Loading...
HomeMy WebLinkAboutFile Documents.555 E Durant Ave.0025.2019 (20).ACBK555 Durant 2E_BuildingComments_1 Page: [1] 24442 NON Lockers 190227-A0 Cover File Name: Gorsuch - Aspen - Locker Rm 190410 ARCH SET.pdf Author: bonniem Subject: PlanCheck Color: Provide additional information regarding the new mechanical system including a mechanical plan and calculations showing that adequate ventilation will be provided per 2015 IEBC 1009.1 and 2015 IBC Table 403.3.1.1 Gorsuch - Aspen - Locker Rm 190410 ARCH SET.pdf (8) Page: [1] 24442 NON Lockers 190227-A0 Cover File Name: Gorsuch - Aspen - Locker Rm 190410 ARCH SET.pdf Author: bonniem Subject: PlanCheck Color: Given that the locker room provides changing rooms and lounge space, it more closely resembles a B occupancy than S-1 which would be strictly storage. Correct the occupancy classification on sheet A0 Page: [2] 24442 NON Lockers 190227-A1 Accessibility Plan File Name: Gorsuch - Aspen - Locker Rm 190410 ARCH SET.pdf Author: bonniem Subject: PlanCheck Color: Will the snack area contain a service counter or point of sale? If yes provide interior elevations and/or plan notes showing that they meet the dimension requirements in ICC A117.1-2009. Page: [3] 24442 NON Lockers 190227-A2 Plans File Name: Gorsuch - Aspen - Locker Rm 190410 ARCH SET.pdf Author: bonniem Subject: PlanCheck Color: Provide U-factor information for new exterior door. Must be .77 or better per 2015 IECC C402.4 Page: [3] 24442 NON Lockers 190227-A2 Plans File Name: Gorsuch - Aspen - Locker Rm 190410 ARCH SET.pdf Author: bonniem Subject: PlanCheck Color: Door 2 to the cleaning/storage area must meet the minimum clear opening width of 32" 1010.1.1 Exception 3 for storage closets is limited to closets that are 10 sqft or less. Tel: 970 Vail Tel: 415 San Franc www.Pier info@Pier PI + ARCH Provide additionalinformation regardingthe new mechanicalsystem including amechanical plan andcalculations showingthat adequateventilation will beprovided per 2015IEBC 1009.1 and 2015IBC Table 403.3.1.1 CONTROLLEDACCESS ENTRY 7 6 1 F N 2 1 0 (E) S T E P S U P (E) ENTRY/EXITTO REMAIN (E) COMMERCIALTENANT SPACE DEA N S T R E E T GALENA STREE S-1STORAGE NOTE:OCCUPANCY BELOW: PARKING GARAGE (S2)OCCUPANCY ABOVE: RESIDENTIAL (R2) GONDOLA PLAZ C:\U s e r s \ t f r y e \ D r o p b o x ( R e s o r t D e s i g n ) \ R e s o r t D e s i g n T e a m F o l d e r \ 2 4 4 4 2 G o r s u c h - A s p e n I I \ C A D \ 2 4 4 4 2 N O N L o c k e r s 1 9 0 2 2 7 . d w g , A 0 C o v e r , 4 / 1 0 / 2 0 1 9 1 : 0 8 : 2 5 A M Given that the lockerroom provideschanging rooms andlounge space, it moreclosely resembles a Boccupancy than S-1which would be strictlystorage. Correct theoccupancyclassification on sheetA0 LOCKER ROOMATTENDANT BEVERAGE AND SNACKS CONTROLLEDACCESS ENTRY LOC K E R S LOC K E R S 2 7 1 2 (E) A C C E S S I B L E R O U T E (E) ENTRY/EXITTO REMAIN DE A N S T R E E T LOC K E R S LOCKERS LOC K E R S tion 305.3 is provided etail this page.) a forward reach or side(1015 mm) minimum and Will the snack areacontain a servicecounter or point ofsale? If yes provideinterior elevationsand/or plan notesshowing that they meetthe dimensionrequirements in ICCA117.1-2009. LOCKER ROOMATTENDANT CONTROLLED ACCESS ENTRY 1 2 LOCKERS LO C K E R S Provide U-factor information for new exterior door. Must be .77 or better per 2015IECC C402.4 SKI TUNINGTROLLEYS LOCKER ROOMATTENDANT LEDTRY CONTROLLEDACCESS ENTRY 2 3 1 LOCKERS (E) COMMON AREAINTERIOR ARCADE LOCKERS LOC K E R S LOCK E R S Drawing T Issue Dat TAG ROOMNO.ROOM NAME SIZE (WXH)HARDWARE NOTES COMMENTS 04/10/19 LIMIT OFALTERATIONWORK 8A4 Door 2 to thecleaning/storage areamust meet theminimum clearopening width of 32"1010.1.1 Exception 3 forstorage closets islimited to closets thatare 10 sqft or less. Page: [3] 24442 NON Lockers 190227-A2 Plans File Name: Gorsuch - Aspen - Locker Rm 190410 ARCH SET.pdf Author: bonniem Subject: PlanCheck Color: Provide a wall assembly for the exterior wall that showing that the 