. NOTES CONCERNING PLUMBING ROUGH-INS:
A. FURNISH AND INSTALL ALL WATER, WASTE, GAS, AND STEAM LINES AND SIZE
SERVICE LINES TO PROVIDE FULL-FLOW VOLUME FOR ALL EQUIPMENT
SUPPLIED BY RESPECTIVE MAINS AND BRANCHES. PROVIDE BRASS BALL
VALVE (MINIMUM) STOP VALVES AND TAG ROUGH-INS WITH THE APPROPRIATE
IDENTIFYING LABELS. SERVICE LINES STUBBED OUT OF WALLS, UP FROM
FINISHED FLOORS, OR A CONCRETE CURB A MINIMUM OF 2” (50MM). VENT
PIPES MUST BE CONCEALED IN WALLS OR COLUMN CHASE. USE A LOOP-VENT
OR AIR GAP ASSEMBLY FOR ISLAND FIXTURES. ALL FLOOR PENETRATIONS
MUST BE SEALED WATERTIGHT.
B. WASTE LINES SHOWN ARE DESIGNED TO COMPLY WITH THE BEST KNOWN AND
GENERALLY-ACCEPTED HEALTH AND SANITARY CONDITIONS AND CODES.
PLUMB LINES TO ENSURE NO INTERFERENCE WITH THE INTENDED USE OR
SERVICING OF FOODSERVICE EQUIPMENT. RUN LINES BELOW EQUIPMENT AT
THE HIGHEST POSSIBLE ELEVATION ABOVE FINISHED FLOOR. NO LINES ARE TO
LAY ON OR BE SECURED TO THE FLOOR. FIELD-CUTTING OF ANY
FOODSERVICE EQUIPMENT TO MAKE WAY FOR WASTE LINES WITHOUT
CONSENT OF KITCHEN EQUIPMENT CONTRACTOR IS PROHIBITED.
C. SUPPLY 140-DEGREE FAHRENHEIT HOT WATER TO ALL WAREWASHING
EQUIPMENT, 105-DEGREE FAHRENHEIT HOT WATER TO HAND-WASH SINKS AND
120-DEGREE FAHRENHEIT HOT WATER TO ALL OTHER EQUIPMENT UNLESS
OTHERWISE INSTRUCTED BY CODE. INSULATE WATER AND STEAM LINES (IF
REQUIRED) TO CONFORM WITH ACCEPTED PRACTICE. EXPOSED PIPES AND
FITTINGS ABOVE A WORKING HEIGHT OF 34” (863MM) ABOVE FINISHED
FLOOR SHALL BE CHROME-PLATED OR COVERED WITH A STAINLESS-STEEL
SLEEVE.
D. SIZE FUEL GAS SERVICE LINES TO PROVIDE THE REQUIRED BTU RATING
INDICATED FOR THE EQUIPMENT, AT A LOW PRESSURE OF APPROXIMATELY 7”
TO 9” WATER COLUMN. INSTALL AUTOMATIC MECHANICAL SHUT-OFF VALVES -
FURNISHED BY FIRE SUPPRESSION SYSTEM CONTRACTOR - IN GAS SUPPLY
LINES TO EQUIPMENT UNDER EXHAUST HOOD ASSEMBLIES.
E. PROVIDE CHILLED WATER (OR CONDENSER WATER) TO AND FROM
COMPRESSOR FROM COOLING TOWER (OR BUILDING’S CONDENSER SYSTEM)
AS SHOWN. PROVIDE RICCA DESIGN STUDIOS WITH CHILLED WATER
TEMPERATURE TO PROPERLY ENGINEER REFRIGERATION EQUIPMENT.
CHILLED WATER PRESSURE SHALL BE PROVIDED AT NO GREATER THAN
150 PSI.
9. NOTES CONCERNING PLUMBING CONNECTIONS:
A. ALL WATER, GAS, AND STEAM (WHERE APPLICABLE) SERVICES FOR PORTABLE
AND COUNTERTOP EQUIPMENT MUST BE CONNECTED TO THE EQUIPMENT
WITH A COMMERCIAL TYPE FLEXIBLE HOSE AND QUICK DISCONNECT
FITTINGS TO MEET A.G.A. APPROVAL FOR COMMERCIAL KITCHEN EQUIPMENT.
