HomeMy WebLinkAboutFile Documents.506 E Main St.0054.2019 (18).ACBK 1 CR A F T B A L A N C E WH I M S Y 30 3 2 7 8 4 3 7 8 7 1 5 F O U R T E E N T H S T R E E T , G O L D E N , C O 8 0 4 01 AN D A R C H . C O M Building Permit Comment Responses Date: 2019.08.14 Project Name: 2017910 Pitkin County Courthouse Remodel 506 East Main Street, Aspen, Colorado Permit Number: 0054.2019.ACBK Code: 2015 IEBC, IBC Reviewer: Bonnie Muhigirwa Plans Examiner Community Development 2019.05.29 Mechanical pdf: M0.1 Mechanical Legend and Notes Thermostat heights to comply with reach ranges in ICC A117.1-2009.308 Response: Sheet M0.1, Mechanical Note, III Execution note C has been updated with the following language, “Thermostats shall be mounted at a maximum of 48” above finished floor to the top of the thermostat.” Per ICCA117.1-2009.308 2019.05.29 Pitkin Permit Electrical: ED1.0 Garden Level Electrical Plan 620.22, Branch Circuits for car lighting receptacle(s) ventilation, heating and air conditioning (A) Car light source. A separate branch circuit shall supply the car lights, receptacle(s) auxiliary lighting power source and ventilation on each elevator car. The over current device protecting the branch circuit shall be located in the elevator machine room or control room/machinery space or control space. Required lighting shall not be connected to the load side of the ground fault circuit interrupter. Response: Keynote #4, Sheet ED1.0 and keynote#17, Sheet E1.0 have been revised asking the contractor to verify the existing elevator cab lights are on a dedicated circuit to comply with NEC 620.22 (A). 2019.06.14 Pitkin Permit – Architectural: A1.0 Garden Level Floor Plan Per the code summary on G0.4, the occupant load in the garden level courtroom exceeds 50, correct the door swing so that the doors swing in the direction of egress travel per 2015 IEBC 805.4.2 08/21/2019 CR A F T B A L A N C E WH I M S Y 30 3 2 7 8 4 3 7 8 7 1 5 F O U R T E E N T H S T R E E T , G O L D E N , C O 8 0 4 01 AN D A R C H . C O M AN D E R S O N H A L L A S A R C H I T E C T S 2 Response: Courtroom 3 occupancy was calculated per the 2015IBC, Table 1004.1.2 Courtroom 40sf net per occupant Room Area load factor occupant load Courtroom 1,244sf 40sf per occ 32 total occupants Sheet A1.0 door swing from Court Room 3 remains unchanged. Sheet G.04 has been revised 2019.06.14 Pitkin Permit – Architectural: A1.0 Garden Level Floor Plan Per 2015 IEBC 705, 705.2, this alteration affects the area of primary function and therefore the toilet facilities serving the area of primary function shall be accessible to the maximum extent possible that is technically feasible. Revise door widths to provide clear openings widths of 32 inches minimum. Provide an accessible route toilet compartment, grab bars and under counter pipe protection in the men’s restroom. Response: No work is associated with Women’s Room 00C or Men’s Room 00D. Graphically, both restrooms have been updated to better reflect existing conditions. Doors 00C and 00D into the Women’s and Men’s restroom are not 32 inches clear. Due to the historic nature of the historic stone openings, increasing the size of the existing restroom doors is technically infeasible. Door stalls have been updated to reflect a 32inch clear opening. Door reach ranges, however, do not meet accessibility. Per 2015 IEBC: 705.1 General: Where compliance with this section, is technically infeasible, the alteration shall provide access to the maximum extent possible. Both Women’s Room 00C and Men’s Room 00D currently have horizontal grab bars. The project will provide new vertical grab bars per ANSI 604.5.1 Fixed Side Wall Grab Bars and pipe protection per ANSI 606.6 Exposed Pipes and Surfaces. Keynote 30 has been added on Sheet A1.0 to reflect the inclusion of fixed vertical grab bars and knee protection. The existing hardware is being removed and replaced with new accessibly compliant hardware Per the 2015 IEBC section 1204.1.4 toilet and Bathing Facilities: Where toilet rooms are provided, at least one accessible family or assisted-use toilet room complying with Section 1109.1.1 of the International Building Code shall be provided. Per the 2015 IBC section 1109.2.4.1 Location: Family or assisted-use toilet and bathing rooms shall be located on an accessible route. Family or assisted-use toilet rooms shall be located not more than one story above or below separate sex toilet rooms. The accessible route from any separate sex toilet room to a family or assisted-use toilet room shall not exceed 500 feet. 08/21/2019 CR A F T B A L A N C E WH I M S Y 30 3 2 7 8 4 3 7 8 7 1 5 F O U R T E E N T H S T R E E T , G O L D E N , C O 8 0 4 01 AN D A R C H . C O M AN D E R S O N H A L L A S A R C H I T E C T S 3 . Existing Women’s Room 114 and Men’s Room 113 on the Main Level will be made fully compliant (see following comments referencing A1.1 Main Level Floor Plan). In addition, all new restrooms will be fully accessible. Travel distance from the Garden Level to the Main Level is less than 500 feet Travel distance from the Second Level to the Main Level is less than 500 feet. 2019.06.14 Pitkin Permit – Architectural: A1.1 Main Level Floor Plan Per 2015 IEBC 705 and 705.2, this alteration affects that primary function and therefore the toilet facilities serving the area of primary function shall be accessible to the maximum extent that is technically feasible. Revise door widths to provide clear opening width of 32 inches minimum. Provide an accessible toilet compartment, grab bars and under counter pipe protection in men’s restroom. Response: No work is anticipated in Women’s Room 114 or Men’s Room 113. Men’s Restroom 113 was revised graphically to reflect the existing door swing properly. Both restrooms are accessible, however, are missing vertical grab bars and pipe protection. Both Women’s Room 114 and Men’s Room 114 currently have horizontal grab bars. The project will provide new vertical grab bars per ANSI 604.5.1 Fixed Side Wall Grab Bars and pipe protection per ANSI 606.6 Exposed Pipes and Surfaces. Keynote 30 has been added on Sheet A1.1 to reflect the inclusion of fixed vertical grab bars and knee protection. See updated sheet A1.1 2019.06.14 Pitkin Permit – Architectural: A5.0 Door Schedule 1. Confirm that the following 2’-10” doors provide the minimum clear width of 32” per 2015 IBC 1010.1:00, 04 100; 105C, 108A, 113. 114. 2020C, 203. Response: Doors 100, 105C, 108A, 113, 114, 202C and 203 are existing historic doors. The doors are hung within their original frames in deep masonry walls. On either side of the door are decorative moldings that are integral with the original transom above. The doors and trim are character defining features. Existing doors slabs are 34 inches wide and 1.75 inches thick. Existing doorstops are 3/8” thick. The clear opening is 31-7/8” clear. To provide a 32” clear opening would cause irrevocable damage to existing historic fabric and is technically infeasible per IEBC section1204.4 accessibility requirements, where compliance with the requirements would threaten or destroy the historic significance of the building or facility. Existing door hardware does not meet accessibility requirements. All existing hardware will be replaced and updated for compliance. Reference specification section 08 71 00 for door hardware schedule. 08/21/2019 CR A F T B A L A N C E WH I M S Y 30 3 2 7 8 4 3 7 8 7 1 5 F O U R T E E N T H S T R E E T , G O L D E N , C O 8 0 4 01 AN D A R C H . C O M AN D E R S O N H A L L A S A R C H I T E C T S 4 2019.06.14 Pitkin permit – Architectural: A5.0 Door Schedule Correct the following doors to provide the required 32” clear width per 2015 IBC 1010.1.1: 108B, 108C. Response: Doors 108B and 108 C are existing historic doors to remain with no work. On either side of the door are decorative moldings that are integral with the original transom above. The doors and trim are character defining features. Existing doors slabs are 2’-8” inches wide and 1.75 inches thick. Existing doorstops are 3/8” thick. The clear openings are 29-7/8” clear. To provide a 32” clear opening would cause irrevocable damage to existing historic fabric and is technically infeasible per IEBC section1204.4 accessibility requirements, where compliance with the requirements would threaten or destroy the historic significance of the building or facility. Existing door hardware does not meet accessibility requirements. All existing hardware will be replaced and updated for compliance. A new accessible office will be provided within the Probation Suite. The accessible door will provide a 32” clear opening. See sheet A1.1 2019.06.14 Pitkin Permit – Architectural: A7.3 Enlarged Plans at New Lift Entry 3’-5” Response: Sheet A7.3 has been updated to reflect a 42” clear side door opening at the main level. 2019.06.14 Pitkin Permit – Architectural: A7.3 Enlarged Plans at New Lift Entry Side door on lift require a clear opening width of 42” minimum. ICC A117.1-2009 410.2.1 Response: Sheet A7.3 has been updated to reflect a 42” clear side door opening at the main level. 08/21/2019 CR A F T B A L A N C E WH I M S Y 30 3 2 7 8 4 3 7 8 7 1 5 F O U R T E E N T H S T R E E T , G O L D E N , C O 8 0 4 01 AN D A R C H . C O M AN D E R S O N H A L L A S A R C H I T E C T S 5 2019.06.14 Pitkin Permit – Architectural: A9.2 Interior Elevations Knee and toe clearances must be provided at the jury deliberation sinks. ICC A117.1-2009 606.2. Response: The following drawings have been updated to reflect a front approach to new sinks. 2 & 5: A9.2 1:A9.8 2& 3:A9.11 The swing clear cabinet doors at base cabinet locations have been removed and replaced with a removable apron. The removable apron will provide the required knee and toe floor space at the front of each sink and provide knee protection. 2019.06.14Pitkin Permit – Architectural: A9.2 Interior Elevations A parallel approach to the sink is required when knee/toe clearances are not provided. ICC A117.1-2009 606.2 exception 1. The dishwasher in the open position cannot encroach in the clear floor space of the sink 804.5.3. Response: See comment above. All swing clear cabinet doors have been removed and replaced with a removeable sink apron. The removable apron will provide the required knee and toe floor space at the front of each sink and provide knee protection. 2019.06.14 Pitkin Permit – Architectural A9.7 Interior Elevations – DA A parallel approach to the sink is required when knee/toe clearances are not provided. OCC A117.1-2009 606.2 exception 1 Response: Sink in DA office 101 has been updated to provide a front approach to the sink. The swing away cabinet doors have been replaced with a removable apron. The removable apron will provide the required knee and toe floor space at the front of each sink and provide knee protection. See revised interior elevation 2:A9.7. 08/21/2019 CR A F T B A L A N C E WH I M S Y 30 3 2 7 8 4 3 7 8 7 1 5 F O U R T E E N T H S T R E E T , G O L D E N , C O 8 0 4 01 AN D A R C H . C O M AN D E R S O N H A L L A S A R C H I T E C T S 6 2019.06.14 Pitkin Permit – Architectural: G0.1 Cover Sheet Per information provided on the asbestos verification checklist, this project requires an asbestos test. Provide an asbestos test report that includes the following: Inspector’s narrative including sampling locations 2. Inspector’s certificate 3. Lab data. If asbestos is found, a final air clearance report must be provided to building permit issuance. Response: Asbestos report is attached. 2019.06.14 Pitkin Permit – Architectural G0.1 Cover Sheet The special inspection agreement needs to be completed and signed by all parties prior to permit issuance. Response: See Attached 2019.06.14 Pitkin Permit – Architectural G0.3 General Information Provide the full installation instruction from the Gypsum Manual for WP 1072, WP 3510, WP6800, FCU3510 in the plan set for reference and inspection. Response: Sheet G0.3 wall types have been updated with full installation instructions from the Gypsum Manual. Revised sheets G0.3G0.4A1.0A1.1A5.0A7.3A9.2A9.7A9.8A9.11A0.1E1.0ED1.0 08/21/2019 506 E Main_BuildingComments_1_Markup Summary File Name: 2019.05.29 Mechanical.pdf Author: bonniem Subject: PlanCheck Color: Page Label: M0.1 MECHANICAL LEGEND AND NOTES Thermostat heights to comply with reach ranges in ICC A117.1-2009 308. 2019.05.29 Mechanical.pdf (1) File Name: 2019.05.29 Pitkin Permit Electrical.pdf Author: mitchm Subject: Electrical Code Color: Page Label: ED1.0 GARDEN LEVEL ELECTRICAL PLAN DEMO 620.22 Branch Circuits for Car Lighting, Receptacle(s), Ventilation, Heating, and Air-Conditioning. (A) Car Light Source. A separate branch circuit shall supply the car lights, receptacle(s), auxiliary lighting power source, and ventilation on each elevator car. The overcurrent device protecting the branch circuit shall be located in the elevator machine room or control room/machinery space or control space. Required lighting shall not be connected to the load side of a ground-fault circuit interrupter 2019.05.29 Pitkin Permit Electrical.pdf (1) File Name: 2019.06.14 Pitkin Permit - Architectural.pdf Author: bonniem Subject: PlanCheck Color: Page Label: A1.0 GARDEN LEVEL FLOOR PLAN Per the code summary on G0.4, the occupant load of the garden level courtroom exceeds 50, correct door swing so that doors swing in the direction of egress travel per 2015 IEBC 805.4.2 2019.06.14 Pitkin Permit - Architectural.pdf (13) File Name: 2019.06.14 Pitkin Permit - Architectural.pdf Author: bonniem Subject: PlanCheck Color: Page Label: A1.0 GARDEN LEVEL FLOOR PLAN Per 2015 IEBC 705, 705.2, this alteration affects the area of primary function and therefore the toilet facilities serving the area of primary function shall be accessible to the maximum extent that is technically feasible. Revise door widths to provide clear opening width of 32 inches minimum. Provide an accessible toilet compartment, grab bars and under counter pipe protection in the men's restroom. PRESSURE SENSOR THERMOSTAT METER FLOW ARROWG. FIRE/SMOKE DAMPERS: COMBINATION FIRE/SMOKE DAMPERS SHALL BE FABRICATED IN ACCORDANCE WITH NFPA 90A ANDUL555S CLASS II. FIRE/SMOKE DAMPERS SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S UL INSTALLATIONINSTRUCTIONS. ACTUATORS SHALL BE POWER OPEN/SPRING CLOSED OPERATION, 120 VOLT. THE FIRE FAIL/SAFE MODE SHALLBE A UL 33 HEAT ACTUATED LINK FOR CLOSURE AND CONTAINMENT OF FIRE ZONE, INDEPENDENT OF ACTUATOR POSITIONINGOR SIGNALING. MANUFACTURED BY PREFCO, MODEL 5020 OR EQUAL. H. HOT WATER HEATING PIPING/CHILLED WATER PIPING/CONDENSER WATER PIPING: ABOVEGROUND, NPS 2" AND SMALLER, SHALLBE ANY OF THE FOLLOWING:1. TYPE L, DRAWN-TEMPER, COPPER TUBING, WROUGHT-COPPER FITTINGS, AND SOLDERED JOINTS.2. SCHEDULE 40, GRADE B, TYPE 96 STEEL PIPE; CLASS 150, MALLEABLE IRON FITTINGS, CAST-IRON FLANGES AND FLANGEFITTINGS, AND THREADED JOINTS. K. HYDRONIC PIPING INSULATION: MINERAL-FIBER, PREFORMED PIPE INSULATION: TYPE 1, 850° F. MINERAL OR GLASS FIBERSBONDED WITH A THERMOSETTING RESIN. COMPLY WITH ASTMC 