1-hour fire resistance rating will be maintained. (Table 601) Page: [5] 24442 NON Lockers 190227-A4 Int Elevs and Details File Name: Gorsuch - Aspen - Locker Rm 190410 ARCH SET.pdf Author: bonniem Subject: 3/16" Scale Color: 0'-1" Page: [5] 24442 NON Lockers 190227-A4 Int Elevs and Details File Name: Gorsuch - Aspen - Locker Rm 190410 ARCH SET.pdf Author: bonniem Subject: PlanCheck Color: The front of the lavatory must be 34" maximum above the floor measured to whatever is higher the rim of the sink or the counter surface. Revise so that the rim of the sink does not exceed 34" from the floor. ICC A117.1-2009 606.3 Page: 1 File Name: Gorsuch - Aspen - Locker Rm 190410 COMcheck LIGHTING COMP REP.pdf Author: bonniem Subject: PlanCheck Color: Clarify in the description for the HP-2 that they are per linear foot. Gorsuch - Aspen - Locker Rm 190410 COMcheck LIGHTING COMP REP.pdf (4) Page: 1 File Name: Gorsuch - Aspen - Locker Rm 190410 COMcheck LIGHTING COMP REP.pdf Author: bonniem Subject: PlanCheck Color: Cut sheet lists wattage as 32. Correct COMcheck or provide the correct spec. L1 K 7A4 Provide a wall assembly for the exterior wall that showing that the 1-hour fire resistance rating will be maintained. (Table 601) 0' - 1 " 7A4 The front of thelavatory must be 34"maximum above thefloor measured towhatever is higher therim of the sink or thecounter surface. Revise so that the rimof the sink does notexceed 34" from thefloor. ICCA117.1-2009 606.3 Interior Lighting Compliance Certificate Project Title:2015 IECC Project Type:Alteration Construction Site:Owner/Agent:Designer/Contractor: Project InformationEnergy Code:Gorsuch Aspen - Locker Room Allowed Interior Lighting PowerAArea Category BFloor Area(ft2) CAllowedWatts / ft2 DAllowed Watts(B X C) 1-East and West Locker Room Areas (Common Space Types:Locker Room) 767 0.75 5751.00 260 (b)Allowance: Decorative Appearance / Fix. ID: P 260 (a)2-North Lobby Area (Common Space Types:Lobby - General) 101 0.90 913-South Lobby Area (Common Space Types:Lobby - General) 105 0.90 944-North Vanity Area and Toilet Compartment (Common Space Types:Restrooms) 105 0.98 1035-South Vanity Area and Toilet Compartment (Common Space Types:Restrooms) 108 0.98 1066-North Changing Room (Retail:Dressing/Fitting Room) 37 0.71 267-South Changing Room (Retail:Dressing/Fitting Room) 41 0.71 298-Cleaning and Storage Room (Common Space Types:Storage <50 sq.ft.) 20 1.24 251310Total Allowed Watts =(a) Area claimed must not exceed the illuminated area permitted for this allowance type.(b) Allowance is (B x C) or the actual wattage of the fixtures given in Proposed Power section, whichever is less. Proposed Interior Lighting Power E(C X D)DFixtureWatt. AFixture ID : Description / Lamp / Wattage Per Lamp / Ballast BLamps/Fixture C# ofFixtures East and West Locker Room Areas ( Common Space Types:Locker Room 767 sq.ft.)LED 26: HP-2: Finelite -Linear Direct/Indirec: Other: 1 48 10 504LED 28: MP: Tech Lighting - Monopoint: Other: 1 2 7 14Incandescent 1: P: Bover Siam 200: Other: 8 1 480 480 North Lobby Area ( Common Space Types:Lobby - General 101 sq.ft.)LED 3: A4-40: Element Recessed Downlight - 4": Other: 1 3 18 54 Clarify in thedescription for theHP-2 that they are perlinear foot. er: 8 1 480 480 ypes:Lobby - General 101 sq.ft.) ight - 4": Other: 1 3 18 54 ypes:Lobby - General 105 sq.ft.) ight - 4": Other: 1 2 18 36 ment ( Common Space Types:Restrooms 105 sq.ft.) t: Other: 1 2 27 54 Other: 1 1 21 21 Cut sheet lists wattage as 32. Correct COMcheck or provide the correct spec. Page: 1 File Name: Gorsuch - Aspen - Locker Rm 190410 COMcheck LIGHTING COMP REP.pdf Author: bonniem Subject: PlanCheck Color: Could do 17 watt per housing spec. Page: 1 File Name: Gorsuch - Aspen - Locker Rm 190410 COMcheck LIGHTING COMP REP.pdf Author: bonniem Subject: PlanCheck Color: All low voltage lighting needs to be entered per transformer. ie: Lamps/fixture = 1, # of fixtures = # of transformers, fixture watt = transformer wattage. Put per transformer