Color:
I believe the site plan was
supposed to be revised so that
guards were not required around
the window wells set into walking
surfaces as is shown here.
Please revise, building will have
to require guards around any
light wells or emergency escape
egress wells that are surrounded
by a walking surface. If the patio
layout is changed please be sure
to also update the REMP plan,
etc. as applicable.
Architectural Plans. 533 W HALLAM.pdf (22)
Subject: PlanCheck
Page Label: A101
Author: justinh
File Name: Architectural Plans. 533 W HALLAM.pdf
Color:
Identify patio materials, there is
a detail for permeable pavers
and the site plan should clearly
show where this is proposed.
Subject: PlanCheck
Page Label: A203
Author: justinh
File Name: Architectural Plans. 533 W HALLAM.pdf
Color:
Show all electrical panel
locations on your architectural
floor plans.
Subject: PlanCheck
Page Label: A205
Author: justinh
File Name: Architectural Plans. 533 W HALLAM.pdf
Color:
Show your radon mitigation
system termination pipe on the
roof plan along with any other
venting that is not currently
shown.
Subject: PlanCheck
Page Label: A205
Author: justinh
File Name: Architectural Plans. 533 W HALLAM.pdf
Color:
Show compliant secondary roof
drainage per IRC 903.4.1, either
scuppers or secondary drains. If
secondary drains are used they
must discharge to a different
location than the primary drains
where they will be observed by
the building occupant per IPC
1108.2.
7914
7913
7915
14
14
14
13
14 13
15
10' SETBACK
PROPERTY LINE N14°50'49"E 100.00'
10' SE
T
B
A
C
K
5TH STREET
HALLAM
S
T
R
E
E
T
GRAVEL
A
L
L
E
Y
60' - 0
"
60' - 0
"
100' - 0"
100' - 0"
AA
1
1
LIGHT WELL LIGHT WELL LIGHT WELL LIGHT WELL BELOWBELOWBELOWBELOW LIGHT WELL LIGHT WELL LIGHT WELL LIGHT WELL BELOWBELOWBELOWBELOW
LIGHT WELL LIGHT WELL LIGHT WELL LIGHT WELL BELOWBELOWBELOWBELOWLIGHT WELL LIGHT WELL LIGHT WELL LIGHT WELL BELOWBELOWBELOWBELOW
8' - 6" + V.I.F.
V.I.F.
SETBACK10' - 0"
V.I.F.
SETBACK5' - 0"
PROPOSED 36" FENCE
5' SETBACK
6' PRIVACY FENCE
3' WIDE GATE
SETBACK10' - 0"
PROPE
R
T
Y
L
I
N
E
S
7
5
°
0
9
'
1
1
"
E
6
0
.
0
0
'
12' - 2 1/4"
11' - 11 1/2"
PROPERTY LINE
PROPERT
Y
L
I
N
E
DRIP LINE OF COTTONWOOD ESTABLISHED BY PARKS DEPT.VIA PHONE ON 9.12.2018
LINE OF NO FOUNDATION / DIGGING ESTABLISHED BY PARKS IN PERSON MEETING ON 06.19.2018
COTTONWOOD TREE LOCATED ON THE SURVEY
1' - 6"
1. BUILDING ELEVATION 100' - 0" = USGS ELEVATION 7915.7'2. REFER TO CIVIL DRAWINGS FOR FINAL GRADING.3. REFER TO CIVIL AND LANDSCAPE PLANS FOR ALL SITE RELATED WORK AND VEGETATION.
ARCHITECTURAL SITE PLAN NOTESARCHITECTURAL SITE PLAN NOTESARCHITECTURAL SITE PLAN NOTESARCHITECTURAL SITE PLAN NOTES
NOR
Consultant
ARCHITECTUREARCHITECTUREARCHITECTUREARCHITECTURE
(((( TTTT )))) 9999 7777 0000 //// 9999 2222 5555 4444 7777 5555 5555 6666 0000 5555 EEEE AAAA SSSS TTTT MMMM AAAA IIII NNNN SSSS TTTT RRRR EEEE EEEE TTTT AAAA
SHEET TITLE
BILL POSS AND ASSO ARCHITECTURE AND THE INFORMATION AND DESIGN INTENT CON PROPERTY OF BILL POSS AND ASSOCIATES, OF THIS INFORMATION MAY BE USED WITHO POSS AND ASSOCIATES, ARCHITECTURE AN ARCHITECTURE AND PLANNING, P.C. SHALL OTHER RESERVED RIGHTS, INCLUDINGCOP
c2018
PROJECT NO:
Issue:
11/28/20
1
8
9
:
4
9
:
4
3
A
M
DDDDUUUUNNNNCCCCAAAANNNN RRRREEEESSSSIIIIDDDD
533 W HALLAM ST AS
A101A101A101A101
AAAARRRRCCCCHHHHIIIITTTTEEEECCCCTTTTUUUURRRRAAAA
21708.00
SCALE 1/4" = 1'-0"1ARCHITECTURAL SITE PLAN
1 11.27.2018
I believe the site plan wassupposed to be revised so thatguards were not required aroundthe window wells set into walkingsurfaces as is shown here. Please revise, building will have torequire guards around any lightwells or emergency escapeegress wells that are surroundedby a walking surface. If the patiolayout is changed please be sureto also update the REMP plan,etc. as applicable.
14
10' SETBACK
N14°50'49"E 100.00'
100' - 0"
LIGHT WELL LIGHT WELL LIGHT WELL LIGHT WELL BELOWBELOWBELOWBELOW
V.I.F
.
SETBACK
10' - 0"
PROPOSED 36" FENCE
LINE OF NO FOUNDATION / DIGGING ESTABLISHED BY PARKS IN PERSON MEETING ON 06.19.2018
Identify patio materials,there is a detail forpermeable pavers andthe site plan shouldclearly show wherethis is proposed.
A
PR
O
P
E
R
T
Y
L
I
N
B
4'
-
6
"
6"
12
'
-
2
3
/
8
"
Show all electrical panel locations on
your architectural floor plans.
NE OF OW
Show your radon mitigation
system termination pipe on the
roof plan along with any other
venting that is not currently shown.
Show compliant secondary roof drainage per
IRC 903.4.1, either scuppers or secondary
drains. If secondary drains are used they
must discharge to a different location than the
primary drains where they will be observed by
the building occupant per IPC 1108.2.
REMP Calculations have been Updated.
MECHANICAL RESPONSE
2019-08-07
Shown on arch plans.
10/16/2019
Subject: PlanCheck
Page Label: A404
Author: justinh
File Name: Architectural Plans. 533 W HALLAM.pdf
Color:
Please dimension the height and
opening size on your guard to
show compliance with IRC 312
Subject: PlanCheck
Page Label: A404
Author: justinh
File Name: Architectural Plans. 533 W HALLAM.pdf
Color:
Please show utility meters on
your elevations.
Subject: PlanCheck
Page Label: A702
Author: justinh
File Name: Architectural Plans. 533 W HALLAM.pdf
Color:
Show a compliant handrail and
guard on the lower level stairs.
Subject: PlanCheck
Page Label: A702
Author: justinh
File Name: Architectural Plans. 533 W HALLAM.pdf
Color:
Please add dimensions to show
that both the guard and open
risers meet the opening
limitation requirements of IRC
312.1.3.
Subject: PlanCheck
Page Label: A804
Author: justinh
File Name: Architectural Plans. 533 W HALLAM.pdf
Color:
Please verify that HPC will allow
you to spray foam the existing
wall cavities of the historic
building. How are you proposing
to waterproof behind the existing
historic siding as this detail
shows?
04
03
GUARDRAIL
PER CODE
LIGHTWELL
Please dimension the
height and opening
size on your guard to
show compliance withIRC 312
04
DRYER VENT
UARDRAIL PER CODE
LIGHTWELL Please show utility
meters on yourelevations.
T.O. F.F. @ MAIN100' - 0"
T.O. F.F. @ UPPER110' - 4 1/2"
T.O. PLY @ MAIN99' - 9"
T.O. PLY @ UPPER110' - 1 1/2"
6' - 8"MIN. HEAD
HEIGHT
MIN. HEAD HEIGHT
10 3/4"
7"
T.O. PLY @ BASEMENT86' - 4"
T.O. F.F. @ BASEMENT86' - 7"
T.O. CONC. @ CRAWL SPACE79' - 6 3/8"
6' - 8"
6' - 8"
3' - 0"
001
FAMILY /FAMILY /FAMILY /FAMILY /GAMEGAMEGAMEGAME
M01
MECHANICALMECHANICALMECHANICALMECHANICALCRAWLSPACECRAWLSPACECRAWLSPACECRAWLSPACE
106LIVINGLIVINGLIVINGLIVING
STAIRSTAIRSTAIRSTAIR
MECHANICAL ACCESS HATCH
6' - 8"
MIN. HEAD HEIGHT
MIN. HEAD HEIGHT
11 3/4"
7"
6' - 8"
M01
MECHANICALMECHANICALMECHANICALMECHANICALCRAWLSPACECRAWLSPACECRAWLSPACECRAWLSPACE
STAIRSSTAIRSSTAIRSSTAIRS
STAIRSSTAIRSSTAIRSSTAIRS
004STO.STO.STO.STO.001
FAMILY /FAMILY /FAMILY /FAMILY /GAMEGAMEGAMEGAME
ANICAL S HATCH
SCALE 1/4" = 1'-0"1 STAIR SECTION - NORTHSOUTH
Show a complianthandrail and guard onthe lower level stairs.
