For the thermal envelope,
provide a REScheck for the R2
occupancies. COMcheck only for
the R1 and common areas.
Energy Code Compliance ComCheck.2017.01.pdf (2)
Page: 1
File Name: Energy Code Compliance ComCheck.2017.01.pdf
Subject: PlanCheck
Author: nickt
Color:
Include overhangs in the
COMcheck, such as at the inset
area used to access storage
218.
Page: A-011
File Name: Plan Set201701.pdf
Subject: PlanCheck
Author: nickt
Color:
What is the outdoor area
exception? The code section
you've given does not exist.
Plan Set201701.pdf (44)
Page: A-012
File Name: Plan Set201701.pdf
Subject: PlanCheck
Author: nickt
Color:
Main entry 101 is an exit
discharge lobby; label it as such
and protect the floor with 1 hour
fire rated construction, including
supporting construction. (2009
IBC 1027.1 ex1)
Page: A-013
File Name: Plan Set201701.pdf
Subject: PlanCheck
Author: nickt
Color:
Park Entry 207 must be
protected as a 2 hour exit
passageway. this includes the
walls, ceiling, floor, and
supporting construction. Doors
must be 90 minute rated. Label
the space as an exit
passageway.
are Version 4.0.5.2
Compliance Certificate
nt:Designer/Contractor:
n St
Martin Zourek
AEC
P.O.Box 8489
For the thermal envelope,
provide a REScheck for the
R2 occupancies. COMcheck
only for the R1 and common
areas.
COMcheck Software V
Envelope Com
Section 1: Project Information
Energy Code: 2009 IECC
Project Title: Hotel Lenado
Project Type: New Construction
Construction Site:Owner/Agent:
City & Townsite of Aspen
block 75. Lot A thru C
Aspen, CO 81611
Lori Gerety
Forum Phi
715 W. Main St
Include overhangs in the
COMcheck, such as at the inset
area used to access storage 218.
OUTDOOR AREA EXCEPTION 2 IBC 1004.5
Both outdoor areas associated with GroupR-3 and individual dwelling units of GroupR-2.
What is the outdoorarea exception? The
code section you've
given does not exist.
DN
103C103B103A
101
102
F
351.00 sq ft
62.75 sq ft 104A
105A
105B
134B
A
A
104A 104B 104C 104D
35'-5" EXIT SEPARATIONDISTANCE PER 1007.1.1EXCEPTION 2
35'-5" EXIT SEPARATION DISTANCEPER 1007.1.1 EXCEPTION 2
UNIT 101200 GrossOccupancy Type: R-1Program: ResidentialOccupancy Load: 2
UNIT 107200 GrossOccupancy Type: R-1Program: ResidentialOccupancy Load: 3
MANAGEMENT/VALET300 GrossOccupancy Type: R-1Program: StorageOccupancy Load: 1
2
17
11 MAIN ENTRY101
LODGE 1 BED104
LODGE 1 BATH105
HA1
STAIR 2103
MECH
WATER CLOSET
WATER CLOSET
MECH
LODGE 7 BATH134
LODGE 7 BED133
F
117B
118
117C
59'-10" DISTANCE TO NEAREST EXIT,80'-11" DISTANCE TO 2ND EXIT,LESS THAN 250'-0" PER IBC 1017.236'-6" TRAVEL DISTANCE TO COMMONPATH, LESS THAN 75'-0" PER IBC1006.2.1
58L3P1
80'-5" DISTANCE TONEAREST EXIT, 110'-1"DISTANCE TO 2ND EXIT,LESS THAN 250'-0" PER IBC1017.261'-5" TRAVEL DISTANCE TOCOMMON PATH, LESS THAN75'-0" PER IBC 1006.2.1
TOTAL OCCUPANT LOADAT STAIR = 17
MGMNT VALET102
