Page: [1] 24442 NON Lockers 190227-A0 Cover
File Name: Gorsuch - Aspen - Locker Rm 190410 ARCH
SET.pdf
Author: bonniem
Subject: PlanCheck
Color:
Provide additional information
regarding the new mechanical
system including a mechanical
plan and calculations showing
that adequate ventilation will be
provided per 2015 IEBC 1009.1
and 2015 IBC Table 403.3.1.1
Gorsuch - Aspen - Locker Rm 190410 ARCH SET.pdf (8)
Page: [1] 24442 NON Lockers 190227-A0 Cover
File Name: Gorsuch - Aspen - Locker Rm 190410 ARCH
SET.pdf
Author: bonniem
Subject: PlanCheck
Color:
Given that the locker room
provides changing rooms and
lounge space, it more closely
resembles a B occupancy than
S-1 which would be strictly
storage. Correct the occupancy
classification on sheet A0
Page: [2] 24442 NON Lockers 190227-A1 Accessibility Plan
File Name: Gorsuch - Aspen - Locker Rm 190410 ARCH
SET.pdf
Author: bonniem
Subject: PlanCheck
Color:
Will the snack area contain a
service counter or point of sale?
If yes provide interior elevations
and/or plan notes showing that
they meet the dimension
requirements in ICC
A117.1-2009.
Page: [3] 24442 NON Lockers 190227-A2 Plans
File Name: Gorsuch - Aspen - Locker Rm 190410 ARCH
SET.pdf
Author: bonniem
Subject: PlanCheck
Color:
Provide U-factor information for
new exterior door. Must be .77
or better per 2015 IECC C402.4
Page: [3] 24442 NON Lockers 190227-A2 Plans
File Name: Gorsuch - Aspen - Locker Rm 190410 ARCH
SET.pdf
Author: bonniem
Subject: PlanCheck
Color:
Door 2 to the cleaning/storage
area must meet the minimum
clear opening width of 32"
1010.1.1
Exception 3 for storage closets
is limited to closets that are 10
sqft or less.
Tel: 970
Vail
Tel: 415
San Franc
www.Pier info@Pier
PI +
ARCH
Provide additionalinformation regardingthe new mechanicalsystem including amechanical plan andcalculations showingthat adequateventilation will beprovided per 2015IEBC 1009.1 and 2015IBC Table 403.3.1.1
CONTROLLEDACCESS ENTRY
7
6
1
F N
2
1
0
(E) S
T
E
P
S
U
P
(E) ENTRY/EXITTO REMAIN
(E) COMMERCIALTENANT SPACE
DEA
N
S
T
R
E
E
T
GALENA STREE
S-1STORAGE
NOTE:OCCUPANCY BELOW: PARKING GARAGE (S2)OCCUPANCY ABOVE: RESIDENTIAL (R2)
GONDOLA PLAZ
C:\U
s
e
r
s
\
t
f
r
y
e
\
D
r
o
p
b
o
x
(
R
e
s
o
r
t
D
e
s
i
g
n
)
\
R
e
s
o
r
t
D
e
s
i
g
n
T
e
a
m
F
o
l
d
e
r
\
2
4
4
4
2
G
o
r
s
u
c
h
-
A
s
p
e
n
I
I
\
C
A
D
\
2
4
4
4
2
N
O
N
L
o
c
k
e
r
s
1
9
0
2
2
7
.
d
w
g
,
A
0
C
o
v
e
r
,
4
/
1
0
/
2
0
1
9
1
:
0
8
:
2
5
A
M
Given that the lockerroom provideschanging rooms andlounge space, it moreclosely resembles a Boccupancy than S-1which would be strictlystorage. Correct theoccupancyclassification on sheetA0
LOCKER ROOMATTENDANT
BEVERAGE AND SNACKS
CONTROLLEDACCESS ENTRY
LOC
K
E
R
S
LOC
K
E
R
S
2
7
1
2
(E)
A
C
C
E
S
S
I
B
L
E
R
O
U
T
E
(E) ENTRY/EXITTO REMAIN
DE
A
N
S
T
R
E
E
T
LOC
K
E
R
S
LOCKERS
LOC
K
E
R
S
tion 305.3 is provided
etail this page.)
a forward reach or side(1015 mm) minimum and
Will the snack areacontain a servicecounter or point ofsale? If yes provideinterior elevationsand/or plan notesshowing that they meetthe dimensionrequirements in ICCA117.1-2009.