547, TYPE 1, GRADE A, WITH FACTORY APPLIED ASJ.1. HEATING WATER 1-1/2" AND SMALLER = 1.5" THICK, HEATING WATER 2" AND LARGER = 2" THICK, CONDUCTIVITY = 0.27 @125° F.2. CHILLED WATER = 1.0 " THICK, CONDUCTIVITY = 0.25 @ 75° F. III. EXECUTION A. BALANCING:1. CONTRACTOR SHALL ADJUST AND BALANCE VARIABLE VOLUME BOXES (VAV'S), FAN POWERED BOXES (FPB'S), AIRCONDITIONING UNITS (AC'S), AND DIFFUSERS TO THE QUANTITIES SHOWN ON THE DRAWING. BALANCING WORK SHALL BEPERFORMED IN ACCORDANCE WITH NEBB OR TABB STANDARDS BY A NEBB OR TABB CERTIFIED CONTRACTOR. SUBMITBALANCING REPORT TO THE ENGINEER.2. EXISTING DIFFUSER DESIGNATION INDICATES CFM ONLY.3. VAV BOX DESIGNATION INDICATES MAXIMUM CFM ADJUST MINIMUM TO 10% OF MAXIMUM.4. WHERE LOW PRESSURE AIR HANDLING SYSTEMS CROSS INTO AN ADJACENT TENANT AREA, CONTRACTOR SHALLBALANCE ALL DIFFUSERS ASSOCIATED WITH THE SYSTEM. DIFFUSERS NOT SHOWN OR SHOWN WITH NO CFM SHALLMAINTAIN EXISTING CFM.5. ADJUST WATER SYSTEMS, AFTER AIR BALANCING, TO PROVIDE DESIGN QUANTITIES.6. ADJUST SYSTEMS TO PROVIDE SPECIFIED PRESSURE DROPS AND FLOWS THROUGH HEAT TRANSFER ELEMENTS PRIORTO THERMAL TESTING. PERFORM BALANCING BY MEASUREMENT OF TEMPERATURE DIFFERENTIAL IN CONJUNCTION WITHAIR BALANCING. B. CONTRACTOR SHALL COORDINATE WORK WITH OTHER TRADES AND NOTIFY 360 ENGINEERING, INC. IF ANY CONFLICTS OCCUR. C. THERMOSTAT LOCATIONS AND HEIGHTS TO BE COORDINATED WITH BUILDING MANAGEMENT, VERIFIED BY THE ENGINEER.CONTRACTOR TO CALIBRATE ALL THERMOSTATS SHOWN ON THIS PLAN. IT SHALL BE THE GENERAL CONTRACTOR'SRESPONSIBILITY TO ENSURE THAT ALL EXISTING THERMOSTATS REMAIN INTACT DURING DEMOLITION. HEATING THERMOSTATSMUST REMAIN OPERATIONAL AT ALL TIMES. IF REQUIRED FOR BETTER PROTECTION, THERMOSTATS MAY BE TEMPORARILYMOUNTED IN THE CEILING PLENUM DURING DEMOLITION. D. PROVIDE VOLUME DAMPERS AT ALL DIFFUSER TAKEOFFS. E. ALL TAKEOFFS, RUNOUTS, AND FLEX DUCTWORK TO DIFFUSERS SHALL BE THE SAME SIZE AS DIFFUSER INLET UNLESSOTHERWISE NOTED. F. MECHANICAL CONTRACTOR TO CHECK OPERATION AND CONDITION OF ALL EXISTING MECHANICAL EQUIPMENT WITHIN THECONFINES OF THIS SPACE AND PREPARE A WRITTEN LIST OF ANY DEFICIENCIES IN EQUIPMENT OPERATION OR CONDITION. LIST SHALL BE SUBMITTED TO OWNER TWO WEEKS AFTER THE AWARD OF THE CONTRACT. G. THERMOSTAT CONTROL LINES SHALL BE SUPPORTED AT INTERVALS NOT TO EXCEED 4'0". H. PROVIDE EXTERNAL INSULATION ON ALL NEW RIGID ROUND DUCTWORK. I. PROVIDE ACCESS DOORS IN DUCTWORK AS REQUIRED FOR ACCESS TO FIRE DAMPERS, FIRE/SMOKE DAMPERS, OR ANY OTHERMECHANICAL EQUIPMENT REQUIRING MAINTENANCE OF SERVICE.J. ALL PIPE AND DUCT PENETRATIONS THROUGH RATED WALLS SHALL BE SEALED PER 2015 IBC. MT P Thermostat heights tocomply with reachranges in ICCA117.1-2009 308. (R) (R) (R) (R) (R) (R)(R) (E) (E) (E) PITKIN COUNTY COURTHOUSE REMODEL PITKIN COUNTY, CO 506 E Main St St 300, Aspen, CO 81611 No. Description Date1 Addendum #2 05-23-2019 INTERCEPTING CONDUITS IN THE VISITING JUDGE'S CHAMBERS ANDRE-ROUTING AROUND THE LOWER LIFT LOBBY BACK INTO COURTROOM 3. 3 EXISTING ELEVATOR EQUIPMENT TO BE REPLACED WITH NEW IN SAMELOCATION. NEW ELEVATOR ELECTRICAL CHARACTERISTICS (3OHP) ARESAME AS EXISTING (30HP). CONTRACTOR SHALL MAINTAIN EXISTING FIREALARM CONNECTIONS AND EXISTING POWER CIRCUITRY IF VERIFIED TOMATCH NEW. REFER TO ELEVATOR EQUIPMENT INFORMATION INMECHANICAL SCHEDULE FOR MORE INFORMATION.4 EXISTING CAB LIGHT DISCONNECT IS A TOGGLE SWITCH AND SHALL BEREPLACED WITH FUSED DISCONNECT. REMOVE EXISTING TOGGLE SWITCHAND MAINTAIN EXISTING CIRCUITRY FOR CONNECTION TO NEWDISCONNECT SWITCH IN NEW WORK.5 CONTRACTOR SHALL MAINTAIN EXISTING FUSED DISCONNECT IF VERIFIEDTO BE A 150A FUSE IN 200A3P DISCONNECT. OTHERWISE REPLACE WITHNEW IN SAME LOCATION. VERIFY FEED TO DISCONNECT MATCHES NEWFEEDER PER EQUIPMENT INDICATED IN MECHANICAL EQUIPMENTSCHEDULE. 1 620.22 Branch Circuits for Car Lighting, Receptacle(s),Ventilation, Heating, and Air-Conditioning.(A) Car Light Source. A separate branch circuit shall supplythe car lights, receptacle(s), auxiliary lighting power source, andventilation on each elevator car. The overcurrent device protectingthe branch circuit shall be located in the elevator machineroom or control room/machinery space or control space.Required lighting shall not be connected to the load side ofa ground-fault circuit interrupter 176 SF BOILER01A 72 SF MECH/ELEC02D 35 SF JAN.00A 98 SF STORAGE00B 332 SF HOLDING06 143 SF CONF. RM08 87 SF JUDGE RR14 715 SF COURTROOM 305 53 SF HALL16 13B 05A 17 06 NF6 NF6 NF6NF6NF6 NF3 NF8UP UP 5' - 0" UP NEW ACCESSIBLE CONC RAMP. MAX SLOPE 1:12. RE: CIVIL 102 SF WOMEN00C 113 SF MEN00D INFILL <E> OPENING, RE:STRUCT. M.O.4' - 1"5' - 0" 6' - 2 1/2" A9.91 A9.82 A4.02 47 SF STORAGE15 70 SF SECURE HALL13 49 SF ELEV. MECH.00E A7.31 . 615 SF HALL00 110 SF HALL09 59 SF HALL10 408 SF VISITING JUDGE'SCHAMBERS04 49 SF HALL05A <N> RAISED PLATFORM FOR JUDGE'S BENCH 06A 06B 85 SF ATTORNEY06A 20 SF MECH.06B 4' - 6" NF6 NF9NF9 NF9 NF9 3 49 SF JURY RR07 07 116 SF OFFICE 102C SF ST.2 55 SF ELEV.11 UP B B A A C F A C A7.51 A9.121 F C ALIGN O.2"" 13A 08 A4.01 10' - 6 " 1/2" 4' - 5 1/2" 3' - 11 1/2" 12' - 5" 6' - 1 1 1 / 2 " 5' - 8" 9 1/2 " 5" R.O.3' - 2" 5" D 100' - 0" 100' - 0" 76 SF LOWER LIFT LOBBY17 A I NF10 NF10 04 12 M.O.3' - 4" 3' - 5" R.O.3' - 2" 1' - 5" R.O.3' - 2" 1' - 5" 1' - 6" 10' - 0" R.O.3' - 2" 8 1/2" R.O.3' - 2" R.O.3' - 2" R.O. 1' - 0"1' - 0" ALIGN F.O. <N> WALL WITH CENTER LINE OF <E> COLUMN. NF15 00B 00A 00E 05 04A00D00C 02D 01A HOLD3' - 6" 16 F D VERTICAL INTERIOR ROOF DRAIN TO REMAIN D NF20 NF20 06B 05A 05B 05C 05D 05E 06CNF6 3' - 6" 9 1/4" 7" UP RTICAL GRAB BLE STALL & PIPE M.O.3' - 4" A0.25 NF26 NF27NF28NF29 05B 05C 15 14 B NF9 NF9NF9 NF9 NF9 NF9 NF9NF9 C NF9 NF9 A AA A G GNF15 NF37 REF STRUCTURAL FOR MATERIAL AND SIZING FOR STRUCTURAL ELEMENTS IN WALL TYPA AT NEW LIFT STRUCTURE SIM SIM E 1 LEGEND <E> WALL NEW WALL NEW DOOR NEW FLOOR STRUCTURE, RE: STRUC REPAIR CONCRETE SLAB. PROVIDE CONSISTENT FLOOR LEVEL PRIOR TO INSTALLING NEW FLOOR FINISH. FLOOR ELEVATION KEYNOTE DOOR TAG WALL TYPE # - 101 X GENERAL NOTES1. PATCH AND REPAIR ALL FINISHES AFFECTED BY CONSTRUCTION. MATCH ADJACENT FINISH.2. COORDINATE REUSE, SALVAGE, OR DISPOSAL OF ALL DEMO ITEMS WITH OWNER.3. REMOVE & SALVAGE <E> WINDOW TREATMENTS. COORDINATE REINSTALLATION WITH PITKIN COUNTY/ 9TH JUDICIAL DISTRICT.4. FURNITURE BY OTHERS. SHOWN FOR REFERENCE.5. PITKIN COUNTY TO BE RESPONSIBLE FOR REMOVING / RELOCATING ALL <E> FURNITURE.6. REFERT TO M, P, E, & S SHEETS FOR ADDITIONAL INFORMATION.7. REFER TO FINISH PLANS AND RCPS FOR ADDITIONAL INFORMATION.8. ALL REPOSITIONED COURTROOM FURNITURE TO PROVIDE 30" CLEAR.9. REMOVE AND SALVAGE <E> SIGNAGE (FLAGS AND WALL MOUNTED). MODIFY FOR <N> ROOM NAMES. INSTALL <N> TO MATCH <E> WHERE NEEDED.10. REFER TO A 9.7 FOR ADDITIONAL CLERESTORY. PROVIDE SMOOTH AND FLUSH FINISH MATCH <E> ADJACENT FURRING ANDFINISH.NF20 INSTALL <N> HIGH IMPACT RESISTANTGYP. BD. WALL FINISH ON <E> FURRIN INSTALL <N> FURRING (TO MATCH <E> AS NEEDED FOR <N> OPENING ATEXISTING ELEVATOR CORE.NF26 THE CAB HAS THREE SETS OFCONTROLS. (2) AT STANDARD HEIGHT REAR AND FRONT OF CAB AND A THIR SET OF CONTROLS MOUNTED AT 29" A REMOVE THIRD SET OF CONTROLS.UPDATETHE CONTROL OPTIONS TOINCORPORATE <N> CALL BUTTON TO < SIDE OF GARDEN LEVEL, ANDSECURE/DESIGNATED ACCESS FORIN-CUSTODIES AND STAFF.NF27 REMOVE <E> VINYL TILE FLOOR.PROVIDE <N> CARPET TILE FLOORFINISH. PROVIDE <N> INTERIOR CABFINISH ON ALL 4 WALLS. PROVIDE <N>CEILING FINISH AND LIGHTING. REMOV <E> AUXILIARY PANEL.NF28 PROVIDE CAB CONTROLS VIA CARDACCESS TO ALLOW FOR LOCKOUT FO EITHER JUDGE OR IN-CUSTODYTRANSPORT.NF29 PROVIDE VERTICAL ACCESSIBLE GRA BAR IN <E> RESTOOM. RE: A 9.3NF37 PROVIDE <N> PLUMBING CHASE FOR < ROOF DRAIN WITH 6" MIN INTERIORCLEAR. SIZE OF PIPE TO BE CONFIRME VIA DESIGN BUILD. 1 Per the code summaryon G0.4, the occupantload of the gardenlevel courtroomexceeds 50, correctdoor swing so thatdoors swing in thedirection of egresstravel per 2015 IEBC805.4.2 176 SF BOILER01A 72 SF MECH/ELEC02D 35 SF JAN.00A 98 SFSTORAGE00B 332 SF HOLDING06 143 SF CONF. RM08 87 SF JUDGE RR14 715 SF COURTROOM 305 53 SF HALL16 372 SF JURY DELIBERATION03 13B 01 05A 17 06 NF6 NF6 NF6NF6NF6 NF3 UPUP UP UP 102 SF WOMEN00C 113 SF MEN00D INFILL <E> OPENING, RE:STRUCT. M.O.4' - 1"5' - 0" 6' - 2 1/2" 5" A9.82 47 SF STORAGE15 70 SF SECURE HALL13 49 SFELEV. MECH.00E 55 SF VEST.03A 122 SF ATTORNEY01 615 SF HALL00 110 SF HALL09 59 SF HALL10 408 SF VISITING JUDGE'SCHAMBERS04 49 SF HALL05A 06A 06B 85 SFATTORNEY06A 4' - 6 " NF6 NF9NF9 NF9 NF9 03 JURY RR07 07 89 SF ALPINE LEGAL02E 116 SF OFFICE 102C103 SF OFFICE 202B 197 SF BREAK ROOM02A 85 SF VEST.02 02C02B 02A 02E DW 55 SF ELEV.11 UP UP A A B B A A A A A A C F A C <N> CABINET A7.51 F C ALIGN 9' - 2" R.O.3' - 2"5 1/2" 13A 08 A4.0113' - 4 1/2" 2' - 10" 8' - 2" 10' - 6 " 8' - 1 1/2" R.O.3' - 2"4' - 5 1/2" 3' - 11 1/2" 6' - 1 1 " 12' - 5" 6' - 11 1 / 2 " 5' - 8" 9 1/2 " 5" R.O.3' - 2" 5" 13' - 3" 7" D ALIGN 100' - 0" 100' - 0" A9.21 A I NF10 NF10 04 12 00 09 M.O.3' - 4" 3' - 5" R.O.3' - 2" 1' - 5" R.O.3' - 2" 1' - 5" R.O.3' - 2" 8 1/2" R.O.3' - 2" R.O.3' - 2" HOLD1' - 0"R.O.3' - 2"R.O.'3' - 2" R.O.3' - 2"1' - 4" R.O.3' - 2" R.O.3' - 2" 1' - 0"1' - 0" ALIGN F.O. <N> WALL WITH CENTER LINE OF <E> COLUMN. NF15 1' - 6" FIN.4' - 6" 00B 00A 00E 05 04A00D00C 02D 01A HOLD3' - 6" 16 F 18 REF. D D NF20 NF20 0 05A 05B 05C 0 0 0 06A06D06E NF6 NF6NF6NF6 3' - 6" 9 1/4" 7" UP A9.26 INSTALL <N> SCREEN OVER CONDUIT INSTALL <N> SCREEN OVER CONDUIT PROVIDE <N> VERTICAL GRAB BAR AT ACCESSIBLE STALL & UNDERCOUNTER PIPE PROTECTION M.O.3' - 4" NF26 NF27NF28NF29 05B 05C 15 14 B NF9 NF9NF9 NF9 NF9 NF9 NF9NF9 C A AA A G GNF15 INSTALL <N> 2" THICK CONC "BENCH" OVER FOUNDATION INSTALL <N> 4X4 STL ANGLE TO SUPPORT CONC BENCH ENDEGRESS STAIR FOUNDATION, RE: STRUC NF37 CONTRACTOR SHALL CONNECTNEW INTERNAL ROOF DRAIN TO NEW STORM SEWER: REF CIVIL REF STRUCTURAL FOR MATERIAL AND SIM SIM D E 1 1 PROVIDE MINIMAL WALL PENETRATION INVERT OF 7903.83' TO ACHIEVE A MINIMUM 1% SLOPE TO STORM SEWER TIE-IN 1 Per 2015 IEBC 705, 705.2, thisalteration affects the area of primaryfunction and therefore the toilet facilitiesserving the area of primary functionshall be accessible to the maximumextent that is technically feasible.Revise door widths to provide clearopening width of 32 inches minimum.Provide an accessible toiletcompartment, grab bars and undercounter pipe protection in the men'srestroom. 08/21/2019 File Name: 2019.06.14 Pitkin Permit - Architectural.pdf Author: bonniem Subject: PlanCheck Color: Page Label: A1.1 MAIN LEVEL FLOOR PLAN Per 2015 IEBC 705, 705.2, this alteration affects the area of primary function and therefore the toilet facilities serving the area of primary function shall be accessible to the maximum extent that is technically feasible. Revise door widths to provide clear opening width of 32 inches minimum. Provide an accessible toilet compartment, grab bars and under counter pipe protection in the men's restroom. File Name: 2019.06.14 Pitkin Permit - Architectural.pdf Author: bonniem Subject: PlanCheck Color: Page Label: A5.0 DOOR SCHEDULE 1. Confirm that the following 2'10" doors will provide the minimum clear width of 32" per 2015 IBC 1010.1.1: 00, 04, 100, 105C, 108A, 113, 114, 202C, 203. File Name: 2019.06.14 Pitkin Permit - Architectural.pdf Author: bonniem Subject: PlanCheck Color: Page Label: A5.0 DOOR SCHEDULE Correct the following doors to provide the required 32" clear width per 2015 IBC 1010.1.1: 108B, 108C File Name: 2019.06.14 Pitkin Permit - Architectural.pdf Author: bonniem Subject: 3/16" Scale Color: Page Label: A7.3 ENLARGED PLANS AT NEW LIFT ENTRY 3'-5" File Name: 2019.06.14 Pitkin Permit - Architectural.pdf Author: bonniem Subject: PlanCheck Color: Page Label: A7.3 ENLARGED PLANS AT NEW LIFT ENTRY Side door on the lift requires a clear opening width of 42" minimum. ICC A117.1-2009 410.2.1 IT106 FILE/COPY102D STORAGE112 PROBATION108 PROBATION RR108D OFFICE 1108E OFFICE 2108C OFFICE 3108B WAITING108A CLOSET108F HALL105 OFFICE 2105B MEETINGROOM105C CLERKS102 WAITING/SELF HELP102A CLERKWORKSTATIONS103 FAMILY COURT/COLLECTIONS102B OFFICE 1104 108E 104 NF3 DN DN <N> CONC. RAMP, MAX. SLOPE 1:12. RE: CIVIL MEN113 WOMEN114 11' - 9" 10' - 11 " ALIGN 10' - 0 1/2"6' - 7 " R.O.3' - 2"7" 1' - 4" UP UP DN DN A9.92 HALL100 4' - 3 1/2" 102B TRANSACTION COUNTER : REF 5:A9.3 SECURITYSCREENING115 VEST.100A EST.10 HALL103AELEV.111 INFORMAL MTG105A B A F A AA A <N> ACCESSIBLE RAILINGS<N> ACCESSIBLE RAILINGS ALIGN 101C101B OFFICE 1101B OFFICE 2101C WITNESSWAITING101D DA OFFICE101 OFFICE 4101E 101EAAA101D OFFICE 3101F 101F A WAITING101A OPEN TO BELOW A9.6 2 A9.6 3 A9.4 4 A9.4 5 A9.34 A9.3 5 V.I.F.15' - 7" 10 1/2" V.I.F. 4' - 10 1/2" 1"HOLD5' - 0"1" V.I.F.0" 1' - 0" V.I.F.11' - 4" 9' - 6" 9' - 11 1/2" 6' - 8" 4 1/2"ALIGN A A A9.41108 ALIGN 2A9.3 A ALIGN R.O.3' - 2" 4' - 0 1/2" ALIGN R.O.3' - 2" R.O.3' - 2" 6 1/2"R.O.3' - 2" R.O.3' - 2" R.O.3' - 2" R.O.3' - 2" F.4"R.O.3' - 2"1' - 0"HOLD1' - 6" ALIGN 7' - 1" A 110 100A 100B 6"6" NF14 E A9.61 152 C 102D 115102102A 106 105B 105C 108C 108B 100C 101A 113 100 112 114 108F 108A NF19A4.04 X RAY 73" x 47" MAGNETOMETERS 36" x 28"DEMOUNTABLE GLASS PARTITION 6' HT 1' - 6"R.O.3' - 2"102C A9.71 1' - 10" 4' - 4"1' - 8" 4' - 4"1' - 6" 2' - 7"2' - 2" H H H PROVIDE <N> VERTICAL GRAB BAR AT ACCESSIBLE STALL & UNDERCOUNTER PIPE PROTECTION WALL-MOUNTED SWING SECURITY EXIT GATE A4.03 A4.06 108D 103A 6 NF25 NF23 1' - 4 1/2"1' - 0 1/2" E SECUR I T Y STAF F MIN3' - 0" MIN3' - 6" A4.07 A4.08 A9.31 3A9.3 A9.7 5 MIN.1' - 0" 4 7' - 0" H 1' FLOOR A NF30 NF30 TAIN 48 INCHES CLEAR MANUEVERING SPACE AT H SIDES OF OPENING.ENTIRE DEPTH OF MASONRY WALL.3.VERIFY 32 INCHES CLEAR OPENING4.MAINTAIN 48 INCHES CLEAR MANUEVERING SPACE AT BOTH SIDES OF OPENING. 