in the "fixture ID/description" Page: [1] S2.001 File Name: Gorsuch - Aspen - Locker Rm 190410 STRUCT SET.pdf Author: bonniem Subject: PlanCheck Color: As this is a Type IIIA building, all primary structure requires a 1 hour fire-resistance rating (Table 601). Provide a listed tested assembly for the structural columns. Gorsuch - Aspen - Locker Rm 190410 STRUCT SET.pdf (2) Page: [1] S6.001 File Name: Gorsuch - Aspen - Locker Rm 190410 STRUCT SET.pdf Author: bonniem Subject: PlanCheck Color: The special inspection form provided does not have all of the required signatures. All signatures must be received prior to permit issuance. 8-Cleaning and Storage Room (Common Space Types:Storage <50 sq.ft.) 20 1.24 25 1310Total Allowed Watts = (a) Area claimed must not exceed the illuminated area permitted for this allowance type.(b) Allowance is (B x C) or the actual wattage of the fixtures given in Proposed Power section, whichever is less. Proposed Interior Lighting Power E (C X D) D FixtureWatt. AFixture ID : Description / Lamp / Wattage Per Lamp / Ballast B Lamps/Fixture C # ofFixtures East and West Locker Room Areas ( Common Space Types:Locker Room 767 sq.ft.)LED 26: HP-2: Finelite -Linear Direct/Indirec: Other: 1 48 10 504LED 28: MP: Tech Lighting - Monopoint: Other: 1 2 7 14 Incandescent 1: P: Bover Siam 200: Other: 8 1 480 480 North Lobby Area ( Common Space Types:Lobby - General 101 sq.ft.)LED 3: A4-40: Element Recessed Downlight - 4": Other: 1 3 18 54South Lobby Area ( Common Space Types:Lobby - General 105 sq.ft.)LED 3: A4-40: Element Recessed Downlight - 4": Other: 1 2 18 36 North Vanity Area and Toilet Compartment ( Common Space Types:Restrooms 105 sq.ft.)LED 27: FM: Modern Forms Flush Mount: Other: 1 2 27 54LED 29: S: Modern Forms Wall Sconce: Other: 1 1 21 21 Could do 17 watt perhousing spec. Project Title:2015 IECC Project Type:Alteration Construction Site:Owner/Agent:Designer/Contractor: Project Information Energy Code:Gorsuch Aspen - Locker Room Allowed Interior Lighting Power AArea Category BFloor Area(ft2) CAllowedWatts / ft2 DAllowed Watts(B X C) 1-East and West Locker Room Areas (Common Space Types:Locker Room) 767 0.75 5751.00 260 (b)Allowance: Decorative Appearance / Fix. ID: P 260 (a)2-North Lobby Area (Common Space Types:Lobby - General) 101 0.90 913-South Lobby Area (Common Space Types:Lobby - General) 105 0.90 944-North Vanity Area and Toilet Compartment (Common Space Types:Restrooms) 105 0.98 1035-South Vanity Area and Toilet Compartment (Common Space Types:Restrooms) 108 0.98 1066-North Changing Room (Retail:Dressing/Fitting Room) 37 0.71 267-South Changing Room (Retail:Dressing/Fitting Room) 41 0.71 298-Cleaning and Storage Room (Common Space Types:Storage <50 sq.ft.) 20 1.24 251310Total Allowed Watts =(a) Area claimed must not exceed the illuminated area permitted for this allowance type.(b) Allowance is (B x C) or the actual wattage of the fixtures given in Proposed Power section, whichever is less. Proposed Interior Lighting Power E(C X D)DFixtureWatt. AFixture ID : Description / Lamp / Wattage Per Lamp / Ballast BLamps/Fixture C# ofFixtures East and West Locker Room Areas ( Common Space Types:Locker Room 767 sq.ft.)LED 26: HP-2: Finelite -Linear Direct/Indirec: Other: 1 48 10 504LED 28: MP: Tech Lighting - Monopoint: Other: 1 2 7 14Incandescent 1: P: Bover Siam 200: Other: 8 1 480 480North Lobby Area ( Common Space Types:Lobby - General 101 sq.ft.)LED 3: A4-40: Element Recessed Downlight - 4": Other: 1 3 18 54South Lobby Area ( Common Space Types:Lobby - General 105 sq.ft.)LED 3: A4-40: Element Recessed Downlight - 4": Other: 1 2 18 36 North Vanity Area and Toilet Compartment ( Common Space Types:Restrooms 105 sq.ft.)LED 27: FM: Modern Forms Flush Mount: Other: 1 2 27 54LED 29: S: Modern Forms Wall Sconce: Other: 1 1 21 21 All low voltage lightingneeds to be enteredper transformer. ie:Lamps/fixture = 1, # offixtures = # oftransformers, fixturewatt = transformerwattage. Put pertransformer in the"fixture