LOCKER ROOMATTENDANT
CONTROLLED
ACCESS ENTRY
1
2
LOCKERS
LO
C
K
E
R
S
Provide U-factor
information for new
exterior door. Must be
.77 or better per 2015IECC C402.4
SKI TUNINGTROLLEYS
LOCKER ROOMATTENDANT
LEDTRY
CONTROLLEDACCESS ENTRY
2
3
1
LOCKERS
(E) COMMON AREAINTERIOR ARCADE
LOCKERS
LOC
K
E
R
S
LOCK
E
R
S
Drawing T
Issue Dat
TAG ROOMNO.ROOM NAME SIZE (WXH)HARDWARE NOTES COMMENTS
04/10/19
LIMIT OFALTERATIONWORK
8A4
Door 2 to thecleaning/storage areamust meet theminimum clearopening width of 32"1010.1.1 Exception 3 forstorage closets islimited to closets thatare 10 sqft or less.
Page: [3] 24442 NON Lockers 190227-A2 Plans
File Name: Gorsuch - Aspen - Locker Rm 190410 ARCH
SET.pdf
Author: bonniem
Subject: PlanCheck
Color:
Provide a wall assembly for the
exterior wall that showing that
the 1-hour fire resistance rating
will be maintained. (Table 601)
Page: [5] 24442 NON Lockers 190227-A4 Int Elevs and
Details
File Name: Gorsuch - Aspen - Locker Rm 190410 ARCH
SET.pdf
Author: bonniem
Subject: 3/16" Scale
Color:
0'-1"
Page: [5] 24442 NON Lockers 190227-A4 Int Elevs and
Details
File Name: Gorsuch - Aspen - Locker Rm 190410 ARCH
SET.pdf
Author: bonniem
Subject: PlanCheck
Color:
The front of the lavatory must be
34" maximum above the floor
measured to whatever is higher
the rim of the sink or the counter
surface. Revise so that the rim
of the sink does not exceed 34"
from the floor. ICC A117.1-2009
606.3
Page: 1
File Name: Gorsuch - Aspen - Locker Rm 190410 COMcheck
LIGHTING COMP REP.pdf
Author: bonniem
Subject: PlanCheck
Color:
Clarify in the description for the
HP-2 that they are per linear
foot.
Gorsuch - Aspen - Locker Rm 190410 COMcheck LIGHTING COMP REP.pdf (4)
Page: 1
File Name: Gorsuch - Aspen - Locker Rm 190410 COMcheck
LIGHTING COMP REP.pdf
Author: bonniem
Subject: PlanCheck
Color:
Cut sheet lists wattage as 32.
Correct COMcheck or provide
the correct spec.