1' - 11" 2' - 10" HOLD 3' - 10 1/2" ALIGN V.I.F.' - 4" V.I.F.1" A E AA NF31 NF32 NF32 NF32 NF32 NF33 NF34 A A A AA9.7 76 3' - 5" 101 REF. 1 NF37 LEGEND <E> WALL NEW WALL NEW DOOR NEW FLOOR STRUCTUR STRUC REPAIR CONCRETE SLA PROVIDE CONSISTENT F LEVEL PRIOR TO INSTAL NEW FLOOR FINISH. FLOOR ELEVATION KEYNOTE DOOR TAG WALL TYPE # - 101 X GENERAL NOTES1. PATCH AND REPAIR ALL FINISHES AFFEC CONSTRUCTION. MATCH ADJACENT FINI 2. COORDINATE REUSE, SALVAGE, OR DISP DEMO ITEMS WITH OWNER.3. REMOVE & SALVAGE <E> WINDOW TREA COORDINATE REINSTALLATION WITH PIT JUDICIAL DISTRICT.4. FURNITURE BY OTHERS. SHOWN FOR RE 5. PITKIN COUNTY TO BE RESPONSIBLE FO RELOCATING ALL <E> FURNITURE.6. REFERT TO M, P, E, & S SHEETS FOR ADD INFORMATION.7. REFER TO FINISH PLANS AND RCPS FOR INFORMATION.8. ALL REPOSITIONED COURTROOM FURNI 30" CLEAR.9. REMOVE AND SALVAGE <E> SIGNAGE (F MOUNTED). MODIFY FOR <N> ROOM NAM TO MATCH <E> WHERE NEEDED.10. REFER TO A 9.7 FOR ADDITIONAL CLERE N MIRRORED FILM APP GLASS. REMOVE DOO INFILL HOLE WHERE HARDWARE REMOVE FLUSH FINISH WITHSURROUNDING WD, P MATCH.NF23 FIX DOOR IN OPEN PO NF25 CUT THROUGH <E> S FOUNDATION WALL. P <N> DOOR ACCESS T NORTH OF THE <E> E NF30 PROTECT <E> SAFE D REMAIN IN PLACE.NF31 ALIGN <N> WALL WIT COLUMNS.NF32 <N> CLERESTORY WI ABOVE. RE: INT. ELEV NF33 <E> COLUMN TO REM NF34 REINSTALL SALVAGE MILLWORK ON <N> W PROVIDE <N> WD AC PANEL.NF37 PROVIDE <N> PLUMB FOR <N> ROOF DRAIN MIN INTERIOR CLEAR PIPE TO BE CONFIRM DESIGN BUILD. DRAWINGS BASED ON FLO PROVIDED BY PITKIN COUN 0 4' 8 1 Per 2015 IEBC 705, 705.2, thisalteration affects the area of primaryfunction and therefore the toilet facilitiesserving the area of primary functionshall be accessible to the maximumextent that is technically feasible.Revise door widths to provide clearopening width of 32 inches minimum.Provide an accessible toiletcompartment, grab bars and undercounter pipe protection in the men'srestroom. S 1. Confirm that the following 2'10" doors will provide the minimum clear width of 32" per 2015 IBC 1010.1.1: 00, 04, 100, 105C, 108A, 113, 114, 202C, 203. HIS Correct the following doors to provide the required 32" clear width per 2015 IBC 1010.1.1: 108B, 108C LIFT 3' - 5 " <N> POST MOUNTE AUTOMATIC ACCES DOOR OPENER BUT LOCATION (EXTERIO NEW WALL MOUNTE AUTOMATIC ACCES DOOR OPENER BUT LOCATION (INTERIO PRE-FINISHED GATE ASSEMBLY BY LIFT INSTALLED BY G.C. PRE-FINISHED LIFT ASSEMBLY - INSTAL BY G.C. T-SHAPED TURNING CLEARANCE <E> WINDOW TO DOOR PROVIDED B MFG INSTALLED BY CLOSET108F 3A7.3 LIFT5 A7.3 TO BE REMOVED AND SALVAGED EXISTING DOOR LOCATION (V.I.F.) 1' - 7"NEW CLR OPENING 4' - 9" ,<E> STAIR AND <E> ENTRY VESTIBULE OPEN TO BELOW (V.I.F.) 4' - 8" (V.I.F.) 5' - 5 1/2" (V.I.F.) 1' - 10" ADA CLEAR FLOOR SPACE <E> WINDOW AND FRAME TO REMAIN FIN. TO STUD4' - 0" (V.I.F.) <N> STRUCTURAL FLOOR AT LIFT PLATFORM LOCATION <N> ENCLOSURE AT LIFT WALL PRE-FINISHED LIFT INSTALLED BY G.C. <E> MECHANICAL DUCT TO REMAIN NOTE: NEW WALL FRAMING AT LIFT LOCATION SHALL BE (1) HOUR RATED (SHOWN WITH DIAGONAL CROSS HATCH) STEEL FRAMING: GA FILE NO WP1072WOOD FRAMING: GA FILE NO WP 2510 MAIN LEVEL110' - 3 5/8" LOOR STRUCTURE AND LIFT SO ATFORM OF LIFT ALIGNS WITH BEYOND LL CONSTRUCTION WITH RESISTANT GYP. BOARD ON PUBLIC SIDE OF LIFT URE <N> CARPET FINISH ON <N> ITH 3/4" T&G PLYWD -ALIGN <N> WITH <E> MAIN FLOOR LL ENCLOSURE F <N> OPENING BEYOND SONRY WALL TO REMAIN, RE: OR TO REMAIN D BASE - PT TO MATCH <E> 2 Side door on the liftrequires a clearopening width of 42"minimum. ICCA117.1-2009 410.2.1 08/21/2019 File Name: 2019.06.14 Pitkin Permit - Architectural.pdf Author: bonniem Subject: PlanCheck Color: Page Label: A9.2 INTERIOR ELEVATIONS Knee and toe clearances must be provided at the jury deliberation sinks. ICC A117.1-2009 606.2 File Name: 2019.06.14 Pitkin Permit - Architectural.pdf Author: bonniem Subject: PlanCheck Color: Page Label: A9.2 INTERIOR ELEVATIONS A parallel approach to the sink is required when knee/toe clearances are not provided. ICC A117.1-2009 606.2 exception 1. The dishwasher in the open position cannot encroach into the clear floor space of the sink 804.5.3. File Name: 2019.06.14 Pitkin Permit - Architectural.pdf Author: bonniem Subject: PlanCheck Color: Page Label: A9.7 INTERIOR ELEVATIONS - DA A parallel approach to the sink is required when knee/toe clearances are not provided. ICC A117.1-2009 606.2 exception 1. File Name: 2019.06.14 Pitkin Permit - Architectural.pdf Author: bonniem Subject: PlanCheck Color: Page Label: G0.1 COVER SHEET Per information provided on the asbesos verification checklist this project requires an asbestos test. Provide an asbestos test report that includes the following: 1.Inspector’s narrative including sampling locations 2. Inspector’s certificate 3. Lab data If asbestos is found, a final air clearance report must be provided prior to building permit issuance. File Name: 2019.06.14 Pitkin Permit - Architectural.pdf Author: bonniem Subject: PlanCheck Color: Page Label: G0.1 COVER SHEET The special inspection agreement needs to be completed and signed by all parties prior to permit issuance. A9.22 1' - 11 1 / 2 " 2' - 6" 3" 2' - 1" 2A9.11Sim FINISHED FACE PANEL <E> COLUMN TO REMAIN, LOCATION V.I.F. 30" X 4 8 " CLEA R S P A C E (E) SIGNAGE, MODIFY TO ACCOMODATE (N) ROOM NAME, COMPLY W/ ADA PROVIDE <N> OR RELOCATED FLAG SIGNAGE AT THE FOLLOWING ROOMS:• 05• 102A• 105C• 108A• 101A• 201• 203 PROVIDE <N> OR RELOCATED WALL SIGNAGE TO MATCH EXISTING AT ALL ROOMS. SOLID SURFACE COUNTERTOP WITH INTEGRAL 4" BACKSPLASH 2A9.11SimSB30 FINISHED FACE PANEL; BEHIND COLUMN <E> COLUMN TO REMAIN, LOCATION V.I.F. FILLERFILLER BC30 BC30 DW24 SB36 3'-0" MIN. CLR 2' - 1"DW REF. 3A9.11Sim1A9.11Sim 2' - 10" 2' - 3" BC36BC36SB36DW24REF. ADJACENT STONE 3A9.11Sim 1A9.11Sim FILLER; SCRIBE TO ADJACENT STONE CABINET LEGEND BC =BASE CABINETSB=SINK BASE CABINETDW=DISHWASHERTC=TALL CABINETWC=WALL CABINETREF=REFRIGERATOR BC15 BC30 2' - 10" SOLID SURFACE COUNTERTOP WITH INTEGRAL 4" BACKSPLASH 2A9.11Sim FINISHED END PANELS A9.251' - 3" 2' - 6" 1"2' - 0 1/2" 2A9.11Sim FINISHED END PANEL 30" X 48 " CLEAR S P A C E FINISHED END PANEL Project Number DateDrawn byChecked by COPYRIGHT 2019ANY UNAUTHORIZED USE OF THESE DOCUMENT IS PROHIBITED WITHOUT THE WRITTEN CONSEN OF:ANDERSON HALLAS ARCHITECTS, P.C. PLANNING Issue 715 FOURTEENTH STREETGOLDEN, COLORADO 80401(303) 278-4378FAX (303) 278-0521 Scale AS NOT A9.2 INTERIORELEVATIONS 20179 PITKIN COUNTY COURTHOUSE REMODEL PITKIN COUNTY, CO 5/2/ LW RAS/NA 506 E Main St St 300, Aspen, CO 81611 PER 1/2" = 1'-0"1JURY DELIB. 03 ENLARGED PLAN DRAWINGS BASED ON FLOOR PLANS PROVIDED BY PITKIN COUNTY. CONTRACTOR TO NOTIFY ARCHITECT OF ANY DEVIATIONS FROM ACTUAL FIELD CONDITIONS, PRIOR TO COMMENCING WITH WORK. 0 2' 4' 1 1/2" = 1'-0"EXISTING SIGNAGE 1/2" = 1'-0"2JURY DELIB. 03 INTERIOR ELEVATION EAST 1/2" = 1'-0"6BREAK RM 02A ENLARGED PLAN 1/2" = 1'-0"7BREAK RM 02A INTERIOR ELEVATION SOUTH 1/2" = 1'-0"5JURY DELIB. 204 INTERIOR ELEVATION WEST 1/2" = 1'-0"4JURY DELIB. 204 ENLARGED PLAN 1 No. Description Dat 1 ADDENDUM 01 4/26/20 Knee and toeclearances must beprovided at the jurydeliberation sinks. ICC A117.1-2009606.2 A9.2 7 BC30 BC30 DW24 SB36 3'-0" MIN. CLR 2' - 1"DW REF. 3A9.11 Sim1A9.11 Sim 30" X 48" CLEAR SPACE 2' - 1 0 " WC24 WC30 WC30C36 BC36BC3636DW24 SOLID SURFACE COUNTERTOP WITH INTEGRAL 4" BACKSPLASH; SCRIBE TO ADJACENT STONE 3A9.11Sim 1A9.11 Sim FILLER; SCRIBE TO ADJACENT STONE FILLER; SCRIBE TO ADJACENT STONE BC15 BC30 2' - 1 0 " SOLID SURFACE COUNTERTOP WITH INTEGRAL 4" BACKSPLASH 2A9.11Sim FINISHED END PANELS A9.251' - 3 " 2' - 6 " 1"2' - 0 1/2" 2A9.11Sim FINISHED END PANEL 30" X 4 8 " CLEA R S P A C E FINISHED END PANEL Anderson HallasArchitects, PCARCHITECTUREHISTORIC PRESERVATION COPYRIGHT 2019ANY UNAUTHORIZED USE OF THESE DOCUMENTS IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF:ANDERSON HALLAS ARCHITECTS, P.C. PLANNING715 FOURTEENTH STREETGOLDEN, COLORADO 80401(303) 278-4378FAX (303) 278-0521 PITKIN COUNTY OURTHOUSE REMODEL PITKIN COUNTY, CO 506 E Main St St 300, Aspen, CO 81611 1/2" = 1'-0"6 BREAK RM 02A ENLARGED PLANA INTERIOR ELEVATION SOUTH LIB. 204 INTERIOR ELEVATION WEST 1/2" = 1'-0"4 JURY DELIB. 204 ENLARGED PLAN A parallel approach tothe sink is requiredwhen knee/toeclearances are notprovided. ICCA117.1-2009 606.2exception 1. Thedishwasher in theopen position cannotencroach into the clearfloor space of the sink804.5.3. WC36 WC12WC36 BC24BC24SB36 SOLID SURFACE COUNTERTOP WITH INTEGRAL 4" BACKSPLASH 1A9.11 Sim2A9.11 Sim CABINET LEGE BC =BASE CABINETSB=SINK BASE CABINET DW =DISHWASHER TC =TALL CABINETWC=WALL CABINET REF =REFRIGERATOR A9.7 2 3 BC24 TC30 SB36 2' - 0" CLR.BC24 1' - 10" 1' - 10" 2A9.11 Sim 1A9.11 Sim 1A9.11Sim30" X 48" CLEAR SPACE REF.2' - 0" APT. SIZE REF. PROVIDED BY OWNER EQ EQ 101F 101F DRAWINGS BASED ON FLOO PROVIDED BY PITKIN COUNTY TO NOTIFY ARCHITECT OF AN FROM ACTUAL FIELD CONDIT COMMENCING WITH WORK. 0 2' = 1'-0"101 INTERIOR ELEVATION NORTH 1/2" = 1'-0"1DA 101 ENLARGED PLAN 1/2" = 1'-0"4DA OFFICE 101 NORTH A parallel approach tothe sink is requiredwhen knee/toeclearances are notprovided. ICCA117.1-2009 606.2exception 1. And Arc AR HISTORI COPYRIGHT 2019ANY UNAUTHORIZ IS PROHIBITED W OF:ANDERSON HALL P 715 FO GOLDE FA Per information provided on the asbesos verification checklist this project requires an asbestos test. Provide an asbestos test report that includes the following: 1.Inspector’s narrative including sampling locations 2. Inspector’s certificate 3. Lab data If asbestos is found, a final air clearance report must be provided prior to building permit issuance. An A A HISTOR COPYRIGHT 20 ANY UNAUTHOR IS PROHIBITED OF:ANDERSON HA 715 GOL The special inspection agreement needs to be completed and signed by all parties prior to permit issuance. 08/21/2019 File Name: 2019.06.14 Pitkin Permit - Architectural.pdf Author: bonniem Subject: PlanCheck Color: Page Label: G0.3 GENERAL INFORMATION / EGRESS PLAN Provide the full installation instructions from the Gypsum Manual for WP 1072, WP 3510, WP 6800, FC3510 in the plan set for reference at inspection. NEW ACCESSIBLE ENTRANCE MAX TRAVEL DISTANCE: 57' 1231 / 40SF / OCC= 31 OCC DELAYED EGRESS DOOR. PROVIDE WEATHER PROOF SIGNAGE: PUSH UNTIL ALARM SOUNDS, DOOR CAN BE OPENED IN 15 SECONDS FEC FEC AX TRAVEL DISTANCE: 115' EC FEC FECFEC FEC FEC MAX TRAVEL DISTANCE: 125' FEC LEGEND FEC EGRESS PATHEGRESS DOOR WITH EXIT SIGNAGE FIRE EXTINGUISHER CABINETEXIT SIGNAGE, RE: ELEC TRAVEL DISTANCEBUILDING DIAGONAL DISTANCESIGNAGE: EMERGENCY EXIT ONLY, ALARM WILL SOUND UNLESS ACTIVATED BY KEY CARD WALL TYPES X A TYPE GRAPHIC REPRESENTATION FIRE RATING NA5/8" GWB5 1/2" WD STUDS AT 16" OCFULL DEPTH MINERAL WOOL ACOUSTIC INSULATION5/8" GWB6 3/4" B NA5/8" GWB5 1/2" WD STUDS AT 16" OCFULL DEPTH MINERAL WOOL ACOUSTIC INSULATION3/8" PORCELAIN TILE, 5/8" CTBB / 5/8" MOISTURE RESISTANT GWB ABOVE6 3/4" C: SECURE WALLS NA1/2" PLYWOOD5 1/2" WD STUDS AT 16" OCFULL DEPTH MINERAL WOOL ACOUSTIC INSULATION1/2" PLYWOOD SHEATHING RR SIDE 5/8" IMPACT RESISTANT GWB 5/8" IMPACT RESISTANT GWB D: PLUMB. CHASE WALLS 5 1/2" WD STUDS AT 16" OCFULL DEPTH MINERAL WOOL ACOUSTIC INSULATION3/8" PORCELAIN TILE, 5/8" CTBB / 5/8" MOISTURE RESISTANT GWB 7 3/4" 6 1/8" RR SIDE 2 1/8"E: NA NA 5/8" GWB1 1/2" WD FURRING AT 16" OCFULL DEPTH MINERAL WOOL ACOUSTIC INSULATION PUBLIC SECURE F: ACOUSTIC ISOLATION NA 5/8" GWB5 1/2" STAGGERED WD STUDS AT 8" OC FULL DEPTH MINERAL WOOL ACOUSTIC INSULATION RUNNING CONTINUOUSLY IN BETWEEN STUDS5/8" GWB 7 3/4"1" SPACE IN BETWEEN STUDS AND GWB, BOTH SIDES G: MASONRY INFILL NAMASONRY INFILL, RE: STRUCT.WD STUD S AT 16"O.C., ADJUST FURRING TO PROVIDE FLUSH FINISH 5/8" IMPACT RESISTANT GWB 5/8" IMPACT RESISTANT GWB VARIES WD STUD S AT 16"O.C., ADJUST FURRING TO PROVIDE FLUSH FINISH H: SHAFT WALLGA FILE #:WP 6800 1" X 24" PROPRIETARY TYPE X GYPSUM PANELS INSERTED BETWEEN 2 1/2" FLOOR AND CEILING RUNNERS WITH T SECTION OF 2 1/2" STEEL C-T STUDS BETWEEN PANELSONE LAYER 5/8' PROPRIETARY TYPE X GYPSUM WALLBOARD APPLIED PARALLEL TO STUDS WITH 1" TYPE S DRYWALL SCREWS 12" O.C. 3 1/8"1HR 5 1/4"I: DATA CABINET WALL NA 5/8" GWB1/2" PLYWD SHEATHINGFULL DEPTH MINERAL WOOL ACOUSTIC INSULATIONDATA SECURE 5/8" GWB3 1/2" WD STUDS AT 16" OC GENERAL: GENERAL ALL WALL TYPES, GWB BD TO EXTEND TO STRUCTURE NOTE: WHERE (1) HR FIRE RATING IS REQUIRED STEEL FRAMING GA FILE: WP1072WOOD FRAMING GA FILE: WP3510 1. DO NOT SCALE DRAWINGS2. ALL WORK TO BE PERFORMED TO APPLICABLE BUILDING CODES.3. ALL DIMENSIONS ARE TO FACE OF FINISH UNLESS OTHERWISE NOTED. ALL DIMENSIONS INDICATING REQUIRED CLEARANCES ARE TO FACE OF FINISH UNLESS OTHERWISE NOTED.4. THE CONTRACTOR SHALL BE RESPONSIBLE FOR FAMILIARIZING HIM OR HERSELF WITH THE CONTRACT DOCUMENTS, VERIFYING FIELD CONDITIONS AND DIMENSIONS, AND CONFIRMING THAT THE WORK MAY BE ACCOMPLISHED AS SHOWN PRIOR TO PROCEEDING WITH CONSTRUCTION. CONTRACTOR SHALL NOTIFY ARCHITECT IN WRITING OF ANY DISCREPANCY WITHIN THE CONTRACT DOCUMENTS AND REQUEST CLARIFICATION PRIOR TO PROCEEDING WITH CONSTRUCTION.5. SHOULD THERE BE ANY QUESTIONS CONCERNING THE CONTRACT DOCUMENTS, EXISTING CONDITIONS, AND/OR DESIGN INTENT, THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING A CLARIFICATION FROM THE ARCHITECT PRIOR TO PROCEEDING WITH THE WORK, OR RELATED WORK IN QUESTION.6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR FAMILIARIZING HIMSELF WITH THE PROJECT SCOPE OF WORK, SCHEDULE, AND DEADLINES. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ADVISING THE ARCHITECT OF ALL ITEMS REQUIRING A LONG LEAD TIME UPON NOTICE TO PROCEED THAT WILL AFFECT THE SCHEDULE, AND SHALL SUBMIT ORDER CONFIRMATIONS AND DELIVERY DATES FOR THE ITEMS IN QUESTION TO THE OWNER.7. INSTALL ALL MANUFACTURED ITEMS, MATERIALS, AND EQUIPMENT IN STRICT ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDED SPECIFICATIONS, EXCEPT WHERE THE CONTRACT DOCUMENTS ARE MORE STRINGENT. ANY MISCELLANEOUS ITEMS OR MATERIALS NOT SPECIFICALLY NOTED, BUT REQUIRED FOR PROPER INSTALLATION SHALL BE FURNISHED AND INSTALLED BY THE CONTRACTOR. THE CONTRACTOR SHALL FURNISH TO THE OWNER ALL WARRANTIES AND GUARANTEES REQUIRED AT THE CONCLUSION OF THE PROJECT.8. ALL CONTRACTOR OR SUPPLIER REQUESTS FOR SUBSTITUTIONS OF SPECIFIED ITEMS SHALL BE SUBMITTED IN WRITING TO THE ARCHITECT WITHIN 14 DAYS OF NOTICE TO PROCEED, AND BE ACCOMPANIED WITH THE ALTERNATIVE PRODUCT INFORMATION. SUBSTITUTIONS WILL BE CONSIDERED ONLY IF IT DOES NOT SACRIFICE QUALITY, APPEARANCE, DELIVERY TIME, OR FUNCTION.9. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL HOOK UPS / UTILITY CONNECTIONS, ETC. TO TEMPORARY TRAILERS. GENERAL NOTES CEILING TYPES X TYPE GRAPHIC REPRESENTATION FIRE RATING GARDEN LEVEL CEILING ASSEMBLYGA FILE # 5310 ONE LAYER 5/8" TYPE X GYPSUM WALLBOARD OR GYPSUM VENEER BASE APPLIED AT RIGHT ANGLES TO RIGID FURRING CHANNELS 24" O.C. WITH 1" TYPE S DRYWALL SCREWS 12 O.C. GYPSUM BOARD END JOINTS LOCATED MIDWAY BETWEEN CONTINUOUS CHANNELS AND ATTACHED TO ADDITIONAL PIECES OF CHANNEL 60" LONG WITH SCREWS 12" O.C. RIGID FURRING CHANNELS APPLIED AT RIGHT ANGLES TO 4 X 10 OR DOUBLE 2 X 10 WOOD JOISTS 48" O.C. WITH TWO 1 1/4" TYPE S DRYWALL SCREWS AT EACH JOIST. WOOD JOISTS SUPPORTING 1 1/8" T &G PLYWOOD FLOOR. 1 5/8"1HR Project NumberDateDrawn byChecked by Anderson HallasArchitects, PCARCHITECTUREHISTORIC PRESERVATION COPYRIGHT 2019ANY UNAUTHORIZED USE OF THESE DOCUMENTS IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF:ANDERSON HALLAS ARCHITECTS, P.C. PLANNING Issue 715 FOURTEENTH STREETGOLDEN, COLORADO 80401(303) 278-4378FAX (303) 278-0521 Scale AS NOTED G0.3 GENERALINFORMATION /EGRESS PLAN 2017910 PITKIN COUNTY COURTHOUSE REMODEL PITKIN COUNTY, CO 5/2/19LWBRAS/NAA 506 E Main St St 300, Aspen, CO 81611 PERMIT 1/16" = 1'-0"1GARDEN LEVEL EGRESS PLAN6" = 1'-0"AIN LEVEL EGRESS PLAN 16" = 1'-0"ECOND LEVEL EGRESS PLAN DRAWINGS BASED ON FLOOR PLANS PROVIDED BY PITKIN COUNTY. CONTRACTOR TO NOTIFY ARCHITECT OF ANY DEVIATIONS FROM ACTUAL FIELD CONDITIONS, PRIOR TO COMMENCING WITH WORK. 10.10.12 DIRECTION OF SWING PIVOT OR SIDE-HINGED SWINGING DOORS SHALL SWING IN THE DIRECTION OF EGRESS TRAVEL WHEN SERVING A ROOM OR AREA CONTAINING AN OCCUPANCY LOAD OF 50 OR MORE PERSONS. 119'-10"/3 = 39'-11" 45'-5" 119'-10"/3 = 39'-11" 52'-11"119'-10"/3 = 39'-11" 59'-10" No. Description Date1 ADDENDUM 01 4/26/20193 ADDENDUM 03 6/12/2019 3 1 Provide the full installationinstructions from the GypsumManual for WP 1072, WP3510, WP 6800, FC3510 in theplan set for reference atinspection. 