Main entry 101 is anexit discharge lobby;label it as such andprotect the floor with 1hour fire ratedconstruction, includingsupportingconstruction. (2009IBC 1027.1 ex1)
UP
1,442.00 sq ft
211
524.75 sq ft
209
208
212
210B
210A
210C203A
B
210A
DN
UNIT 203200 GrossOccupancy Type: R-2Program: ResidentialOccupancy Load: 3
GAME LOUNGE/BAR200 GrossOccupancy Type: R-1Posted Max Occupancy Load: 49
BARRIER PER2009 IBC 1023.8
25
18 136
118
6
ACCESSORY OCCUPANCIES PER IBC 508.2.1
ACCESSORY USES TO R-1 OCCUPANCY:HOUSEKEEPING = 64.50 SQ FTTOTAL = 64.50 SQ FT
TOTAL AREA OF LOWER LEVEL = 5,511.50 SQ FT10% OF TOTAL AREA = 551.15 SQ FT
25
AH 1 LIVING / KITCHEN209
AH 1STORAGE210
HALL 2205
ELEV206
T
GAME LOUNGE/ BAR203
STAIR 1208
PARK ENTRY207207A
205
DN
F
DW
F
34' 1" EXIT SEPARATION DISTANCE
19'-4" DISTANCE TONEAREST EXIT ACESS,77'-4" DISTANCE TO 2NDEXIT,LESS THAN 250'-0" PERIBC 1017.28'-9" TRAVEL DISTANCETO COMMON PATH, LESSTHAN 75'-0" PER IBC1006.2.1
TOTAL OCCUPANT LOAD ATSTAIR = 118MIN. WIDTH = 44"
TOTAL OCCUPANT LOAD ATCORRIDOR = 136MIN. WIDTH = 36"
GE
STATE
LICEN
STRUCTURA
CONSULTASURVEYOR
MECHANICA
CIVIL
200 Sou20
715 WesAspP: 970.27
Tuttle Surveying727 Blake AveGlenwood Springs(970) 928-9708jeff@tss-us.com
Roaring Fork Eng0123 Emma RoadBasalt, CO 81621(970) 948-7474richardg@rfeng.bi
Architectural Engi40801 US-6 #214Avon, CO 81620(970) 748-8520taylor@aec-vail.co
KL&A215 N. 12th StreeCarbondale, CO 8(970) 927-5174mlyons@klaa.com
Park Entry 207 mustbe protected as a 2hour exit passageway.this includes the walls,ceiling, floor, andsupportingconstruction. Doorsmust be 90 minuterated. Label the spaceas an exitpassageway.
We accidentally quoted 2015 IBC. In the
2009 IBC, it is 1004.8. This has been
updated.
This space has been labeled as an exit
discharge lobby. Floor and supporting structure
has been protected (1 hour). Notes regarding
locations are on A-011 and A-012. Detail for
beam protection (FP-4) and column protection
(FP-3) are on sheet A-503.
This space has been labeled as an exit
passageway. Floor, walls, ceiling and supporting
structure has been protected (2 hour). Notes
regarding locations are on A-011, A-012, and
A-013. Detail for beam protection (FP-4) and
column protection (FP-3) are on sheet A-503.
Detail for 2 hour floor (F-7) is on sheet A-503 as
well.
This has been updated and a new
COMcheck has been provided.
This has been updated and a new
COMcheck and REScheck have been
provided.
City of Aspen
Received
7/10/17
Building Department
Page: A-013
File Name: Plan Set201701.pdf
Subject: PlanCheck
Author: nickt
Color:
At the park level, measure the
exit travel distance not to end at
door 218 but to where you leave
the overhanging building and
enter the alley.
Page: A-014
File Name: Plan Set201701.pdf
Subject: PlanCheck
Author: nickt
Color:
Provide the door locking
arrangements for doors 309A
and 401 in stair 1. 2009 IBC
1008.1.9.10. If any other stair
doors are intended to be
lockable, demonstrate
compliance per this code
section.