L1 K
7A4
Provide a wall
assembly for the
exterior wall that
showing that the
1-hour fire resistance
rating will be
maintained. (Table
601)
0'
-
1
"
7A4
The front of thelavatory must be 34"maximum above thefloor measured towhatever is higher therim of the sink or thecounter surface. Revise so that the rimof the sink does notexceed 34" from thefloor. ICCA117.1-2009 606.3
Interior Lighting Compliance Certificate
Project Title:2015 IECC
Project Type:Alteration
Construction Site:Owner/Agent:Designer/Contractor:
Project InformationEnergy Code:Gorsuch Aspen - Locker Room
Allowed Interior Lighting PowerAArea Category BFloor Area(ft2)
CAllowedWatts / ft2
DAllowed Watts(B X C)
1-East and West Locker Room Areas (Common Space Types:Locker Room) 767 0.75 5751.00 260 (b)Allowance: Decorative Appearance / Fix. ID: P 260 (a)2-North Lobby Area (Common Space Types:Lobby - General) 101 0.90 913-South Lobby Area (Common Space Types:Lobby - General) 105 0.90 944-North Vanity Area and Toilet Compartment (Common Space Types:Restrooms) 105 0.98 1035-South Vanity Area and Toilet Compartment (Common Space Types:Restrooms) 108 0.98 1066-North Changing Room (Retail:Dressing/Fitting Room) 37 0.71 267-South Changing Room (Retail:Dressing/Fitting Room) 41 0.71 298-Cleaning and Storage Room (Common Space Types:Storage <50 sq.ft.) 20 1.24 251310Total Allowed Watts =(a) Area claimed must not exceed the illuminated area permitted for this allowance type.(b) Allowance is (B x C) or the actual wattage of the fixtures given in Proposed Power section, whichever is less.
Proposed Interior Lighting Power E(C X D)DFixtureWatt.
AFixture ID : Description / Lamp / Wattage Per Lamp / Ballast BLamps/Fixture
C# ofFixtures
East and West Locker Room Areas ( Common Space Types:Locker Room 767 sq.ft.)LED 26: HP-2: Finelite -Linear Direct/Indirec: Other: 1 48 10 504LED 28: MP: Tech Lighting - Monopoint: Other: 1 2 7 14Incandescent 1: P: Bover Siam 200: Other: 8 1 480 480
North Lobby Area ( Common Space Types:Lobby - General 101 sq.ft.)LED 3: A4-40: Element Recessed Downlight - 4": Other: 1 3 18 54
Clarify in thedescription for theHP-2 that they are perlinear foot.
er: 8 1 480 480
ypes:Lobby - General 101 sq.ft.)
ight - 4": Other: 1 3 18 54
ypes:Lobby - General 105 sq.ft.)
ight - 4": Other: 1 2 18 36
ment ( Common Space Types:Restrooms 105 sq.ft.)
t: Other: 1 2 27 54
Other: 1 1 21 21
Cut sheet lists wattage
as 32. Correct
COMcheck or provide
the correct spec.
Page: 1
File Name: Gorsuch - Aspen - Locker Rm 190410 COMcheck
LIGHTING COMP REP.pdf
Author: bonniem
Subject: PlanCheck
Color:
Could do 17 watt per housing
spec.
Page: 1
File Name: Gorsuch - Aspen - Locker Rm 190410 COMcheck
LIGHTING COMP REP.pdf
Author: bonniem
Subject: PlanCheck
Color:
All low voltage lighting needs to
be entered per transformer. ie:
Lamps/fixture = 1, # of fixtures =
# of transformers, fixture watt =
transformer wattage. Put per
transformer in the "fixture
ID/description"
Page: [1] S2.001
File Name: Gorsuch - Aspen - Locker Rm 190410 STRUCT
SET.pdf
Author: bonniem
Subject: PlanCheck
Color:
As this is a Type IIIA building, all
primary structure requires a 1
hour fire-resistance rating (Table
601). Provide a listed tested
assembly for the structural
columns.
Gorsuch - Aspen - Locker Rm 190410 STRUCT SET.pdf (2)
Page: [1] S6.001
File Name: Gorsuch - Aspen - Locker Rm 190410 STRUCT
SET.pdf
Author: bonniem
Subject: PlanCheck
Color:
The special inspection form
provided does not have all of the
required signatures. All
signatures must be received
prior to permit issuance.
8-Cleaning and Storage Room (Common Space Types:Storage <50 sq.ft.) 20 1.24 25
1310Total Allowed Watts =
(a) Area claimed must not exceed the illuminated area permitted for this allowance type.(b) Allowance is (B x C) or the actual wattage of the fixtures given in Proposed Power section, whichever is less.