B. WATER PROVIDED FOR STEAM-PRODUCING EQUIPMENT MUST HAVE A WATER
HARDNESS NO GREATER THAN 2.0 GRAINS AND A PH LEVEL BETWEEN 7.0
AND 7.5.
C. WATER USED FOR COOLING WATER TO CONDENSING UNITS OR
COMPRESSORS MUST BE TREATED TO INHIBIT THE FORMATION OF
DEPOSITS IN THE CONDENSING TUBES.
D. STEAM (WHERE APPLICABLE) THAT COMES IN DIRECT CONTACT WITH FOOD,
FOOD HOLDING EQUIPMENT, OR WAREWASHING EQUIPMENT MUST BE
POTABLE STEAM.
E. INTERPIPE HOT WATER SUPPLY LINES BETWEEN BOOSTER HEATER AND
WAREWASHING EQUIPMENT WHEN SPECIFIED SEPARATELY. LINES SHALL BE
INSULATED THE LENGTH OF THE LINE-RUN.
F. INTERPIPE WATER LINES BETWEEN WATER WASH VENTILATOR ASSEMBLIES
AND CONTROL PANELS. SUPPLY A MINIMUM OF 140-DEGREE FAHRENHEIT
HOT WATER AT CONTROL PANEL. LINES SHALL BE INSULATED THE LENGTH
OF THE LINE-RUN. REFER TO MANUFACTURER DRAWINGS FOR EXACT
REQUIREMENTS.
G. INTERPIPE CENTRALIZED WASTE GREASE PLUMBING LINE FROM
PUMPING/COLLECTION STATION TO GREASE WASTE COLLECTION TANK
IN PITCHED MANNER PER MANUFACTURER’S DIRECTION. PROVIDE HEAT
TRACE CABLE/TAPE ON LINE-RUN WHERE AMBIENT AIR TEMPERATURE
ALONG LINE- RUN IS BELOW 70 DEGRESS FAHRENHEIT. HEAT TRACE
CABLE/TAPE SHALL BE PROVIDED BY E.C.
H. WASTE CONNECTIONS FOR INDIVIDUAL SECTIONS OF WATER WASH
VENTILATORS TO A MAIN DRAIN CONNECTION. REFER TO MANUFACTURER’S
DRAWINGS FOR EXACT REQUIREMENTS.
I. INSTALL IN-LINE WATER FILTERS AS WELL AS INCOMING AND OUTGOING
LINES AS FURNISHED BY KITCHEN EQUIPMENT CONTRACTOR.
J. WATER PIPES BETWEEN THE BACKFLOW PREVENTER AND WATER FILTERS
SHALL BE STAINLESS STEEL, NOT COPPER OR ALLOYS CONTAINING COPPER
(SUCH AS BRASS).
9. NOTES CONCERNING PLUMBING CONNECTIONS:
K. WATER PIPES BETWEEN THE BACKFLOW PREVENTER AND WATER FILTER AT
SODA SYSTEM CARBONATOR SHALL BE STAINLESS STEEL - NOT COPPER OR
ALLOYS CONTAINING COPPER (SUCH AS BRASS). DRAIN PIPE AT SODA
DISPENSERS SHALL BE STAINLESS STEEL OR PLASTIC PIPE WASTE LINE
UNTIL A POINT WHERE THE WASTE HAS BEEN DILUTED BY AN UPSTREAM
FIXTURE.
L INTERCONNECT FOOD WASTE SYSTEMS PER MANUFACTURER’S DRAWINGS.
M. EQUIPMENT THAT IS CONNECTED TO POTABLE WATER AND UTILIZES
AUTOMATICALLY DISPENSED CHEMICALS FOR CLEANING SHALL HAVE AN
ACCESSIBLE BACK FLOW PREVENTION DEVICE INSTALLED.
N. DRAIN LINES FROM ICE BINS ARE TO BE INSULATED THE ENTIRE LINE-RUN
TO FLOOR SINK.
