Field Plan Set Must Be Printed In Color
SEPARATE PERMITS ARE
REQUIRED FOR ELECTRICAL,
PLUMBING, MECHANICAL, OR
FIRE SPRINKLER WORK
0061-2020-BCHO
WEST END HOUSE LLC
209 E BLEEKER ST
273707320002
1
08/28/2020
bonniem
SEE NOTES #1 PLANS
External Energy Use Approved
RREMP CREMP
PERMIT #:0061-2020-BCHO DATE:__8/28/20
SNOWMELT:_1381 SF____________________
POOL: __0_______________________
SPA: __51 SF + 40 SF EXEMPT______
OFFSET:_7.68KW SOLAR PV + GSHP_
REMP SHEET: __A1.3___________________
REVIEWED BY: __BONNIE MUHIGIRWA
SNOWMELT SYSTEM AND EQUIPMENT MANDATORY REQ’S.
All snowmelt systems shall meet the following:
-Any portions in the Right of Way must be on a separate zone. A ROW
permit and Permanent Encroachment License are required.
-R10 insulation shall be installed under the area to be snow melted or R5
insulation shall be installed under and at the slab edges. (Ordinance 11
Series 2011)
-Automatic controls installed for system shut off when pavement
temperature is above 50°F and no precipitation is falling. (2009 IECC
Sec. 403.8 & 503.2.4.5)
-Automatic or manual controls installed for system shut off when outdoor
temperature is above 40°F. (2009 IECC Sec. 403.8 & 503.2.4.5)
-Inspection by testing hydrostatically at 1½ times max system design
pressure, but not less than 100psi, for 15minutes. (2009 IMC Sec.
1208.1)
MINIMUM BOILER AFUE: _.95%__________
09/08/2020