HomeMy WebLinkAboutFile Documents.232 E Main St.0078-2020-BCHO (78)COMcheck Software Version 4.1.1.0
Exterior Lighting Compliance Certificate
Project Title:
2015 IECC
Project Type:New Construction
Permit No.0132.2018.ACBK
Permit Date:2019
Construction Site:
232 East Main Street
Aspen, CO 81611
Owner/Agent:
Brad Hribar
Centaur Construction
1200 W Lake St Ste 200
Chicago, IL 60607
3127148519
bhribar@centaurco.com
Designer/Contractor:
Zachary Gains
AEC
9707488520
zach@aec-vail.com
Project Information
Energy Code:
232 East Main Street
4 (High activity metropolitan commercial district)Exterior Lighting Zone
Allowed Exterior Lighting Power
A
Area/Surface Category
B
Quantity
C
Allowed
Watts / Unit
D
Tradable
Wattage
E
Allowed Watts
(B X C)
Main entry 90 ft of door 30 Yes 2700
Total Tradable Watts (a) =
Total Allowed Watts =
Total Allowed Supplemental Watts (b) =
2700
2700
1300
(a)Wattage tradeoffs are only allowed between tradable areas/surfaces.
(b)A supplemental allowance equal to 1300 watts may be applied toward compliance of both non-tradable and tradable areas/surfaces.
Proposed Exterior Lighting Power
E
(C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
Main entry (90 ft of door width): Tradable Wattage
LED 1: FIXTURE A: Other:1 11 17 187
LED 2: FIXTURE B: Other:1 4 10 42
LED 3: FIXTURE H: Other:1 1 25 25
254Total Tradable Proposed Watts =
Exterior Lighting Compliance Statement
Compliance Statement: The proposed exterior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed exterior lighting systems have been
designed to meet the 2015 IECC requirements in COMcheck Version 4.1.1.0 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist.
Name - Title Signature Date
Exterior Lighting PASSES: Design 94% better than code
Project Title:
Data filename:
232 East Main Street
P:\Current Projects\18029.00 - 232 East Main Street\Calculations\COMcheck\Electrical
COMcheck.cck
03/08/21Report date:
51 ofPage
Zachary Gains 03/08/2021
4/14/2021
04/23/2021
nickt
Inspection Checklist
Requirements: 0.0% were addressed directly in the COMcheck software
COMcheck Software Version 4.1.1.0
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Energy Code: 2015 IECC
Section
#
& Req.ID
Plan Review Complies?Comments/Assumptions
C103.2
[PR8]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the exterior lighting
and electrical systems and equipment
and document where exceptions to
the standard are claimed. Information
provided should include exterior
lighting power calculations, wattage of
bulbs and ballasts, transformers and
control devices.
Complies
Does Not
Not Observable
Not Applicable
C406
[PR9]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the additional energy
efficiency package options.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
232 East Main Street
P:\Current Projects\18029.00 - 232 East Main Street\Calculations\COMcheck\Electrical
COMcheck.cck
03/08/21Report date:
52 ofPage
4/14/2021
Section
#
& Req.ID
Rough-In Electrical Inspection Complies?Comments/Assumptions
C405.2.5
[EL25]null
Automatic lighting controls for exterior
lighting installed. Controls will be
daylight controlled, set based on
business operation time-of-day, or
reduce connected lighting > 30%.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
232 East Main Street
P:\Current Projects\18029.00 - 232 East Main Street\Calculations\COMcheck\Electrical
COMcheck.cck
03/08/21Report date:
53 ofPage
4/14/2021
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
C405.5.1
[FI19]1
Exterior lighting power is consistent
with what is shown on the approved
lighting plans, demonstrating
proposed watts are less than or equal
to allowed watts.
Complies
Does Not
Not Observable
Not Applicable
See the Exterior Lighting fixture schedule for values.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
232 East Main Street
P:\Current Projects\18029.00 - 232 East Main Street\Calculations\COMcheck\Electrical
COMcheck.cck
03/08/21Report date:
54 ofPage
4/14/2021
Project Title:
Data filename:
232 East Main Street
P:\Current Projects\18029.00 - 232 East Main Street\Calculations\COMcheck\Electrical
COMcheck.cck
03/08/21Report date:
55 ofPage
4/14/2021