City of Aspen Plan Correction List
2009 International Codes and 2014 National Electrical Code Plan Review
Plans received from City of Aspen via electronic file transfer: 3/22/17
Preliminary Review/Report Date: 4/5/17
This report incorporates and supersedes any red line comments on plans.
The plans and all construction must comply with the 2009 IBC, IMC, IPC,
IECC, IFGC and the 2014 NEC whether noted on the plans or not. This
review is of the architectural, mechanical, electrical, plumbing, and energy
conservation construction drawings and documents only. Structural
review is to be done by HCDA Engineering, Inc. Structural Consultants and
is not included in this review.
Hotel Lenado Permit #: TBD
Building Address 200 S. Aspen Street
Aspen, Colorado 81611
Type of Construction V-B
Occupancy Classification Lower Level: S-2 (Parking Garage)
Two R-1 (Hotel Occ.)
Main Level: Seven R-1 (Hotel Occ.)
Two R-2 (Non-transient)
Park Level: Two R-1 (Hotel Occ.)
Two R-2 (Non-transient)
S-2 (Parking Garage)
Upper Level:Two R-2 (Non-transient)
Roof Top Level: R-2 (Residential)
11 (R-1 (Hotel Occ.) & 6 (Non-transient)
Plus associated S-2 storage/parking
Actual Building Area Lower Level: 5,788 SF
Main Level: 5,933 SF
Park Level: 5,515 SF
Upper Level: 3,889 SF
Rooftop Level: 202 SF
Covered Exterior
Space: 1,210 SF
Total: 22,537 SF
Actual Stories 2 Stories with Walkout basement and
sub-basement
Basic Allowable Height & Area
Without Frontage and Sprinkler
Increases: R-1: 7,000 SF 2 Stories
R-2: 7,000 SF 2 Stories
S-2: 13,500 SF 2 Stories
(R-1/R-2 are most restrictive)
City of Aspen
Received
7/10/17
Building Department
2
Fire Sprinklered NFPA 13 and 13R required
throughout
Occupant load Lower Level: 34 Persons
Main Level: 27 Persons
Park Level: 111 Persons
Upper Level: 18 Persons
190 Persons
Use Mixed use affordable housing, hotel,
and parking garage uses.
Description of work and assumptions: New freestanding building
constructed as Type V-B
construction, fully sprinklered with
NFPA 13 and 13R systems
throughout (required). Accessible
parking has been approved as part of
the overall site plan. The structural
plan review will be performed by a
Colorado Licensed PE under
separate cover and is not included in
this review. The civil plans are to be
reviewed by the City of Aspen
Engineering Department or their
designee and are not part of this
review. Fire protection drawings are
to be reviewed by the appropriate
Fire Authority.
Architect Forum Phi
Steven Wilson
(970) 279-4157
________________________________________________________________
The following items were found to be in violation of codes, unclear,
missing from plans or need further explanation. Please make corrections
on plans and prepare a plan review response letter indicating where on
plans the items and corrections are and what type of corrective action was
taken. When all corrections have been made, the plans will be approved
and the plan correction list will be attached to the approved plans and
become part of the approved construction documents.
1. Sheet A-001: The eaves of the building appear to encroach into the
required setbacks. Confirm with City of Aspen that this is acceptable.
The architectural projections are allowed up to 18” past the setback line
per Title 26 Land Use Code Section 26.575.020.E.5.g.
City of Aspen
Received
7/10/17
Building Department
3
2. Sheet A-009: There is a reference on this sheet to IBC 809.1.6. There is
no such code section. Please correct.
This reference has been removed.
3. Sheet A-009: The rooftop deck is shown as an occupancy of 49. The
occupancy is group R and the occupant load is 49. Please correct. In fact,
the term occupancy load is used throughout the plans instead of the correct
term occupant load. Please see IBC 1002 and 1004. See item 8 below.
Occupant Load terminology has been corrected.