Page: A-016
File Name: Plan Set201701.pdf
Subject: PlanCheck
Author: nickt
Color:
Provide the dimensions of all
clear spaces and turnarounds
rather than noting the code
sections on all of the
accessibility plans.
Page: A-016
File Name: Plan Set201701.pdf
Subject: PlanCheck
Author: nickt
Color:
Provide enlarged plans and
interior elevations with
dimensions of each accessible
facility, including the employee
lounge kitchenette and each
accessible bathroom in the hotel.
Provide the dimensions of all
clearspaces, turnarounds, door
maneuvering clearances, grab
bars, and control and fixture
locations.
Page: A-016
File Name: Plan Set201701.pdf
Subject: PlanCheck
Author: nickt
Color:
Show all parking spaces
including accessible parking
space on accessibility plan.
276.75 sq ft
220A
64.50 sq ft
219
217A
220A
A
UP
18
15
GARAGE217 CAR LIFT216
AH 1 POWDER211
STORAGE218
219
216217
220B
220A
220C
220D
220E
218
221A
TOTAL OCCUPANT LOADAT CORRIDOR = 18
Occupancy Type: R-1Program: ResidentialOccupancy Load: 1
GARAGE200 GrossOccupancy Type: S-2Program: StorageOccupancy Load: 2
PARK LEVEL
At the park level,measure the exit traveldistance not to end atdoor 218 but to whereyou leave theoverhanging buildingand enter the alley.
DN
UP 313A
310C
312
311
303A
309A
52.50 sq ft
UNIT 302200 GrossOccupancy Type: R-2Program: ResidentialOccupancy Load: 9
14 253
63
HALL 3307
RESIDENCE 2 KITCHEN310
STAIR 1309
ELEV308
RESIDENCE 2 SITTING311
DECK
DW
F
DW
314B
314A
314C
315
317A
TOTAL OCCUPANTLOAD AT STAIR = 63
TOTAL OCCUPANT LOADAT CORRIDOR = 18
STRUCT
CONSUSURVEY
MECHAN
CONTRA
CIVIL
INTERIO
Tuttle Surve727 Blake AGlenwood S(970) 928-9jeff@tss-us
Roaring Fo0123 EmmaBasalt, CO (970) 948-7richardg@r
Architectura40801 US-6Avon, CO 8(970) 748-8taylor@aec
Madigan + PO Box 968Aspen, CO (970) 319-2chris@mad
KL&A215 N. 12thCarbondale(970) 927-5mlyons@kl
dg+a interio5401 N CenDallas, TX 7(214) 522-6
Provide the doorlocking arrangementsfor doors 309A and401 in stair 1. 2009IBC 1008.1.9.10. If anyother stair doors areintended to belockable, demonstratecompliance per thiscode section.
Provide the dimensions
of all clear spaces and
turnarounds rather than
noting the code
sections on all of the
accessibility plans.
DW
1'-6"3'-5"
F
SINK CLEAR FLOOR SPACE PER ANSI804.5.6
REFRIGERATOR CLEAR FLOOR SPACEPER ANSI 804.5.6
60" TURNING RADIUS INCLUDING KNEEAND TOE SPACE PER ANSI 304.3.1
R SPACE.2.3.1
E PER ANSI 604.3
PER ANSI 305.3ACE PER ANSI 305.3
S INCLUDING KNEER ANSI 304.3.1
R SPACE.2.3.1R SPACE.2.3.1R SPACE.2.3.1R SPACE.2.3.1S INCLUDING KNEER ANSI 304.3.1
R SPACE.2.3.1S INCLUDING KNEER ANSI 304.3.1
DISHWASHER CLEAR FLOOR SPACEPER ANSI 804.5.6
200 South A8
200 S
715 West MainAspen, CoP: 970.279.415
Provide enlarged plansand interior elevationswith dimensions ofeach accessiblefacility, including theemployee loungekitchenette and eachaccessible bathroom inthe hotel. Provide thedimensions of allclearspaces,turnarounds, doormaneuveringclearances, grab bars,and control and fixturelocations.