P-C. ADDITIONAL NOTES
REFER TO INDICATED NOTE
AREA FLOOR DRAIN (FD)
FLOOR SINK AND GRATE (FS)
HOSE BIBB, HOT and COLD WATER
with MIXING VALVE and VACUUM BREAKER
HOSE BIBB, HOT or COLD WATER
STEAM CONDENSATE RETURN
ROUGH-IN and CONNECTION
STEAM SUPPLY
ROUGH-IN and CONNECTION
FUEL GAS
ROUGH-IN and CONNECTION
DIRECT WASTE (DW)
ROUGH-IN and CONNECTION
INDIRECT WASTE (IW)
HOT / COLD WATER
ROUGH-IN and CONNECTION
ABOVE FINISHED FLOORAFF
BELOW FINISHED FLOORBFF
BRANCH TO CONNECTIONBTC
DOWN FROM ABOVEDFA
COOLING WATER SUPPLY
ROUGH-IN and CONNECTION
FD
Plumbing Symbol Legend
CS
COOLING WATER RETURN
ROUGH-IN and CONNECTIONCR
5325 South Valentia Way, Greenwood Village, CO 80111
Phone 303 221 0500 Fax 303 221 0600
www.ricca.com
Key Plan
It is the responsibility of the Construction
Manager/General Contractor and all
Sub-Contractors to verify all dimensions and
accept conditions of prior work by related
trades before proceeding with any work.
Date
Drawn By
Scale
Seal
Project Title
Project Address
Project Number
Drawing Title and Number
PROJECT
NORTH
Revisions
FO
R
R
E
F
E
R
E
N
C
E
O
N
L
Y
As indicated
C:
\
U
s
e
r
s
\
j
j
u
r
g
e
n
s
\
D
o
c
u
m
e
n
t
s
\
1
9
2
0
1
_
A
s
p
e
n
M
o
u
n
t
a
i
n
C
l
ub
_
F
o
o
d
s
e
r
v
i
c
e
_
R
1
6
_
j
j
u
r
g
e
n
s
@
r
i
c
c
a
.
c
o
m
.
r
v
t
12
/
1
9
/
2
0
1
9
1
0
:
0
1
:
4
8
A
M
Issue Date
Author
Aspen Mountain Club
19201
675 E Durant Ave
Aspen, CO 81611
19201
Foodservice Plumbing
Plan
QF401-4
SCALE: 1/4" = 1'-0"1 Foodservice Plumbing Plan - Lock Room - Area C
Rev.
No.Description Date
Construction Documents 11/22/19
J
C2
C3.1
B.W
B1.W
B1W
3.W 4.W
C1
ELECTRICAL NOTES
THE NOTES BELOW MAY APPLY TO ONE OR ALL DESIGN, CONSTRUCTION, OR
CLOSE-OUT PHASES OF THIS PROJECT
E-A. GENERAL NOTES
1. THE ASSIGNED KITCHEN EQUIPMENT CONTRACTOR SHALL PERFORM A THOROUGH
PROJECT REVIEW OF ALL CURRENT CONTRACT DOCUMENTS THAT APPLY TO
FOODSERVICE ZONES AND EQUIPMENT. KITCHEN EQUIPMENT CONTRACTOR SHALL
GENERATE ENGINEERING INDEPENDENT OF THIS SHEET CONFORMING TO FIELD
CONDITIONS WHERE REQUIRED AND MANUFACTURER’S REQUIREMENTS FOR
EQUIPMENT SPECIFIED AND THUS INTENDED TO BE PURCHASED AND SET-IN-PLACE.
2. ALL ELECTRICAL WORK SHOWN ON THIS PLAN MUST COMPLY WITH ALL APPLICABLE
CODES AND REGULATIONS AS THEY APPLY TO FOODSERVICE EQUIPMENT
AND ZONES.
3. ALL WORK SERVICES, INTERCONNECTIONS, FIELD CONNECTIONS, AND FINAL
CONNECTIONS INDICATED ON THIS PLAN SHALL BE COMPLETED BY CONTRACTORS
OTHER THAN THE KITCHEN EQUIPMENT CONTRACTOR UNLESS SPECIFICALLY
ASSIGNED TO THE KITCHEN EQUIPMENT CONTRACTOR.