4. Sheet A-013: The game room/bar is classified as R-1 on the plans. The
area of the game room/bar exceeds 10% of the story in which it is located
so it therefore does not comply as an accessory occupancy. This area
should be classified as Group A-2 per IBC 303 and 508.2.
This has been revised.
5. Sheet A-013: The occupant load for the game room/bar is shown at 49
occupants. The area of this space is 1,442 square feet. With an occupant
load of 15 for tables and chairs, the correct occupant load for this space is
97 occupants. Please correct.
The occupant load has been revised.
6. Sheet A-013: The door from stair 1 into the Park Entry Corridor must not
reduce the required exit width of the corridor by more than 50% in any
position nor more than 7 inches when fully opened per IBC 1005.2.
This door is conforming and a note has been added to show conformance.
Minimum exit width of this corridor is 36”. When door is open, the width
remaining is 2’- ¾”. The door will not encroach more than 7” when fully
opened.
7. Sheet A-013: The stair barrier code reference in Stair 2 (IBC 1023.8) is
incorrect. This reference should be changed to 1022.7.
This reference has been revised.
8. Sheet A-015: The rooftop deck/pool/hot tub area is classified as R-2. All
occupants of the building appear to have access to this space through
Stairwell 1 including the hotel and residence occupancies. As such, it would
be more appropriate to classify this space as A-3 per IBC 303. Please
address.
City of Aspen
Received
7/10/17
Building Department
4
The rooftop deck is only accessible to the Residence 1 and 2 on the Upper
Level. The door onto the rooftop deck area is locked on the stair side only
per 2009 IBC 1008.1.9.10.
9. Sheet A-015: The rooftop deck/pool/hot tub area is 1,599 square feet.
With an occupant load factor of 15 for tables and chairs the occupant load
should be 107 persons. The occupant load shown on the plans is 49.
Please address. Additionally, an occupant load of 50 or more requires two
exits from the occupied roof per IBC Table 1015.1. Only one exit is
provided from the roof.
This has been approved previously by the building official per IBC 1004.8.
based on the rooftop deck only being accessible to the Residence 1 and 2
with a posted maximum occupant load of 49.
10. Sheet A-401: Both stair sections on this sheet are labeled Stair 1. Please
clarify.
These sheets have been reorganized and re-labeled.
11. Sheet A-406: Guardrails on the roof do not comply with the exception for
guardrails within R-2 dwelling units as the roof level is accessible by all
occupants of the building including the hotel (R-1 occupancy). As such,
these guards must be 42 inches above the adjacent walking surfaces per
IBC 1013.2.
The rooftop deck is only accessible to the Residence 1 and 2 on the Upper
Level and therefore it is an R-2 occupancy. However, at the upper deck
level, the parapet wall is about 7” in height with a 35” railing on top so, it
does comply with 42” height above the finished floor.
12. Sheet A-501: Please specify the thickness of the exterior Type X GWB for
the 1-hour rated exterior stud wall with brick veneer. This is not shown on
this detail.
This information has been added to W-21. The exterior Type X gyp will be
5/8” thick.
13. Sheet A-501: The 2-hour rated elevator shaft w/ horizontal wood siding
detail references IBC Table 721.2.1.1, Minimum Equivalent Thickness of
Cast-In-Place or Precast Concrete walls, Load-Bearing or Nnonload-
Bearing. However, the detail does not reference the concrete type nor the
thickness. This information is necessary in order to establish the fire
resistance rating of the shaft. Please provide this information for all fire-
resistance rated walls using concrete as the fire-resistive membrane.
This information has been added. The concrete type is siliceous and will be
8” minimum thick in all wall applications.
City of Aspen
Received
7/10/17
Building Department
5
14. Sheet A-502: Please specify the thickness and type of concrete for 1-hour
fire-resistance rated typical floor assembly on this sheet.
