HomeMy WebLinkAboutFile Documents.210 S West End St.0011-2021-BCHO (17)Holesaw size (R) (diameter): 0 inches
On Center Spacing (T): 0 inches
% Open (30% minimum req'd): #DIV/0!
Minimum required thickness of EPS/XPS
insulation to get overall R-10:#DIV/0! inches
Holesaw size (R) (diameter): 2.5 inches
Vertical On Center Spacing (U1): 4 inches
Horizontal On Center Spacing (U2): 4 inches
% Open (30% minimum req'd): 30.7%
Minimum required thickness of EPS/XPS
insulation to get overall R-10: 2.61 inches
City of Aspen
V1 modified 1/25/2017
Pervious Snowmelt Insulation Perforation Calculator
The City of Aspen has created and provided this software solely as
a reference. Users should obtain assistance from a qualified
professional to verify accuracy and applicability before
proceeding. The City of Aspen makes no express or implied
warranty with respect to this software or any information
contained herein. To the full extent permissible by law, the City of
Aspen disclaims all responsibility for any damages or losses
(including, without limitation, structural damage, building defects,
financial loss, damages for loss in business projects, loss of profits
or other consequential losses) arising in contract, tort or
otherwise from the use of or inability to use this software, or from
any action or decision taken as a result of using this software.
Sand with snowmelt tubing
Pervious pavers
3" of insulation (R-15) with holes sized and spaced as calculated
Screened rock below filter fabric
example section detail
Compacted road base
08/10/2021
SEE CIVIL SHEET C7 FOR
CORRESPONDING DETAILING
08/31/2021