Proposed Interior Lighting Power E
(C X D)
D
FixtureWatt.
AFixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/Fixture
C
# ofFixtures
East and West Locker Room Areas ( Common Space Types:Locker Room 767 sq.ft.)LED 26: HP-2: Finelite -Linear Direct/Indirec: Other: 1 48 10 504LED 28: MP: Tech Lighting - Monopoint: Other: 1 2 7 14
Incandescent 1: P: Bover Siam 200: Other: 8 1 480 480
North Lobby Area ( Common Space Types:Lobby - General 101 sq.ft.)LED 3: A4-40: Element Recessed Downlight - 4": Other: 1 3 18 54South Lobby Area ( Common Space Types:Lobby - General 105 sq.ft.)LED 3: A4-40: Element Recessed Downlight - 4": Other: 1 2 18 36
North Vanity Area and Toilet Compartment ( Common Space Types:Restrooms 105 sq.ft.)LED 27: FM: Modern Forms Flush Mount: Other: 1 2 27 54LED 29: S: Modern Forms Wall Sconce: Other: 1 1 21 21
Could do 17 watt perhousing spec.
Project Title:2015 IECC
Project Type:Alteration
Construction Site:Owner/Agent:Designer/Contractor:
Project Information
Energy Code:Gorsuch Aspen - Locker Room
Allowed Interior Lighting Power
AArea Category BFloor Area(ft2)
CAllowedWatts / ft2
DAllowed Watts(B X C)
1-East and West Locker Room Areas (Common Space Types:Locker Room) 767 0.75 5751.00 260 (b)Allowance: Decorative Appearance / Fix. ID: P 260 (a)2-North Lobby Area (Common Space Types:Lobby - General) 101 0.90 913-South Lobby Area (Common Space Types:Lobby - General) 105 0.90 944-North Vanity Area and Toilet Compartment (Common Space Types:Restrooms) 105 0.98 1035-South Vanity Area and Toilet Compartment (Common Space Types:Restrooms) 108 0.98 1066-North Changing Room (Retail:Dressing/Fitting Room) 37 0.71 267-South Changing Room (Retail:Dressing/Fitting Room) 41 0.71 298-Cleaning and Storage Room (Common Space Types:Storage <50 sq.ft.) 20 1.24 251310Total Allowed Watts =(a) Area claimed must not exceed the illuminated area permitted for this allowance type.(b) Allowance is (B x C) or the actual wattage of the fixtures given in Proposed Power section, whichever is less.
Proposed Interior Lighting Power E(C X D)DFixtureWatt.
AFixture ID : Description / Lamp / Wattage Per Lamp / Ballast BLamps/Fixture
C# ofFixtures
East and West Locker Room Areas ( Common Space Types:Locker Room 767 sq.ft.)LED 26: HP-2: Finelite -Linear Direct/Indirec: Other: 1 48 10 504LED 28: MP: Tech Lighting - Monopoint: Other: 1 2 7 14Incandescent 1: P: Bover Siam 200: Other: 8 1 480 480North Lobby Area ( Common Space Types:Lobby - General 101 sq.ft.)LED 3: A4-40: Element Recessed Downlight - 4": Other: 1 3 18 54South Lobby Area ( Common Space Types:Lobby - General 105 sq.ft.)LED 3: A4-40: Element Recessed Downlight - 4": Other: 1 2 18 36
North Vanity Area and Toilet Compartment ( Common Space Types:Restrooms 105 sq.ft.)LED 27: FM: Modern Forms Flush Mount: Other: 1 2 27 54LED 29: S: Modern Forms Wall Sconce: Other: 1 1 21 21
All low voltage lightingneeds to be enteredper transformer. ie:Lamps/fixture = 1, # offixtures = # oftransformers, fixturewatt = transformerwattage. Put pertransformer in the"fixture ID/description"
DATE4/5/2019
PROJECT #: 19.