T.O. F.F. @ MAIN100' - 0"
T.O. F.F. @ UPPER110' - 4 1/2"
T.O. PLY @ MAIN99' - 9"
T.O. PLY @ UPPER110' - 1 1/2"
6' - 8"MIN. HEAD
HEIGHT
MIN. HEAD
HEIGHT
10 3/4"
7"
006A004A
ELEVB
ELEVC
T.O. PLY @ BASEMENT86' - 4"
T.O. F.F. @ BASEMENT86' - 7"
6' - 8"
6' - 8"
3' - 0"
004STO.STO.STO.STO.
005LAUNDRYLAUNDRYLAUNDRYLAUNDRY
001
FAMILY /FAMILY /FAMILY /FAMILY /GAMEGAMEGAMEGAME
106LIVINGLIVINGLIVINGLIVING
STAIRSTAIRSTAIRSTAIR
STAIRSSTAIRSSTAIRSSTAIRS
MECHANICAL ACCESS HATCH
Please adddimensions to showthat both the guardand open risers meetthe opening limitationrequirements of IRC312.1.3.
INTERIORINTERIORINTERIORINTERIOR PER P
PANEL MODULE
1/2"
PANEL MODULE
PER P 5/8"3/4"1/4"3/4"1 1/2"EXTERIOREXTERIOREXTERIOREXTERIORPER PLAN5/8"
INTERIOR FINISHREF. FINISH SHCHED.
WATERPROOFING
SPRAYED FOAM INSULATION(R-20 MIN.)
EXISTING WOOD FRAMINGREF. STRUCT. DWGS.
5/8" GYPSUM WALL BOARD
EXISTING WOOD SIDING
INTERIORINTERIORINTERIORINTERIOR
EXTERIOREXTERIOREXTERIOREXTERIOR
4"3/4"1/2"5/8"
3/4" PLYWOOD SHEATHING
SCALE 3 W-8 METAL
SCALE 3 W-9 WOOD C
SCALE 3" = 1'-0"W-11 EXISTING HISTORIC WOOD SIDING
SCALE 3" = 1'-0"W-12 NEW HISTORIC WOOD SIDING
Please verify that HPC willallow you to spray foamthe existing wall cavitiesof the historic building. How are you proposing towaterproof behind theexisting historic siding asthis detail shows?
10/16/2019
Subject: PlanCheck
Page Label: A804
Author: justinh
File Name: Architectural Plans. 533 W HALLAM.pdf
Color:
All basement/foundation wall
details should be showing
waterproofing, please revise.
Subject: PlanCheck
Page Label: A805
Author: justinh
File Name: Architectural Plans. 533 W HALLAM.pdf
Color:
This wall assembly is not
required to be fire rated, we
measure fire separation distance
to the center of the alley on the
south side of the building.
Please revise.
Subject: PlanCheck
Page Label: A806
Author: justinh
File Name: Architectural Plans. 533 W HALLAM.pdf
Color:
I believe you may have a
layering issue here, the detail is
not actually shown. Please
revise.
Subject: PlanCheck
Page Label: A808
Author: justinh
File Name: Architectural Plans. 533 W HALLAM.pdf
Color:
Provide documentation of class
A assembly for these assemblies
similar to what you provided for
both the flat membrane roof and
sloped shingle roof.
Subject: PlanCheck
Page Label: A808
Author: justinh
File Name: Architectural Plans. 533 W HALLAM.pdf
Color:
Provide a detail showing your
proposed hole pattern in the rigid
insulation that will achieve a R10
weighted average while still
meeting engineering's 30% open
requirement to be permeable
(this detail only shows 20%, but
I believe engineering requires
30%). Attached is our pervious
snowmelt calculator that can
help to find the pattern that best
suits your situation.
EXTERIOR
R-15/19
HYDRODUCT COIL 600
5/8" TYPE X GWB
2X FURRING
RUCTURAL 1/2"3"
1/2" FURRING GAP
UNDATION WALL WEST
All basement/foundation wall details should be
showing waterproofing, please revise.
. PAINTED WOOD G
IOR FINISHINISH SHCHED.
HER RESISTIVE ER
AGE MAT
YED FOAM INSULATIONMIN.)
FRAMINGSTRUCT. DWGS.
YPSUM WALL BOARD
ATED SHEATHING L (R-5 MIN.)
R WALL SHEATHINGSTRUCT. DWGS.
INTERIOR FINISHREF. FINISH SHCHED.
WEATHER RESISTIVE BARRIER
DRAINAGE MAT
SPRAYED FOAM INSULATION(R-20 MIN.)
WOOD FRAMINGREF. STRUCT. DWGS.
5/8" GWB TYPE X
INSULATED SHEATHING PANEL (R-5 MIN.)
HORIZ. CHANNEL LAP WOOD SIDING
3/4"1/4"2 1/8"
INTERIORINTERIORINTERIORINTERIOR
EXTERIOREXTERIOREXTERIOREXTERIOR
PER PLAN5/8"
8 5/8"
3/4"
1/2"
9 7/8"
1"
SHEET TITLE
BILL POSS AND ASSOCIATES,ARCHITECTURE AND PLANNING, P.C.THE INFORMATION AND DESIGN INTENT CONTAINED ON THIS DOCUMENT IS THE PROPERTY OF BILL POSS AND ASSOCIATES, ARCHITECTURE AND PLANNING, P.C.NO PART OF THIS INFORMATION MAY BE USED WITHOUT THE PRIOR WRITTEN PERMISSION OF BILL POSS AND ASSOCIATES, ARCHITECTURE AND PLANNING, P.C. BILL POSS AND ASSOCIATES, ARCHITECTURE AND PLANNING, P.C. SHALL RETAIN ALL COMMON LAW STATUTORY AND OTHER RESERVED RIGHTS, INCLUDINGCOPYRIGHT THERETO.
c2018
PROJECT NO:
SCALE: 3" = 1'-0"
533 W HALLAM ST ASPEN, CO 81611
A805A805A805A805
ASSEMBLIES ASSEMBLIES ASSEMBLIES ASSEMBLIES ---- EEEEXXXXTTTTEEEERRRRIIIIOOOORRRRWALLWALLWALLWALL
21708.00
WALL SCALE 3" = 1'-0"W-13 WOOD CHANNEL LAP SIDING - 1HR RATED
This wall assembly isnot required to be firerated, we measure fireseparation distance tothe center of the alleyon the south side ofthe building. Pleaserevise.
ON THINSET MORTAR
CEMENTITIOUS KERBOARD W/ FLUID LIED WATERPROOFING
ND-ATTENUATIONT INSULATION
GWB
FRAMING, STRUCT.
6 WD. FRAMING
SHEET TITLE
BILL POSS AND ASSOCIATES,ARCHITECTURE AND PLANNING, P.C.
THE INFORMATION AND DESIGN INTENT CONTAINED ON THIS DOCUMENT IS THE PROPERTY OF BILL POSS AND ASSOCIATES, ARCHITECTURE AND PLANNING, P.C.NO PART OF THIS INFORMATION MAY BE USED WITHOUT THE PRIOR WRITTEN PERMISSION OF BILL POSS AND ASSOCIATES, ARCHITECTURE AND PLANNING, P.C. BILL POSS AND ASSOCIATES ARCHITECTURE AND PLANNING, P.C. SHALL RETAIN ALL COMMON LAW STATUTORY AND OTHER RESERVED RIGHTS, INCLUDINGCOPYRIGHT THERETO.
c2018
PROJECT NO:
SCALE: 3" = 1'-0"
533 W HALLAM ST ASPEN, CO 81611
A806A806A806A806
ASSEMBLIES ASSEMBLIES ASSEMBLIES ASSEMBLIES ---- IIIINNNNTTTTEEEERRRRIIIIOOOORRRR
WALLWALLWALLWALL
21708.00
EXISTING
INTERIOR
WALL
SCALE 3" = 1'-0"WI-2 INTERIOR WALL @ GWB/GWB
SCALE 3" = 1'-0"WI-1 INTERIOR WALL @ EXISTING WALL
I believe you mayhave a layering issuehere, the detail is notactually shown. Please revise.
PER STRUCT.
5/8" SHEATHING, REF. STRUCTURAL
SPRAY FOAM INSULATIONR-49 MIN.
TJI RAFTER, REF. STRUCTURAL
5/8" GYPSUM WALL BOARD, REF. INTERIOR FINISH SCHED.
R-49 MIN.