ID/description" DATE4/5/2019 PROJECT #: 19. DRAWN BY: BW CHECKED BY: B NO R T H O F N E L L G O R S U C H 55 5 E A S T D U R A N T A V E N U E AS P E N , C O L O R A D O S2.0 (E) W12x19 Roof Beam 1 S6.001 3S6.001 ng Plan (Partial) As this is a Type IIIAbuilding, all primarystructure requires a 1hour fire-resistancerating (Table 601). Provide a listed testedassembly for thestructural columns. SCALE: 3/ 1 DOUB SCALE: 3/ 3 BEAM 2-123/16 2-123/16 3/16 2-12 SCALE: 3/ 2 LINTE as shown on these drawings. STRUCTURAL STEEL1.All detailing, fabrication, and erection of structural and miscellaneous steel shall be in accordance with the requirements of theAmerican Institute of Steel Construction (AISC) Code of Standard Practice, latest edition, and the American Welding Society(AWS) Specifications.2.All structural steel rolled shapes, except angles and plates, shall conform to ASTM A992, 50 ksi.3.Angles, channels & plates shall conform to ASTM A36, 36 ksi, unless otherwise noted on the Drawings.4.All bolts for steel-to-steel connections shall conform to ASTM A325, unless otherwise noted on the Drawings.5.All welding shall be in accordance with the requirements of the IBC and the Structural Welding Code, AWS D1, latest edition, bythe American Welding Society. Shop welding shall be performed in shops approved by the Building Official, per IBC. Weldingshall be done using E70XX electrodes, unless noted otherwise on the Drawings. STRUCTURAL ERECTION AND BRACING REQUIREMENTS1.The Structural Drawings illustrate the completed structure with all elements in their final positions, properly supported and braced.2.The Contractor, in the proper sequence, shall provide shoring and bracing as required during construction to achieve the finalcompleted structure. Design, sequencing, location, placement, etc., of bracing and shoring is the responsibility of the Contractor.3.The Contractor shall be responsible for the safety of the building and workers during construction. The Contractor shall complywith all applicable safety regulations. ABBREVIATIONS AND SYMBOLSBMBEAMCMUCONCRETE MASONRY UNIT(S)CONT CONTINUOUSDTLDETAIL(E)EXISTINGEAEACH o.c.ON CENTERREQ'D REQUIREDSTLSTEEL @ ATØDIAMETER DOUBLE-ANGLE LINTEL INSTALLATION SEQUENCE1.Saw cut in horizontal plane on only one side of stone masonry wall to provide for horizontal leg of angle to fit.2.Set first angle into place as shown on drawing.3.Saw cut in horizontal plane on opposite side of stone masonry wall and set second angle.4.Drill through CMU and roof joist at bolt locations and set bolts. Do not overtighten. Where no CMU is being supported, use nutson inside faces of angles to maintain separation distance.5.Shim and bolt angles to supporting steel beams.6.Remove stone masonry below angles.7.Weld bottom plate to angles as shown. SPECIAL INSPECTION1.The owner shall employ a special inspector per IBC Chapter 17. The special inspector shall submit a copy of all his reports to theOwner, Architect, Structural Engineer, and the Building Department. When the work is completed, the special inspector shallsubmit a final signed report stating whether the work was, to the best of his knowledge, in conformance with the approved set ofplans and specifications and the applicable workmanship provisions of the building code. The Structural Engineer will make visitsto the site to observe general compliance with the approved structural plans, specifications, and change orders. The contractorshall coordinate with the special inspector in order to ensure that the special inspection as indicated below can be performed withminimal impact to the project schedule.2.Special inspection is required for the following types of work. Refer to Chapter 17 of the 2015 IBC for additional testing andspecific requirements.2.1.All shop and field welding (periodic).2.2.All high-strength bolted connections (periodic). The special inspectionform provided doesnot have all of therequired signatures. All signatures must bereceived prior topermit issuance.