4. THIS PLAN IS INTENDED TO SHOW ELECTRICAL REQUIREMENTS FOR FOODSERVICE
EQUIPMENT ONLY. ELECTRICAL INFORMATION IS BASED ON A 60 HERTZ ELECTRICAL
SYSTEM AND IS INTENDED TO SHOW FOODSERVICE FIXTURES AND EQUIPMENT
RECEPTACLE TYPES, LOCATIONS, LOADS, AND CONNECTION POSITIONS ONLY.
FURNISH ANY ADDITIONAL RECEPTACLES AS REQUIRED BY LOCAL CODES OR AS
REQUESTED BY OWNER. REFER TO ARCHITECTURAL/ENGINEERING PLANS FOR
SCOPE OUTSIDE OF FOODSERVICE EQUIPMENT.
5. THIS DRAWING IS ISSUED FOR DESIGN INTENT PURPOSES ONLY. REFER TO THE
KITCHEN EQUIPMENT CONTRACTOR’S DIMENSIONED ROUGH-IN DRAWINGS AND
APPROVED SHOP DRAWINGS FOR SUPPLEMENTAL COORDINATION AND
INSTALLATION REQUIREMENTS FOR FOODSERVICE EQUIPMENT ON THIS PLAN.
6. ALL EQUIPMENT PROVIDED BY OTHERS -INCLUDING BY OWNER/OPERATOR/
PURVEYOR- SHOWN ON THIS PLAN ARE MINIMUM GUIDELINES ONLY. VERIFY
INFORMATION, TECHNICAL DATA, AND SPECIFICATIONS FOR THIS EQUIPMENT.
GENERAL CONTRACTOR AND KITCHEN EQUIPMENT CONTRACTOR TO VERIFY AND
MAKE FINAL ROUGH-IN CONNECTIONS AS REQUIRED.
7. EXISTING, TO-REMAIN-IN-PLACE, OR TO-BE-RELOCATED EQUIPMENT SHOWN ON
THIS PLAN ARE MINIMUM GUIDELINES ONLY AND MUST BE VERIFIED. CONTACT
OWNER/OPERATOR FOR INFORMATION, TECHNICAL DATA, AND SPECIFICATIONS
FOR THIS EQUIPMENT. GENERAL CONTRACTOR TO VERIFY, DISCONNECT, AND MAKE
FINAL ROUGH-IN CONNECTIONS AS REQUIRED.
8. ENGINEERS SHALL PROVIDE AT LEAST 15% ADDITIONAL POWER THAN THE MINIMUM
REQUIRED WITHIN KITCHEN/CULINARY ZONES FOR CURRENT OR FUTURE
EQUIPMENT NEEDS.
9. ANY EXPOSED LOCATION SERVICE STUBBED UP OUT OF THE FLOOR MUST BE
PROTECTED AND INSTALLED IN A MANNER THAT WILL PREVENT DAMAGE FROM
WATER OR BY COLLISION WITH PORTABLE KITCHEN EQUIPMENT, HEAVILY-LOADED
CARTS, OR FLOOR CLEANING EQUIPMENT.
10. PRIOR TO THE INSTALLATION OF FOODSERVICE EQUIPMENT, THE KITCHEN
EQUIPMENT CONTRACTOR MUST CONFIRM THAT ELECTRICAL WIRING HAS BEEN
PULLED THROUGH JUNCTION BOXES AND THAT LIGHTING FIXTURES ARE WORKING.
E-B. ELECTRICAL NOTES
ELECTRICAL ENGINEER IS RESPONSIBLE FOR SPECIFYING THE FOLLOWING. ELECTRICAL
CONTRACTOR IS RESPONSIBLE FOR PROVIDING, INSTALLING, AND MAKING FINAL
CONNECTIONS TO FOODSERVICE EQUIPMENT AND SHALL PROVIDE THE FOLLOWING.