SELF ADHERED WATERPROOF MEMBRANE
MINERAL SURFACED CAP SHEET, CLASS A
EXPOSURE
5"
CEDAR BREATHER, CLASS A
CLASS A ROOF ASSEMBLY
20% PERMEABLE RATIO CAN BE ACHIEVED AT 4"
3" THICK PAVERS
COMPACTED SANDRADIANT TUBING
FILTER FABRIC -HYDRODRAIN AL 3" RIGID INSULATIONR-15 MIN.DRAINAGE MAT -HYDRODRAIN 990
CONCRETE, REF. STRUCTURALSPRAY FOAM INSULATION R-35 MIN.STEEL, REF. STRUCTURAL
5/8" GYPSUM CEILING,REF. INTERIOR FINISH SCHED.
WATERPROOF MEMBRANE - MM6125 EV
3"
2"1/4"
3"
1/2"
4"
PER ST
R
U
C
T
.
R-49 MIN.
COMPACTED SANDFILTER FABRIC -HYDRODRAIN AL 3" RIGID INSULATIONR-15 MIN.DRAINAGE MAT -HYDRODRAIN 990
CONCRETE, REF. STRUCTURALSPRAY FOAM INSULATIONR-35 MIN.STEEL, REF. STRUCTURAL5/8" GYPSUM CEILING,REF. INTERIOR FINISH SCHED.
WATERPROOF MEMBRANE - MM6125 EV
VARIES
2"1/4"
3"
1/2"
PER ST
R
U
C
T
.
SOD
R-49 MIN.
SHEET TITLE
BILL POSS AND ASSOCIATES,ARCHITECTURE AND PLANNING, P.C.THE INFORMATION AND DESIGN INTENT CONTAINED ON THIS DOCUME PROPERTY OF BILL POSS AND ASSOCIATES, ARCHITECTURE AND PLAN OF THIS INFORMATION MAY BE USED WITHOUT THE PRIOR WRITTEN PE POSS AND ASSOCIATES, ARCHITECTURE AND PLANNING, P.C. BILL POS ARCHITECTURE AND PLANNING, P.C. SHALL RETAIN ALL COMMON LAW OTHER RESERVED RIGHTS, INCLUDINGCOPYRIGHT THERETO.
c2018
PROJECT NO:
SCALE: 1 1/2" = 1'-0"
DDDDUUUUNNNNCCCCAAAANNNN RRRREEEESSSSIIIIDDDDEEEENNNNCCCCEEEE
533 W HALLAM ST ASPEN, CO 8161
A808A808A808A808
ASSEMBLIES ASSEMBLIES ASSEMBLIES ASSEMBLIES ---- RRRROOOOOOOOFFFF
21708.00
SCALE 1 1/2" = 1'-0"R-2 CEDAR SHINGLE ROOF 12:12
SCALE 1 1/2" = 1'-0"R-1 PERMEABLE PAVERS @ PATIO GREEN ROOFSCALE 1 1/2" = 1'-0"R-4 SOD @ GREEN ROOF
Provide documentation of class Aassembly for these assemblies similar towhat you provided for both the flatmembrane roof and sloped shingle roof.
PER STR
5/8" SHEATHING, REF. STRUCTURAL
SPRAY FOAM INSULATIONR-49 MIN.
TJI RAFTER, REF. STRUCTURAL
5/8" GYPSUM WALL BOARD, REF. INTERIOR FINISH SCHED.
R-49 MIN.
SELF ADHERED WATERPROOF MEMBRANE
MINERAL SURFACED CAP SHEET, CLASS A
CLASS A ROOF ASSEMBLY
20% PERMEABLE RATIO CAN BE ACHIEVED AT 4"
3" THICK PAVERS
COMPACTED SANDRADIANT TUBING
FILTER FABRIC -HYDRODRAIN AL
3" RIGID INSULATIONR-15 MIN.DRAINAGE MAT -HYDRODRAIN 990
CONCRETE, REF. STRUCTURAL
SPRAY FOAM INSULATION R-35 MIN.STEEL, REF. STRUCTURAL
5/8" GYPSUM CEILING,REF. INTERIOR FINISH SCHED.
WATERPROOF MEMBRANE - MM6125 EV
3"
2"1/4"
3"
1/2"
4"
PER
S
T
R
U
C
T
.
R-49 MIN.
COMPACTED SANDFILTER FABRIC -HYDRODRAIN AL
3" RIGID INSULATIONR-15 MIN.DRAINAGE MAT -HYDRODRAIN 990
CONCRETE, REF. STRUCTURAL
SPRAY FOAM INSULATIONR-35 MIN.STEEL, REF. STRUCTURAL5/8" GYPSUM CEILING,REF. INTERIOR FINISH SCHED.
WATERPROOF MEMBRANE - MM6125 EV
VARIE
S
2"1/4"
3"
1/2"
PER
S
T
R
U
C
T
.
SOD
R-49 MIN.
SHEET TITLE
BILL POSS AND ASSOCIATES,ARCHITECTURE AND PLANNING, P.C.THE INFORMATION AND DESIGN INTENT CONTAINED ON THIS DOCUMENT IS THE PROPERTY OF BILL POSS AND ASSOCIATES, ARCHITECTURE AND PLANNING, P.C.NO PAR OF THIS INFORMATION MAY BE USED WITHOUT THE PRIOR WRITTEN PERMISSION OF BIL POSS AND ASSOCIATES, ARCHITECTURE AND PLANNING, P.C. BILL POSS AND ASSOCIATE ARCHITECTURE AND PLANNING, P.C. SHALL RETAIN ALL COMMON LAW STATUTORY AND OTHER RESERVED RIGHTS, INCLUDINGCOPYRIGHT THERETO.
c2018
PROJECT NO:
SCALE: 1 1/2" = 1'-0"
DDDDUUUUNNNNCCCCAAAANNNN RRRREEEESSSSIIIIDDDDEEEENNNNCCCCEEEE
533 W HALLAM ST ASPEN, CO 81611
A808A808A808A808
ASSEMBLIES ASSEMBLIES ASSEMBLIES ASSEMBLIES ---- RRRROOOOOOOOFFFF
21708.00
SCALE 1 1/2" = 1'-0"R-2 CEDAR SHINGLE ROOF 12:12
SCALE 1 1/2" = 1'-0"R-1 PERMEABLE PAVERS @ PATIO GREEN ROOFSCALE 1 1/2" = 1'-0"R-4 SOD @ GREEN ROOF
Provide a detail showing your proposedhole pattern in the rigid insulation thatwill achieve a R10 weighted averagewhile still meeting engineering's 30%open requirement to be permeable (thisdetail only shows 20%, but I believeengineering requires 30%). Attached isour pervious snowmelt calculator thatcan help to find the pattern that bestsuits your situation.
10/16/2019
Subject: PlanCheck
Page Label: A812
Author: justinh
File Name: Architectural Plans. 533 W HALLAM.pdf
Color:
Revise all drawings
(architecturals, structurals, civils)
so grade is 6” or more below the
top of each foundation wall per
2015 IRC R404.1.6 (clearly
dimensioned in the architectural
details). Alternatively, the City
will accept a lesser distance if all
of the following are provided.
Note this requirement at all
applicable wall sections and
details:
1.All wood materials within 6” of
grade to be protected from
decay per R317.1 5.
2.Waterproof membrane
extending up wall a minimum of
6” above grade.
3.Capillary break separating
concrete from wood materials.
If you go that route you will also
need to have the structural plan
revised to show treated lumber
as a specified material and have
them list the proper fasteners for
treated wood as the chemicals
used to treat lumber can
degrade typical fasteners.
Subject: PlanCheck
Page Label: A815
Author: justinh
File Name: Architectural Plans. 533 W HALLAM.pdf
Color:
Indicate how you will accomplish
the air sealing requirements of
2015 IECC table R402.4.1.1
using notes and details. Indicate
the continuity of the air barrier
and where it is located
throughout the building. Note
locations that require caulking,
sealing, taping, etc. Note which
components are included in the
air barrier such as spray foam,
gypsum, housewrap, and/or
exterior insulation. You may
have all of the above but you
need to pick one continuous
barrier and stick to it. It needs to
follow the thermal barrier. The
better detail you provide, the
easier it will be for the contractor
and inspector to be successful.
This is a new 2015 code
requirement in lieu of a blower
door test. I've attached our
standard air sealing detail sheets
to this comment letter as an
example of the type of detailing
we're looking for.
W-1
T.O. CONC. @ CRAWL SPACE79' - 6 3/8"
F-1
WATERPROOFINGHYDRODUCT COIL 600
WRAP HYDRODUCT 220 PERMANUFACTURER'S RECOMMENDATIONS.
PER STRUCT.
PER STRUCT.
T.O. CONC. @ BASEMENT83' - 2"
F-1
W-2SIM
MECHANICAL VOID SPACE
PER STRUCT.
EXPANSION JOINTHYDRODUCT 220
HYDRODUCT COIL 600
PER STRUCT.