This information has been added. The concrete type is siliceous and will be
4” minimum thickness in all floor applications. More assemblies have been
added so these assemblies are now on sheet A-503.
15. Sheet A-502: Please be aware that UL detail X 526 is proprietary requiring
the use of one of the specific brands of GWB listed in the detail.
Part 2 of this detail states “Gypsum Board – Any 5/8 in. thick or ½ in. thick
wallboard bearing the UL Fire Resistance Classification Marking.” This
does not appear to require a proprietary brand. Part 2A and 2B do show a
proprietary brand as an alternate however, we do not intend to use one of
those alternates.
16. Sheet A-504: The Fire-Rated Partition @ Ceiling details shown on this
sheet do not reference a generic or calculated assembly within the IBC nor
any tested assemblies. One of these methods must be utilized for all fire-
resistance rated assemblies. Please address.
The intent of this detail is to show that the fire rated wall is to extend to the
bottom of the fire rated floor slab above using fire-resistant joints per
Section 714. This assembly has been moved to sheet A-503.
17. Sheet A-601: Door 003A into Stair 2 is not shown as fire-resistance rated
on the door schedule. This door must be 1 hour rated per IBC Table 715.4.
Please address.
This has been revised.
18. Sheet A-601: Door 013A into Stair 2 on the lower level is not shown as
fire-resistance rated on the door schedule. This door must be 90 minute
rated per IBC Table 715.4. Please address.
This has been revised. This door has also been relabeled as 018C.
19. Sheet A-601: The door to the vehicle lift does not appear to be specified
on the door schedule. This door must be 1 hour fire-resistance rated per
IBC Table 715.4. Please address.
This door has been added and is shown as Door 216 on sheet A-609.
20. Sheet A-601: Door 101A into Stair 2 on the Main Level is shown as a 20-
minute rated door. This door is required to be 1-hour rated per IBC Table
715.4. Please address.
This has been revised.
City of Aspen
Received
7/10/17
Building Department
6
21. Sheet A-602: The door into Stair 1 on the main level is shown as 1-hour
fire-resistance rated. This door is required to be 90 minute rated per IBC
Table 715.4. Please address.
This door has been revised and labeled as 113 A.
22. Sheet A-602: Door 129A is shown as unrated on the door schedule. This
door must be 20-minute rated per IBC Table 715.4. Please address.
This has been revised.
23. Sheet A-601: Door 104A is shown as 45-minute fire-resistance rated but
is only required to be 20-minute rated. Please explain.
This has been revised.
24. Sheet A-603: The door into Stair 1 on the Park Level is only identified as
Door B with no corresponding information on the door schedule. Please
Clarify.
This has been revised and labeled as 207 B.
25. Sheet A-603: Door 218 from the garage to the corridor is not shown on the
door schedule. Please add.
This is labeled as 217A.
26. Sheet A-604: This sheet is missing entirely from the plan set. As such,
The fire-resistance rating of door 309A into the 2-hour stair enclosure
cannot be verified. This door is required to be 90-minute rated per IBC
Table 715.4. Please provide Sheet A-604 showing the correct fire rating of
the doors detailed on this sheet.
This has been revised.
27. Sheet F-1-F-5: The fire protection drawings are required to be reviewed by
the appropriate Fire Authority and are not part of this review. Additionally,
the Fire Protection Drawings are not stamped as required by State Statute.
The fire sprinkler permit will be a deferred submittal reviewed by AFPD.
28. Sheet P-002: Provide certification for RP backflow preventer to the Building
Department upon installation.
This will be provided after installation (or during installation as all
certification will arrive with the purchased valves).
29. Plumbing General Note: Please provide plumbing DWV and gas isometric
drawings for review.
City of Aspen
Received
7/10/17
Building Department
7
This has been provided.
30. Sheet M-001: Provide a copy of the balance report for the HVAC system
referenced on this sheet to the Building Department upon completion of the
HVAC system.
This is after the HVAC is installed and start up provided.