1. ALL WIRING, WIRING CONDUITS, JUNCTION BOXES, ELECTRICAL RECEPTACLES,
SWITCHES, COVER PLATES, PLUG MOLDING, ETC. AS SHOWN ON PLAN AND NOT
PROVIDED BY OTHERS. RUN ALL OF THE ELECTRICAL SERVICE LINES IN WALLS OR
CONCEALED WHEREVER POSSIBLE. ALL EXPOSED SERVICES, COMPONENTS, AND
CONNECTIONS SHALL BE VAPOR AND WATER-TIGHT.
2. ALL DISCONNECTS OR OTHER DEVICES AS REQUIRED BY LOCAL CODES. DO NOT
LOCATE DISCONNECTS OR OTHER DEVICES (OTHER THAN JUNCTION BOX
CONNECTIONS OR CORD & PLUG RECEPTACLES) BEHIND COOKING EQUIPMENT
OR BELOW EXHAUST HOOD ASSEMBLIES.
3. ALL SHUNT-TRIP CIRCUIT BREAKERS OR DISCONNECTIONS FOR FIRE SUPPRESSION
SYSTEM SHUT-OFF OF ALL ELECTRICAL BELOW AND IN EXHAUST HOODS
INTERWIRED WITH FIRE SUPPRESSION AS REQUIRED BY N.F.P.A. STANDARDS.
4. ALL RECEPTACLES, CORD & PLUG ASSEMBLIES TO BE NEMA-SIZED, UL-APPROVED,
AND RATED FOR THE SERVICE INDICATED ON THESE PLANS. PROVIDE GFCI
RECEPTACLES AS REQUIRED BY THE NEC AND LOCAL CODES. ENSURE THAT GFCI
RECEPTACLES AND NOT BREAKERS-ONLY ARE ALLOWED FOR APPLICABLE
FOODSERVICE EQUIPMENT.
5. AT ALL WALK-IN COOLER/FREEZER LOCATIONS SHOWN ON THIS PLAN:
A. ALL VAPOR-PROOF LIGHT FIXTURES, AS PROVIDED BY KITCHEN EQUIPMENT
CONTRACTOR.
B. ALL DISCONNECTS AND SWITCHES AT BLOWER COILS.
C. ALL VAPOR-PROOF DUPLEX CONVENIENCE RECEPTACLES AS INDICATED ON
THIS PLAN.
D. ALL INTERCONNECTIONS FOR ELECTRICAL COMPONENTS IN THE WALK-IN
COOLER/FREEZER COMPARTMENTS.
E. ALL INTERCONNECTIONS AND SWITCHES FOR FREEZER EVAPORATORS AND
COMPRESSORS.
F. VERIFY EXACT WIRE SIZES WITH MANUFACTURERS SPECIFICATIONS. KITCHEN
EQUIPMENT CONTRACTOR TO PROVIDE WIRING DIAGRAM FOR ALL WIRING
REQUIRED FOR WALK-IN COOLER/FREEZER COMPARTMENTS.
6. ALL WIRING AND CONDUITS INTO WALK-IN COOLER/FREEZER COMPARTMENTS FOR
THE FOLLOWING:
A. EACH EVAPORATOR COIL
B. EACH VAPOR-PROOF CEILING LIGHT
C. EACH PERSONNEL ALARM SWITCH AND LIGHT
D. EACH DOOR HEATER AND ANY FREEZER COIL DRAIN HEATERS REQUIRED
E. EACH HIGH-TEMPERATURE WARNING ALARM SYSTEM
ALL PENETRATIONS MUST BE MADE THROUGH THE CEILING INSULATION AND ARE
REQUIRED TO BE VAPOR-TIGHT. ALL CONDUIT TO RUN ABOVE THE WALK-IN
COMPARTMENTS. INSTALLATION OF CONDUIT LINE-RUNS INSIDE OF WALK-IN
COMPARTMENTS IS PROHIBITED.