DOOR SWING CLEAR SPACEPER ANSI TABLE 404.2.3.1
60" TURNING RADIUS INCLUDING KNEEAND TOE SPACE PER ANSI 304.3.1
CLEAR FLOOR SPACE PER ANSI 305.3
60" TURNING RADIUS INCLUDING KNEEAND TOE SPACE PER ANSI 304.3.1
60" MIN WIDTH PER ANSI 502.4.1
Show all parking
spaces including
accessible parking
space on accessibility
plan.
This has been updated on A-016.
This has been updated.
The door schedule has been updated to reflect a
lock on the stair side only of door 309A (sheet
A-605) and 401 (sheet A-614).
These have been provided on sheets
A-016 through A-020.
These have been provided on sheets
A-016 through A-040.
City of Aspen
Received
7/10/17
Building Department
Page: A-017
File Name: Plan Set201701.pdf
Subject: PlanCheck
Author: nickt
Color:
Flip the water closet
compartment door in the
accessible lodge bathroom so
that the approach is from the
latch side (but still swings
outward) (ICC/ANSI
A117.1-2003 section 604.8.3).
Page: A-017
File Name: Plan Set201701.pdf
Subject: PlanCheck
Author: nickt
Color:
Provide enlarged plans and
interior elevations with
dimensions of each accessible
facility, including the valet
counter. Provide the dimensions
of the clear space, height and
depth of the counter.
Page: A-017
File Name: Plan Set201701.pdf
Subject: PlanCheck
Author: nickt
Color:
Operable windows within the
accessible lodge room must
have their hardware within
accessible reach ranges.
Demonstrate compliance on the
plans. (ICC/ANSI A117.1-2003
section 1002.9 and 1002.13)
Page: A-017
File Name: Plan Set201701.pdf
Subject: PlanCheck
Author: nickt
Color:
Provide enlarged plan and
interior elevations of accessible
lodge unit fridge and storage
areas with dimensions. Fridge
and storage must be accessible
(ICC/ANSI A117.1-2003 section
1002.14). If this is a kitchen, a
work surface is required per
1002.12.
Page: A-018
File Name: Plan Set201701.pdf
Subject: PlanCheck
Author: nickt
Color:
Housekeeping 220 shows the
turnaround and door clearance
overlapping fixtures and built ins.
Revise.
1'-6"
3'
2'-6"
3'3'
2'-6"
3'-1"
11" MIN
11" MIN
3'-1"
DIUS INCLUDING KNEE PER ANSI 304.3.1
PACE PER ANSI 604.3
OR SPACE PER ANSI 305.3
FLOOR SPACE PER ANSI
OOR SPACE PER ANSI 305.3
MAIN LEVEL
Flip the water closet
compartment door inthe accessible lodgebathroom so that theapproach is from the
latch side (but stillswings outward)(ICC/ANSIA117.1-2003 section
604.8.3).
DN
3'-4"
3'
3'
60" TURNING RADIUS INCLUDING KNEEAND TOE SPACE PER ANSI 304.3.1
DOOR SWING CLEAR SPACEPER ANSI TABLE 404.2.3.1DOOR SWING CLEAR SPACEPER ANSI TABLE 404.2.3.1DOOR SWING CLEAR SPACEPER ANSI TABLE 404.2.3.1
DPDPDP
OA
Provide enlarged plansand interior elevationswith dimensions ofeach accessiblefacility, including thevalet counter. Providethe dimensions of theclear space, heightand depth of thecounter.