08/21/2019 NEW ACCESSIBLE ENTRANCE MAX TRAVEL DISTANCE: 57' 1144 / 40SF / OCC = 32 OCC DELAYED EGRESS DOOR. PROVIDE WEATHER PROOF SIGNAGE: PUSH UNTIL ALARM SOUNDS, DOOR CAN BE OPENED IN 15 SECONDS FEC FEC MAX TRAVEL DISTANCE: 115' FEC FEC FEC FEC FEC FEC MAX TRAVEL DISTANCE: 125' FEC LEGEND FEC EGRESS PATH EGRESS DOOR WITH EXIT SIGNAGE FIRE EXTINGUISHER CABINET EXIT SIGNAGE, RE: ELEC TRAVEL DISTANCE BUILDING DIAGONAL DISTANCE SIGNAGE: EMERGENCY EXIT ONLY, ALARM WILL SOUND UNLESS ACTIVATED BY KEY CARD WALL TYPES X A TYPE GRAPHIC REPRESENTATION FIRE RATING NA WP1072: ONE LAYER 5/8" TYPE X GYPSUM WALLBOARD OR GYPSUM VENEER BASE APPLIED PARALLEL OR AT RIGHT ANGLES TO EACH SIDE OF 3 5/8" STEEL STUDS 24" O.C. WITH 1" TYPE S DRYWALL SCREWS 8" O.C. AT VERTICAL JOINTS AND 12" O.C. AT FLOOR AND CEILING RUNNERS AND INTERMEDIATE STUDS. JOINTS STAGGERED 24" ON EACH SIDE AND ON OPPOSITE SIDES. SOUND TESTED WITH 3 1/2" GLASS FIBER FRICTION FIT IN STUD SPACE. WP3510: ONE LAYER 5/8" TYPE X GYPSUM WALLBOARD OR GYPSUM VENEER BASE APPLIED PARALLEL OR AT RIGHT ANGLES TO EACH SIDE OF 2X4 WOOD STUDS 24" O.C. WITH 6D COATED NAILS, 1 7/8" LONG, 0.0915" SHANK, 1/4" HEADS, 7" O.C. JOINTS STAGGERED 24" ON OPPOSITE SIDES. 5 1/2" WD STUDS AT 16" OC FULL DEPTH MINERAL WOOL ACOUSTIC INSULATION 6 3 / 4 " B NA 5/8" GWB 5 1/2" WD STUDS AT 16" OC FULL DEPTH MINERAL WOOL ACOUSTIC INSULATION 3/8" PORCELAIN TILE, 5/8" CTBB / 5/8" MOISTURE RESISTANT GWB ABOVE 6 3 / 4 " C: SECURE WALLS NA 1/2" PLYWOOD 5 1/2" WD STUDS AT 16" OC FULL DEPTH MINERAL WOOL ACOUSTIC INSULATION 1/2" PLYWOOD SHEATHING RR SIDE 5/8" IMPACT RESISTANT GWB 5/8" IMPACT RESISTANT GWB D: PLUMB. CHASE WALLS 5 1/2" WD STUDS AT 16" OC FULL DEPTH MINERAL WOOL ACOUSTIC INSULATION 3/8" PORCELAIN TILE, 5/8" CTBB / 5/8" MOISTURE RESISTANT GWB 7 3 / 4 " 6 1 / 8 " RR SIDE 2 1 / 8 " E: NA NA 5/8" GWB 1 1/2" WD FURRING AT 16" OC FULL DEPTH MINERAL WOOL ACOUSTIC INSULATION PUBLIC SECURE F: ACOUSTIC ISOLATION NA 5/8" GWB 5 1/2" STAGGERED WD STUDS AT 8" OC FULL DEPTH MINERAL WOOL ACOUSTIC INSULATION RUNNING CONTINUOUSLY IN BETWEEN STUDS 5/8" GWB 7 3 / 4 " 1" SPACE IN BETWEEN STUDS AND GWB, BOTH SIDES G: MASONRY INFILL NAMASONRY INFILL, RE: STRUCT. WD STUD S AT 16"O.C., ADJUST FURRING TO PROVIDE FLUSH FINISH 5/8" IMPACT RESISTANT GWB 5/8" IMPACT RESISTANT GWB VA R I E S WD STUD S AT 16"O.C., ADJUST FURRING TO PROVIDE FLUSH FINISH H: SHAFT WALL GA FILE #:WP 6800 ONE LAYER: 1" X 24" PROPRIETARY TYPE X GYPSUM PANELS INSERTED BETWEEN 2 1/2" FLOOR AND CEILING RUNNERS WITH T SECTION OF 2 1/2" STEEL C-T STUDS BETWEEN PANELS OPPOSITE SIDE: ONE LAYER 5/8" PROPRIETARY TYPE X GYPSUM WALLBOARD APPLIED PARALLEL TO STUDS WITH 1" TYPE S DRYWALL SCREWS 12" O.C. 3 1 / 8 " 1HR 5 1 / 4 " I: DATA CABINET WALL NA 5/8" GWB 1/2" PLYWD SHEATHING FULL DEPTH MINERAL WOOL ACOUSTIC INSULATION DATA SECURE 5/8" GWB 3 1/2" WD STUDS AT 16" OC GENERAL: GENERAL ALL WALL TYPES, GWB BD TO EXTEND TO STRUCTURE NOTE: WHERE (1) HR FIRE RATING IS REQUIRED STEEL FRAMING GA FILE: WP1072 WOOD FRAMING GA FILE: WP3510 4 4 1. DO NOT SCALE DRAWINGS 2. ALL WORK TO BE PERFORMED TO APPLICABLE BUILDING CODES. 3. ALL DIMENSIONS ARE TO FACE OF FINISH UNLESS OTHERWISE NOTED. ALL DIMENSIONS INDICATING REQUIRED CLEARANCES ARE TO FACE OF FINISH UNLESS OTHERWISE NOTED. 4. THE CONTRACTOR SHALL BE RESPONSIBLE FOR FAMILIARIZING HIM OR HERSELF WITH THE CONTRACT DOCUMENTS, VERIFYING FIELD CONDITIONS AND DIMENSIONS, AND CONFIRMING THAT THE WORK MAY BE ACCOMPLISHED AS SHOWN PRIOR TO PROCEEDING WITH CONSTRUCTION. CONTRACTOR SHALL NOTIFY ARCHITECT IN WRITING OF ANY DISCREPANCY WITHIN THE CONTRACT DOCUMENTS AND REQUEST CLARIFICATION PRIOR TO PROCEEDING WITH CONSTRUCTION. 5. SHOULD THERE BE ANY QUESTIONS CONCERNING THE CONTRACT DOCUMENTS, EXISTING CONDITIONS, AND/OR DESIGN INTENT, THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING A CLARIFICATION FROM THE ARCHITECT PRIOR TO PROCEEDING WITH THE WORK, OR RELATED WORK IN QUESTION. 6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR FAMILIARIZING HIMSELF WITH THE PROJECT SCOPE OF WORK, SCHEDULE, AND DEADLINES. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ADVISING THE ARCHITECT OF ALL ITEMS REQUIRING A LONG LEAD TIME UPON NOTICE TO PROCEED THAT WILL AFFECT THE SCHEDULE, AND SHALL SUBMIT ORDER CONFIRMATIONS AND DELIVERY DATES FOR THE ITEMS IN QUESTION TO THE OWNER. 7. INSTALL ALL MANUFACTURED ITEMS, MATERIALS, AND EQUIPMENT IN STRICT ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDED SPECIFICATIONS, EXCEPT WHERE THE CONTRACT DOCUMENTS ARE MORE STRINGENT. ANY MISCELLANEOUS ITEMS OR MATERIALS NOT SPECIFICALLY NOTED, BUT REQUIRED FOR PROPER INSTALLATION SHALL BE FURNISHED AND INSTALLED BY THE CONTRACTOR. THE CONTRACTOR SHALL FURNISH TO THE OWNER ALL WARRANTIES AND GUARANTEES REQUIRED AT THE CONCLUSION OF THE PROJECT. 8. ALL CONTRACTOR OR SUPPLIER REQUESTS FOR SUBSTITUTIONS OF SPECIFIED ITEMS SHALL BE SUBMITTED IN WRITING TO THE ARCHITECT WITHIN 14 DAYS OF NOTICE TO PROCEED, AND BE ACCOMPANIED WITH THE ALTERNATIVE PRODUCT INFORMATION. SUBSTITUTIONS WILL BE CONSIDERED ONLY IF IT DOES NOT SACRIFICE QUALITY, APPEARANCE, DELIVERY TIME, OR FUNCTION. 9. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL HOOK UPS / UTILITY CONNECTIONS, ETC. TO TEMPORARY TRAILERS. GENERAL NOTES CEILING TYPES X TYPE GRAPHIC REPRESENTATION FIRE RATING GARDEN LEVEL CEILING ASSEMBLY GA FILE # 5310 ONE LAYER 5/8" TYPE X GYPSUM WALLBOARD OR GYPSUM VENEER BASE APPLIED AT RIGHT ANGLES TO RIGID FURRING CHANNELS 24" O.C. WITH 1" TYPE S DRYWALL SCREWS 12 O.C. GYPSUM BOARD END JOINTS LOCATED MIDWAY BETWEEN CONTINUOUS CHANNELS AND ATTACHED TO ADDITIONAL PIECES OF CHANNEL 60" LONG WITH SCREWS 12" O.C. RIGID FURRING CHANNELS APPLIED AT RIGHT ANGLES TO 4 X 10 OR DOUBLE 2 X 10 WOOD JOISTS 48" O.C. WITH TWO 1 1/4" TYPE S DRYWALL SCREWS AT EACH JOIST. WOOD JOISTS SUPPORTING 1 1/8" T &G PLYWOOD FLOOR. 1 5 / 8 " 1HR Project Number Date Drawn by Checked by Anderson Hallas Architects, PC ARCHITECTURE HISTORIC PRESERVATION COPYRIGHT 2019 ANY UNAUTHORIZED USE OF THESE DOCUMENTS IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF: ANDERSON HALLAS ARCHITECTS, P.C. PLANNING Issue 715 FOURTEENTH STREET GOLDEN, COLORADO 80401 (303) 278-4378 FAX (303) 278-0521 Scale AS NOTED 8/ 1 4 / 2 0 1 9 6 : 1 6 : 0 0 P M G0.3 GENERAL INFORMATION / EGRESS PLAN 2017910 PITKIN COUNTY COURTHOUSE REMODEL PITKIN COUNTY, CO 5/2/19 LWB RAS/NAA 506 E Main St St 300, Aspen, CO 81611 PERMIT 1/16" = 1'-0"1 GARDEN LEVEL EGRESS PLAN 1/16" = 1'-0"2 MAIN LEVEL EGRESS PLAN 1/16" = 1'-0"3 SECOND LEVEL EGRESS PLAN DRAWINGS BASED ON FLOOR PLANS PROVIDED BY PITKIN COUNTY. CONTRACTOR TO NOTIFY ARCHITECT OF ANY DEVIATIONS FROM ACTUAL FIELD CONDITIONS, PRIOR TO COMMENCING WITH WORK. 10.10.12 DIRECTION OF SWING PIVOT OR SIDE-HINGED SWINGING DOORS SHALL SWING IN THE DIRECTION OF EGRESS TRAVEL WHEN SERVING A ROOM OR AREA CONTAINING AN OCCUPANCY LOAD OF 50 OR MORE PERSONS. 119'-10"/3 = 39'-11" 45'-5" 119'-10"/3 = 39'-11" 52'-11" 119'-10"/3 = 39'-11" 59'-10" No. Description Date 1 ADDENDUM 01 4/26/2019 3 ADDENDUM 03 6/12/2019 4 BUILDING COMMENTS 8/14/2019 3 1 4 08/21/2019 Project Number Date Drawn by Checked by Anderson Hallas Architects, PC ARCHITECTURE HISTORIC PRESERVATION COPYRIGHT 2019 ANY UNAUTHORIZED USE OF THESE DOCUMENTS IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF: ANDERSON HALLAS ARCHITECTS, P.C. PLANNING Issue 715 FOURTEENTH STREET GOLDEN, COLORADO 80401 (303) 278-4378 FAX (303) 278-0521 Scale AS NOTED 8/ 1 4 / 2 0 1 9 6 : 1 6 : 0 3 P M G0.4 CODE SUMMARY 2017910 PITKIN COUNTY COURTHOUSE REMODEL PITKIN COUNTY, CO 5/2/19 LWB RAS/NAA 506 E Main St St 300, Aspen, CO 81611 PERMIT BUILDING CODE ANALYSIS • 705.1 General. A facility that is altered shall comply with the applicable provisions in section 705.1 through 705.1.14 and Chapter 11 of the International Building Code unless it is technically infeasible, the alteration shall provide access to the maximum extent that is technically feasible. A facility that is constructed or altered to be accessible shall be maintained accessible during occupancy. 2015 International Building Code OCCUPANCY A-3 B CONSTRUCTION Type III B Type IIB Construction: Construction is that type of construction in which they exterior walls are of non- combustible;e material and interior building elements are of any material permitted by code. FLOOR AREA ACTUAL FLOOR AREA Floor A-3 B Total Garden Level 1,473 3,827 5,300 First Floor 4,931 4,931 Second Floor 4,780 1,157 5,937 Total Area (sf)6,253 9,915 16,168 ALLOWABLE FLOOR AREA Allowable Area Limitations, Table 506.2: Allowable Area for Type III B, Occupancy A-3 = 8,000 sf/story Allowable Area for Type III B, Occupancy B = 76,000,000 sf/story FLOOR AREA COMPLIANCE BUILDING HEIGHT ACTUAL BUILDING HEIGHT ALLOWABLE BUILDING HEIGHT Maximum Height and Stories Limitations, Table 504.3: For III B, A-3, maximum allowable building height = 75 feet For III B, B, maximum allowable building height = 75 feet; maximum Actual Building Height *45 feet -7 inches * +/-70 feet with tower Building Complies with Code OCCUPANCY AREA and LOAD Table 1004.1.2 Garden Level Area Occupancy Type Area Load Factor Occ Load Office 3,837 Business 100 39 Court Room 1,244 Courtroom 40 32 Main Level Office 4,931 Business 100 31 Second Level Office 1,158 Business 100 12 District Court 2,444 Courtroom 40 62 County Court 1,087 Courtroom 40 28 Total 204 Section 1007.1.1 Two Exits or Exit Access Doorways: Where two exits or exit access doorways are required from any portion of the exit access, the exit doors or exit access doorways shall be placed a distance apart to not less than one-half of the length of the maximum overall diagonal dimension of the building or area to be served measured in a straight line between exit doors or exit access doorways. Exception 2. Where buildings are equipped throughout with an automatic sprinkler system in accordance with section 903.3.1.1 or 903.3.1.2. The separation distance shall be not less than one-third of the length of the maximum overall dimension of the area served. Area Allowable Diagonal Min Distance Actual Exit Distance Garden Level 119'-10"39'-11"59'-10" First Level 119'-10"39'-11"52'-11" Second Level 119'-10"39'-11"45'-5" Restrooms 2902.1 Minimum number of required plumbing facilities Occupancy A3 B men = 136 women = 136 Fixtures Ratio Number Req'd Provide Water Closet male 1/25 for the first 50 1/50 exceeding 50 4 3 WC 1 urinal female 1/25 for the first 50 1/50 exceeding 50 4 5 WC Lavatories male 1/40 for the first 80 1/80 exceeding 80 4 3 female 1/40 for the first 80 1/80 exceeding 80 4 3 Drinking Fountain 1/100 1 2 Service Sink 1 1 Unisex 5 WC 5 Lavs Building Complies with Code if unisex fixtures can be counted towards the total required fixtures. 2015 International Energy Conservation Code Table C301.1 Pitkin zone 7 C402.1 Building Envelope Fenestration U Factor zone 7 Entrance Doors 0.77 SHGC SEW 0.45 Date:2019.03.15 Analysis By: Andy Duckett-Emke Project Number:2017910 Project Name: Pitkin County Courthouse Code analysis is based: 2015 International Building Code 2015 International Existing Building Code 2015 International Mechanical Code 2015 International Plumbing Code 2015 International Energy Conservation Code 2017 International Electrical Code 2015 International Existing Building Code Section 505 505.1 Scope. Level 3 alterations apply where the work area exceeds 50 percent of the building area. 505.2 Application, Level 3 alterations shall comply with the provisions of Chapters 7 and 8 for level 1 and level 2 alterations, respectively, as well as the provisions of Chapter 9. • 803.2.1 Existing Vertical Opening: All existing interior openings shall comply with the provision of this section 803.2.1, 803.2.2 and 803.2.3 1. 803.2.1 Existing Vertical Openings. All existing interior vertical openings connection two or more floors shall be enclosed with approved assemblies having a fire resistance rating of not less than (1) hour with an approved opening protective. exception 3: The enclosure shall not be required where : 3.1 connects the main floor and mezzanine. Provide (1) hour door at door 100 from Garden Level / Main Level door on magnetic hold opens. • 804.1 scope: The requirements of this section shall be limited to work areas in which Level 2 Alterations are being performed and where specified they shall apply throughout the story. The required fire-resistance rating for any corridor located on the story shall be permitted to be reduced in accordance with the International Building Code. In order to be considered for a corridor rating reduction, such system shall provide coverage for the stairway landing serving the floor and intermediate landings immediately below. • 805.3 Number of Exits: The number of exits shall be in accordance with Section 805.31 through 805.3.3 • 805.3.1 Minimum Number. Every story utilized for human occupancy on which there is a work area that includes exits or corridors shared by more than one tenant within the work area shall be provided with the minimum number of exits based on the occupancy and the occupant load in accordance withe the International Building Code. In addition the exits shall comply with the Section 805.3.1.1 (2) exits shall be provided at each level. • 805.3.1.2 Fire Escapes Required: For other than group I-2 where more than (1) exit is required, and existing or newly or constructed fire escape comply with this section 805.3.1.2 shall be accepted as providing one of the required means of egress. 