Page: A-7.22 ELECTRICAL EQUIPMENT ENCLOSURE AND
CONDENSER ENCLOSURE
Page Index: 3
Author: nickt
Color:
File Name: 395 THUNDERBOWL - CO2 Responses - ARCH
DRAWINGS.pdf
This comment was intended to
apply to the condensers:
At all equipment screens,
provide and dimension the
following per 2015 IMC 306:
1. 30"x30" clear working space
in front of the control side of
each piece of equipment for
service access. 306.1
2. Provide a door that when
opened, provides a minimum 24"
clearance, provided the
equipment can be removed
without dismantling the screen.
Otherwise, make the door wide
enough to remove the appliance.
306.2
3. Provide clearances as
required by manufacturer's
installation instructions.
395 THUNDERBOWL - CO2 Responses - ARCH DRAWINGS.pdf (1)
DRAWING ISSUE
LO
T
7
TH
U
N
D
E
R
B
O
39
5
Th
u
n
d
e
r
b
o
w
l
La
n
e
, As
p
e
n
, CO
SHEET No.
DRAWN BY:
PROJECT No:1605
RH
PERMIT SETDRB SET
ASPEN STAMPS
PERMIT RESUBMITTAL 1
PRICING SETPERMIT RESUBMITTAL 2
SHELL & CORE C.D. SET
CONSTRUCTION DOCSLANDSCAPING CD'S
FULL ARCH. SET
C.O.-2 RESPONSES
A-7.22
ELECTRICAL EQUIPMENTENCLOSURE ANDCONDENSER ENCLOSURE
07/13/201705/18/2017
01/16/2018
01/19/201804/19/2018
04/27/2018
08/27/201802/14/2020
03/03/2020
03/06/2020
SHEET No.
2'-31/2"4'-2"4'-2"2'-111/2"8"24'-61/2"8"
3'-8"-CLR
3'-8"-CLR 3'-8"-CLR
11"2'-01/2"
6'-71/2"
1'-
0
"
1'-
0
"
EQ EQ EQ EQ
98'-5"
101'-0"
RS AND WALLS
HANDLES, TBD
WOOD SLAT SCREENINGWITH SOUND MITIGATIONPANELS MOUNTED BETWEENPOSTS AT INTERIOR SIDE
PV METERHOUSEMETER GENERATOR+/S C/T CAN
4 5 6 7
T.O. SLAB
T.O. WALL
ELEC. EQUIP. AND CONDENSER ENCLOSURE - ENLARGED EAST ELEVATION
ELEC. EQUIP. AND CONDENSER ENCLOSURE - ENLARGED PLAN
1/2" = 1'-0"
1/2" = 1'-0"
2A-7.25
8"
5'-
1
0
"
6"101/2"
6"1'-1"7"1'-1"6"5"5"1'-0"6"1'-5"5"5"51/2"2'-10"51/2"
5'-21/2"-CLR
PV DISCONNECT - FACE OFCONTROLS TO BE SETBACK 1" MAX. FROM FACEOF CABINET
DASHED LINE INDICATES30"W X 36" DEEPCLEARANCE AT PVDISCONNECT
. -2 RESPONSES
C.O. -2 RESPONSES
This comment was intended to
apply to the condensers:
At all equipment screens,
provide and dimension the
following per 2015 IMC 306:
1. 30"x30" clear working space
in front of the control side of
each piece of equipment for
service access. 306.12. Provide a door that whenopened, provides a minimum 24"clearance, provided theequipment can be removedwithout dismantling the screen.Otherwise, make the door wideenough to remove the appliance.306.23. Provide clearances asrequired by manufacturer'sinstallation instructions.
RH/DJA RESPONSE:
1. SEE SHEETS A-7.22 AND A7.23 WHICH NOW
SHOW THE 30" X 30" CLEARANCES AS REQUIRED
BY 2015 IMC 306.
2. SEE SHEETS A-7.22 AND A-7.23 WHICH SHOW
DOORS AT THE CONDENSER ENCLOSURES.
3. SEE SHEETS A-7.22 AND A7.23 WHICH NOW
SHOW THE CONDENSER MANUFACTURER
CLEARANCES .
NOTE: I'VE ALSO INCLUDED A MECHANICAL PLAN
(SHEET M-112) WHICH IS COORDINATED WITH THE
CONDENSER LAYOUT SHOWN IN THE
ARCHITECTURAL DRAWINGS.
04/01/2020