40" MIN CLEAR SPACE PER ANSI 804.2.1
REFRIGERATOR CLEAR FLOOR SPACE PERANSI 804.5.6
60" TURNING RADIUS INCLUDING KNEEAND TOE SPACE PER ANSI 304.3.1
60" TURNING RADIUS INCLUDING KNEEAND TOE SPACE PER ANSI 304.3.1
TOILET CLEAR SPACE PER ANSI 604.3
SINK CLEAR FLOOR SPACE PER ANSI 305.3
SHOWER CLEAR FLOOR SPACE PER ANSI305.3BATH CLEAR FLOOR SPACE PER ANSI 305.3
POCKET APPROACHPER ANSI TABLE 404.2.3.3
Operable windowswithin the accessible
lodge room must havetheir hardware withinaccessible reachranges. Demonstratecompliance on theplans. (ICC/ANSI
A117.1-2003 section1002.9 and 1002.13)
W/D
W/D
W/D
W/D
1'-6"
3'
3'
3'
2'-6"
3'3'
2'-6"
UPF
3'-43/4"
3'-1"11" MIN
11" MIN
3'-1"
40" MIN CLEAR SPACE PER ANSI 804.2.1
60" TURNING RADIUS INCLUDING KNEEAND TOE SPACE PER ANSI 304.3.1DOOR SWING CLEAR SPACEPER ANSI TABLE 404.2.3.1
REFRIGERATOR CLEAR FLOOR SPACE PERANSI 804.5.6
60" TURNING RADIUS INCLUDING KNEEAND TOE SPACE PER ANSI 304.3.1
60" TURNING RADIUS INCLUDING KNEEAND TOE SPACE PER ANSI 304.3.1
TOILET CLEAR SPACE PER ANSI 604.3
SINK CLEAR FLOOR SPACE PER ANSI 305.3
SHOWER CLEAR FLOOR SPACE PER ANSI305.3BATH CLEAR FLOOR SPACE PER ANSI 305.3
DOOR SWING CLEAR SPACEPER ANSI TABLE 404.2.3.1
POCKET APPROACHPER ANSI TABLE 404.2.3.3
MAIN LEVEL
Provide enlarged planand interior elevationsof accessible lodgeunit fridge and storageareas withdimensions. Fridgeand storage must beaccessible (ICC/ANSIA117.1-2003 section1002.14). If this is akitchen, a worksurface is required per1002.12.
W/DW/D
RG
DW RG
DW
UP
UP
1'-6"
1'-5"1'-6"
1'-6"1'-6"
6'-111/2"
3'3'
DN
F
F
TOILET CLEAR SPACE PER ANSI 604.360" TURNING RADIUS INCLUDING KNEEAND TOE SPACE PER ANSI 304.3.1
CLEAR FLOOR SPACE PER ANSI 305.3SINK CLEAR SPACE PER ANSI 305.3
TOILET CLEAR SPACE PER ANSI 604.3
DOOR SWING CLEAR SPACEPER ANSI TABLE 404.2.3.1
60" TURNING RADIUS INCLUDING KNEEAND TOE SPACE PER ANSI 304.3.1SINK CLEAR SPACE PER ANSI 305.3
REFRIGERATOR CLEAR FLOOR SPACE PER ANSI 804.5.6
OVEN CLEAR FLOOR SPACE PER ANSI 804.5.5DISHWASHER CLEAR FLOOR SPACE PER ANSI 804.5.3SINK CLEAR FLOOR SPACE PER ANSI 305.3
WASHER/DRYER CLEAR SPACE PERANSI 611.2POCKET APPROACHPER ANSI TABLE 404.2.3.3DOOR SWING CLEAR SPACEPER ANSI TABLE 404.2.3.1DOOR SWING CLEAR SPACEPER ANSI TABLE 404.2.3.1
60" TURNING RADIUS INCLUDING KNEEAND TOE SPACE PER ANSI 304.3.1
REFRIGEPER ANS
DISHWASHER CLEAR FLOOR SPACE PER ANSI 804.5.3
DOOR STABLE 4
60" TURNING RADIUS INCLUDING KNEEAND TOE SPACE PER ANSI 304.3.1
DOOR SWING CLEAR SPACEPER ANSI TABLE 404.2.3.160" TURNING RADIUS INCLUDING KNEEAND TOE SPACE PER ANSI 304.3.1
60" TURNAND TOE
OPTION A
O
PROVIDE BLOCKING - FUTURE INSTALL
PROVID
PARK LEVEL 3/16"
Housekeeping 220shows the turnaroundand door clearanceoverlapping fixturesand built ins. Revise.