7. ALL WIRING TO AND INTERWIRING BETWEEN EXHAUST HOOD COMPONENTS.
INCLUDING, BUT NOT LIMITED TO: CONTROL SYSTEMS AND WIRING, DAMPERS,
SOLENOIDS, LIGHTS, VFDS, FIRE SUPPRESSION SYSTEMS, BUILDING MANAGEMENT
SYSTEM, ETC. AS SHOWN ON MANUFACTURER’S DRAWINGS AND ON MECHANICAL
ENGINEER’S DRAWINGS.
8. SWITCHES/CONTROLS FOR EXHAUST HOODS, EXHAUST FANS, SUPPLY FANS,
MAKEUP FANS, AND HVAC COMPONENTS AS SPECIFIED BY THE MECHANICAL
ENGINEER.
9. ALL REQUIRED MATERIALS TO MAKE FINAL CONNECTIONS TO ALL FOODSERVICE
EQUIPMENT SHOWN ON THIS PLAN.
10. FOR FLOOR PENETRATION ROUGH-INS, UTILIZE A SINGLE CONDUIT STUB-UP FOR
MULTIPLE CIRCUITS WHEREVER POSSIBLE.
11. FLOOR RECEPTACLES IN FRONT-OF-HOUSE, NON-KITCHEN AREAS, BUT UTILIZED BY
SERVICE TEAM, SHOULD BE VAPOR-PROOF FLUSH TYPE, UNLESS OTHERWISE
NOTED. NO FLUSH TYPE RECEPTACLES SHALL BE INSTALLED IN KITCHEN AREAS.
12. INTERCONNECT/INTERWIRE FOOD WASTE SYSTEM CONTROL PANEL WITH FOOD
WASTE SYSTEM COMPONENTS AS SHOWN ON MANUFACTURER’S DRAWINGS.
13. WHERE INDICATED, THIS COUNTER OR TABLE WILL BE PROVIDED BY THE KITCHEN
EQUIPMENT CONTRACTOR COMPLETELY PRE-WIRED WITH A BUILT-IN CIRCUIT
BREAKER MINI-PANEL/LOAD CENTER- SIZED AS SPECIFIED BY THE ELECTRICAL
ENGINEER- PER THE INDIVIDUAL EQUIPMENT REQUIREMENTS NOTED ON THE
PLANS AND SCHEDULES. ALL FINAL CONNECTIONS, INCLUDING INTERWIRING
BETWEEN COUNTER SEGMENTS, TO BE MADE BY THE ELECTRICAL CONTRACTOR.
DATA LINE RUNS SHALL BE SEPARATE FROM ELECTRICAL CONDUIT AND TERMINATE
WITHIN DATA PULL BOX. DATA LINE RUNS AND FINAL DATA CONNECTIONS BY
ELECTRICAL CONTRACTOR.
14. WHERE INDICATED, THIS COUNTER OR TABLE WILL BE PROVIDED BY THE KITCHEN
EQUIPMENT CONTRACTOR COMPLETELY PRE-WIRED TO A BUILT-IN ACCESSIBLE
PULL BOX, WITH PIGTAILS TAGGED WITH THE REQUIREMENTS AND IDENTIFICATION
OF THE EQUIPMENT THEY SERVE. ELECTRICAL COMPONENTS PRE-WIRED TO THIS
PULL BOX ARE AS NOTED ON THE PLANS AND SCHEDULES. ALL FINAL
CONNECTIONS, INCLUDING INTERWIRING BETWEEN COUNTER SEGMENTS, TO BE
MADE BY THE ELECTRICAL CONTRACTOR. DATA LINE RUNS SHALL BE SEPARATE
FROM ELECTRICAL CONDUIT AND TERMINATE WITHIN DATA PULL BOX. DATA LINE
RUNS AND FINAL DATA CONNECTIONS BY ELECTRICAL CONTRACTOR.
