HomeMy WebLinkAboutFile Documents.120 S Spring St.0326.2017 (14).ARBK 1
HealthSafe Inspections Inc
390 Apple Drive
Basalt CO 81621
970-920-2100
Jim Baker
CDPHE Asbestos Building Inspector, Asbestos Air Monitoring Specialist (AMS) &
Project Designer Certification #13437
CDPHE Lead-Based Paint Inspector & Lead Hazard Assessor Certification #23607
ASBESTOS REPORT
DATE
11/06/2017
CLIENT
Gary Ruth
c/o A & L Construction Company
PO Box 2782
Aspen CO 81612
PROJECT PROPERTY ADDRESS
120 South Spring Street, Aspen, Colorado 81611
01/29/2018
2
COLORADO & FEDERAL ASBESTOS REGULATIONS SUMMARY
Regulation No. 8 Part B – Asbestos of the Colorado Department of Public Health and
Environment (CDPHE), Air Quality Control Commission requires a State-certified
Asbestos Building Inspector to inspect and collect bulk samples of all suspect asbestos
containing materials (ACM) or suspect asbestos containing building materials (ACBM)
prior to their disturbance, removal or demolition and disposal. The suspect materials shall
be analyzed by a NVLAP accredited laboratory by polarized light microscopy (PLM)
using EPA 600 analytical method. A material which is estimated to contain more than 1%
asbestos is classified as ACM/ACBM and regulated by the State and Federal
governments. Any friable (able to crush or reduce to powder by finger pressure) asbestos
with trace amounts of asbestos fibers or less than 1% must be point-counted using EPA
400 analytical method to prove that it is indeed less than 1%; if not, it must be classified
as ACM/ACBM and shall be treated as a State and Federal regulated material. Any
friable asbestos containing material (greater than 1% asbestos concentration) or
ACM/ACBM that could be rendered friable during its removal or demolition and disposal
shall require an asbestos abatement by a certified asbestos abatement contractor to
remove and dispose of the material(s).
A Colorado State (CDPHE) issued asbestos abatement permit is required for the
following trigger levels of ACM/ACBM:
1. Residential buildings of four or fewer units--if more than 32 square feet of any
surface coverage (e.g., gypsum wallboard or drywall and associated applied surfacing
materials/textures, acoustic sprays, joint compounds, plaster, etc.), 50 feet of asbestos
covered or asbestos insulated pipe or any material which would fill a 55-gallon drum is
going to be disturbed, removed or disposed of, an asbestos abatement permit is required.
2. Residential complexes with more than four residential units, public access areas to a
residential building, commercial and retail buildings, public and civic buildings,
industrial buildings--if more than 160 square feet of surfacing materials, 260 linear feet
or more than 35 cubic feet (NESHAP) or 55-gallon drum (CDPHE) of suspect
ACM/ACBM is going to be disturbed, removed or disposed of, an asbestos abatement
permit is required under NESHAP and by the CDPHE. See note below on OSHA.
The regulations require an absolute minimum of 3 samples (EPA suggests 9) per
homogenous suspect surfacing and TSI materials and an absolute minimum of 1 sample
of homogenous miscellaneous materials or any number of “samples sufficient to
determine whether a material is ACM” (Reg8.IV.D.3). More samples are required based
on surface area or volume. These are minimums; the asbestos building inspector has the
field responsibility to determine homogenous materials and the number of samples to
collect per material; more than the minimum number of samples may be necessary at the
discretion of the inspector. An assessment of friability and functional space conditions of
the materials are also the inspector’s field responsibilities.
01/29/2018
3
OSHA compliance is required for all employers and employees no matter the
quantity of asbestos present with strict regulations regarding 10 sf or more of TSI or
friable surfacing materials, and therefore it does not matter what the quantity or
State trigger levels are: all suspect ACM/ACBM shall be inspected and tested for
asbestos prior to their disturbance, removal and disposal for worker protection and
safety. See EPA 40 CFR 763.121 Worker Protection Rule, OSHA 29 CFR 1910.134
Respirator Protection Standard, OSHA 29 CFR 1910.1001 General Industry Standard and
OSHA 29 CFR 1926.1101 Construction Standard regulations when dealing with asbestos
hazards.
Note: County or City regulations may be more stringent.
CLIENT BACKGROUND
A & L Construction Company, the general contractor (GC) hired HealthSafe Inspections,
Inc. (hereinafter, HealthSafe) to perform an asbestos building inspection, bulk sampling
and report for the interior materials of the tri-level house. The slated remodel plan
includes some wall changes, updating some areas and plumbing and electrical changes.
This required an asbestos inspection of all suspect interior building materials. This
asbestos inspection is limited to all interior building materials visible and available
without invasive destruction into interior wall and ceiling or interstitial spaces.