This has been updated.
These windows are not operable. This has
been updated in the window schedule on
A-606.
This has been updated.
Enlarged plans with interior elevations have
been provided on sheets A-021 - A-040.
The valet counter is a furniture piece.
Enlarged plans with interior elevations have been
provided on sheets A-021 - A-040. This is not a
kitchen. It is provided on sheet A-022.
City of Aspen
Received
7/10/17
Building Department
Page: A-018
File Name: Plan Set201701.pdf
Subject: PlanCheck
Author: nickt
Color:
Provide enlarged plans and
interior elevations with
dimensions of each accessible
facility, including the Type B unit
kitchens. Provide the dimensions
of the clear spaces, height of the
counter, width of space between
counter and opposing walls, etc
(demonstrate compliance with all
kitchen Type B accessibility
provisions).
Page: A-018
File Name: Plan Set201701.pdf
Subject: PlanCheck
Author: nickt
Color:
Type B Option A toilet in AHU 2
Powder must be 18" from the
side wall and 15" min from the
lavatory. (ICC/ANSI
A117.1-2003 section
1004.11.3.1.2)
Page: A-018
File Name: Plan Set201701.pdf
Subject: PlanCheck
Author: nickt
Color:
The lounge/bar restroom
lavatory accessible clearspace
must be for a forward approach.
(ICC/ANSI A117.1-2003 606.2)
Page: A-018
File Name: Plan Set201701.pdf
Subject: PlanCheck
Author: nickt
Color:
Provide enlarged plans and
interior elevations with
dimensions of each accessible
facility, including the bar. Provide
the dimensions of the clear
space, height and depth of the
counter. If the bar back is self
serve, it must comply as a
kitchenette. Provide all
dimensions for accessibility.
Page: A-018
File Name: Plan Set201701.pdf
Subject: PlanCheck
Author: nickt
Color:
Provide enlarged plans and
interior elevations with
dimensions of each accessible
facility, including the ski storage.
A portion must be accessible per
2009 IBC 1109.8.
UP
RG
DW RG
DW
DN
1'-6"
1'-5"1'-6"
3'-2"
3'
3'
3'
6'-111/2"
3'
F
F
DN
F
DW
F
4'-1/4"
3'
PACE PER ANSI 804.5.5LOOR SPACE PER ANSI 804.5.3ACE PER ANSI 305.3
DOOR SWING CLEAR SPACEPER ANSI TABLE 404.2.3.1DOOR SWING CLEAR SPACEPER ANSI TABLE 404.2.3.1
REFRIGERATOR CLEAR FLOOR SPACEPER ANSI 804.5.6
OVEN CLEAR FLOOR SPACE PER ANSI 804.5.5DISHWASHER CLEAR FLOOR SPACE PER ANSI 804.5.3
DOOR SWING CLEAR SPACE PER ANSITABLE 404.2.3.1
NCLUDING KNEE
SINK CLEAR FLOOR SPACE PER ANSI 305.3
60" TURNING RADIUS INCLUDING KNEEAND TOE SPACE PER ANSI 304.3.1
40" MIN CLEAR SPACE PER ANSI 804.2.1
60" TURNING RADIUS INCLUDING KNEEAND TOE SPACE PER ANSI 304.3.1CLEAR FLOOR SPACE PER ANSI 305.3
REFRIGERATOR CLEAR FLOOR SPACEPER ANSI 804.5.6REFRIGERATOR CLEAR FLOORSPACE PER ANSI 804.5.6
SINK CLEAR SPACE PER ANSI 305.3
DISHWASHER CLEAR FLOOR SPACEPER ANSI 804.5.3
DOOR SWING CLEAR SPACEPER ANSI TABLE 404.2.3.1