4. Openings within 10 feet of fire escape stairways shall be protected by fire assemblies having a minimum 3/4 hour fire resistance rating. exception: Opening protection shall not be required in buildings equipped throughout with an approved automatic fire sprinkler. Existing openings are within 4'-6" of the proposed new egress. Building is equipped throughout with an automatic fire suppression system. • 805.4.4 Panic Hardware: In any work area and in the egress path for any work area to the exit discharge in buildings or portions thereof of group A occupancy with an occupant load greater than 100. All required exit doors equipped with latching devices shall be equipped with approved panic hardware. Provide panic hardware at all existing doors in the patch of egress. • 805.9 Requirement if section 805.9.1 and 805.9.2 shall apply to handrails from the work floor area to and including the level of the exit of discharge. • 805.9.1 Minimum Requirement. Every required exit stairway that is part of the means of egress for any work area that has three or more risers and is not provided with at least one handrail , or in which the existing handrails are judged to e in danger of collapse, shall be provided with handrails for the length of the stairway on at least one side. All egress stairways with a required egress width of more than 66 inches shall have handrails on both sides. Existing stair is 61 inches wide. Provide new code compliant handrail to wall Stair to second level is 102 inches wide. Provide new code compliant handrail at center of stair. • 805.11 Guards. The requirement of section 805.11.1 and 805.11.2 shall apply to guards from the work area floor and including the level of exit of discharge shall be confined to egress path of an work area. • 805.11.1 Minimum Requirements. Every open portion of a stairway landing, or balcony that is more than 30 inches above the floor or grade below and is not provided with guards or those portions in which existing guards are judged in danger of collapse, shall be provided with guards. Existing guard rails at second level are 32 inches tall and are not to code. Provide new code complaint guard at second level. • 901.2 Compliance. In addition to the provisions of this chapter, work shall comply with all of the requirements of Chapters 7 and 8. The requirements of Sections 803, 804 and 805 shall apply within all work areas whether or not they include exits and corridors shared by more than one tenant and regardless of the occupant load. • 902.1.2 Elevators. Where these is an elevator or elevators for public use, at least one elevator serving the work area shall comply with this section. Existing elevators with a travel distance of 25 feet or more above or below the main floor or other level of a building and intended to serve the needs of emergency personnel for fire fighting or rescue purposed shall be provided with emergency operation in accordance with ASME A17.3. New elevators shall be provided with Phase I emergency recall operations and Phase II emergency in-car operation in accordance with ASME A17.1. • 903.1 Existing shafts and vertical openings. Existing stairway that are part of the means of egress shall be enclosed in accordance with Section 803.2.1 from the highest work area floor to and including, the level of exit discharge and all floors below. The Main and Second Level are connected by an existing open stair. The Garden and Main level are not separated by one- hour construction. Provide a one hour enclosure between the Garden Level and Main Level. • 904.1 Automatic sprinkler system. An automatic sprinkler system shall be provided in a work area where required by Section 804.2 of this section. • 804.2 Groups A,B,E,F1.H1,M,I,S1 and S2. In buildings with indicated occupancies, work areas that have exits or corridors shared by more than one tenant or that have exits or corridors serving an occupant load greater than 30 shall be provided with automatic sprinkler protection where all of the following conditions occur: 1. The work areas is required to be provided with automatic sprinkler protection in accordance with the International Building Code as applicable to new construction and. 2. The work areas exceed 50 percent of the floor area. The work area is required to be provided with an automatic sprinkler system in accordance with the International Building Code applicable to new constriction; and (E) Automatic sprinkler system to be modified via design build to accommodate (N) layout. • 904.2 Fire alarm and detection system. Fire alarm and detection shall be provided in accordance with Section 907 of the International Building Code as required for new construction. • (E) Fire alarm and detection system to be modified • 905.1 General. The means of egress shall comply with the requirements of Section 805 except as specifically required in Sections 905.2 and 905.3. see sections above • 905.2 Means of egress lighting. Means of egress from the highest work area floor to the floor of exit of discharge shall be provided with artificial lighting within the exit enclosure in accordance with the requirements of the International Building Code. • Emergency egress lighting to be provided, Re: Electrical • 905.3 Exit signs. Means of egress from the highest work area floor to the floor of exit discharge shall be provided with exit signs in accordance with the requirements of the International Building code. • 906.1 General. A building, facility or elements that is altered shall comply with this section and sections 705 and 806. BUILDING HEIGHT COMPLIANCE Building complies with building code BUILDING NUMBER OF STORIES ACTUAL BUILDING NUMBER OF STORIES = 3 ALLOWABLE BUILDING NUMBER OF STORIES Maximum Stories Limitations, Table 504.4: For III B, A-3, allowable stories = 3 For III B, B, maximum allowable stories = 4 BUILDING HEIGHT AND NUMBER OF STORIES COMPLIANCE Actual number of stories = 3 Building Complies with Code OTHER BUILDING ELEMENTS FIRE RATINGS Fire-Resistance Rating Requirements for Building Elements, Table 601: ELEMENT III B RATING Structural frame 0 hour Bearing walls Exterior 2 hour Interior 0 hour Non-bearing walls & partitions Exterior 0 hour Interior 0 hour Floor construction 0 hour Roof construction 0 hour OTHER BUILDING ELEMENTS FIRE RATINGS COMPLIANCE Building complies with code requirements. OCCUPANCY SEPARATIONS No separation required between occupancies based on: Non-separated Occupancies, Sec. 508.3.: Building or portions of buildings that comply with the provisions of this section shall be considered non-separated occupancies. 508.3.2 Allowable building area and height. The allowable building area and height of the building or portion thereof shall be based on the most restrictive allowances for the occupancy groups under consideration (for this building Occupancy A2 is assumed to be the most restrictive) for the type of construction of the building in accordance with Section 503.1. Building complies with code requirements. No. Description Date 4 BUILDING COMMENTS 8/14/2019 4 08/21/2019 176 SF BOILER 01A 72 SF MECH/ELEC 02D 35 SF JAN. 00A 98 SF STORAGE 00B 332 SF HOLDING 06 143 SF CONF. RM 08 87 SF JUDGE RR 14 709 SF COURTROOM 3 05 53 SF HALL 16 372 SF JURY DELIBERATION 03 13B 01 05A 17 ACCESSIBLE NEW WALK. RE: CIVIL 06 NF6 NF6 NF6NF6NF6 NF3 NF8UP U P UP UP UP 5' - 0 " UP NEW ACCESSIBLE CONC RAMP. MAX SLOPE 1:12. RE: CIVIL 102 SF WOMEN 00C 113 SF MEN 00D INFILL <E> OPENING, RE:STRUCT. M.O. 4' - 1"5' - 0 " 6' - 2 1/2" 5" A9.9 1 A9.8 2 A4.0 2 47 SF STORAGE 15 70 SF SECURE HALL 13 49 SF ELEV. MECH. 00E A7.3 1 55 SF VEST. 03A 122 SF ATTORNEY 01 615 SF HALL 00 110 SF HALL 09 59 SF HALL 10 408 SF VISITING JUDGE'S CHAMBERS 04 49 SF HALL 05A <N> RAISED PLATFORM FOR JUDGE'S BENCH 06A 06B 85 SF ATTORNEY 06A 20 SF MECH. 06B 4' - 6 " NF6 NF9NF9 NF9 NF9 03 49 SF JURY RR 07 07 89 SF ALPINE LEGAL 02E 116 SF OFFICE 1 02C 103 SF OFFICE 2 02B 197 SF BREAK ROOM 02A 85 SF VEST. 02 02C02B 02A 02E DW 55 SF ELEV. 11 UP UP UP A A B B A A A A A A C F A C <N> CABINET A7.5 1 A9.12 1 F C ALIGN 9' - 2 " R.O. 3' - 2" 5 1/2" 13A 08 A4.0 1 13' - 4 1/2" 2' - 10" 8' - 2" 10 ' - 6 " 8' - 1 1/2" R.O. 3' - 2"4' - 5 1/2" 3' - 11 1/2" 6' - 1 1 " 12' - 5" 6' - 1 1 1 / 2 " 5' - 8" 9 1 / 2 " 5" R.O. 3' - 2" 5" 13' - 3" 7" D ALIGN 100' - 0" 100' - 0" A7.1 1 76 SF LOWER LIFT LOBBY 17 A9.2 1 A I NF10 NF10 04 12 00 09 M.O. 3' - 4" 3' - 5" R.O. 3' - 2" 1' - 5" R.O. 3' - 2" 1' - 5" 1' - 6" 10' - 0" R.O. 3' - 2" 8 1/2" R.O. 3' - 2" R.O. 3' - 2" HOLD 1' - 0" R.O. 3' - 2" R.O.' 3' - 2" R.O. 3' - 2"1' - 4" R.O. 3' - 2" R.O. 3' - 2" 1' - 0"1' - 0" ALIGN F.O. <N> WALL WITH CENTER LINE OF <E> COLUMN. NF15 1' - 6" FIN. 4' - 6" 00B 00A 00E 05 04A00D 00C 02D 01A HOLD 3' - 6" 16 F 18 REF. D D NF20 NF20 06B 05A 05B 05C 05D 05E 06C 06A06D 06E NF6 NF6NF6 NF6 3' - 6" 8 1/4" 7" A9.2 6 INSTALL <N> SCREEN OVER CONDUIT INSTALL <N> SCREEN OVER CONDUIT PROVIDE <N> VERTICAL GRAB BAR AT ACCESSIBLE STALL & UNDERCOUNTER PIPE PROTECTION M.O. 3' - 4" A0.25 NF26 NF27 NF28 NF29 05B 05C 15 14 B NF9 NF9NF9 NF9 NF9 NF9 NF9NF9 C NF9 NF9 A A A A G G NF15 DN INSTALL <N> 2" THICK CONC "BENCH" OVER FOUNDATION INSTALL <N> 4X4 STL ANGLE TO SUPPORT CONC BENCH END EGRESS STAIR FOUNDATION, RE: STRUC NF37 CONTRACTOR SHALL CONNECT NEW INTERNAL ROOF DRAIN TO NEW STORM SEWER: REF CIVIL REF STRUCTURAL FOR MATERIAL AND SIZING FOR STRUCTURAL ELEMENTS IN WALL TYPA AT NEW LIFT STRUCTURE SIM SIM D E 1 1 PROVIDE MINIMAL WALL PENETRATION INVERT OF 7903.83' TO ACHIEVE A MINIMUM 1% SLOPE TO STORM SEWER TIE-IN 1 2' - 5" 4 NF30 NF30 4 4 5 4 NF30 NF30 4 4 LEGEND <E> WALL NEW WALL NEW DOOR NEW FLOOR STRUCTURE, RE: STRUC REPAIR CONCRETE SLAB. PROVIDE CONSISTENT FLOOR LEVEL PRIOR TO INSTALLING NEW FLOOR FINISH. FLOOR ELEVATION KEYNOTE DOOR TAG WALL TYPE # - 101 X GENERAL NOTES 1. PATCH AND REPAIR ALL FINISHES AFFECTED BY CONSTRUCTION. MATCH ADJACENT FINISH. 2. COORDINATE REUSE, SALVAGE, OR DISPOSAL OF ALL DEMO ITEMS WITH OWNER. 3. REMOVE & SALVAGE <E> WINDOW TREATMENTS. COORDINATE REINSTALLATION WITH PITKIN COUNTY/ 9TH JUDICIAL DISTRICT. 4. FURNITURE BY OTHERS. SHOWN FOR REFERENCE. 5. PITKIN COUNTY TO BE RESPONSIBLE FOR REMOVING / RELOCATING ALL <E> FURNITURE. 6. REFERT TO M, P, E, & S SHEETS FOR ADDITIONAL INFORMATION. 7. REFER TO FINISH PLANS AND RCPS FOR ADDITIONAL INFORMATION. 8. ALL REPOSITIONED COURTROOM FURNITURE TO PROVIDE 30" CLEAR. 9. REMOVE AND SALVAGE <E> SIGNAGE (FLAGS AND WALL MOUNTED). MODIFY FOR <N> ROOM NAMES. INSTALL <N> TO MATCH <E> WHERE NEEDED. 10. REFER TO A 9.7 FOR ADDITIONAL CLERESTORY. N Project Number Date Drawn by Checked by Anderson Hallas Architects, PC ARCHITECTURE HISTORIC PRESERVATION COPYRIGHT 2019 ANY UNAUTHORIZED USE OF THESE DOCUMENTS IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF: ANDERSON HALLAS ARCHITECTS, P.C. PLANNING Issue 715 FOURTEENTH STREET GOLDEN, COLORADO 80401 (303) 278-4378 FAX (303) 278-0521 Scale AS NOTED 8/14/2019 6:15:28 PM A1.0 GARDEN LEVEL FLOOR PLAN 2017910 PITKIN COUNTY COURTHOUSE REMODEL PITKIN COUNTY, CO 5/2/19 LWB RAS/NAA 506 E Main St St 300, Aspen, CO 81611 PERMIT 3/16" = 1'-0"1 GARDEN LEVEL FLOOR PLAN KEYNOTES Key Value Keynote Text NF3 PROVIDE <N> ACCESSIBLE WHEELCHAIR LIFT. NF6 ADD ALT #1: PROVIDE <N> INTERIOR STORM WINDOW WITH BULLET RESISTANT GLAZING. NF8 PROVIDE <N> POST-MOUNTED AUTO OPENER. POWDER COAT POST TO MATCH HANDRAILS. NF9 PROVIDE FROSTED PRIVACY FILM ON <E> WINDOWS. NF10 PROVIDE <N> WALL MOUNTED WD 1 1/2" DIAMETER WD HANDRAILS. NF15 INFILL WALL WITH MASONRY, RE: STRUC. PROVIDE SMOOTH AND FLUSH FINISH TO MATCH <E> ADJACENT FURRING AND FINISH. NF20 INSTALL <N> HIGH IMPACT RESISTANT GYP. BD. WALL FINISH ON <E> FURRING, INSTALL <N> FURRING (TO MATCH <E>) AS NEEDED FOR <N> OPENING AT EXISTING ELEVATOR CORE. NF26 THE CAB HAS THREE SETS OF CONTROLS. (2) AT STANDARD HEIGHT ON REAR AND FRONT OF CAB AND A THIRD SET OF CONTROLS MOUNTED AT 29" AFF. REMOVE THIRD SET OF CONTROLS. UPDATETHE CONTROL OPTIONS TO INCORPORATE <N> CALL BUTTON TO <N> SIDE OF GARDEN LEVEL, AND SECURE/DESIGNATED ACCESS FOR IN-CUSTODIES AND STAFF. NF27 REMOVE <E> VINYL TILE FLOOR. PROVIDE <N> CARPET TILE FLOOR FINISH. PROVIDE <N> INTERIOR CAB FINISH ON ALL 4 WALLS. PROVIDE <N> CEILING FINISH AND LIGHTING. REMOVE <E> AUXILIARY PANEL. NF28 PROVIDE CAB CONTROLS VIA CARD ACCESS TO ALLOW FOR LOCKOUT FOR EITHER JUDGE OR IN-CUSTODY TRANSPORT. NF29 PROVIDE VERTICAL ACCESSIBLE GRAB BAR IN <E> RESTOOM. RE: A 9.3 NF30 PROVIDE <N> VERTICAL, ACCESSIBLE GRAB BARS. RE: 1/A9.8 FOR MOUNTING LOCATION. PROVIDE PIPE PROTECTION AT SINK. NF37 PROVIDE <N> PLUMBING CHASE FOR <N> ROOF DRAIN WITH 6" MIN INTERIOR CLEAR. SIZE OF PIPE TO BE CONFIRMED VIA DESIGN BUILD. DRAWINGS BASED ON FLOOR PLANS PROVIDED BY PITKIN COUNTY. CONTRACTOR TO NOTIFY ARCHITECT OF ANY DEVIATIONS FROM ACTUAL FIELD CONDITIONS, PRIOR TO COMMENCING WITH WORK. DRAWINGS BASED ON FLOOR PLANS PROVIDED BY PITKIN COUNTY. CONTRACTOR TO NOTIFY ARCHITECT OF ANY DEVIATIONS FROM ACTUAL FIELD CONDITIONS, PRIOR TO COMMENCING WITH WORK. 0 4' 8'12' 1 No. Description Date 1 ADDENDUM 01 4/26/2019 4 BUILDING COMMENTS 8/14/2019 5 ASI #1 8/14/2019 08/21/2019 IT 106 FILE/COPY 102D STORAGE 112 PROBATION 108 PROBATION RR 108D OFFICE 1 108E OFFICE 2 108C OFFICE 3 108B WAITING 108A CLOSET 108F HALL 105 OFFICE 2 105B MEETING ROOM 105C CLERKS 102 WAITING/ SELF HELP 102A CLERK WORKSTATIONS 103 FAMILY COURT/ COLLECTIONS 102B OFFICE 1 104 108E 104 NF3 DN DN D N DN DN PROVIDE NEW MTL EGRESS STAIR AND SECURITY ENCLOSURE. DN <N> CONC. RAMP, MAX. SLOPE 1:12. RE: CIVIL A7.3 2 MEN 113 WOMEN 114 11' - 9" 10 ' - 1 1 " ALIGN 10' - 0 1/2" 6' - 7 " R.O. 3' - 2" 7" 1' - 4" UP UP DN DN A9.9 2 HALL 100 UP 4' - 3 1/2" 102B TRANSACTION COUNTER : REF 5:A9.3 3 SELF-HELP STATIONS SECURITY SCREENING 115 VEST. 100A VEST. 110 HALL 103A ELEV. 111 INFORMAL MTG 105A B A F A A A A <N> ACCESSIBLE RAILINGS<N> ACCESSIBLE RAILINGS ALIGN 101C 101B OFFICE 1 101B OFFICE 2 101C WITNESS WAITING 101D DA OFFICE 101 OFFICE 4 101E 101E A A A101D OFFICE 3 101F 101F A WAITING 101A OPEN TO BELOW A9.6 2 A9.6 3 A9.4 4 A9.4 5 A9.34 A9.3 5 V.I.F. 15' - 7" 12' - 2 1/2" 10 1/2" V.I.F. 4' - 10 1/2" 1" HOLD 5' - 0" 1" V.I.F. 0" 1' - 0" V.I.F. 11' - 4" 9' - 6" 9' - 11 1/2" 6' - 8" 4 1/2"ALIGN A A A9.4 1 108 ALIGN 2 A9.3 A7.1 1 A ALIGN R.O. 3' - 2" 4' - 0 1/2" ALIGN R.O. 3' - 2" R.O. 3' - 2" 6 1/2" R.O. 3' - 2" R.O. 3' - 2" R.O. 3' - 2" R.O. 3' - 2" V.I.F. 4' - 4"R.O. 3' - 2"1' - 0" 12' - 2 1/2" HOLD 1' - 6" ALIGN 7' - 1" A AL I G N 110A 110 100A 100B 6" 6" NF14 E A9.6 1 152 C 102D 115 102102A 106 105B 105C 108C 108B 100C 101A 113 100 112 114 108F 108A NF19 A4.0 4 X RAY 73" x 47" MAGNETOMETERS 36" x 28" DEMOUNTABLE GLASS PARTITION 6' HT 1' - 6" R.O. 3' - 2" 102C A9.7 1 1' - 10" 4' - 4" 1' - 8" 4' - 4"1' - 6" 2' - 7" 2' - 2" H H H PROVIDE <N> VERTICAL GRAB BAR AT ACCESSIBLE STALL & UNDERCOUNTER PIPE PROTECTION WALL-MOUNTED SWING SECURITY EXIT GATE A4.0 3 A4.0 6 108D 103A 6 NF25 NF23 1' - 4 1/2" 1' - 0 1/2" E SE C U R I T Y ST A F F MIN 3' - 0" MIN 3' - 6" A4.0 7 A4.0 7 A4.0 7 A4.0 8 A9.3 1 3 A9.3 A9.7 5 MIN. 1' - 0" 4 7' - 0" H 1' FLOOR A NF30 NF30 VAULT DOOR WORK: 1. PROTECT EXISTING ROOM SIDE VAULT DOORS REMAIN. 2.PROVIDE NEW ACCESSIBLE HALF SADDLE THRESHOLD AT VAULT DOOR OPENING. NEW THRESHOLD TO BE THE ENTIRE DEPTH OF MASONRY WALL. 3.VERIFY 32 INCHES CLEAR OPENING 4.MAINTAIN 48 INCHES CLEAR MANUEVERING SPACE AT BOTH SIDES OF OPENING. VAULT DOOR WORK: 1. PROTECT EXISTING ROOM SIDE VAULT DOORS REMAIN. 2.PROVIDE NEW ACCESSIBLE HALF SADDLE THRESHOLD AT VAULT DOOR OPENING. NEW THRESHOLD TO BE THE ENTIRE DEPTH OF MASONRY WALL. 3.VERIFY 32 INCHES CLEAR OPENING 4.MAINTAIN 48 INCHES CLEAR MANUEVERING SPACE AT BOTH SIDES OF OPENING. 1' - 11" 2' - 10" HOLD 3' - 10 1/2" AL I G N V.I.F. 6' - 4" V.I.F. 1" A E AA NF38 NF32 NF32 NF32 NF32 NF32 NF33 NF34 A A A A A9.7 76 3' - 5" 101 REF. 1 NF37 4 4 1' FLOOR 4 NF30 NF30 4 LEGEND <E> WALL NEW WALL NEW DOOR NEW FLOOR STRUCTURE, RE: STRUC REPAIR CONCRETE SLAB. PROVIDE CONSISTENT FLOOR LEVEL PRIOR TO INSTALLING NEW FLOOR FINISH. FLOOR ELEVATION KEYNOTE DOOR TAG WALL TYPE # - 101 X GENERAL NOTES 1. PATCH AND REPAIR ALL FINISHES AFFECTED BY CONSTRUCTION. MATCH ADJACENT FINISH. 2. COORDINATE REUSE, SALVAGE, OR DISPOSAL OF ALL DEMO ITEMS WITH OWNER. 3. REMOVE & SALVAGE <E> WINDOW TREATMENTS. COORDINATE REINSTALLATION WITH PITKIN COUNTY/ 9TH JUDICIAL DISTRICT. 4. FURNITURE BY OTHERS. SHOWN FOR REFERENCE. 5. PITKIN COUNTY TO BE RESPONSIBLE FOR REMOVING / RELOCATING ALL <E> FURNITURE. 6. REFERT TO M, P, E, & S SHEETS FOR ADDITIONAL INFORMATION. 