VISUAL INSPECTION & LABORATORY FINDINGS
An inspection was conducted by Jim Baker of HealthSafe on [], 2017 with [] of [] present
during the inspection. Suspect ACM/ACBM (drywall and surfacing materials only)
were identified and sampled. Those materials are the following:
1. A homogeneous taped and joint compounded drywall system (classified as a
miscellaneous material as a complete integral system) [samples 1-3: 120-J-1-2];
these composite layered taped and joint compounded drywall materials are on
ceilings and walls of the house interior of all three floor levels and the garage. The
estimated surface area is more than 5,000 sf, requiring a minimum of at least one
composite core sample from each floor level of all drywall layers (“…number of
samples sufficient to determine” …if asbestos is present or not). The PLM
analytical estimated results: NONE DETECTED.
2. A homogeneous trowel-applied ceiling plaster surfacing material/texture [samples
4-8: 120-ST-CLG-T-1,2,3,4,5]. This surfacing material/texture is on ceilings of
the house interior. The estimated surface area is more than 1,000 sf, but less than
5,000 sf, requiring a minimum of at least five surfacing/texture material samples.
The PLM analytical estimated results: NONE DETECTED.
3. A homogeneous trowel-applied plaster surfacing material/texture [samples 9-13:
120-PLST-T-1,2,3,4,5]. This surfacing material/texture is on walls of the main
entry, stairwell and main third level. The estimated surface area is more than
1,000 sf, but less than 5,000 sf, requiring a minimum of at least five
01/29/2018
4
surfacing/texture material samples. The PLM analytical estimated results: NONE
DETECTED.
4. A homogeneous trowel-applied flat-finish gypsum surfacing material/texture
[samples 14-18: 120-F-T-1,2,3,4,5]. This surfacing material/texture is on ceilings
and walls of the first and second floor bedrooms, bathrooms, closets, laundry
room and garage. The estimated surface area is more than 1,000 sf, but less than
5,000 sf, requiring a minimum of at least five surfacing/texture material samples.
The PLM analytical estimated results: NONE DETECTED.
There were no other additional suspect asbestos building materials to sample which were
slated to be disturbed, removed or disposed of in the interior spaces of the single-family
house with attached garage. A total of 18 suspect homogeneous ACM/ACBM bulk
samples were collected and 18 samples were analyzed. The bulk samples were analyzed
by PLM by a NVLAP accredited laboratory in accordance with Colorado State
Regulation 8 for the presence of asbestos mineral fibers. There is NO asbestos in all 18
samples analyzed.
See supporting Hayes Microbial Consulting, Inc. data report #17033410.
HEALTHSAFE CONCLUSIONS
There is NO asbestos in any of the suspect building materials slated to be impacted by the
remodel/renovation and wall changes. NO asbestos abatement will be required. All
building materials needing to be removed or disturbed can be dealt with without the
concerns for asbestos fibers. All building waste and debris can be disposed of in any
landfill which accepts normal, non-hazardous building waste.
If the contractor happens to open up walls and ceilings and discovers any new or different
suspect building material that is not listed above, please contact HealthSafe to inspect and
sample that material.
Sincerely Submitted,
Jim Baker
01/29/2018
HMC #17033410
contact@hayesmicrobial.com
http://hayesmicrobial.com/
Analysis Report prepared for
HealthSafe Inspections
390 Apple Drive
Basalt, CO. 81621
Phone: 970-920-2100
Job Name: Gary Ruth
120 S. Spring St.
Aspen, CO 81611
Date Sampled: 10-30-2017
Date Analyzed: 11-03-2017
Report Date: 11-06-2017
EPA Laboratory ID# VA01419
NVLAP Lab Code: 500096-0 Asbestos License: 300435 License: #PH-0198
Page 1 of 5
01/29/2018
HMC #17033410
HealthSafe Inspections
390 Apple Drive
Basalt, CO 81621
November 6, 2017
Client Job Number:
Client Job Name:Gary Ruth
120 S. Spring St.
Aspen, CO 81611
Dear HealthSafe Inspections,
We would like to thank you for trusting Hayes Microbial for your analytical needs. On October 31, 2017 we received 18 samples by FedEx for the job
referenced above. 18 samples were received in good condition.
The results in this analysis pertain only to this job, collected on the stated date and should not be used in the interpretation of any other job. This report
may not be duplicated, except in full, without the written consent of Hayes Microbial Consulting, LLC.
This laboratory bears no responsibility for sample collection activities, analytical method limitations, or your use of the test results. Interpretation and
use of test results are your responsibility. Any reference to health effects or interpretation of mold levels is strictly the opinion of Hayes Microbial
Consulting. In no event, shall Hayes Microbial Consulting or any of its employees be liable for lost profits or any special, incidental or consequential
damages arising out of your use of the test results.