OPTION A
PROVIDE BLOCKING - FUTURE INSTALL
ELEV. PERANSI 407.4.1.B
STEVENWILSON402127
STATE LOR
LICENSEDARCHIT
STRUCTURAL
CONSULTANTS
SURVEYOR
MECHANICAL
CONTRACTOR
CIVIL
INTERIOR DESIGNER
1/26/17
Tuttle Surveying727 Blake AveGlenwood Springs, CO 81601(970) 928-9708jeff@tss-us.com
Roaring Fork Engineering0123 Emma Road, Suite 200bBasalt, CO 81621(970) 948-7474richardg@rfeng.biz
Architectural Engineering Consultants40801 US-6 #214Avon, CO 81620(970) 748-8520taylor@aec-vail.com
Madigan + CompanyPO Box 9682Aspen, CO 81612(970) 319-2232chris@madiganco.co
KL&A215 N. 12th Street, Unit ECarbondale, CO 81623(970) 927-5174mlyons@klaa.com
dg+a interiors5401 N Central Expressway, Suite 30Dallas, TX 75205(214) 522-6716, Ext 12donna@dgainteriors.com
Provide enlarged plansand interior elevationswith dimensions ofeach accessiblefacility, including theType B unit kitchens.Provide thedimensions of theclear spaces, height ofthe counter, width ofspace betweencounter and opposingwalls, etc(demonstratecompliance with allkitchen Type Baccessibilityprovisions).
1'-5"1'-6"
3'
3'
6'-111/2"
F
CE PER ANSI 604.3
R SPACE.2.3.1
S INCLUDING KNEER ANSI 304.3.1
PER ANSI 305.3
PER ANSI 804.5.6
OPTION A
PROVIDE BLOCKING - FUTURE INSTALL
DR
C
IN
Av(9tay
MaPOAs(9ch
dg54Da(2do
Type B Option A toilet
in AHU 2 Powder must
be 18" from the side
wall and 15" min fromthe lavatory.(ICC/ANSIA117.1-2003 section1004.11.3.1.2)
1'-6"1'-6"
3'-2"
3'
4'
3'
40
TOILET CLEAR SPACE PER ANSI 604.3
DOOR SWING CLEAR SPACEPER ANSI TABLE 404.2.3.1
60" TURNING RADIUS INCLUDING KNEEAND TOE SPACE PER ANSI 304.3.1
CLEAR FLOOR SPACE PER ANSI 305.3
SINK CLEAR SPACE PER ANSI 305.3
TOILET CLEAR SPACE PER ANSI 604.3
CLEAR FLOOR SPACE PER ANSI 305.3
DOOR SWING CLEAR SPACEPER ANSI TABLE 404.2.3.1
REPERESP
SI
DOOR SWING CLEAR SPACEPER ANSI TABLE 404.2.3.1DOOR SWING CLEAR SPACEPER ANSI TABLE 404.2.3.1
POCKET APPROACHPER ANSI TABLE 404.2.3.3
DIPE
The lounge/barrestroom lavatoryaccessible clearspacemust be for a forwardapproach. (ICC/ANSIA117.1-2003 606.2)
DW
4'-1/4"
40" MIN CLEAR SPACE PER ANSI 804.2.1
R ANSI 604.3
ACE1
CLUDING KNEESI 304.3.1
R ANSI 305.3
ANSI 305.3
R ANSI 604.3
R ANSI 305.3
ACE1
REFRIGERATOR CLEAR FLOOR SPACEPER ANSI 804.5.6REFRIGERATOR CLEAR FLOORSPACE PER ANSI 804.5.6
SINK CLEAR SPACE PER ANSI 305.3
3
DISHWASHER CLEAR FLOOR SPACEPER ANSI 804.5.3
STEVENWILSON402127
STATE OFCOLORADO
LICENSE CHITECT
200 South Aspen Aspen C81611
200 S Aspen
715 West Main Street, Suite 204Aspen, Colorado 81611P: 970.279.4157 F: 866.770.558
1/26/17
Provide enlarged plansand interior elevationswith dimensions ofeach accessiblefacility, including thebar. Provide thedimensions of theclear space, heightand depth of thecounter. If the barback is self serve, itmust comply as akitchenette. Provide alldimensions foraccessibility.