7. REFER TO FINISH PLANS AND RCPS FOR ADDITIONAL INFORMATION. 8. ALL REPOSITIONED COURTROOM FURNITURE TO PROVIDE 30" CLEAR. 9. REMOVE AND SALVAGE <E> SIGNAGE (FLAGS AND WALL MOUNTED). MODIFY FOR <N> ROOM NAMES. INSTALL <N> TO MATCH <E> WHERE NEEDED. 10. REFER TO A 9.7 FOR ADDITIONAL CLERESTORY. Project Number Date Drawn by Checked by Anderson Hallas Architects, PC ARCHITECTURE HISTORIC PRESERVATION COPYRIGHT 2019 ANY UNAUTHORIZED USE OF THESE DOCUMENTS IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF: ANDERSON HALLAS ARCHITECTS, P.C. PLANNING Issue 715 FOURTEENTH STREET GOLDEN, COLORADO 80401 (303) 278-4378 FAX (303) 278-0521 Scale AS NOTED 8/14/2019 6:15:31 PM A1.1 MAIN LEVEL FLOOR PLAN 2017910 PITKIN COUNTY COURTHOUSE REMODEL PITKIN COUNTY, CO 5/2/19 LWB RAS/NAA 506 E Main St St 300, Aspen, CO 81611 PERMIT N 3/16" = 1'-0"1 MAIN LEVEL FLOOR PLAN KEYNOTES Key Value Keynote Text NF3 PROVIDE <N> ACCESSIBLE WHEELCHAIR LIFT. NF14 PROVIDE <N> CHASE. MINIMUM 5" INTERIOR CLEARANCE. NF19 <E> DOOR TO BE FASTENED IN THE CLOSED POSITION. <E> TRANSOM ABOVE SHOULD HAVE MIRRORED FILM APPLIED BEHIND GLASS. REMOVE DOOR KNOB INFILL HOLE WHERE WHERE HARDWARE REMOVED. PROVIDE FLUSH FINISH WITH SURROUNDING WD, PAINT TO MATCH. NF23 FIX DOOR IN OPEN POSITION. NF25 CUT THROUGH <E> STONE FOUNDATION WALL. PROVIDE <N> DOOR ACCESS TO THE NORTH OF THE <E> ELEVATOR. NF30 PROVIDE <N> VERTICAL, ACCESSIBLE GRAB BARS. RE: 1/A9.8 FOR MOUNTING LOCATION. PROVIDE PIPE PROTECTION AT SINK. NF32 <N> CLERESTORY WINDOW ABOVE. RE: INT. ELEVATIONS NF33 <E> COLUMN TO REMAIN. NF34 REINSTALL SALVAGED MILLWORK ON <N> WALL. PROVIDE <N> WD ACCESS PANEL. NF37 PROVIDE <N> PLUMBING CHASE FOR <N> ROOF DRAIN WITH 6" MIN INTERIOR CLEAR. SIZE OF PIPE TO BE CONFIRMED VIA DESIGN BUILD. NF38 ALIGN <N> WALLS WITH <E> COLUMNS. DRAWINGS BASED ON FLOOR PLANS PROVIDED BY PITKIN COUNTY. CONTRACTOR TO NOTIFY ARCHITECT OF ANY DEVIATIONS FROM ACTUAL FIELD CONDITIONS, PRIOR TO COMMENCING WITH WORK. 0 4' 8'12' 1 No. Description Date 1 ADDENDUM 01 4/26/2019 4 BUILDING COMMENTS 8/14/2019 4 08/21/2019 Project Number Date Drawn by Checked by Anderson Hallas Architects, PC ARCHITECTURE HISTORIC PRESERVATION COPYRIGHT 2019 ANY UNAUTHORIZED USE OF THESE DOCUMENTS IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF: ANDERSON HALLAS ARCHITECTS, P.C. PLANNING Issue 715 FOURTEENTH STREET GOLDEN, COLORADO 80401 (303) 278-4378 FAX (303) 278-0521 Scale AS NOTED 8/ 1 4 / 2 0 1 9 6 : 1 5 : 3 5 P M A5.0 DOOR SCHEDULE 2017910 PITKIN COUNTY COURTHOUSE REMODEL PITKIN COUNTY, CO 5/2/19 LWB RAS/NAA 506 E Main St St 300, Aspen, CO 81611 PERMIT DOOR SCHEDULE MARK <E> FRAME TYP FRAME MATERIAL DOOR TYPE DOOR MATERIAL NEW TRIM SIZE HARDWARE COMMENTSTHICK WIDTH HEIGHT 00 No <E> WD B WD No 1 3/4" 2' - 11" 7' - 11" 01 NEW EXTERIOR WOOD DOOR: VERIFY OPENING SIZE 00A Yes <E> WD <E> WD No 1 3/4" 2' - 4" 7' - 0" 02 00B Yes <E> STL <E> WD No 1 3/4" 2' - 8" 7' - 0" SF01 EXISTING SAFE DOOR: NO WORK 00C Yes <E> WD <E> WD No 1 3/4" 2' - 6" 7' - 0" 04 00D Yes <E> WD <E> WDW No 1 3/4" 3' - 0" 7' - 0" 04 00E Yes <E> WD <E> WD No 1 3/4" 3' - 0" 7' - 0" 03 01 No A WD A WD Yes 1 3/4" 3' - 0" 7' - 0" 35 01A Yes <E> WD <E> WD No 1 3/4" 3' - 0" 7' - 0" 02 02A No B WD A WD Yes 1 3/4" 3' - 0" 7' - 0" 36 02B No A WD A WD Yes 1 3/4" 3' - 0" 7' - 0" 06 02C No A WD A WD Yes 1 3/4" 3' - 0" 7' - 0" 06 02D Yes <E> WD <E> WD No 1 3/4" 2' - 8" 7' - 0" 02 02E No A WD A WD Yes 1 3/4" 3' - 0" 7' - 0" 36 03 No A WD A WD Yes 1 3/4" 3' - 0" 7' - 0" 35 04 No <E> WD B WD No 1 3/4" 2' - 11" 7' - 11" 09 NEW EXTERIOR WOOD DOOR: VERIFY OPENING SIZE 04A Yes <E> WD <E> WD No 1 3/4" 3' - 0" 7' - 0" 08 05 Yes <E> WD <E> WD No 1 3/4" 3' - 2" 7' - 0" 08 05A No A WD A WD Yes 1 3/4" 3' - 0" 7' - 0" 10 05B No - WD E WD No 1 3/4" 3' - 0" 3' - 0" 05 HALF-HEIGHT SWINGING GATE 05C No - WD E WD No 1 3/4" 3' - 0" 3' - 0" 05 HALF-HEIGHT SWINGING GATE 06 No A WD A WD Yes 1 3/4" 3' - 0" 7' - 0" 31 06A No B WD A WD Yes 1 3/4" 3' - 0" 7' - 0" 12 06B No A WD A WD Yes 1 3/4" 3' - 0" 7' - 0" 03 07 No A WD A WD Yes 1 3/4" 3' - 0" 7' - 0" 13 08 No A WD A WD No 1 3/4" 3' - 0" 7' - 0" 36 09 No <E> WD B WD No 1 3/4" 3' - 0" 7' - 0" 01 NEW EXTERIOR WOOD DOOR: VERIFY OPENING SIZE 12 No <E> WD B WD No 1 3/4" 3' - 0" 7' - 0" 15 NEW EXTERIOR WOOD DOOR: VERIFY OPENING SIZE 13A No A WD A WD Yes 1 3/4" 3' - 0" 7' - 0" 11 13B No A WD A WD Yes 1 3/4" 3' - 0" 7' - 0" 11 14 No A WD A WD Yes 1 3/4" 3' - 0" 7' - 0" 16 15 No A WD A WD Yes 1 3/4" 3' - 0" 7' - 0" 02 16 No A WD A WD Yes 1 3/4" 3' - 0" 7' - 0" 17 EXISTING DOOR: PROVIDE POWER ASSIST OPENER 17 No RE: A5.1 WD B WD Yes 1 3/8" 3' - 0" 7' - 0" 18 NEW EXTERIOR WOOD DOOR: VERIFY OPENING SIZE 18 No - STL F No 1 3/4" 3' - 6" 6' - 0" SG01 SECURITY GATE 19 No - STL - STL No 1 3/4" 3' - 6" 6' - 0" SG01 SECURITY GATE 100 Yes <E> WD <E> WD No 1 3/4" 2' - 10" 6' - 4" 19 EXISTING DOOR: PROVIDE NEW ELECTRIC DOOR HOLD OPENS 100A No <E> WD C WD No 2" 5' - 8" 8' - 11" 20 NEW EXTERIOR WOOD DOOR: VERIFY OPENING SIZE 100B No <E> WD C WD No 2" 5' - 8" 8' - 11" 21 NEW EXTERIOR WOOD DOOR: VERIFY OPENING SIZE 100C Yes <E> WD <E> WD No 1 3/4" 2' - 10 1/2" 7' - 0" EX01 FIX DOOR IN CLOSED POSITION, APPLY MIRRORED FILM TO TRANSOM, REMOVE DOOR KNOB - PROVIDE MTL PLATE TO MATCH HARDWARE FINISH TO CONCEAL HOLES 101 Yes <E> WD A WD Yes 1 3/4" 3' - 0" 7' - 0" 36 101A Yes <E> WD <E> WD No 1 3/4" 3' - 0" 7' - 0" 22 101B No C WD A WD Yes 1 3/4" 3' - 0" 7' - 0" 06 101C No C WD A WD Yes 1 3/4" 3' - 0" 7' - 0" 06 101D No C WD A WD Yes 1 3/4" 3' - 0" 7' - 0" 23 101E No C WD A WD Yes 1 3/4" 3' - 0" 7' - 0" 06 101F No C WD A WD Yes 1 3/4" 3' - 0" 7' - 0" 06 102 Yes <E> WD <E> WD No 1 3/4" 3' - 0" 7' - 0" 22 102A Yes <E> WD <E> WD No 1 3/4" 3' - 0" 7' - 0" 22 102B No A WD A WD Yes 1 3/4" 3' - 0" 7' - 0" 24 102C No A WD A WD Yes 1 3/4" 3' - 0" 7' - 0" 24 102D Yes <E> WD <E> WD No 1 3/4" 2' - 8" 7' - 0" SF01 EXISTING SAFE DOOR: REFER TO PLANS FOR WORK 103A Yes <E> WD <E> WD No 1 3/4" 3' - 0" 7' - 0" 02 104 No A WD A WD Yes 1 3/4" 3' - 0" 7' - 0" 06 105B Yes <E> WD <E> WD No 1 3/4" 3' - 0" 7' - 0" 06 105C Yes <E> WD <E> WD No 1 3/4" 2' - 10" 7' - 0" 36 <E> DOOR 106 Yes <E> WD <E> WD No 1 3/4" 3' - 0" 7' - 0" 22 108 No A WD A WD Yes 1 3/4" 3' - 0" 7' - 0" 26 108A Yes <E> WD <E> WD No 1 3/4" 2' - 10" 7' - 0" 26 <E> DOOR 108B Yes <E> WD <E> WD No 1 3/4" 2' - 8" 7' - 0" 06 <E> DOOR 108C Yes <E> WD <E> WD No 1 3/4" 2' - 8" 7' - 0" 06 <E> DOOR 108D No A WD A WD Yes 1 3/4" 3' - 0" 7' - 0" 27 108E No A WD A WD Yes 1 3/4" 3' - 0" 7' - 0" 06 108F Yes <E> WD <E> WD No 1 3/4" 2' - 6" 7' - 0" 03 110 No <E> WD C WD No 2" 5' - 8" 8' - 11" 21 NEW EXTERIOR WOOD DOOR: VERIFY OPENING SIZE 110A No <E> WD C WD No 2" 5' - 8" 8' - 11" 20 NEW EXTERIOR WOOD DOOR: VERIFY OPENING SIZE 112 Yes <E> WD <E> WD No 1 3/4" 3' - 0" 7' - 0" SF01 EXISTING SAFE DOOR: REFER TO PLANS FOR WORK 113 Yes <E> WD <E> WD No 1 3/4" 2' - 10" 7' - 0" 13 <E> DOOR 114 Yes <E> WD <E> WD No 1 3/4" 2' - 10" 7' - 0" 28 <E> DOOR 115 Yes <E> WD <E> WD No 1 3/4" 3' - 0" 7' - 0" 13 200B Yes <E> WD <E> WD No 1 3/4" 3' - 0" 7' - 0" 03 200D Yes <E> WD <E> WD No 1 3/4" 2' - 4" 7' - 0" 13 200E Yes <E> WD <E> WD No 1 3/4" 2' - 4" 7' - 0" 13 201 Yes <E> WD <E> WD No 2" 6' - 2" 6' - 8" 29 201B Yes A WD A WD Yes 1 3/4" 3' - 0" 7' - 0" 17 REFRAME AND INSTALL SALVAGED DOOR AT FLOOR LEVEL REPAIR PLASTER AND INSTALL SALVAGED DOOR TRIM ON BOTH SIDES. 201C No A WD A WD Yes 1 3/4" 3' - 0" 7' - 0" 07 201D No A WD A WD Yes 1 3/4" 3' - 0" 7' - 0" 22 201E No A WD A WD Yes 1 3/4" 3' - 0" 7' - 0" 30 202 Yes <E> WD <E> WD No 1 3/4" 3' - 0" 7' - 0" 14 202A No A WD A WD Yes 1 3/4" 3' - 0" 7' - 0" 13 202B No A WD A WD Yes 1 3/4" 3' - 0" 7' - 0" 22 202C Yes <E> WD <E> WD No 1 3/4" 2' - 10" 7' - 0" 25 <E> DOOR 202D No SEE ELEV WD B WD Yes 1 3/8" 3' - 2" 8' - 5" 32 NEW EXTERIOR WOOD DOOR: VERIFY OPENING SIZE 203 Yes <E> WD <E> WD No 1 3/4" 2' - 10" 7' - 0" 22 <E> DOOR 203B Yes A WD A WD No 1 3/4" 3' - 0" 7' - 0" 11 INSTALL SALVAGED DOOR IN SAME OPENING WITH DOOR SWING AS SHOWN. 203C No - WD E WD No 1 3/4" 3' - 0" 3' - 0" 05 ADD ALT #2: HALF-HEIGHT SWINGING GATE 204 Yes <E> WD <E> WD No 1 3/4" 3' - 0" 7' - 0" 08 204A No A WD A WD Yes 1 3/4" 3' - 0" 7' - 0" 13 204B Yes <E> WD <E> WD No 1 3/4" 3' - 0" 7' - 0" 08 205 Yes <E> WD <E> WD No 1 3/4" 3' - 2" 7' - 0" 08 206 Yes <E> WD <E> WD No 1 3/4" 3' - 2" 7' - 0" 33 206A Yes <E> WD <E> WD No 1 3/4" 3' - 0" 7' - 0" 34 207 No A WD A WD Yes 1 3/4" 3' - 0" 7' - 0" 08 NEW DOOR AND TRANSOM DRAWINGS BASED ON FLOOR PLANS PROVIDED BY PITKIN COUNTY. CONTRACTOR TO NOTIFY ARCHITECT OF ANY DEVIATIONS FROM ACTUAL FIELD CONDITIONS, PRIOR TO COMMENCING WITH WORK. GENERAL NOTES 1. SALVAGE AND REUSE EXISTING DOORS WHERE NOTED 2. AT ALL SALVAGED WOOD DOORS PROVIDE NEW HARDWARE 3. ALL NEW WOOD DOORS SHALL BE SOLID WOOD STILE AND RAIL WOOD DOORS WITH RAISED WOOD PANELS AS INDICATED WITH CLEAR FINISH 4. ALL GLAZING WITHIN DOORS OR WITHIN 24INCHES OF DOOR SHALL BE SAFETY GLAZING. 5. CONTRACTOR SHALL FIELD VERIFY ALL OPENINGS PRIOR TO COMMENCING WORK. 6. REFER TO SPECIFICATIONS FOR DOOR HARDWARE. 1 1 No. Description Date 1 ADDENDUM 01 4/26/2019 08/21/2019 HALL 16 17<N> POST MOUNTED AUTOMATIC ACCESSIBLE DOOR OPENER BUTTON LOCATION (EXTERIOR) UP 3 A7.3 LIFT 5 A7.3 USGS = 7,912.2' USGS = 7,911.54' ALIGN <N> CONCRETE LANDING WITH <E> SIDEWALK -DOWEL INTO <E> SIDEWALK WITH #3 REBAR AT 12" O.C. WITH 6" MIN. EMBED - <N> LANDING NOT TO EXCEED 2% SLOPE IN ANY DIRECTION, RE: CIVIL <N> CONCRETE RAMP NOT TO EXCEED 1:12 SLOPE IN RUNNING DIRECTION AND NOT TO EXCEED 2% CROSS SLOPE, RE: CIVIL PROVIDE <N> PRE-FINISHED PIPE HANDRAIL TO 36" MIN. AFF (TO TOP OF RAIL)WITH VERTICAL POST AT 4'-0" O.C. - PROVIDE 12" MIN. RAIL EXTENSIONS AT TOP AND BOTTOM OF RAMP <N> PERMEABLE PAVING AT LANDING AT NEW DOOR LOCATION - NEW LANDING NOT TO EXCEED 2% SLOPE IN ANY DIRECTION, RE: CIVIL 5' - 0 " RAMP NOT TO EXCEED 1:20 9' - 2 1/2" LANDING 5' - 0" CLR 5' - 0" <E>SIDEWALK TO REMAIN <E> STAIR AND WALL TO REMAIN MIN. 12" <N> WALL MOUNTED AUTOMATIC ACCESSIBLE DOOR OPENER BUTTON LOCATION (INTERIOR) PRE-FINISHED GATE ASSEMBLY BY LIFT MFG INSTALLED BY G.C. PRE-FINISHED LIFT ASSEMBLY - INSTALLED BY G.C. FIN. TO STUD 1' - 3"STUD TO STUD 5' - 3" (V.I.F.) <N> CARPET ON <N> CONC. FLOOR <E> DOOR TO REMAIN, PROVIDE POWER ASSISTED OPENER T-SHAPED TURNING CLEARANCE SECURE <E> WROUGHT IRON GATE IN THE OPEN POSITION 6" CONCRETE CURB 3' - 0" <E> FENCE TO REMAIN <E> FENCE TO REMAIN <E> WINDOW TO REMAIN HOLD 3' - 6" DOOR PROVIDED BY LIFT MFG INSTALLED BY G.C. 4 A7.4 Sim 3 PROVIDE 6INCH CONC BOARDER: REF CIVIL 36" CLEAR 4 CLOSET 108F DN SECURE <E> WROUGHT IRON GATE IN THE OPEN POSITION 3 A7.3 LIFT5 A7.3 TO BE REMOVED AND SALVAGED <E> DOOR LOCATION (V.I.F.) 1' - 7" <N> CLR OPENING 4' - 9" ,<E> STAIR AND LANDING TO REMAIN <E> ENTRY VESTIBULE OPEN TO BELOW (V.I.F.) 4' - 8" (V.I.F.) 5' - 5 1/2" (V.I.F.) 1' - 10" ADA CLEAR FLOOR SPACE <E> WINDOW AND FRAME TO REMAIN FIN. TO STUD 4' - 0" (V.I.F.) <N> STRUCTURAL FLOOR AT LIFT PLATFORM LOCATION <N> ENCLOSURE AT LIFT WALL PRE-FINISHED LIFT - INSTALLED BY G.C. <E> MECHANICAL DUCT TO REMAIN NOTE: NEW WALL FRAMING AT LIFT LOCATION SHALL BE (1) HOUR RATED (SHOWN WITH DIAGONAL CROSS HATCH) STEEL FRAMING: GA FILE NO WP1072 WOOD FRAMING: GA FILE NO WP 2510 42" CLEAR 4 GARDEN LEVEL 100' - 0" MAIN LEVEL 110' - 3 5/8" <E>FOUNDATION WALL TO REMAIN <N> PERMEABLE PAVING LANDING. SLOPE LANDING MAX 2% AWAY FROM BUILDING <E> WINDOW AND FRAME TO REMAIN WALKOFF CARPET FINISH ON CONC PRE-FINISHED GATE ASSEMBLY PROVIDED BY FROM LIFT MFG. OFFSET FLOOR STRUCTURE SO THAT FINISH FLOOR OF FLOOR STRUCTURE AND LIFT PLATFORM ALIGN WITH NO VERTICAL TRANSITION. COORDINATE WITH LIFT MANUFACTURER <N> WALL 2X WD. WALL CONSTRUCTION WITH HIGH IMPACT RESISTANT GYP. BD. ON PUBLIC SIDE OF WALL BEYOND COMMERCIAL WHEELCHAIR LIFT EXISTING WALL TO REMAIN <N> WALL ENCLOSURE BEYOND AT LIFT <N> FLOOR STRUCTURE BEYOND, RE: STRUC INSTALL PRE- FINISHED GATE ASSEMBLY FROM LIFT MFG. PROVIDE NEW WD 1X TRIM CLOSER AT EXISTING FLOOR - STN 5 A7.3 FIN. TO STUD 1' - 1" A5.2 1 V.I.F. 4' - 5 1/2" V.I.F. 4' - 7 1/2" A5.2 4 Sim DOOR PROVIDED BY FROM LIFT MFG. REPAIR <E> PLASTER WALL BEYOND - PT 3 GARDEN LEVEL 100' - 0" MAIN LEVEL 110' - 3 5/8" 3 A7.3 (V.I.F.) 4' - 5 1/2" <E> MASONRY WALL TO REMAIN ALIGN FLOOR STRUCTURE AND LIFT SO THAT PLATFORM OF LIFT ALIGNS WITH FLOOR BEYOND <N> WALL CONSTRUCTION WITH IMPACT RESISTANT GYP. BOARD FINISH ON PUBLIC SIDE OF LIFT ENCLOSURE INSTALL <N> CARPET FINISH ON <N> JOIST WITH 3/4" T&G PLYWD -ALIGN <N> FLOOR WITH <E> MAIN FLOOR <N> WALL ENCLOSURE JAMB OF <N> OPENING BEYOND <E> MASONRY WALL TO REMAIN, RE: STRUC INSTALL <N> CARPET FINISH ON <N> FLOOR, RE: STRUC. ALIGN <N> FLOOR FINISH WITH <E> MAIN FLOOR <N> WALL CONSTRUCTION WITH 5/8" IMPACT RESISTANT GYP. BD. FINISH ON PUBLIC SIDE OF LIFT ENCLOSURE AND 5/8" GYP. BD. ON CLOSET SIDE <N> WALL CONSTRUCTION WITH 5/8" IMPACT RESISTANT GYP. BOARD FINISH ON PUBLIC SIDE OF LIFT ENCLOSURE AND 5/8" GYP. BOARD ON STORAGE SIDE LIFT ASSEMBLY AND LIFT PLATFORM (V.I.F) 5' - 10" FIN. TO STUD 3' - 6" (V.I.F.) <E> WALL TO REMAIN INSTALL 1x8 WD BASE BD. WITH 3/4" QUARTER ROUND TRIM <E> FLOOR TO REMAIN HALL 16 CLOSET 108F DOOR AS PART OF THE LIFT BEYOND RUBBER BASE AT STORAGE <N> WD BASE - PT TO MATCH <E> Project Number Date Drawn by Checked by Anderson Hallas Architects, PC ARCHITECTURE HISTORIC PRESERVATION COPYRIGHT 2019 ANY UNAUTHORIZED USE OF THESE DOCUMENTS IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF: ANDERSON HALLAS ARCHITECTS, P.C. PLANNING Issue 715 FOURTEENTH STREET GOLDEN, COLORADO 80401 (303) 278-4378 FAX (303) 278-0521 Scale AS NOTED 8/14/2019 6:15:40 PM A7.3 ENLARGED PLANS AT NEW LIFT ENTRY 2017910 PITKIN COUNTY COURTHOUSE REMODEL PITKIN COUNTY, CO 5/2/19 DAM RAS/NAA 506 E Main St St 300, Aspen, CO 81611 PERMIT 1/4" = 1'-0"1 GARDEN LEVEL LIFT PLAN 1/4" = 1'-0"2 MAIN LEVEL LIFT PLAN 1/2" = 1'-0"3 BUILDING SECTION - NEW ADA LIFT ENTRY 4 3D-Cube - ISO 1/2" = 1'-0"5 BUILDING SECTION AT NEW ADA LIFT ENTRY <N> LIFT ENCLOSURE <N> FLOOR STRUCTURE, RE: STRUC INSTALL <N> LIFT ASSEMBLY AND LIFT PLATFORM <E>GARDEN LEVEL FLOOR TO REMAIN LIFT DOOR PROVIDED BY LIFT MANUFACTURER <N> EXTERIOR DOOR, RE: TO DOOR SCHEDULE AND JAMB DETAILS FOR ADDITIONAL INFORMATION <N> ACCESSIBLE LANDING WITH PERMEABLE PAVERS AT <N> DOOR LOCATION - SLOPE LANDING MAX 2%AWAY FROM BUILDING, RE: CIVIL DRAWINGS BASED ON FLOOR PLANS PROVIDED BY PITKIN COUNTY. CONTRACTOR TO NOTIFY ARCHITECT OF ANY DEVIATIONS FROM ACTUAL FIELD CONDITIONS, PRIOR TO COMMENCING WITH WORK. NOTE: CONTRACTOR TO LAYOUT RAMP PRIOR TO EXCAVATION TO ASSURE EXISTING GATE LOCATION WORKS WITH SLOPE MINIMUM AND MAXIMUM CLEARANCES <N> FLOOR STRUCTURE, RE: STRUC 2 No. Description Date 2 ADDENDUM 02 5/29/2019 3 ADDENDUM 03 6/12/2019 4 BUILDING COMMENTS 8/14/2019 3 08/21/2019 A9.2 2 1' - 1 1 1 / 2 " 2' - 6 " 3" 2' - 1" 2 A9.11 Sim FINISHED FACE PANEL <E> COLUMN TO REMAIN, LOCATION V.I.F. 30 " X 4 8 " CL E A R S P A C E (E) SIGNAGE, MODIFY TO ACCOMODATE (N) ROOM NAME, COMPLY W/ ADA PROVIDE <N> OR RELOCATED FLAG SIGNAGE AT THE FOLLOWING ROOMS: • 05 • 102A • 105C • 108A • 101A • 201 • 203 PROVIDE <N> OR RELOCATED WALL SIGNAGE TO MATCH EXISTING AT ALL ROOMS. SOLID SURFACE COUNTERTOP WITH INTEGRAL 4" BACKSPLASH 2 A9.11 Sim 2' - 11" FINISHED FACE PANEL; BEHIND COLUMN <E> COLUMN TO REMAIN, LOCATION V.I.F. FILLER PROVIDE REMOVABLE ACCESSIBLE APRON TO MATCH CASEWORK. CONCEAL PIPING AND PROVIDE KNEE PROTECTION. 