REFERENCE SOIL RETENSION PLANS FOR SYSTEM TO USE
A
T.O. PLY @ MAIN99' - 9"
B
T.O.F.F. @ PATIO & GARAGE99' - 11"
R-1 R-4
WOOD CLAD STEEL COLUMN.PAINT TO MATCH SIDING.KEEP WOOD 1" UP FROM FIN. GRADE
1"
COLUMN BASE PER STRUCTURALWATERPROOFING PER WJECONCRETE DECKING PER STRUCTURAL
MICROPILE WALL DEMO CAP AS NECESSARY. VERIFY LOCATIONS WITH ENGINEER.STEEL PER STRUCTURAL
PER STRUCTURAL
T.O. F.F. @ MAIN100' - 0"
A
T.O. PLY @ MAIN99' - 9"
B
W-2
EXISTING HISTORIC STUDS AND SIDING VIF LOCATION AND CONNECTION TO NEW STRUCTURAL FOOTING WITH ARCHITECT AND STRUCTURAL ENGINEER DURING DEMO PHASE.
W-11 1/2" DENSGLASS BACKER OVER WATERPROOFING.CONCRETE SCRACTH COAT TO MATCH EXISTING CONDITION. VIF COLOR WITH ARCHITECT.
PROPOSED GRADE TO MATCH RELATIONSHIP OF EXISTING GRADE TO HISTORIC HOUSE. REF CIVIL AND GRADING PLAN
RIGID INSULATION3"
DRAINAGE MAT
CONTINUE SPRAY INSULATION UP TO THE BOTTOM OF SHEATHING (TYP)
T.O. F.F. @ MAIN100' - 0"
LK
T.O. PLY @ MAIN99' - 9"
METAL FLASHING CONTINUOUSUNDER WINDOW 1/2" DENSGLASS OVER ZIP PANELFOR PROTECTION.WATERPROOFING PER WJECONCRETE TOPPING SLOPED 1/4" PER FOOT
CONTINUE SPRAY FOAM INSULUP TO UNDERSIDE OF SHEATHING(TYP)CONCRETE PER STRUCTURAL
W-3PER STRUCT.
PER STRUCT.
10
T.O. PLY @ MAIN99' - 9"T.O.F.F. @ PATIO & GARAGE99' - 11"
F-2
EXPANSION JOINT
CONC FILL AS NECESSARY VIF WITH STRUCTURALALLEY GRAVEL
CONCRETE DRIVE UP FROM PROPERTY LINE TO GARAGE ENTRY.
GARAGE DOOR
MICROPILE WALL
PER STRUCT.
STEEL PER STRUCTURALSTEEL DECKING AND GARAGE CONC PERSTRUCTURAL
LK
T.O. PLY @ MAIN99' - 9"T.O.F.F. @ PATIO & GARAGE99' - 11"
F-2
W-1
W-7 METAL FLASHING CONTINUOUSUNDER DRAINAGE MAT AND OVER FOUNDATION INSULATIONMETAL FLASHING WITH DRIP EDGE COLOR TO MATCHSIDING
CONTINUOUS METALFOUNDATION FLASHING. POWEDER COAT TO MATCHMETAL PANNEL SYSTEM.
SELF ADHERED FLASHINGTO OVERLAP ALL METAL FLASHING
PER STRUCT.
PER STRUCT.
STEEL PER STRUCTURAL
T.O. F.F. @ MAIN100' - 0"
C
T.O. PLY @ MAIN99' - 9"
T.O.F.F. @ PATIO & GARAGE99' - 11"
R-1
SELF ADHERED FLASHINGTO OVERLAP ALL METAL FLASHINGMETAL FLASHING CONTINUOUSUNDER DRAINAGE MAT AND OVER FOUNDATION INSULATIONMETAL FLASHING WITH DRIP EDGE COLOR TO MATCH SIDING.
W-7
WATERPROOFING PER WJE3" RIGID INSULATION1/2" DENSGLASSCONC PER STRUCTURALSTEEL PER STRUCTURAL
T.O. F.F. @ MAIN100' - 0"T.O. PLY @ MAIN99' - 9"
W-7SIM
W-1
SELF ADHERED FLASHINGTO OVERLAP ALL METAL FLASHINGMETAL FLASHING CONTINUOUSUNDER DRAINAGE MAT AND OVER FOUNDATION INSULATIONMETAL FLASHING WITH DRIP EDGE COLOR TO MATCHSIDING
FLOOR FRAMING. REF STRUCT.
CONTINUOUS METALFOUNDATION FLASHING. POWEDER COAT TO MATCHMETAL PANNEL SYSTEM.
A
T.O. F.F. @ UPPER110' - 4 1/2"T.O. PLY @ UPPER110' - 1 1/2"
F-3
W-7
METAL FLASHING W/ DRIP EDGE,COLOR TO MATCH SIDING
WOOD FASCIA TO MATCH SIDING
CONTINUOUS SPRAY FOAM INSULATION
STEEL BEAM, REF. STRUCT.
SAW-CUT DRIP EDGE
WOOD WRAPPED COLUMN
SELF-ADHERED FLASHING TO OVERLAP METAL FLASHING
WEATHER RESISTANT BARRIER
SCALE 1 1/2" = 1'-0"A8124DTL_Foundation @ Office West
SCALE 1 1/2" = 1'-0"A8126 FOUNDATION WALL @ STAIR HALL
SCALE 1 1/2" = 1'-0"A8127DTL_Foundation Wall @ Garage DoorSCALE 1 1/2" = 1'-0"A8128FOUNDATION WALL @ GARAGE SLAB - EAST
SCALE 1 1/2" = 1'-0"A8129PATIO @ EXTERIOR WALLSCALE 1 1/2" = 1'-0"A81210TYPICAL FOUNDATION WALL @ WOOD JOIST SCALE 1 1/2" = 1'-0"A8125COLUMN @ MASTER BATH
Revise all drawings (architecturals, structurals, civils) sograde is 6” or more below the top of each foundation wallper 2015 IRC R404.1.6 (clearly dimensioned in thearchitectural details). Alternatively, the City will accept alesser distance if all of the following are provided. Note thisrequirement at all applicable wall sections and details:1.All wood materials within 6” of grade to be protected fromdecay per R317.1 5.2.Waterproof membrane extending up wall a minimum of 6”above grade.3.Capillary break separating concrete from wood materials.If you go that route you will also need to have the structuralplan revised to show treated lumber as a specified materialand have them list the proper fasteners for treated wood asthe chemicals used to treat lumber can degrade typicalfasteners.
Indicate how you will accomplish the air sealing
requirements of 2015 IECC table R402.4.1.1 using
notes and details. Indicate the continuity of the airbarrier and where it is located throughout the building.Note locations that require caulking, sealing, taping, etc.Note which components are included in the air barrier
such as spray foam, gypsum, housewrap, and/or
exterior insulation. You may have all of the above but
you need to pick one continuous barrier and stick to it. It
needs to follow the thermal barrier. The better detail you
provide, the easier it will be for the contractor andinspector to be successful. This is a new 2015 coderequirement in lieu of a blower door test. I've attachedour standard air sealing detail sheets to this comment
letter as an example of the type of detailing we're
looking for.
10/16/2019
Subject: PlanCheck
Page Label: A901
Author: justinh
File Name: Architectural Plans. 533 W HALLAM.pdf
Color:
One of these windows should be
marked egress as you have
done for the bedrooms in the
basement. The master bedroom
requires emergency escape
egress as well.
Subject: PlanCheck
Page Label: A901
Author: justinh
File Name: Architectural Plans. 533 W HALLAM.pdf
Color:
All windows and exterior doors
are required to have a U value of
.28 or better. Note this
requirement on the window and
door schedules. If you are
unable to accomplish this with
the historic replicas you will need
to submit a formal request,
addressed to the Chief Building
Official, to be exempted from this
requirement per IECC R501.6
due to the fact that compliance
would degrade the historic form
of the building.
Subject: PlanCheck
Page Label: G001
Author: justinh
File Name: Architectural Plans. 533 W HALLAM.pdf
Color:
Provide a copy of the state demo
license for the demolition of the
non-historic addition. You may
submit other responses without
this piece, but the building
department will not be able to
fully sign off on this permit until
that has been submitted.
Subject: PlanCheck
Page Label: G010
Author: justinh
File Name: Architectural Plans. 533 W HALLAM.pdf
Color:
Fire area/gross building area is
measured from the interior face
of the exterior walls rather than
the exterior face. You also do
not need to include areas under
the standard 1' eave overhang,
just areas under larger roof
projections such as your covered
exterior doors and front porch.
Please revise, and note on the
plan that fire sprinklers will be
required.
Subject: PlanCheck
Page Label: G011
Author: justinh
File Name: Architectural Plans. 533 W HALLAM.pdf
Color:
Show the property line on the
REMP plan, snowmelt in the
ROW needs to be on a separate
zone from snowmelt on your
property. This should be noted
on the plan and shown as
separate zones in the
mechanical plans.
HARDWARE FINISHES WITH OWNER PRIOR TO ORDERING. PROVIDED IN ALL HAZARDOUS AREAS PER SECTION R308 2015 IRC.