31. Sheet M-004: The ventilation table on this sheet shows the minimum
required ventilation of the enclosed parking garage of 0.05 CFM / square
foot. This ventilation rate should be 0.75 per IMC 404.2 and Table 403.3.
The parking garage is shown to be 2,800 square feet which would require a
ventilation rate of 2,100 CFM. The plans show a ventilation rate of only 155
CFM. Please address.
The table on M-004 shows standard ventilation only and the means for
providing it. We do not list emergency ventilation as it doesn’t run
continuously to provide minimum fresh air supply (or natural air) to zones
which require it. An emergency ventilation is not considered “fresh air
supply”.
We are providing emergency ventilation in the enclosed garage via exhaust
fan EF-1 (see M-100 for its location) and MAU via SF-5 (see M-100 for its
location). Both fans are interlocked with CO and NO2 sensors and unlike
fresh air supply /ventilation listed in the table M-001 are operating only
upon a call from those sensors (see sequence of operation on M-004). Thus
we are providing both code required means of ventilation – continuous and
emergency.
32. Sheet M-100: Spaces connecting to enclosed parking garages must be
maintained at a positive pressure per IMC 404.3. Please address how this
code provision is met.
Please refer to floor plans and equipment providing pressurization of those
areas. All those areas are pressurized either via ERV units or SF supply
fans. For example, Stair #2 is pressurized via SF-1, Lobby #1 via ERV-1, etc.
Please review M-100 plans. Also table “outdoor air ventilation” on M-004
lists how much air is supplied to those areas. Since there is no exhaust
from those areas then they are pressurized to meet the code.
33. Sheet E-001: The plumbing plans show the water service as ductile iron.
As such, it must be part of the grounding electrode system as required by
NEC 250.50. This is not shown on the grounding diagram on this sheet.
Please correct.
We are currently showing a 3/0 CU grounding electrode conductor
connected to the incoming water service in the ‘Service Grounding Detail’
on sheet E-001.
City of Aspen
Received
7/10/17
Building Department
8
34. Sheet E-002: Main disconnects must be grouped together per NEC
230.72(A). Please add note to plans.
Updated plans to include note.
35. Sheet E-102: Dishwashers within dwelling units must be GFCI-protected
per NEC 210.8(D) (Typical). They are not shown as such on the plans.
Please address.
Updated plans to include note.
36. Sheet E-103: 120-volt receptacles in laundry areas are required to be
GFCI-protected per NEC 210.8(A)(10) (Typical). This does not appear to be
addressed on the plans. Please address.
Currently all 120V outlets shown in laundry area (Laundry 010 &
Housekeeping 220) are GFI rated.
37. General Electrical Note: Please provide electrical fault current
calculations. This does not appear to be addressed on the plans.
Fault currents calculations are shown as the AIC rating the one-line
diagram on sheet E-002.
38. General Electrical Note: AFCI protection within the dwelling units does
not appear to be addressed at all on the plans. AFCI protection is required
within dwelling units per NEC 210.12. Please address.
There is a note included on the dwelling unit power panel schedules, seen
on sheet E-004 Update to include in specs on sheet E-001.
39. Sheet Lights 000 – Light 106: These sheets are not stamped by a
Colorado Licensed Professional Engineer as required by State Law. The
lighting system and layout is part of the electrical design and, as such, must
be performed by a Colorado Licensed PE. Please address.
The lighting plans have been prepared by a designer, with specs provided
and a matching comcheck as requested by the local building official.
40. Sheets E-1-01 & E-2-01: This review does not include a review of the
photovoltaic system as complete plans have not been submitted. The PV
system will be reviewed under separate permit.
We will provide under separate permit.
Preliminary Plan Review:
Dan Swallow, Master Code Professional, CBO, ICC Certified Combination
Plans Examiner, Colorado Master Electrician License #600450
City of Aspen
Received
7/10/17
Building Department
9
Final Report Review and Local Contact