4 4 30" MIN VIF A9.2 7 BC30 BC30 DW24 SB36 3'-0" MIN. CLR 2' - 1 " DW REF. 3 A9.11 Sim1 A9.11 Sim 30" X 48" CLEAR SPACE 2' - 1 0 " WC24 WC30 WC30 MIN. CLR. 3' - 3" BC36BC36REF. SOLID SURFACE COUNTERTOP WITH INTEGRAL 4" BACKSPLASH; SCRIBE TO ADJACENT STONE 3 A9.11 Sim 1 A9.11 Sim FILLER; SCRIBE TO ADJACENT STONE FILLER; SCRIBE TO ADJACENT STONE 30" CLEAR SB36 DW24 4 PROVIDE REMOVABLE ACCESSIBLE APRON TO MATCH CASEWORK. CONCEAL PIPING AND PROVIDE KNEE PROTECTION. 4 CABINET LEGEND BC =BASE CABINET SB =SINK BASE DW =DISHWASHER TC =TALL CABINET WC =WALL CABINET REF =REFRIGERATOR BC15 30" CLEAR MIN 3' - 0" 2' - 1 0 " SOLID SURFACE COUNTERTOP WITH INTEGRAL 4" BACKSPLASH 2 A9.11 Sim FINISHED END PANELS PROVIDE REMOVABLE ACCESSIBLE APRON TO MATCH CASEWORK. CONCEAL PIPING AND PROVIDE KNEE PROTECTION. 4 4 A9.25 1' - 3 " 3' - 0 " 1" 2' - 0 1/2" 2 A9.11 Sim PROVIDE A FINISHED END PANEL 30 " X 4 8 " CL E A R S P A C E FINISHED END PANEL Project Number Date Drawn by Checked by Anderson Hallas Architects, PC ARCHITECTURE HISTORIC PRESERVATION COPYRIGHT 2019 ANY UNAUTHORIZED USE OF THESE DOCUMENTS IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF: ANDERSON HALLAS ARCHITECTS, P.C. PLANNING Issue 715 FOURTEENTH STREET GOLDEN, COLORADO 80401 (303) 278-4378 FAX (303) 278-0521 Scale AS NOTED 8/ 1 4 / 2 0 1 9 6 : 1 5 : 4 1 P M A9.2 INTERIOR ELEVATIONS 2017910 PITKIN COUNTY COURTHOUSE REMODEL PITKIN COUNTY, CO 5/2/19 LWB RAS/NAA 506 E Main St St 300, Aspen, CO 81611 PERMIT 1/2" = 1'-0"1 JURY DELIB. 03 ENLARGED PLAN DRAWINGS BASED ON FLOOR PLANS PROVIDED BY PITKIN COUNTY. CONTRACTOR TO NOTIFY ARCHITECT OF ANY DEVIATIONS FROM ACTUAL FIELD CONDITIONS, PRIOR TO COMMENCING WITH WORK. 0 2' 4' 1 1/2" = 1'-0"3 EXISTING SIGNAGE 1/2" = 1'-0"2 JURY DELIB. 03 INTERIOR ELEVATION EAST 1/2" = 1'-0"6 BREAK RM 02A ENLARGED PLAN 1/2" = 1'-0"7 BREAK RM 02A INTERIOR ELEVATION SOUTH 1/2" = 1'-0"5 JURY DELIB. 204 INTERIOR ELEVATION WEST 1/2" = 1'-0"4 JURY DELIB. 204 ENLARGED PLAN 1 No. Description Date 1 ADDENDUM 01 4/26/2019 4 BUILDING COMMENTS 8/14/2019 08/21/2019 WC36 WC12WC36 BC24BC24SB36 SOLID SURFACE COUNTERTOP WITH INTEGRAL 4" BACKSPLASH 1 A9.11 Sim2 A9.11 Sim 3' - 0" PROVIDE REMOVABLE, ACCESSIBLE APRON TO MATCH CASEWORK, CONCEAL PIPING AND PROVIDE NEW PROTECTION BC24 2' - 1 0 " SOLID SURFACE COUNTERTOP WITH INTEGRAL 4" BACKSPLASH 1 A9.11 Sim TC30 101E WC24 REF. 2' - 0" APT. SIZE REF. PROVIDED BY OWNER CABINET LEGEND BC =BASE CABINET SB =SINK BASE DW =DISHWASHER TC =TALL CABINET WC =WALL CABINET REF =REFRIGERATOR A9.7 2 3 BC 2 4 TC 3 0 SB36 2' - 0" CLR.BC24 1' - 1 0 " 1' - 10" 2 A9.11 Sim 1 A9.11 Sim 1 A9.11 Sim 30" X 48" CLEAR SPACE REF.2' - 0 " APT. SIZE REF. PROVIDED BY OWNER EQ EQ 101F 101F EQ EQ 7' - 3 " 7' - 3 " 101C 101A 101C 101B101D 101B 5' - 0 1/2" 7' - 2 " 101E 101D 7' - 3 " 5' - 1 1/2" Project Number Date Drawn by Checked by Anderson Hallas Architects, PC ARCHITECTURE HISTORIC PRESERVATION COPYRIGHT 2019 ANY UNAUTHORIZED USE OF THESE DOCUMENTS IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF: ANDERSON HALLAS ARCHITECTS, P.C. PLANNING Issue 715 FOURTEENTH STREET GOLDEN, COLORADO 80401 (303) 278-4378 FAX (303) 278-0521 Scale AS NOTED 8/ 1 4 / 2 0 1 9 6 : 1 5 : 4 5 P M A9.7 INTERIOR ELEVATIONS - DA 2017910 PITKIN COUNTY COURTHOUSE REMODEL PITKIN COUNTY, CO 5/2/19 LWB RAS/NAA 506 E Main St St 300, Aspen, CO 81611 PERMIT DRAWINGS BASED ON FLOOR PLANS PROVIDED BY PITKIN COUNTY. CONTRACTOR TO NOTIFY ARCHITECT OF ANY DEVIATIONS FROM ACTUAL FIELD CONDITIONS, PRIOR TO COMMENCING WITH WORK. 0 2' 4' 1/2" = 1'-0"2 DA 101 INTERIOR ELEVATION NORTH 1/2" = 1'-0"3 DA 101 INTERIOR ELEVATION EAST 1/2" = 1'-0"1 DA 101 ENLARGED PLAN 1/2" = 1'-0"4 DA OFFICE 101 NORTH 1/2" = 1'-0"5 DA OFFICE 101 SOUTH 1/2" = 1'-0"6 OFFICE 101 WEST 1/2" = 1'-0"7 OFFICE 101 C EAST No. Description Date 4 BUILDING COMMENTS 8/14/2019 4 08/21/2019 A FRONT VIEW SIDE VIEW B FRONT VIEW SIDE VIEW 23 " * (2 0 " M I N ) (4 4 " M A X ) C FRONT VIEW SIDE VIEW 44 " * (4 0 " M I N . ) (4 8 " M A X ) F FRONT VIEW SIDE VIEW (4 0 " M I N . ) (4 8 " M A X ) SIDE VIEW J FRONT VIEW WALL MOUNTED SINK 33 " * (3 4 " M A X ) (4 0 " M A X ) RI M O F SI N K BO T T O M OF M I R R O R CL E A R F L O O R SP A C E ACCESSIBLE FLOOR MOUNTED WATER CLOSET SIDE VIEW FRONT VIEW TOP OF SEAT AUTOMATIC FLUSH VALVE 18 " * (1 7 " M I N ) (1 9 " M A X ) 38 " * 48 " M A X 18 " M I N ACCESSIBLE WALL MOUNTED LAVATORY PROVIDE UNDER LAVATORY PLUMBING PROTECTION TOILET TISSUE DISPENSER RECESSED PAPER TOWEL DISPENSER AND WASTE RECEPTACLE SOAP DISPENSER MAX 12"42" MIN 40" * (39" MIN) (41" MAX) 34 " * (3 3 " M I N ) (3 6 " M A X ) KEEP 1 1/2" AREA BELOW BAR CLEAR KEEP 18" AREA ABOVE BAR CLEAR MIN 12" MIN 24" 34 " * (3 3 " M I N ) (3 6 " M A X ) ACCESSIBLE WALL ATTACHED GRAB BARS 24" MIN 42" MAX MIN 18 " PROTRUDING DISPENSER BELOW GRAB BAR SANITARY NAPKIN DISPOSAL 1) ALL ACCESSIBLE FIXTURE AND ACCESORIES SHALL BE MOUNTED IN COMPLIENCE WITH ADA 2) ALL LAVATORIES SHALL HAVE UNDERLAVATORY KNEE AND LEG PROTECTION 3) ALL FAUCETS SHALL BE ADA CERTIFIED 4)WHERE TOILET ACCESSORIES TRANSITION FROM CERAMIC TILE TO GWB, SHIM TO PROVIDE CONSISTANT INSTALLATION. * = PREFERED MOUNTING HEIGHT FRONT VIEW SIDE VIEW RECESSED MOUNT WASTE RECEPTICLES MAX 4" 48 " C 4" MAX MIN 36" 54" MIN 17" - 19" 16" - 18" AMBULATORY STALL 3' - 8 " * 41 M A X 39 " M I N 18 " D D.2D.1 D D.1D.2 D D.1D.2 GENERAL NOTES 9" 2' - 3 " 8"3" 1' - 6 " 11" 1" 40" * (39" MIN) (41" MAX) 34 " * (3 3 " M I N ) (3 6 " M A X ) KEEP 1 1/2" AREA BELOW BAR CLEAR KEEP 18" AREA ABOVE BAR CLEAR 41 M A X 39 " M I N 18 " D.1D.3D ACCESSIBLE WALL/FLOOR ATTACHED GRAB BAR 54" MIN A9.8 3 6 5 4 1' - 6 " 07 <N> 5/8" GWB OVER 1 1/2" FURRING B ADD.2 D.1 E C 1' - 6 " F 5' - 0 " D B A D.2 D.1 C J 2' - 0" 3' - 0 " 1' - 6" E 5' - 0 " D A D.2 D.1 1' - 6" F G H J 5' - 0 " E F G H J 5' - 0 " C B G J Project Number Date Drawn by Checked by Anderson Hallas Architects, PC ARCHITECTURE HISTORIC PRESERVATION COPYRIGHT 2019 ANY UNAUTHORIZED USE OF THESE DOCUMENTS IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF: ANDERSON HALLAS ARCHITECTS, P.C. PLANNING Issue 715 FOURTEENTH STREET GOLDEN, COLORADO 80401 (303) 278-4378 FAX (303) 278-0521 Scale AS NOTED 8/ 1 4 / 2 0 1 9 6 : 1 5 : 5 1 P M A9.8 TYP. RR ACCESS AND RR INTERIOR ELEVATIONS 2017910 PITKIN COUNTY COURTHOUSE REMODEL PITKIN COUNTY, CO 5/2/19 LWB RAS/NAA 506 E Main St St 300, Aspen, CO 81611 PERMIT DRAWINGS BASED ON FLOOR PLANS PROVIDED BY PITKIN COUNTY. CONTRACTOR TO NOTIFY ARCHITECT OF ANY DEVIATIONS FROM ACTUAL FIELD CONDITIONS, PRIOR TO COMMENCING WITH WORK. 0 2' 4' 3/8" = 1'-0"1 TOILET ACCESSORIES MOUNTING HEIGHTS 1/2" = 1'-0"2 JURY RR 07 1/2" = 1'-0"3 JURY 07 NORTH 1/2" = 1'-0"6 JURY 07 EAST 1/2" = 1'-0"5 JURY 07 SOUTH 1/2" = 1'-0"4 JURY 07 WEST TOILET ACCESSORY SCHEDULE A NEW STAINLESS STEEL DOUBLE TOILET PAPER DISPENSER B NEW STAINLESS STEEL AUTOMATIC PAPER TOWEL DISPENSER C NEW STAINLESS STEEL FREE-STANDING WASTE RECEPTACLE D 18" MIN. x 1-1/2" DIA. VERTICAL GRAB BARS D.1 36" LG. x 1-1/2" DIA. REAR WALL GRAB BARS D.2 42" MIN. x 1-1/2" DIA. SIDE WALL GRAB BAR D.3 54" MIN. x 1-1/2" DIA. SIDE WALL FLOOR ATTACHED GRAB BAR E NEW WD FRAMEMIRROR (SEE ELEVATION FOR SIZE) SHIM BEHIND MIRROR FOR FLUSH INSTALLATION OVER TILE F NEW WALL MOUNTED LIQUID SOAP DISPENSER G STAINLESS STEEL EDGING ON ALL EXPOSED TILE EDGES H PIPE PROTECTION COVER UNDER LAV. J PORCELAIN WALL TILE SUBWAY PATTERN No. Description Date 08/21/2019 RUBBER BASE PLAM FLAT PANEL LOCKABLE DOOR SOLID SURFACE COUNTERTOP & INTEGRAL BACKSPLASH 2X BLOCKING BLOCKING BLOCKING CABINET BACK 4"4" DRAWER PULL ADJUSTABLE MELAMINE SHELF TY P . 2' - 1 0 " VARIES 4" PRE-MANUFACTURED PLAM BASE CABINET WITH MELAMINE INTERIOR TY P . 2' - 6 " ADJUSTABLE MELAMINE SHELF HOLES W/ MTL SHELF SUPPORTS TYP. 1' - 8" DOOR PULL PLAM FLAT FRONT CABINET DOOR VARIES SOLID SURFACE COUNTERTOP AND INTEGRAL BACKSPLASH RUBBER BASE BLOCKING MELAMINE INTERIOR FINISH (WHITE) 1/4" RADIUS EDGE 5 1/2" MIN. 2' - 3" SINK, RE: MECHANICAL. 6" MAX. DEPTH 2' - 10" MIN. 9" MIN. 8" MIN. 11" BLOCKING PIPE SHIELDING INSULATION ON ALL PLUMBING LINES BELOW SINK WD FALSE DRAWER PANEL 1 1/2" (N) OR (E) GWB OR PLASTER WALL, V.I.F REMOVABLE APRON TO MATCH CASEWORK TO CONCEAL PIPING AND PROVIDE KNEE PROTECTION SOLID SURFACE COUNTERTOP AND INTEGRAL BACKSPLASH RUBBER BASE BLOCKING MELAMINE INTERIOR FINISH (WHITE) 1/4" RADIUS EDGE 2' - 10" BLOCKING PIPE SHIELDING INSULATION ON ALL PLUMBING LINES BELOW SINK <E> MASONRY WALL <N> FURRED OUT WALL. SEE WALL TYPES SINK, RE: MECHANICAL. 6" MAX. DEPTH WD FALSE DRAWER PANEL REMOVABLE APRON TO MATCH CASEWORK TO CONCEAL PIPING AND PROVIDE KNEE PROTECTION 1 1/2" 5 1/2" MIN. 2' - 3" MIN. 8" MIN. 11" MIN. 9" 4 RUBBER BASE PLAM, FLAT PANEL, LOCKABLE DRAWERS, 4 THUS SOLID SURFACE COUNTERTOP 2X BLOCKING BLOCKING BLOCKING CABINET BACK 4" DRAWER PULL. VARIES 1'-6 1/2" U.N.O. 4" PREMANUFACTURED P-LAM BASE CABINET WITH MELAMINE INTERIOR CABINET BACK RUBBER BASE P-LAM FLAT PANEL LOCKABLE DRAWER SOLID SURFACE COUNTERTOP 2X BLOCKING BLOCKING BLOCKING CABINET BACK 4"4" DRAWER PULL VARIES 1'-6 1/2" U.N.O. P-LAM BASE CABINET WITH MELAMINE INTERIOR LINE WORK SHOWN FOR CLARITY ~ PROVIDE TWO (2) DRAWERS TO FIT STANDARD SIZE (9-5/8" x 11-3/4") HANGING FILE FOLDERS P-LAM FLAT PANEL LOCKABLE DRAWER Project Number Date Drawn by Checked by Anderson Hallas Architects, PC ARCHITECTURE HISTORIC PRESERVATION COPYRIGHT 2019 ANY UNAUTHORIZED USE OF THESE DOCUMENTS IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF: ANDERSON HALLAS ARCHITECTS, P.C. PLANNING Issue 715 FOURTEENTH STREET GOLDEN, COLORADO 80401 (303) 278-4378 FAX (303) 278-0521 Scale AS NOTED 8/14/2019 6:15:53 PM A9.11 CASEWORK DETAILS 2017910 PITKIN COUNTY COURTHOUSE REMODEL PITKIN COUNTY, CO 5/2/19 LWB RAS/NAA 506 E Main St St 300, Aspen, CO 81611 PERMIT DRAWINGS BASED ON FLOOR PLANS PROVIDED BY PITKIN COUNTY. CONTRACTOR TO NOTIFY ARCHITECT OF ANY DEVIATIONS FROM ACTUAL FIELD CONDITIONS, PRIOR TO COMMENCING WITH WORK. 1 1/2" = 1'-0"1 ADA CASEWORK 1 1/2" = 1'-0"2 ADA SINK CABINET 1 1/2" = 1'-0"3 ADA SINK CABINET ON FURRED WALL 1 1/2" = 1'-0"4 ADMIN BASE CABINET - 4 DRAWER 1 1/2" = 1'-0"5 ADMIN CASE CABINET - FILING CABINET No. Description Date 4 BUILDING COMMENTS 8/14/2019 4 08/21/2019 CHECK VALVE 2WAY ATC VALVE 3WAY ATC VALVE BALANCING VALVE BUTTERFLY VALVE MECHANICAL LEGEND PRESSURE REDUCING VALVE EXISTING ITEMS TO CONNECTION TO EXISTING BE DEMOLISHED EXISTING ITEMS SAFTEY RELIEF VALVE BACK FLOW PREVENTER NEW WORK PRESSURE SENSOR THERMOSTAT METER P&T TAP FLOW ARROW IN LINE PUMP VENTURI TYPE BALANCING VALVE TEMPERATURE SENSOR THERMOMETER AUTOMATIC AIR VENT GAUGE MANUAL AIR VENT GRADE CLEAN OUT FLOOR CLEAN OUT WALL CLEAN OUT FLOW SENSOR STRAINER DRAIN VALVE FLEXIBLE CONNECTION UNION CAP FLOOR SINK FLOOR DRAIN PIPING SERVICES PIPING SYSTEM COMPONENTS TEE UP TEE DOWN CHWS HWR G CA HWS CHWR CD ELBOW DOWN ELBOW UP DOMESTIC HOT WATER RECIRC DOMESTIC COLD WATER DOMESTIC HOT WATER VENT WASTE DRAWING NOTATION CHILLED WATER SUPPLY CONDENSATE DRAIN HEATING WATER RETURN HEATING WATER SUPPLY CHILLER WATER RETURN COMPRESSED AIR NATURAL GAS GATE VALVE PLUG VALVE BALL VALVE VALVES DIFFUSER CALLOUT SUPPLY DIFFUSER W/ FIRE/SMOKE DAMPER DESIGNATION SCHEDULE CFM NECK SIZE 10"∅ 375 FLEX CONNECTION SLOT DIFFUSER ECCENTRIC REDUCER HVAC SYSTEM COMPONENTS MOTORIZED DAMPER RECT. RETURN DUCT RECT. SUPPLY DUCT SUPPLY DIFFUSER/ DN RETURN GRILLE DUCT SLOPE M 18x12 RECT. 12"ROUND MANUAL DAMPER (R)RELOCATED (N)NEW (E)EXISTING THREE WAY CONTROL VALVE MECHANICAL NOTES I. GENERAL A. ALL WORK SHALL BE IN ACCORDANCE WITH SMACNA STANDARDS AND SPECIFICATIONS, AND LOCAL AUTHORITY HAVING JURISDICTION. B. THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND NOT INTENDED TO SHOW ALL TRANSITIONS, OFFSETS, ETC. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS AND PROVIDE ALL NECESSARY FITTINGS TO COMPLETE THE INTENT OF THE DRAWINGS. ANY DISCREPANCIES BETWEEN DRAWINGS AND FIELD CONDITIONS SHALL BE REPORTED TO THE ENGINEER FOR RESOLUTION. CONTRACTOR MAY LOCATE MECHANICAL EQUIPMENT DIFFERENTLY THAN SHOWN ON DRAWINGS DUE TO CONFLICTS, AS LONG AS FUNCTION AND/OR APPEARANCE ARE NOT AFFECTED. C. COORDINATE SPACE REQUIREMENTS, SUPPORTS, AND INSTALLATION OF MECHANICAL WORK, WHICH ARE INDICATED DIAGRAMMATICALLY ON THE DRAWINGS. FOLLOW ROUTING SHOWN FOR PIPES AND DUCTS AS CLOSELY AS PRACTICABLE; PLACE RUNS PARALLEL WITH LINES OF BUILDING. UTILIZE SPACES EFFICIENTLY TO MAXIMIZE ACCESSIBILITY FOR OTHER INSTALLATIONS, FOR MAINTENANCE, AND FOR REPAIRS. D. COMPLY WITH MANUFACTURER'S INSTRUCTIONS INCLUDING EACH STEP IN SEQUENCE. SHOULD MANUFACTURERS' INSTRUCTIONS CONFLICT WITH THE DRAWINGS, REQUEST CLARIFICATION FROM THE ENGINEER BEFORE PROCEEDING. E. DUCT SIZES ARE INSIDE DIMENSION. F. CONTRACTOR SHALL REVIEW THESE DOCUMENTS CAREFULLY. CONTRACTOR SHALL CONTACT THREE SIXTY (360) ENGINEERING, INC. (303-940-2050), FOR RESOLUTION OF ANY DISCREPANCIES, OMISSIONS, OR CLARIFICATIONS, BEFORE BID DATE. IN THE EVENT THAT AN INTERPRETATION OF BID DOCUMENTS IS NECESSARY AFTER THE BID DATE, THE DECISION OF 360 SHALL BE FINAL AND BINDING. G. PRODUCT DELIVERY, STORAGE, AND HANDLING: PROVIDE EQUIPMENT AND PERSONNEL TO HANDLE PRODUCTS BY METHODS TO PREVENT DAMAGE. PROMPTLY INSPECT SHIPMENTS TO ENSURE THAT PRODUCTS ARE UNDAMAGED. STORE AND PROTECT PRODUCTS IN ACCORDANCE WITH MANUFACTURERS' INSTRUCTIONS. H. ALL REMOVED EQUIPMENT SHALL REMAIN THE PROPERTY OF THE BUILDING MANAGER AND SHALL BE STORED PER THEIR DIRECTION. I. THE CONTRACTOR IS RESPONSIBLE FOR THE COSTS OF ALL CHANGE ORDERS, WHICH THE OWNER AND ENGINEER HAVE NOT APPROVED IN WRITING PRIOR TO THE EXECUTION OF THE ASSOCIATED WORK. J. IN THE CASE OF A CONFLICT, UNLESS OTHERWISE NOTED, KEYNOTES ON MECHANICAL PLANS SHALL SUPERCEDE ANY GENERAL NOTES ON THE PLANS. II. EQUIPMENT A. NEW DIFFUSERS: 1. DESIGNATION: NECK SIZE CFM B. RETURN AIR GRILLES: 1. 24X24 OR 24X12 FACE AS SHOWN. 2. COLOR: WHITE C. NEW RIGID ROUND DUCTWORK: 1. MEDIUM PRESSURE: GALVANIZED STEEL SPIRAL WOUND DUCT. 2. LOW PRESSURE: GALVANIZED STEEL SNAP LOCK DUCT. D. NEW RECTANGULAR DUCTWORK: 1. LOCATED IN CONDITIONED SPACE: ZINC COATED GALVANIZED STEEL WITH 1" ACOUSTIC LINER. 2. LOCATED IN UNCONDITIONED SPACE: ZINC COATED GALVANIZED STEEL WITH 1-1/2" ACOUSTIC LINER - MINIMUM R-6. E. RIGID ROUND DUCTWORK INSULATION: FLEX MASTER THERMO SLEEVE TYPE TSM - MINIMUM R-12. F. FLEXIBLE DUCTWORK: 1. LOW PRESSURE: FLEX MASTER TLM (ALUM. FLEX/METAL JACKET), UL181 - CLASS 1APPROVED, 8'0" MAXIMUM LENGTH. 