TH 2015 IECC CHAPTER 4, CLIMATE ZONE 7 & 8, FENESTRATION U-UFACTORER TO PROVIDE DOCUMENTATION FOR THE WINDOW A WEIGHTED AVERAGE OF U-VALUE 0.28 AND STICKER MARKING OF HE CITY OF ASPEN BUILDING DEPARTMENT.
SS.
ERALL FRAME DIMENSIONS.
ENSIONS BEFORE ORDERING.
RABLE WINDOWS. COORDINATE WITH ARCHITECT.
ANS FOR REFERENCED SHADE POCKET DETAILS & DESCRIPTION.
B 01 8' - 0" 2' - 0" 6' - 0" FIXED-FIXEDB 02 3' - 0" 2' - 0" 6' - 0" FIXEDB 03 2' - 0" 2' - 0" 6' - 0" AWNINGB 04 7' - 5 1/2" 9' - 0" 0" FIXED-FIXED TEMPERED GLASSB 05 2' - 6" 4' - 8" 3' - 6" CASEMENTB 06 2' - 6" 4' - 8" 3' - 6" CASEMENTB 08 1' - 11 1/4" 5' - 9 1/2" 1' - 4 1/4" DOUBLE HUNG EXISTING HISTORIC DOUBLE HUNGB 09 2' - 3 3/8" 5' - 9 1/2" 1' - 4 1/4" DOUBLE HUNG EXISTING HISTORIC DOUBLE HUNGB 10 2' - 3 3/8" 5' - 9 1/2" 1' - 4 1/4" DOUBLE HUNG EXISTING HISTORIC DOUBLE HUNGB 11 1' - 11 1/4" 5' - 9 1/2" 1' - 4 1/4" DOUBLE HUNG EXISTING HISTORIC DOUBLE HUNGB 12 2' - 2 3/4" 5' - 10" 1' - 4 1/2" DOUBLE HUNG HISTORIC REPLICA TO MATCH B 19 & B 20B 13 2' - 9" 3' - 11" 3' - 0" FIXED HISTORIC STAINED GLASS, RELOCATEDB 14 1' - 11 1/4" 5' - 9 1/2" 1' - 5" DOUBLE HUNG EXISTING HISTORIC DOUBLE HUNGB 15 2' - 3 1/4" 5' - 9 1/2" 1' - 5" DOUBLE HUNG EXISTING HISTORIC DOUBLE HUNGB 16 2' - 3 1/4" 5' - 9 1/2" 1' - 5" DOUBLE HUNG EXISTING HISTORIC DOUBLE HUNGB 17 1' - 11 1/4" 5' - 9 1/2" 1' - 5" DOUBLE HUNG EXISTING HISTORIC DOUBLE HUNGB 18 1' - 10" 1' - 4" 1' - 2 1/2" FIXED EXISTING HISTORIC STAINED GLASSB 18.2 1' - 10" 1' - 4" 1' - 2 1/2" FIXED HISTORIC REPLICA TO MATCH B 18B 19 2' - 2 3/4" 5' - 10" 1' - 4 1/2" DOUBLE HUNG EXISTING HISTORIC DOUBLE HUNGB 20 2' - 2 3/4" 5' - 10" 1' - 4 1/2" DOUBLE HUNG EXISTING HISTORIC DOUBLE HUNGB 21 2' - 2 3/4" 5' - 10" 1' - 4 1/2" DOUBLE HUNG EXISTING HISTORIC DOUBLE HUNGB 22 2' - 2 3/4" 5' - 10" 1' - 4 1/2" DOUBLE HUNG HISTORIC REPLICA TO MATCH B 19 & B 20B 23 2' - 2 3/4" 5' - 10" 1' - 4 1/2" DOUBLE HUNG HISTORIC REPLICA TO MATCH B 19 & B 20B 24 5' - 0" 5' - 6" 3' - 0" DOUBLE HUNG-DOUBLE HUNGB 25 2' - 0" 3' - 0" 11' - 4" AWNINGC 01 4' - 8" 5' - 6" 3' - 0" DOUBLE HUNG-DOUBLE HUNG TEMPERED GLASSC 02 2' - 0" 3' - 0" 9' - 11 1/2" AWNINGC 03 2' - 6" 5' - 6" 3' - 0" DOUBLE HUNGC 04 2' - 6" 5' - 6" 3' - 0" DOUBLE HUNGC 05 8' - 10" 5' - 6" 3' - 0" CASEMENT-FIXED-CASEMENTC 06 4' - 8" 5' - 6" 3' - 0" DOUBLE HUNG-DOUBLE HUNGC 07 2' - 0" 3' - 0" 9' - 11 1/2" AWNINGC 08 7' - 5 1/2" 9' - 0" 0" FIXED-FIXED TEMPERED GLASSC 09 2' - 6" 5' - 0" 3' - 6" DOUBLE HUNGC 10 2' - 6" 5' - 6" 3' - 0" DOUBLE HUNG
EXTERIOR DOOR SCHEDULE
DOORMARK DOOR TYPE
FRAME NOTESWIDTH HEIGHT101 A SINGLE SWING 3' - 4" 8' - 2" TEMPERED GLASS103 A SINGLE SWING 3' - 4" 8' - 2" TEMPERED GLASS106 A DOUBLE SWING 7' - 5" 9' - 0" TEMPERED GLASS107 A SINGLE SWING 3' - 4" 8' - 2" TEMPERED GLASS109 A 4-PANEL FOLDING 11' - 10 1/8" 9' - 0" TEMPERED GLASS110 A 4-PANEL FOLDING 10' - 8 7/8" 9' - 0" TEMPERED GLASS111 A SINGLE SWING 3' - 4" 7' - 2" NEW ENTRY DOOR.LOWER PROFILEAND PROPORTIONSTO MATCH 113 B.SINGLE WINDOW TOFOLLOW HISTORICSTYLING OF 113 B.113 A HISTORIC SINGLE SWING 2' - 8" 6' - 8" HISTORIC REPLICATO MIRROR 113 B113 B HISTORIC SINGLE SWING 2' - 8" 6' - 8" EXISTING HISTORICDOOR
One of these windowsshould be markedegress as you havedone for the bedroomsin the basement. Themaster bedroomrequires emergencyescape egress as well.
OVERALL FRAME DIMENSIONS.
DIMENSIONS BEFORE ORDERING.
OPERABLE WINDOWS. COORDINATE WITH ARCHITECT.
G PLANS FOR REFERENCED SHADE POCKET DETAILS & DESCRIPTION.
B 12 B 13 B 14 B 15
B 16
B 17
B 18
B 18.2
B 19
B 20
B 21
B 22
B 23
B 24
B 25
C 01
C 02
C 03
C 04
C 05
C 06
C 07 C 08 C 09
C 10
All windows and exterior doors are required to have a U
value of .28 or better. Note this requirement on the
window and door schedules. If you are unable to
accomplish this with the historic replicas you will need to
submit a formal request, addressed to the Chief BuildingOfficial, to be exempted from this requirement per IECCR501.6 due to the fact that compliance would degrade thehistoric form of the building.
G00
G00 G00 G00
G00 G01 G01
G01 G01
D10 D10 D10
D10 D10 D10
SU SU SU SU
1 O
EXC EXC EXC EXC
Provide a copy of the state demo license for the demolition of thenon-historic addition. You may submit other responses without this piece,but the building department will not be able to fully sign off on this permituntil that has been submitted.
FIRE AREA CALCULATIONS
LOWER LEVEL AREA TOTAL
MAIN LEVEL AREA TOTAL
MAIN LEVEL EXTERIOR COVERED AREA
UPPER LEVEL AREA TOTAL
3,571sf
2,682sf
130sf
1,027sf
381sfMAIN LEVEL OVERHANGS TOTAL
UPPER LEVEL OVERHANGS TOTAL 105sf
TOTAL AREA 7,896sf
Fire area/gross building area is measured from the interior face of the exterior walls ratherthan the exterior face. You also do not need to include areas under the standard 1' eaveoverhang, just areas under larger roof projections such as your covered exterior doors andfront porch. Please revise, and note on the plan that fire sprinklers will be required.
14
14
13
83.60 SQ FT
DDDDUUUUNNNNCCCCAAAANNNN RRRREEEESSSSIIIIDDDD
533 W HALLAM ST AS
Show the property lineon the REMP plan,snowmelt in the ROWneeds to be on aseparate zone fromsnowmelt on yourproperty. This shouldbe noted on the planand shown asseparate zones in themechanical plans.
Both walk ways have been shown as separate
zones starting at the property line.
10/16/2019
Subject: PlanCheck
Page Label: 2
Author: justinh
File Name: Energy Code Compliance - Mech'l. 533 W
Hallam.pdf
Color:
Our summer design temperature
is 82°F, please revise.
Energy Code Compliance - Mech'l. 533 W Hallam.pdf (1)
Subject: PlanCheck
Page Label: 1
Author: justinh
File Name: Line Grade Verification Form.533 W Hallam.pdf
Color:
An elevation benchmark is
required, please fill this portion
of the form.