Steve Hayes, BSMT(ASCP)
Laboratory Director
Hayes Microbial Consulting, LLC
Page 2 of 5
01/29/2018
HMC #17033410
EPA 600/R-93, M-4/82-020 (PLM)HealthSafe Inspections
390 Apple Drive
Basalt, CO 81621
Phone: 970-920-2100
Job Number:
Collected by:
Email:
Jim Baker
healthsafeinspections@gmail.com
Job Name:Gary Ruth
120 S. Spring St.
Aspen, CO 81611
Date Collected:
Date Received:
Date Reported:
10/30/2017
10/31/2017
11/06/2017
#Sample Name Description Asbestos Fibers Other Fibers Non- Fibers
1 1 120-J-1 Drywall / White
(None Detected)
10 % Cellulose fibers
90 %
Layer 2 120-J-1 Joint Compound / White
(None Detected)
(None Detected)
100 %
2 2 120-J-2 Drywall / White
(None Detected)
10 % Cellulose fibers
90 %
Layer 2 120-J-2 Joint Compound / White
(None Detected)
(None Detected)
100 %
3 3 120-J-3 Drywall / White
(None Detected)
12 % Cellulose fibers
88 %
Layer 2 120-J-3 Joint Compound / White
(None Detected)
(None Detected)
100 %
Layer 3 120-J-3 Brittle / Tan
(None Detected)
(None Detected)
100 %
4 4 120-St-CLG-T-1 Brittle / Light Brown
(None Detected)
2 % Cellulose fibers
98 %
5 5 120-ST-CLG-T-2 Brittle / Light Brown
(None Detected)
(None Detected)
100 %
6 6 120-ST-CLG-T-3 Brittle / Light Brown
(None Detected)
2 % Cellulose fibers
98 %
7 7 120-ST-CLG-T-4 Brittle / Light Brown
(None Detected)
2 % Cellulose fibers
98 %
Signature: Date:11/03/2017 Reviewed by: Date:11/06/2017
Page 3 of 5
01/29/2018
HMC #17033410
EPA 600/R-93, M-4/82-020 (PLM)HealthSafe Inspections
390 Apple Drive
Basalt, CO 81621
Phone: 970-920-2100
Job Number:
Collected by:
Email:
Jim Baker
healthsafeinspections@gmail.com
Job Name:Gary Ruth
120 S. Spring St.
Aspen, CO 81611
Date Collected:
Date Received:
Date Reported:
10/30/2017
10/31/2017
11/06/2017
#Sample Name Description Asbestos Fibers Other Fibers Non- Fibers
8 8 120-ST-CLG-T-5 Brittle / Light Brown
(None Detected)
2 % Cellulose fibers
98 %
9 9 120-PLS-T-1 Brittle / Light Brown
(None Detected)
(None Detected)
100 %
10 10 120-PLS-T-2 Brittle / Light Brown
(None Detected)
(None Detected)
100 %
11 11 120-PLS-T-3 Brittle / Light Brown
(None Detected)
(None Detected)
100 %
12 12 120-PLS-T-4 Brittle / Light Brown
(None Detected)
(None Detected)
100 %
13 13 120-PLS-T-5 Brittle / Light Brown
(None Detected)
(None Detected)
100 %
14 14 120-F-T-1 Brittle / White
(None Detected)
5 % Cellulose fibers
95 %
15 15 120-F-T-2 Brittle / White
(None Detected)
5 % Cellulose fibers
95 %
16 16 120-F-T-3 Brittle / White
(None Detected)
5 % Cellulose fibers
95 %
17 17 120-F-T-4 Brittle / White
(None Detected)
5 % Cellulose fibers
95 %
18 18 120-F-T-5 Brittle / White
(None Detected)
5 % Cellulose fibers
95 %
Signature: Date:11/03/2017 Reviewed by: Date:11/06/2017
Page 4 of 5
01/29/2018
HMC #17033410
Asbestos - Additional InformationHealthSafe Inspections
390 Apple Drive
Basalt, CO 81621
Phone: 970-920-2100
All samples were received in acceptable condition unless otherwise noted on the report. The Report must not be used by the client to claim product certification, approval, or
endorsement by: AIHA, NIST, NVLAP NY ELAP, or any agency. The results relate only to the items tested. The results include an inherent uncertainty of measurement associated with
estimating percentages by polarized light microscopy. Measurement uncertainty data can be provided when requested. None detected: Below the detected reporting limit of 1% unless
point counting is performed, then the detected, reporting limit is .25%. Per NY ELAP198.6 (NOB) TEM is the only reliable method to declare an NOB material as Non-Asbestos
Containing. Hayes Microbial Consulting reserves the right to dispose of all samples after a period of 60 days in compliance with state and federal guidelines.
Signature: Date:11/03/2017 Reviewed by: Date:11/06/2017
Page 5 of 5
01/29/2018
01/29/2018
01/29/2018