2. MEDIUM PRESSURE: FLEX MATER TLM (ALUM. FLEX/NO INSUL.), UL181 - CLASS 1 APPROVED, 3'0" MAXIMUM LENGTH. G. FIRE/SMOKE DAMPERS: COMBINATION FIRE/SMOKE DAMPERS SHALL BE FABRICATED IN ACCORDANCE WITH NFPA 90A AND UL555S CLASS II. FIRE/SMOKE DAMPERS SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S UL INSTALLATION INSTRUCTIONS. ACTUATORS SHALL BE POWER OPEN/SPRING CLOSED OPERATION, 120 VOLT. THE FIRE FAIL/SAFE MODE SHALL BE A UL 33 HEAT ACTUATED LINK FOR CLOSURE AND CONTAINMENT OF FIRE ZONE, INDEPENDENT OF ACTUATOR POSITIONING OR SIGNALING. MANUFACTURED BY PREFCO, MODEL 5020 OR EQUAL. H. HOT WATER HEATING PIPING/CHILLED WATER PIPING/CONDENSER WATER PIPING: ABOVEGROUND, NPS 2" AND SMALLER, SHALL BE ANY OF THE FOLLOWING: 1. TYPE L, DRAWN-TEMPER, COPPER TUBING, WROUGHT-COPPER FITTINGS, AND SOLDERED JOINTS. 2. SCHEDULE 40, GRADE B, TYPE 96 STEEL PIPE; CLASS 150, MALLEABLE IRON FITTINGS, CAST-IRON FLANGES AND FLANGE FITTINGS, AND THREADED JOINTS. K. HYDRONIC PIPING INSULATION: MINERAL-FIBER, PREFORMED PIPE INSULATION: TYPE 1, 850° F. MINERAL OR GLASS FIBERS BONDED WITH A THERMOSETTING RESIN. COMPLY WITH ASTMC 547, TYPE 1, GRADE A, WITH FACTORY APPLIED ASJ. 1. HEATING WATER 1-1/2" AND SMALLER = 1.5" THICK, HEATING WATER 2" AND LARGER = 2" THICK, CONDUCTIVITY = 0.27 @ 125° F. 2. CHILLED WATER = 1.0 " THICK, CONDUCTIVITY = 0.25 @ 75° F. III. EXECUTION A. BALANCING: 1. CONTRACTOR SHALL ADJUST AND BALANCE VARIABLE VOLUME BOXES (VAV'S), FAN POWERED BOXES (FPB'S), AIR CONDITIONING UNITS (AC'S), AND DIFFUSERS TO THE QUANTITIES SHOWN ON THE DRAWING. BALANCING WORK SHALL BE PERFORMED IN ACCORDANCE WITH NEBB OR TABB STANDARDS BY A NEBB OR TABB CERTIFIED CONTRACTOR. SUBMIT BALANCING REPORT TO THE ENGINEER. 2. EXISTING DIFFUSER DESIGNATION INDICATES CFM ONLY. 3. VAV BOX DESIGNATION INDICATES MAXIMUM CFM ADJUST MINIMUM TO 10% OF MAXIMUM. 4. WHERE LOW PRESSURE AIR HANDLING SYSTEMS CROSS INTO AN ADJACENT TENANT AREA, CONTRACTOR SHALL BALANCE ALL DIFFUSERS ASSOCIATED WITH THE SYSTEM. DIFFUSERS NOT SHOWN OR SHOWN WITH NO CFM SHALL MAINTAIN EXISTING CFM. 5. ADJUST WATER SYSTEMS, AFTER AIR BALANCING, TO PROVIDE DESIGN QUANTITIES. 6. ADJUST SYSTEMS TO PROVIDE SPECIFIED PRESSURE DROPS AND FLOWS THROUGH HEAT TRANSFER ELEMENTS PRIOR TO THERMAL TESTING. PERFORM BALANCING BY MEASUREMENT OF TEMPERATURE DIFFERENTIAL IN CONJUNCTION WITH AIR BALANCING. B. CONTRACTOR SHALL COORDINATE WORK WITH OTHER TRADES AND NOTIFY 360 ENGINEERING, INC. IF ANY CONFLICTS OCCUR. C. THERMOSTAT LOCATIONS AND HEIGHTS TO BE COORDINATED WITH BUILDING MANAGEMENT, VERIFIED BY THE ENGINEER. CONTRACTOR TO CALIBRATE ALL THERMOSTATS SHOWN ON THIS PLAN. IT SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY TO ENSURE THAT ALL EXISTING THERMOSTATS REMAIN INTACT DURING DEMOLITION. HEATING THERMOSTATS MUST REMAIN OPERATIONAL AT ALL TIMES. IF REQUIRED FOR BETTER PROTECTION, THERMOSTATS MAY BE TEMPORARILY MOUNTED IN THE CEILING PLENUM DURING DEMOLITION. THERMOSTATS SHALL BE MOUNTED AT A MAXIMUM 48" ABOVE FINISHED FLOOR. D. PROVIDE VOLUME DAMPERS AT ALL DIFFUSER TAKEOFFS. E. ALL TAKEOFFS, RUNOUTS, AND FLEX DUCTWORK TO DIFFUSERS SHALL BE THE SAME SIZE AS DIFFUSER INLET UNLESS OTHERWISE NOTED. F. MECHANICAL CONTRACTOR TO CHECK OPERATION AND CONDITION OF ALL EXISTING MECHANICAL EQUIPMENT WITHIN THE CONFINES OF THIS SPACE AND PREPARE A WRITTEN LIST OF ANY DEFICIENCIES IN EQUIPMENT OPERATION OR CONDITION. LIST SHALL BE SUBMITTED TO OWNER TWO WEEKS AFTER THE AWARD OF THE CONTRACT. G. THERMOSTAT CONTROL LINES SHALL BE SUPPORTED AT INTERVALS NOT TO EXCEED 4'0". H. PROVIDE EXTERNAL INSULATION ON ALL NEW RIGID ROUND DUCTWORK. I. PROVIDE ACCESS DOORS IN DUCTWORK AS REQUIRED FOR ACCESS TO FIRE DAMPERS, FIRE/SMOKE DAMPERS, OR ANY OTHER MECHANICAL EQUIPMENT REQUIRING MAINTENANCE OF SERVICE. J. ALL PIPE AND DUCT PENETRATIONS THROUGH RATED WALLS SHALL BE SEALED PER 2015 IBC. M T P 360Three Sixty Engineering, Inc. 1600 Jackson St. #360 Golden, CO 80401 303.940.2050 303.940.3322-fax 17-191A DMD Scale Project Number Date Drawn by Checked by Anderson Hallas Architects, PC ARCHITECTURE HISTORIC PRESERVATION COPYRIGHT 2018 ANY UNAUTHORIZED USE OF THESE DOCUMENTS IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF: ANDERSON HALLAS ARCHITECTS, P.C. PLANNING Issue 715 FOURTEENTH STREET GOLDEN, COLORADO 80401 (303) 278-4378 FAX (303) 278-0521 8/ 1 4 / 2 0 1 9 1 0 : 4 4 : 1 7 A M M0.1 MECHANICAL LEGEND AND NOTES 2017910 PITKIN COUNTY COURTHOUSE REMODEL PITKIN COUNTY, CO 4/3/19 KPZ MPC 506 E Main St St 300, Aspen, CO 81611 PERMIT No. Description Date 4 BLDNG COMMENTS 2019.08.14 4 TO THE TOP OF THE THERMOSTAT. 08/21/2019 DN DN DN S S S S S AT S J TC TC J J J S S S EF 1 FCU 1 EWH 4 EWH 1 L 1 WAP S S S S S S S S S PP 1 PP 4 WAP WAP WAP WAP WAP WAP WAP JJJ J S S S S S S S S S S S CR CR CR CR CR CR CR CR CR CR CR CR J CP 1 CUH 1 J J J J J J J ELEV 1 (E) (E) FACP TTB B B1 ADA UH ADA WP JURY DELIBERATION 03 ATTORNEY 01 VEST. 03A WOMEN 00C MEN 00D JUDGE RR 14 STORAGE 15 VISITING JUDGE'S CHAMBERS 04 VISITING JUDGE'S CHAMBERS 04 HALL 16 COURTROOM 3 05 HALL 00 STORAGE 00B HALL 10 ELEV. MECH. 00E CONF. RM 08 SECURE HALL 13 HALL 09 BOILER 01A MECH/ELEC 02D HOLDING 06 HALL 05A ? ? AC GFI (E) 1 OFFICE 2 02B OFFICE 1 02C ATTORNEY 06A MECH. 06B ELEV. 11 ALPINE LEGAL 02E BREAK ROOM 02A VEST. 02 JURY RR 07 B1-9 DISHWASHER B1-7 FRIDGE B1-10 AC GFI B1-11 AC GFI B1-10 AC GFI AC GFI (E) (E) (E) (E) (E) (E) (E) (E) (E)(E) (E) (E) (E) (E) (E) (E) (E) (E) +72" (E) (E) (E)(E)(E) (E) (E) +72"(E) +72" (E) +42" (E) (E) (E) (E) A (E) (E) (E) (E)(E)(E) (E) (E) (E) (E) (E) (E) AC GFI LOWER LIFT LOBBY 17 (E) ZONE G.1 ZONE G.2 ZONE G.3 ZONE G.4 ZONE G.5 (RL) (E) 2 2 2 2 2 +48"+48" 3 3 3 3 3 4 5 6 7 AV RACK 88 8 5 MDP UTILITY METER (E) (E) (E) (E) (E) (E) (E) 3 9 9 9 9 9 B1-20 B1-20 B1-20 B1-20 B1-20 B1-8 B1-8 B1-8 (E) (N) (N) (N) (N) (N) (N) (N) (N) 10 NOT IN SCOPE 8 B1-20 (E) +42" (E)(E) CLG DOOR POWER 11 12 DOOR POWER DOOR POWER ADA PUSHPLATE ADA PUSHPLATE B1-21 CLG B1-21 CLG B1-21 13 D-43 CLG 14 D-43 CLG 14 D-43 CLG 14 D-43 CLG 14 D-43 CLG 14 (E) (E) WIREWAY 15 16 17 18 3/16" = 1'-0"1 GARDEN LEVEL ELECTRICAL PLAN AE DESIGN Integrated Lighting and Electrical Solutions 1900 Wazee Street #205 Denver, CO 80202 303.296.3034 aedesign-inc.com Project #: 3912.00 Project Number Date Drawn by Checked by Anderson Hallas Architects, PC ARCHITECTURE HISTORIC PRESERVATION COPYRIGHT 2018 ANY UNAUTHORIZED USE OF THESE DOCUMENTS IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF: ANDERSON HALLAS ARCHITECTS, P.C. PLANNING Issue 715 FOURTEENTH STREET GOLDEN, COLORADO 80401 (303) 278-4378 FAX (303) 278-0521 Scale AS NOTED 8/ 1 4 / 2 0 1 9 1 0 : 4 5 : 3 5 A M E1.0 GARDEN LEVEL ELECTRICAL PLAN 2017910 PITKIN COUNTY COURTHOUSE REMODEL PITKIN COUNTY, CO 4/03/19 BYF KMD 506 E Main St St 300, Aspen, CO 81611 PERMIT No. Description Date 1 Addendum #2 05-23-2019 4 BLDG COMMENTS 2019.08.14 GENERAL NOTES A B C D E F G HATCHED AREA REPRESENTS AREA WITH NO ELECTRICAL SCOPE. UNLESS OTHERWISE INDICATED, CONNECT NEW DEVICES TO EXISTING NEARBY CIRCUITRY MAINTAINED DURING DEMOLITION. EXTEND CONDUIT AND FEEDERS AS NECESSARY. CONTRACTOR TO VERIFY ANY CIRCUITS MODIFIED ENTIRELY OR IN PART SHALL NOT EXCEED 1920VA AND (8) RECEPTACLES MAXIMUM PER CIRCUIT. REFER TO MECHANICAL EQUIPMENT PLANS FOR ADDITIONAL CIRCUIT INFORMATION. COORDINATE ALL SECURITY ITEM LOCATION AND REQUIREMENTS WITH SECURITY VENDOR PRIOR TO COMMENCEMENT OF WORK. PROVIDE JUNCTION BOXES AND CONDUIT AS NECESSARY PER VENDOR REQUIREMENTS. COORDINATE ALL LOW VOLTAGE AND IT ITEM LOCATION AND REQUIREMENTS WITH LOW VOLTAGE VENDOR PRIOR TO COMMENCEMENT OF WORK. PROVIDE JUNCTION BOXES AND CONDUIT AS NECESSARY PER VENDOR REQUIREMENTS. AS GARDEN LEVEL CEILINGS ARE BEING REPLACED, ROUTE GARDEN LEVEL CONDUITS ABOVE GARDEN LEVEL CEILING, ROUTE MAIN LEVEL CONDUITS DOWN THROUGH GARDEN LEVEL CEILING. CONDUITS ON SECOND FLOOR SHALL BE ROUTED ABOVE SECOND FLOOR CEILING. ALL CONDUITS SHALL BE HIDDEN IN WALLS OR CEILINGS AS MUCH AS POSSIBLE. COORDINATE WITH ARCHITECT IN ALL LOCATIONS WHERE CONDUIT MUST BE SURFACE MOUNT, INCLUDING EXTERIOR OF BUILDING. KEYNOTE LEGEND KEY VALUE KEYNOTE TEXT 1 EXISTING CONDITION REPRESENTATIVE OF A RECEPTACLE PLUG MOLD. DEVICES INTEGRATED INTO MOLD ARE SHOWN ATTACHED. NO NEW WORK. 2 ZONE INDICATED FOR LOAD JUSTIFICATION PURPOSES. ALL DEVICES IN ZONE SHALL BE RECIRCUITED TO EXISTING NEARBY CIRCUIT MAINTAINED DURING DEMOLITION UNLESS OTHERWISE NOTED. EXTEND CIRCUITRY TO NEW DEVICES AS NECESSARY. REFER TO GENERAL NOTES FOR ADDITIONAL INFORMATION. 3 PROVIDE RECESSED FLOORBOX, HUBBELL SYSTEM-ONE 2-GANG RECESSED FLOORBOX WITH CORROSION RESISTANCE OR SIMILAR. BOX SHALL HAVE A MINIMUM OF (2) DUPLEX RECEPTACLES. 4 PROVIDE 2-GANG JUNCTION BOX WITH 3/4" CONDUIT TO AV EQUIPMENT RACK. COORDINATE EXACT LOCATION AND REQUIREMENTS WITH AV VENDOR PRIOR TO INSTALLATION. 5 PROVIDE 4-GANG JUNCTION BOX WITH (2) 3/4" CONDUIT TO AV EQUIPMENT RACK. COORDINATE EXACT LOCATION AND REQUIREMENTS WITH AV VENDOR PRIOR TO INSTALLATION. 6 PROVIDE 1-GANG JUNCTION BOX WITH 3/4" CONDUIT TO AV EQUIPMENT RACK. COORDINATE EXACT LOCATION AND REQUIREMENTS WITH AV VENDOR PRIOR TO INSTALLATION. 7 LOCATION OF AV EQUIPMENT RACK. PROVIDE 3/4" CONDUIT TO ALL CEILING SPEAKERS AND ASSISTED LISTENING PANEL. COORDINATE EXACT LOCATION AND REQUIREMENTS WITH AV VENDOR PRIOR TO INSTALLATION. 8 PROVIDE RECESSED FLOORBOX, HUBBELL SYSTEM-ONE 4-GANG RECESSED FLOORBOX WITH CORROSION RESISTANCE OR SIMILAR. BOX SHALL HAVE A MINIMUM OF 2-GANG AV SPACE WITH (2) 1" CONDUIT ROUTED UNDERFLOOR TO AV RACK LOCATION. COORDINATE EXACT LOCATION WITH AV VENDOR PRIOR TO INSTALLATION. 9 FLOOR RECEPTACLES INDICATED SHALL BE CIRCUITED TOGETHER ON EXISTING CIRCUIT MADE SPARE THROUGH DEMOLITION. 10 CONTRACTOR SHALL REMOVE TEMPORARY POWER PANEL LOCATED APPROXIMATELY 50' NORTH OF COURTHOUSE AND NEAR PITKIN COUNTY JAIL BUILDING TRANSFORMER. COORDINATE WITH OWNER AS NECESSARY. 11 CONNECT NEW POWERED DOOR TO EXISTING CIRCUIT INDICATED. COORDINATE WITH DOOR VENDOR FOR EXACT REQUIREMENTS. 12 NEW EXTERIOR CARD READER AND PANIC HARDWARE WILL BE INSTALLED AT FENCE GATE NEAR PITKIN COUNTY JAIL APPROXIMATELY 43' NORTH OF BUILDING. PROVIDE CONDUIT AND BACKBOX AND COORDINATE WITH SECURITY VENDOR FOR EXACT REQUIREMENTS. REFER TO SHEET A0.1 FOR ADDITIONAL INFORMATION. 13 CONNECT AUTODOOR TO CIRCUIT INDICATED. PROVIDE CONDUIT AND BACKBOX TO ADA PUSHPLATES AND COORDINATE WITH SECURITY AND FIRE ALARM VENDOR FOR SECURITY AND EGRESS PURPOSES AS NECESSARY. 14 PROVIDE 120V POWER FOR FIRE/SMOKE DAMPERS. COORDINATE EXACT QUANTITIES, LOCATIONS, AND REQUIREMENTS WITH MECHANICAL CONTRACTOR. ALSO, COORDINATE WITH FIRE ALARM VENDOR AS NECESSARY. REFER TO DETAIL #1 ON SHEET E7.00 FOR ADDITIONAL INFORMATION. 15 NEW ELEVATOR EQUIPMENT. CONNECT TO EXISTING CIRCUITRY MAINTAINED DURING DEMOLITION, OR NEW CIRCUITRY IF CONTRACTOR DETERMINES EXISTING FEEDERS DO NOT MATCH NEW INDICATED IN EQUIPMENT SCHEDULE. ALSO CONNECT TO EXISTING FIRE ALARM SYSTEM/CIRCUITRY MAINTAINED DURING DEMOLITION AS REQUIRED. 16 CONNECT NEW ELEVATOR EQUIPMENT TO EXISTING ELEVATOR FUSED DISCONNECT PER NEC 620.51(A), NOTIFY ENGINEER IF EXISTING DISCONNECT DOES NOT CONTAIN 150A FUSES. 17 PROVIDE NEW LOCKABLE SPST FUSED DISCONNECT FOR ELEVATOR CAB LIGHT PER NEC 620.22(A) AND CONNECT TO EXISTING CIRCUITRY MAINTAINED DURING DEMOLITION. FUSE SHALL BE 20A FRS-R AND DISCONNECT SHALL BE 30A1P. EC SHALL VERIFY CIRCUIT TO DISCONNECT IS DEDICATED PER THE REQUIREMENTS OF NEC 620.22(A). 18 PROVIDE DEDICATED TELEPHONE LINE TO ELEVATOR MACHINE ROOM PER ELEVATOR VENDOR REQUIREMENTS. 4 8/14/19 08/21/2019 SS S S S S S S WAP S S S S S S S S S AT S J J J J TC TC J J J (E) (R) (R) (R) +42" (R) AC GFI (R) (R) (R) (R) (R) (R) (R) (R) (R) (R) (R) (R) (R) (R) (R) (R) (R) (ER)(R) (R) (R) (R) (R) (R)(R) AC (R) AC GFI (R) (R) (R) (R)(R) (R) (R) (R) (R) (R) (R) (R) (R) (R) (R) (R) (R) (R) (R) (R) (R) (R)(R)(R) (R) (R) (R) (R) (R) (R) (R) (R) (R) (R) (R) (R) (R) (R) (R) (R) (R) (R) (R) (R) (R) (R) (R) (R) (R)(R) (R) (R) +42" (R) (E) +42" (R) (R)(R)(R) (R) +48" (R)(R) (R) (R) (R)(R)(R) (R) (R) (R) (R) (E) (E) (E) (E)(R) (E) (E) (E) (R) (R) (R)(E)(E)(E)(R)(R) (R) (R) (R) (E) (E) (E) (R) CLG (R) (R)(R) (E) +72" (R) (R) (E) (E) +72" (R)(E)(E) (E) (E) (E) (E) (E) (E)(E) (E) (E) (R)(R)(R) (R) (R) (R) (R) (E) (E) (E) +42" (E) +72" (E) (R) ZONE G.1 ZONE G.2 ZONE G.3 ZONE G.4 ZONE G.5 1 1 1 1 1 2 (R) (R) (R) (E) (E)(E) (E) (E) (E) (E) (E) (E) (E) WIREWAY ELEV (R) (R) 3 4 5 Project Number Date Drawn by Checked by Anderson Hallas Architects, PC ARCHITECTURE HISTORIC PRESERVATION COPYRIGHT 2018 ANY UNAUTHORIZED USE OF THESE DOCUMENTS IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF: ANDERSON HALLAS ARCHITECTS, P.C. PLANNING Issue 715 FOURTEENTH STREET GOLDEN, COLORADO 80401 (303) 278-4378 FAX (303) 278-0521 Scale AS NOTED 8/ 1 4 / 2 0 1 9 1 0 : 4 5 : 3 8 A M ED1.0 GARDEN LEVEL ELECTRICAL PLAN DEMO 2017910 PITKIN COUNTY COURTHOUSE REMODEL PITKIN COUNTY, CO 4/03/19 BYF KMD 506 E Main St St 300, Aspen, CO 81611 PERMIT No. Description Date 1 Addendum #2 05-23-2019 4 BLDG COMMENTS 2019.08.14 3/16" = 1'-0"1 GARDEN LEVEL ELECTRICAL PLAN DEMO KEYNOTE LEGEND KEY VALUE KEYNOTE TEXT 1 ZONE INDICATED FOR LOAD JUSTIFICATION PURPOSES. ALL DEVICES INDICATED TO BE REMOVED IN ZONE SHALL BE DEMOLISHED WITH CIRCUITRY MAINTAINED FOR REUSE/EXTENSION TO NEW WORK. REFER TO GENERAL NOTES AND NEW PLANS FOR ADDITIONAL INFORMATION. 2 EXISTING OVERHEAD SOFFIT IN THIS SPACE TO BE DEMOLISHED (BY OTHERS). SOFFIT CONTAINS (4) EXISTING ELECTRICAL CONDUITS WHICH MUST BE RELOCATED. EXISTING ROUTING AND TERMINATION POINTS OF CONDUIT IS CURRENTLY UNKNOWN, EC SHALL TRACE CONDUIT IN FIELD, REMOVE IF NOT IN-USE OR RELOCATE AS NEEDED. ANTICIPATE INTERCEPTING CONDUITS IN THE VISITING JUDGE'S CHAMBERS AND RE-ROUTING AROUND THE LOWER LIFT LOBBY BACK INTO COURTROOM 3. 3 EXISTING ELEVATOR EQUIPMENT TO BE REPLACED WITH NEW IN SAME LOCATION. NEW ELEVATOR ELECTRICAL CHARACTERISTICS (3OHP) ARE SAME AS EXISTING (30HP). CONTRACTOR SHALL MAINTAIN EXISTING FIRE ALARM CONNECTIONS AND EXISTING POWER CIRCUITRY IF VERIFIED TO MATCH NEW. REFER TO ELEVATOR EQUIPMENT INFORMATION IN MECHANICAL SCHEDULE FOR MORE INFORMATION. 4 EXISTING CAB LIGHT DISCONNECT IS A TOGGLE SWITCH AND SHALL BE REPLACED WITH FUSED DISCONNECT. REMOVE EXISTING TOGGLE SWITCH AND MAINTAIN EXISTING CIRCUITRY FOR CONNECTION TO NEW DISCONNECT SWITCH IN NEW WORK. EC SHALL VERIFY CIRCUIT TO DISCONNECT IS DEDICATED PER THE REQUIREMENTS OF NEC 620.22(A). 5 CONTRACTOR SHALL MAINTAIN EXISTING FUSED DISCONNECT IF VERIFIED TO BE A 150A FUSE IN 200A3P DISCONNECT. OTHERWISE REPLACE WITH NEW IN SAME LOCATION. VERIFY FEED TO DISCONNECT MATCHES NEW FEEDER PER EQUIPMENT INDICATED IN MECHANICAL EQUIPMENT SCHEDULE. AE DESIGN Integrated Lighting and Electrical Solutions 1900 Wazee Street #205 Denver, CO 80202 303.296.3034 aedesign-inc.com Project #: 3912.00 GENERAL NOTES A B C D HATCHED AREA REPRESENTS AREA WITH NO ELECTRICAL SCOPE. ALL EQUIPMENT AND DEVICES SHOWN IN DARK LINE WEIGHT SHALL BE DEMOLISHED. MAINTAIN EXISTING CIRCUITRY FOR REUSE IN NEW WORK. CONTRACTOR TO VERIFY ANY CIRCUITS MODIFIED ENTIRELY OR IN PART SHALL NOT EXCEED 1920VA AND (8) RECEPTACLES MAXIMUM PER CIRCUIT. CONTRACTOR TO VERIFY WITH SECURITY VENDOR AND LOW VOLTAGE VENDOR ANY WORK PRIOR TO DEMOLITION OF SECURITY OR LOW VOLTAGE DEVICES OR EQUIPMENT. 4 8/14/19 08/21/2019