Line Grade Verification Form.533 W Hallam.pdf (1)
Subject: PlanCheck
Page Label: [1] 18032-M1(D-48)-M-001
Author: justinh
File Name: Mechanical Plans. 533 W HALLAM.pdf
Color:
There are 5 bedrooms in the
new SFR and I measure over
6000 SF of occupiable floor area
on the floor plans. ERV-1 is
shown in your equipment
schedule as being 110 CFM
rather than 126 CFM shown
here and it is noted as servicing
only crawlspace ventilation.
In the sequence of operations
you note that the ERV shall run
30 minutes per hour, that will
also increase your required CFM
(what you show here is using the
assumption the system will run
continuously). Please revise this
calculation and equipment
schedule as needed to
accurately depict the home size,
number of bedrooms and ERV
unit proposed that will meet the
ventilation requirements.
Mechanical Plans. 533 W HALLAM.pdf (3)
Subject: PlanCheck
Page Label: 6
Author: justinh
File Name: Mechanical Plans. 533 W HALLAM.pdf
Color:
Civil plans reference a sump
pump per MEP in the
crawlspace, revise to show this
in your plans.
OUTDOOR TEMPERATURE -15°F OUTDOOR TEMPERATURE 88°F
INDOOR TEMPERATURE 72°F INDOOR TEMPERATURE 75°F
TOTAL HEAT LOSS 89,782 BTU/HR SENSIBLE HEAT GAIN 85,380 BTU/HR
LATENT HEAT GAIN 4,938 BTU/HR
TOTAL HEAT GAIN 90,318 BTU/HR
MANUAL J DESIGN CONDITIONS
WINTER DESIGN CONDITIONS SUMMER DESIGN CONDITIONS
Our summer designtemperature is 82°F,
please revise.
ASPEN LINE GRADE VERIFICATION FORMASPEN LINE GRADE VERIFICATION FORM Verification of Building Location by Building Contractor For Building and Permit Information, please refer to our website at: http://www.aspenpitkin.com/depts/41/
Exemption A City verification of building location is not needed when the project creates less the 200 square feet of new floor area. PART A: Complete and Submit as part of the Building Permit Application o Building / Job Address or Location: _____________________________________________ o Your Name (Person Completing Part A): ____________________________________________ o Your Company: ________________________________________________________________ o Plans must show horizontal dimensions that ‘tie’ the building to the property boundary. Are building ties shown? (circle one) ‘Yes’ ‘No’ o An elevation benchmark needs to be established on the site by a licensed surveyor and shown on the plans. What is the elevation of this benchmark? _________________________________ o If the garage is located within 10 feet of the roadway or sidewalk, provide spot elevation on the on the roadway or sidewalk. Is a spot elevation shown? ‘Yes’ ‘No’ ‘N/A’ o Provide the equation comparing site (surveyed) elevation to structure/ architectural plan elevation: (i.e., 100’ first floor elev = 7962.50’) _______________________________ ---------------------------------------------------------------------------------------------------------------------------------------------------------------------------- PART B: Complete prior to first Foundation Inspection, by a licensed surveyor or an individual prequalified by the City o Do field measured building ties to property match building ties shown on the plan? (circle one): ‘Yes’ ‘No’ o Surveyor needs to confirm that one spot on the top of the foundation wall is at the same elevation shown on the approved building plans. o What is the field measured elevation of top of foundation wall relative to the site bench mark? ____________ o According to the building plans, what was the design elevation for the same place on the foundation wall? ______________________________ o Was the elevation of the building adjusted in field? (circle one): ‘Yes’ ‘No’
An elevationbenchmark isrequired, please fillthis portion of theform.
AB (A) SECTION CUT LINE(B) SHEET SHOWN ON
THERMOMETER
BE PER THE
REMENTS (UPON
F THE REQUIRED ACCESS TO THEERVICEA MAXIMUM OF 20
NUFACTURER'SMMENDATIONS
RE.
RTERS, THERMALYS, CONTROLED BY THE
SHALL BE LOW
E PROVIDED BY THE
ENT
SYSTEM PER THE
ER, REGARDLESS OF
COMPLETE AND
E LOSS PROTECTION.CONNECTSE ELECTRICAL
Drawn By:
DATE
11-23-1
AEC P
DU
N
C
A
N
S
K
I
H
B
There are 5 bedrooms in the new SFR and Imeasure over 6000 SF of occupiable floorarea on the floor plans. ERV-1 is shown inyour equipment schedule as being 110 CFMrather than 126 CFM shown here and it isnoted as servicing only crawlspaceventilation.
In the sequence of operations you note thatthe ERV shall run 30 minutes per hour, thatwill also increase your required CFM (whatyou show here is using the assumption thesystem will run continuously). Please revisethis calculation and equipment schedule asneeded to accurately depict the home size,number of bedrooms and ERV unit proposedthat will meet the ventilation requirements.
1
3FC
MECHANICALCRAWLSPACE
M01
RM
1 1/4"ø HWR1 1/4"ø HWS 1/2"ø HWR1/2"ø HWS1"ø HWR1"ø HWS
3/4"ø HWR3/4"ø HWS
3/4"ø HWR3/4"ø HWS
3/4"ø HWS3/4"ø HWR
3/4"ø HWS UP3/4"ø HWR UP
10
9
Civil plans reference asump pump per MEPin the crawlspace,revise to show this inyour plans.
Design Temperature has been
revised.
Ventilation Schedule on M-001 Updated with correct
building Square footages.
Sequence on M-002 updated to run ERV
continuously.
Equipment on M-601 Updated to show correct air
flows.
Plumbing will be Design Build.
10/16/2019
Subject: PlanCheck
Page Label: 8
Author: justinh
File Name: Mechanical Plans. 533 W HALLAM.pdf
Color:
Snowmelt square footages
shown here and on the
snowmelt schedule do not match
what is shown on the
architectural REMP sheet.
Revise one or the other so that
the snowmelt quantities and
locations are consistent. You
may exempt 9 SF of snowmelt
for each window well (minimum
size required for an emergency
escape egress well) but you
must include any additional
square footage for each window
well in your REMP calculation.
Subject: PlanCheck
Page Label: 1
Author: justinh
File Name: RREMP Documents.533 W Hallam.pdf
Color:
Please fill out the contact info
portion of this form. If the site
plan/REMP plan are revised per
discussions with HPC and
building regarding the light well
guards, please be sure to update
the square footages on this
sheet accordingly.
RREMP Documents.533 W Hallam.pdf (1)
Subject: PlanCheck
Page Label: 3
Author: justinh
File Name: Special Inspection Agreement.533 W Hallam.pdf
Color:
You need an approved
fabricator's signature for the
shop welds shown in the
structural plans. Please
resubmit the agreement. You
may resubmit responses without
this if you have yet to decide on
your welder/steel fabricator but
building will not be able to sign
off on your permit until this
agreement has been fully
executed.
Special Inspection Agreement.533 W Hallam.pdf (1)
Subject: PlanCheck
Page Label: 1
Author: justinh
File Name: Structural Plans. 533 W HALLAM.pdf
Color:
Our wind speed design criteria is
89 MPH, please revise.
Structural Plans. 533 W HALLAM.pdf (3)
Subject: PlanCheck
Page Label: 1
Author: justinh
File Name: Structural Plans. 533 W HALLAM.pdf
Color:
We are seismic design category
C, please revise.
S
T
T
T
T
T
T
2
2
5
5
6
6
7
7
8
8
9
9
10
10
LL
KK
JJ
FFGG
DD
CC
AA
3
3
4
4
EE
HH
1
1
BB
5BRZ30 SQFT
7ARZ435 SQFT
7BRZ125 SQFT
6BRZ35 SQFT
6ARZ1050 SQFT5ARZ495 SQFT
8RM
9RM 7RM
GARAGE103
MUD ROOM102 ENTRY101
LIVING106
STAIR73
STAIRS49
PDR105
KITCHEN107
CASUAL DINING109
ENTRY HALL110 ENTRY111
DINING113
OFFICE114
BIKES104
1/2"ø HWS1/2"ø HWR
3/4"ø HWR UP3/4"ø HWS UP
3/4"ø HWS1"ø HWR
3/4"ø HWS3/4"ø HWR1"ø HWS DN1"ø HWR DN
1SZ635 SQFT2SZ235 SQFT
3SZ185 SQFT5SZ10 SQFT
4SZ30 SQFT
3SM
2
3
1
4
5
TO FC-4 &RZ-6A
TO FC-5,MD-5B &RZ-7A
TO FC-5,MD-5A &RZ-7B
TO RZ-5B
TO RZ-5A
TO RZ-6B
www.a
e
c
-
v
a
i
l
.