15. WHERE INDICATED, THIS COUNTER OR TABLE WILL BE PROVIDED BY THE GENERAL
CONTRACTOR COMPLETELY PRE-WIRED TO A BUILT-IN ACCESSIBLE PULL BOX, WITH
PIGTAILS TAGGED WITH THE REQUIREMENTS AND IDENTIFICATION OF THE
EQUIPMENT THEY SERVE. ELECTRICAL COMPONENTS PRE-WIRED TO THIS PULL
BOX ARE AS NOTED ON THE PLANS AND SCHEDULES. ALL FINAL CONNECTIONS,
INCLUDING INTERWIRING BETWEEN COUNTER SEGMENTS, TO BE MADE BY THE
ELECTRICAL CONTRACTOR. DATA LINE RUNS SHALL BE SEPARATE FROM
ELECTRICAL CONDUIT AND TERMINATE WITHIN DATA PULL BOX. DATA LINE RUNS
AND FINAL DATA CONNECTIONS BY ELECTRICAL CONTRACTOR.
16. CEILING-MOUNTED RETRACTABLE DROP CORD ASSEMBLY IN LOCATIONS SHOWN
ON PLANS AND ELEVATIONS. RETRACTED CORD HEIGHT TO BE 6'-6" (2M) ABOVE
FINISHED FLOOR. OVERALL CORD LENGTH NOT TO EXCEED FINISHED FLOOR TO
FINISHED CEILING HEIGHT. E.C. TO PROVIDE CONCEALED UNI-STRUT REINFORCED
SUPPORT TO STRUCTURE FOR DROP CORD OR RETRACTABLE CORD ASSEMBLY.
E-C. ADDITIONAL NOTES
JUNCTION BOX (JB)
with FINAL CONNECTIONS to EQUIPMENT
DUPLEX RECEPTACLE (DR)
POWER RECEPTACLE, 1 PHASE
POWER RECEPTACLE, 3 PHASE
CONDUIT STUB
with FINAL CONNECTIONS to EQUIPMENT
FLOOR RECEPTACLE, FLUSH OR PEDESTAL MOUNTED
DROP RECEPTACLE - CORD (DRC)
VAPOR-PROOF LIGHT FIXTURE
SWITCH (SW)
REFER TO INDICATED NOTE
PLUG MOULDING
PRE-WIRED BREAKER PANEL INSTALLED in
EQUIPMENT (by KEC or MANUFACTURER)
LOW TEMP. LED LIGHT FIXTURE
ABOVE FINISHED FLOORAFF
BELOW FINISHED FLOORBFF
BRANCH TO CONNECTIONBTC
DOWN FROM ABOVEDFA
DATA
Electrical Symbol Legend
DROP RECEPTACLE - REEL (DRR)
D
DRR
J
V
PB PULL BOX INSTALLED in EQUIPMENT
(by KEC or MANUFACTURER)
DUPLEX CONVENIENCE RECEPTACLE (DCR)
TAG INDICATING DEVICE INSTALLED in
EQUIPMENT (by KEC or MANUFACTURER)
5325 South Valentia Way, Greenwood Village, CO 80111
Phone 303 221 0500 Fax 303 221 0600
www.ricca.com
Key Plan
It is the responsibility of the Construction
Manager/General Contractor and all
Sub-Contractors to verify all dimensions and
accept conditions of prior work by related
trades before proceeding with any work.
Date
Drawn By
Scale
Seal
Project Title
Project Address
Project Number
Drawing Title and Number
PROJECT
NORTH
Revisions
FO
R
R
E
F
E
R
E
N
C
E
O
N
L
Y
As indicated
C:
\
U
s
e
r
s
\
j
j
u
r
g
e
n
s
\
D
o
c
u
m
e
n
t
s
\
1
9
2
0
1
_
A
s
p
e
n
M
o
u
n
t
a
i
n
C
l
ub
_
F
o
o
d
s
e
r
v
i
c
e
_
R
1
6
_
j
j
u
r
g
e
n
s
@
r
i
c
c
a
.
c
o
m
.
r
v
t
12
/
1
9
/
2
0
1
9
1
0
:
0
1
:
5
1
A
M
Issue Date
Author
Aspen Mountain Club
19201
675 E Durant Ave
Aspen, CO 81611
19201
Foodservice Electrical
Plan
QF401-5
SCALE: 1/4" = 1'-0"1 Foodservice Electrical Plan - Lock Room - Area C
Rev.
No.Description Date
Construction Documents 11/22/19