DRAWN BY: BW
CHECKED BY: B
NO
R
T
H
O
F
N
E
L
L
G
O
R
S
U
C
H
55
5
E
A
S
T
D
U
R
A
N
T
A
V
E
N
U
E
AS
P
E
N
,
C
O
L
O
R
A
D
O
S2.0
(E) W12x19 Roof Beam
1
S6.001
3S6.001
ng Plan (Partial)
As this is a Type IIIAbuilding, all primarystructure requires a 1hour fire-resistancerating (Table 601). Provide a listed testedassembly for thestructural columns.
SCALE: 3/ 1 DOUB
SCALE: 3/ 3 BEAM
2-123/16
2-123/16
3/16 2-12
SCALE: 3/ 2 LINTE
as shown on these drawings.
STRUCTURAL STEEL1.All detailing, fabrication, and erection of structural and miscellaneous steel shall be in accordance with the requirements of theAmerican Institute of Steel Construction (AISC) Code of Standard Practice, latest edition, and the American Welding Society(AWS) Specifications.2.All structural steel rolled shapes, except angles and plates, shall conform to ASTM A992, 50 ksi.3.Angles, channels & plates shall conform to ASTM A36, 36 ksi, unless otherwise noted on the Drawings.4.All bolts for steel-to-steel connections shall conform to ASTM A325, unless otherwise noted on the Drawings.5.All welding shall be in accordance with the requirements of the IBC and the Structural Welding Code, AWS D1, latest edition, bythe American Welding Society. Shop welding shall be performed in shops approved by the Building Official, per IBC. Weldingshall be done using E70XX electrodes, unless noted otherwise on the Drawings.
STRUCTURAL ERECTION AND BRACING REQUIREMENTS1.The Structural Drawings illustrate the completed structure with all elements in their final positions, properly supported and braced.2.The Contractor, in the proper sequence, shall provide shoring and bracing as required during construction to achieve the finalcompleted structure. Design, sequencing, location, placement, etc., of bracing and shoring is the responsibility of the Contractor.3.The Contractor shall be responsible for the safety of the building and workers during construction. The Contractor shall complywith all applicable safety regulations.
ABBREVIATIONS AND SYMBOLSBMBEAMCMUCONCRETE MASONRY UNIT(S)CONT CONTINUOUSDTLDETAIL(E)EXISTINGEAEACH
o.c.ON CENTERREQ'D REQUIREDSTLSTEEL
@ ATØDIAMETER
DOUBLE-ANGLE LINTEL INSTALLATION SEQUENCE1.Saw cut in horizontal plane on only one side of stone masonry wall to provide for horizontal leg of angle to fit.2.Set first angle into place as shown on drawing.3.Saw cut in horizontal plane on opposite side of stone masonry wall and set second angle.4.Drill through CMU and roof joist at bolt locations and set bolts. Do not overtighten. Where no CMU is being supported, use nutson inside faces of angles to maintain separation distance.5.Shim and bolt angles to supporting steel beams.6.Remove stone masonry below angles.7.Weld bottom plate to angles as shown.
SPECIAL INSPECTION1.The owner shall employ a special inspector per IBC Chapter 17. The special inspector shall submit a copy of all his reports to theOwner, Architect, Structural Engineer, and the Building Department. When the work is completed, the special inspector shallsubmit a final signed report stating whether the work was, to the best of his knowledge, in conformance with the approved set ofplans and specifications and the applicable workmanship provisions of the building code. The Structural Engineer will make visitsto the site to observe general compliance with the approved structural plans, specifications, and change orders. The contractorshall coordinate with the special inspector in order to ensure that the special inspection as indicated below can be performed withminimal impact to the project schedule.2.Special inspection is required for the following types of work. Refer to Chapter 17 of the 2015 IBC for additional testing andspecific requirements.2.1.All shop and field welding (periodic).2.2.All high-strength bolted connections (periodic).
The special inspectionform provided doesnot have all of therequired signatures. All signatures must bereceived prior topermit issuance.