c
o
m
of
Drawn By:Checked By:
AEC PROJECT #:
COPYRIGHT 2018 ARCHITECTURAL ENGINEERING CONSULTANTS, INC.c
c
ae
PO Box
8
4
8
9
,
4
0
8
0
1
U
S
H
w
y
6
&
2
4
,
S
t
e
2
1
4
,
A
v
o
n
,
C
o
lorado
,
8
1
6
2
0
Mecha
n
i
c
a
l
,
E
l
e
c
t
r
i
c
a
l
&
L
i
g
h
t
i
n
g
D
e
s
i
g
n
S
e
r
v
i
c
e
s
Archite
c
t
u
r
a
l
E
n
g
i
n
e
e
r
i
n
g
C
o
n
s
u
l
t
a
n
t
s
Telep
h
o
n
e
:
9
7
0
-
7
4
8
-
8
5
2
0
F
a
x
:
9
7
0
-
7
4
8
-
8
5
2
1
An Office
w
i
t
h
L
E
E
D
™
A
c
c
r
e
d
i
t
e
d
P
r
o
f
e
s
s
i
o
n
a
l
s
DATE: ISSUE:
SCALE 1/4" = 1'-0"
18032.00
DUN
C
A
N
S
K
I
H
A
U
S
533 W
E
S
T
H
A
L
L
A
M
ASPE
N
,
C
O
L
O
R
A
D
O
,
8
1
6
1
1
M-122
FIRST FLOORMECHANICALPIPING
10 14
BLU TOC
11/23/18PERMIT/PRICING
1/4" = 1'-0"1MECHANICAL PIPING - 1ST FLOOR
SHEET NOTES:1 CONNECT 1/2" SMS/R TO SM-3.2 CONNECT 1/2" HWS/R TO RM-9.3 CONNECT 3/4" HWS/R TO RM-8.4 CONNECT 3/4" HWS/R TO RM-7.5 INSTALL SNOW & ICE SENSOR IN THE SNOWMELT ZONE AS SHOWN.COORDINATE EXACT LOCATION WITH G.C. ENSURE THE SENSOR ISEQUIDISTANT BETWEEN TUBING & NOT UNDER OVERHANGS OR INWIND EDDIES.6 SEE ARCH SITE PLAN FOR CONTINUATION
1. OFFSET PIPING AS REQUIRED TO AVOID ALL DUCTWORK, LIGHTS, AND STRUCTURE. COORDINATE ALL STRUCTURAL PENETRATIONS WITH THE STRUCTURAL ENGINEER.2. ALL PIPING PASSING THROUGH FIRE-RATED ASSEMBLIES SHALL INCLUDE A FIRE-RATED PIPE SEALANT RATED TO MATCH THAT OF THE ASSEMBLY.3. VERIFY FINAL LOCATIONS OF ALL MANIFOLDS WITH THE G.C. CONTACT ENGINEER IF MANIFOLDS MOVE MORE THAN 10' FROM LOCATIONS SHOWN ON PLANS.4. LOCATION OF ALL THERMOSTATS AND FLOOR SENSORS ARE APPROXIMATE, COORDINATE EXACT LOCATIONS WITH THE ARCHITECT. LOCATE FLOOR SENSORS EQUIDISTANT BETWEEN RADIANT LOOPS, AND DO NOT LOCATE WHERE THEY MAY LIKELY BE COVERED BY FUTURE RUGS OR FURNITURE.5. ALL PIPING SIZED FOR TYPE L COPPER. CONTACT ENGINEER FOR ANY CHANGE TO PEX FOR NECESSARY PIPE SIZING AND/OR PUMP CHANGES.6. INSULATE ALL PIPE LEADERS PASSING THROUGH ADJACENT ZONES.
GENERAL NOTES:
Snowmelt square footages shown here andon the snowmelt schedule do not matchwhat is shown on the architectural REMPsheet. Revise one or the other so that thesnowmelt quantities and locations areconsistent. You may exempt 9 SF ofsnowmelt for each window well (minimumsize required for an emergency escapeegress well) but you must include anyadditional square footage for each windowwell in your REMP calculation.
PROJECT ADDRESS:
Parcel ID #: Permit Number:
CONTACT INFORMATION :Owner:Name:City:
Address:State:
Email:Zip Code:
Phone: Cell Phone:
Owner's Representative :
Name:City:Aspen
Address:State:Colorado
Email:Zip Code:81611
Phone: Cell Phone:`
A.RESIDENTIAL RENEWABLE ENERGY MITIGATION PROGRAMSheets showing snowmelt, pool, spa, and solar/GSHP information: Do you have snowmelt or a spa that has been exempted by the buiding official?Hydro Snowmelt Electric Snowmelt Pool SpaExisting0.00 sqft 0.00 sqft 0.00 sqft 0.00 sqftTo be Demoed 0.00 sqft 0.00 sqft 0.00 sqft 0.00 sqftExisting to Remain 0.00 sqft 0.00 sqft 0.00 sqft 0.00 sqftNew (non-exempt)1128.63 sqft 0.00 sqft 0.00 sqft 0.00 sqftNew (exempt)0.00 sqft 0.00 sqft 0.00 sqftTotal New 1128.63 sqft 0.00 sqft 0.00 sqft 0.00 sqftTotal on site 1128.63 sqft 0.00 sqft 0.00 sqft 0.00 sqftTotal Snowmelt on siteBoiler Efficiency 95.0%100%95.0%95.0%Mitigation Payment -$ -$ Total Payment for Mitigation:40,393.07$ B.ON-SITE RENEWABLE CREDITS Supplemental System REMP CreditUse PV WorksheetPhotovoltaic System -$ Use Thermal WorksheetHot Water Panels -$
2015 IECC RESIDENTIAL RENEWABLE ENERGY MITIGATION PROGRAMCity of Aspen Version 11.3 UpdAted deCember 13, 2017533 West Hallam Aspen CO 81611
Wlewis@BillPoss.com
William Lewis
1128.63 sqft
605 East Main Street
G007
(970) 925-4755
$40,393.07
Yes (enter sqft below on the exempt row)No
Please fill out the contact infoportion of this form. If the siteplan/REMP plan are revised perdiscussions with HPC andbuilding regarding the light wellguards, please be sure toupdate the square footages onthis sheet accordingly.
You need an approved fabricator'ssignature for the shop weldsshown in the structural plans. Please resubmit the agreement. You may resubmit responseswithout this if you have yet todecide on your welder/steelfabricator but building will not beable to sign off on your permit untilthis agreement has been fullyexecuted.
Wind Loading
Basic Wind Speed Vult= 115 MPH Vasd= 90 MPHExposure Category BGCpi0.18Wind Base Shear - Ultimate
21.9 K
Wind Design Pressure Components & Cladding - Ultimate 50ft2
East/West
North/South
Seismic Loading
1.0
Mapped Spectral Response Acceleration
Seismic Importance Factor, Ie
0.315SS0.082S1DSite ClassSpectral Response Coefficients
Local Jurisdiction: City of Aspen
Building Code: 2015 International Building Code
-34.4 PSFInterior Roof Zone (Zone 1)-47.0 PSFRoof End Zone (Zone 2)
-47.7 PSFCorner Roof Zone (Zone 3)
-25.6 PSFInterior Wall Zone (Zone 4)
-29.6 PSFWall End Zone (Zone 5)
STRUCTURAL DESIGN CRITERIA
Risk Category: II
20ft2
-42.3 PSF-54.1 PSF
-55.6 PSF
-27.2 PSF
-32.7 PSF
100ft2
-28.4 PSF-41.7 PSF
-41.7 PSF
-24.5 PSF
-27.2 PSF
(Note 1)
19.8 K
SURANCEactor is responsible for quality assurance, including ship and materials furnished by subcontractors and suppliers. n or testing by the Owner does not relieve the Contractor of his ility to perform the work in accordance with the Contract ts. nship: The Contractor is responsible and shall bear the cost of g work which does not conform to the specified requirements. eficient work by means acceptable to the Architect. The cost of k incurred by the Architect to approve corrective work shall be the Contractor.
NTROLer's Testing Agency shall perform testing and special inspections by the structural documents, building code and the local
The Testing Agency shall comply with ASTM E329 and upon on of work, the Testing Agency shall furnish a certificate of ce, signed by the professional engineer overseeing special ns and testing. The professional engineer must be registered and n the state where the project is located.dual employed by the Testing Agency, responsible for g testing and inspection of soils and foundations shall be a nal engineer practicing the discipline of geotechnical ng, referred to as the Geotechnical Engineer in the structural f the construction documents. The Geotechnical Engineer is le for testing and inspections of soils, earthwork and foundations rmance to the foundation design and the geotechnical report. dation section of the general notes.al inspections section of the general notes for required testing ction.
ABBRE
AB anchor ADDNL addition AFF above f ALT alternat ARCH architec
BLDG buildingBM beamBOT, B/, BOx bottom BRG bearingBS both si BTWN between
CIP cast-in CJ constru CJP complet CLR clearCMU concret COL columnCONC concret CONN connect CONST constru CONT continu
D depthDIA, D diamete DIM dimensi DK deckDTL detailDWGS drawing DWL dowel
(E) existing
Our wind speeddesign criteria is 89MPH, please revise.
GCpi 0.18Wind Base Shear - Ultimate
21.9 K
Wind Design Pressure Components & Cladding - Ultimate 50ft2
East/WestNorth/South
Seismic Loading 1.0
Mapped Spectral Response Acceleration
Seismic Importance Factor, Ie
0.315SS0.082S1
DSite ClassSpectral Response Coefficients
0.325SDS0.131SD1BSeismic Design Category
Wood Shear WallsBasic Seismic Force Resisting System 6.5Response Modification Factor, R
0.050Seismic Response Coefficient, Cs Equivalent Lateral Force MethodAnalysis Procedure UsedSeismic Base Shear - Ultimate
11.5 KEast/West 11.5 KNorth/South
Snow Loading 100 PSFGround Snow Load, Pg 70 PSFMinimum Flat Roof Snow Load, Pf
1.0Importance Factor, Is BTerrain Category
1.0Exposure Factor, Ce 1.0Thermal Factor, Ct See Load KeysSlope Factor, CsLive Loads and Superimposed Dead Loads
(Notes 2,3,5)
(Notes 4,5)
-34.4 PSFInterior Roof Zone (Zone 1)-47.0 PSFRoof End Zone (Zone 2)
-47.7 PSFCorner Roof Zone (Zone 3)
-25.6 PSFInterior Wall Zone (Zone 4)-29.6 PSFWall End Zone (Zone 5)
20ft2
-42.3 PSF-54.1 PSF
-55.6 PSF
-27.2 PSF-32.7 PSF
100ft2
-28.4 PSF-41.7 PSF
-41.7 PSF
-24.5 PSF-27.2 PSF
19.8 K
2.5Over-Strength Factor, Ωo 4Deflection Amplification Factor, Cd
4. Correct deficient work by means acceptable to the Architect. The cost of extra work incurred by the Architect to approve corrective work shall be borne by the Contractor.
QUALITY CONTROL1. The Owner's Testing Agency shall perform testing and special inspections required by the structural documents, building code and the local authority. The Testing Agency shall comply with ASTM E329 and upon completion of work, the Testing Agency shall furnish a certificate of compliance, signed by the professional engineer overseeing special inspections and testing. The professional engineer must be registered and licensed in the state where the project is located.2. The individual employed by the Testing Agency, responsible for overseeing testing and inspection of soils and foundations shall be a professional engineer practicing the discipline of geotechnical engineering, referred to as the Geotechnical Engineer in the structural portion of the construction documents. The Geotechnical Engineer is responsible for testing and inspections of soils, earthwork and foundations for conformance to the foundation design and the geotechnical report. See foundation section of the general notes.3. See special inspections section of the general notes for required testing and inspection.
SPECIAL INSPECTION1. Special inspection and testing shall be performed as required by the local jurisdiction, the building code and the construction documents. See quality assurance section of the general notes. 2. Coordinate and schedule inspection and testing prior to the start of work requiring inspection and testing while providing special inspector reasonable notice. 3. All deficiencies shall be corrected for acceptance by the testing agency. 4. Inspections performed by the local jurisdiction do not replace inspection or testing required by the owners testing agency. 5. Special inspection and testing is required for the items shown in the special inspections and testing table.
SPECIAL INSPECTIONS AND TESTING
ClassCategory/Material
X 54321Component/Work
Footing Soil Bearing Material
Soils
a
n
d
Foun
d
a
t
i
o
n
s
XSlab-on-Grade Subgrade Material
XXXCompaction
XXXFormwork InstallationReinforcing Placement
BM beamBOT, B/, BOx bottom of ( BRG bearingBS both sidesBTWN between
CIP cast-in-pla CJ construction CJP complete jo CLR clearCMU concrete ma COL columnCONC concreteCONN connectionCONST constructionCONT continuous
D depthDIA, D diameterDIM dimensionDK deckDTL detailDWGS drawingsDWL dowel
(E) existing con EA eachEF each faceEJ expansion jo ELEV elevationEOx edge of (S= EW each wayEXP expansionEXT exterior
FDN foundationFLR floorFOx face of (S= FS far sideFTG footing
GA gageGC general con GEN general
HDG hot dip galv HDR headerHK hookHORIZ horizontalHSA headed stud
I.F. inside faceINT interior
JST joist
We are seismic designcategory C, pleaserevise.
REMP calc. Adjusted to reflect window wells and
correct patio areas. Contact info has been provided.
AN APPROVED FABRICATOR SIGNATURE
WILL BE SUBMITTED PRIOR TO ISSUANCE
OF THE PERMIT.
10/16/2019
Are you still planning on using an approved fabricator
for shop welds as this response implies, or will you be
using custom structural steel as an inspected
fabricator for both shop and field welds. Please
clarify, I can accept either but any shop welds done by
the inspected fabricator must still be inspected by
your special inspector.
Subject: PlanCheck
Page Label: 13
Author: justinh
File Name: Structural Plans. 533 W HALLAM.pdf
Color:
Per discussion with HPC the
existing roof framing was to
remain in the historic structure
and be added to as needed.
This appears to be a new roof
framing package entirely.
Please coordinate with HPC and
revise the structural plan to
clearly show existing historic
framing to remain everywhere
that is applicable.
HD1 HD1ZIP9'-3"
HD1 HD1ZIP5'-3"HD1 HD1ZIP5'-3"
HD1
ZIP12'-9"
HD1
HSS
A6'-6"
2567
L
K
J
F
G
D
C
A
34
E
H
1
B
86'-0 1/2"15'-11"11'-9"2'-0 1/2"9'-0 7/8"11'-11 1/8"4'-5 1/2"
15'-11"11'-9"2'-0 1/2"9'-0 7/8"11'-11 1/8"4'-5 1/2"
42'-5 1/2"
1'-8"4'-2 1/2"
12'-5 3/4"
9'-0"
1'-4 1/4"
1'-8"3'-7 1/2"3'-5 1/2"
4'-6"
6"
11 7/8
"
T
J
I
2
1
0
@
1
6
"
O
C
11 7/8
"
T
J
I
2
1
0
@
1
6
"
O
C
(1)1 3
/
4
"
x
9
1
/
2
"
L
V
L
@
1
6
"
O
C
(1)1 3/
4
"
x
9
1
/
2
"
L
V
L
@
1
6
"
O
C
(1)1 3/4"x11 7/8" LVL@24"OC
(1)1 3/4"x11 7/8" LVL@24"OC
(1)1 3
/
4
"
x
1
1
7
/
8
"
L
V
L
@
2
4
"
O
C
(1)1 3
/
4
"
x
1
1
7
/
8
"
L
V
L
@
2
4
"
O
C
(1)1 3/4"x11 7/8" LVL@24"OC
(1)1 3/4"x11 7/8" LVL@24"OC
(1)1 3/
4
"
x
1
1
7
/
8
"
L
V
L
@
2
4
"
O
C
(1)1 3/
4
"
x
1
1
7
/
8
"
L
V
L
@
2
4
"
O
C
W10x22 (BENT)
W10x22 (BENT)(2)1 3/4"x14" LVL(2)1 3/4"x14" LVL(2)1 3/4"x14" LVL(2)1 3/4"x14" LVL(2)1 3/
4
"
x
1
4
"
L
V
L(2)1 3/4"x14" LVL(2)1 3/4"x14" LVL
(2)1
3
/
4
"
x
1
4
"
L
V
L
(2)1 3
/
4
"
x
1
4
"
L
V
L
W8x67109'-10 1/4"
W18x46110'-7 1/4"
W14x2
6
110'-3 1/4"
W10x22109'-11 1/4"
2S402
3S402
4S402
(2)1 3/4"x9 1/2" LVL
(2)1 3
/
4
"
x
9
1
/
2
"
L
V
L
(3)1 3
/
4
"
x
9
1
/
2
"
L
V
L
1S301
1S301
T/SHEATHING110'-1 1/2"
T/SHEATHING109'-11"
No2
(3)1 3/
4
"
x
1
1
7
/
8
"
L
V
L
(2)1 3/4"x11 7/8" LVL
(2)1 3/4"x11 7/8" LVL
2x6 DFL No2@24"OC
2x6 DF
L
N
o
2
@
2
4
"
O
C
2x6 DF
L
N
o
2
@
2
4
"
O
C
2x6 D
F
L
N
o
2
@
2
4
"
O
C
KLA&Engineers Builders215 North 12th Street, Unit ECarbondale, Colorado 81623P: (970) 927 5174 F: (970) 927 5194Buffalo, WY ○ Carbondale, CO ○ Golden, CO ○ Loveland, CO
&
NORTH
Consultant
ARCHITECTUREPLANNING+
( T ) 9 7 0 / 9 2 5 4 7 5 5 ( F ) 9 7 0 / 9 2 0 2 9 5 06 0 5 E A S T M A I N S T R E E T A S P E N, C O L O R A D O 8 1 6 1 1
PROJECT NO:
Issue:
DUNCAN RESIDENCE
533 W. HALLAM
1 UPPER LEVEL / LOW ROOF FRAMING PLAN
10/31/18 PERMIT
10/25/2018
Per discussion with HPC the existingroof framing was to remain in the historicstructure and be added to as needed. This appears to be a new roof framingpackage entirely. Please coordinatewith HPC and revise the structural planto clearly show existing historic framingto remain everywhere that is applicable.
10/16/2019