W/D
UP
W/D
RG
DW RG
DW
UP
UP
DN
1'-6"
1'-5"1'-6"
1'-6"1'-6"
1'-6"1'-6"
3'-2"
3'
3'
3'
3'
3'
6'-111/2"
3'3'
3'
4'
F
F
DN
F
DW
F
4'-1/4"
3'
TOILET CLEAR SPACE PER ANSI 604.360" TURNING RADIUS INCLUDING KNEEAND TOE SPACE PER ANSI 304.3.1
CLEAR FLOOR SPACE PER ANSI 305.3SINK CLEAR SPACE PER ANSI 305.3
REFRIGERATOR CLEAR FLOOR SPACE PER ANSI 804.5.6
OVEN CLEAR FLOOR SPACE PER ANSI 804.5.5DISHWASHER CLEAR FLOOR SPACE PER ANSI 804.5.3SINK CLEAR FLOOR SPACE PER ANSI 305.3
WASHER/DRYER CLEAR SPACE PERANSI 611.2
DOOR SWING CLEAR SPACEPER ANSI TABLE 404.2.3.1DOOR SWING CLEAR SPACEPER ANSI TABLE 404.2.3.1
POCKET APPROACHPER ANSI TABLE 404.2.3.3DOOR SWING CLEAR SPACEPER ANSI TABLE 404.2.3.1DOOR SWING CLEAR SPACEPER ANSI TABLE 404.2.3.1
60" TURNING RADIUS INCLUDING KNEEAND TOE SPACE PER ANSI 304.3.1 REFRIGERATOR CLEAR FLOOR SPACEPER ANSI 804.5.6
OVEN CLEAR FLOOR SPACE PER ANSI 804.5.5DISHWASHER CLEAR FLOOR SPACE PER ANSI 804.5.3
DOOR SWING CLEAR SPACE PER ANSITABLE 404.2.3.1
60" TURNING RADIUS INCLUDING KNEEAND TOE SPACE PER ANSI 304.3.1
SINK CLEAR FLOOR SPACE PER ANSI 305.3
60" TURNING RADIUS INCLUDING KNEEAND TOE SPACE PER ANSI 304.3.1
40" MIN CLEAR SPACE PER ANSI 804.2.1
TOILET CLEAR SPACE PER ANSI 604.3
DOOR SWING CLEAR SPACEPER ANSI TABLE 404.2.3.1
60" TURNING RADIUS INCLUDING KNEEAND TOE SPACE PER ANSI 304.3.1
CLEAR FLOOR SPACE PER ANSI 305.3SINK CLEAR SPACE PER ANSI 305.3
TOILET CLEAR SPACE PER ANSI 604.3
CLEAR FLOOR SPACE PER ANSI 305.3DOOR SWING CLEAR SPACEPER ANSI TABLE 404.2.3.1
60" TURNING RADIUS INCLUDING KNEEAND TOE SPACE PER ANSI 304.3.1CLEAR FLOOR SPACE PER ANSI 305.3
REFRIGERATOR CLEAR FLOOR SPACEPER ANSI 804.5.6REFRIGERATOR CLEAR FLOORSPACE PER ANSI 804.5.6
SINK CLEAR SPACE PER ANSI 305.3
DOOR SWING CLEAR SPACEPER ANSI TABLE 404.2.3.1DOOR SWING CLEAR SPACEPER ANSI TABLE 404.2.3.1
POCKET APPROACHPER ANSI TABLE 404.2.3.3
DISHWASHER CLEAR FLOOR SPACEPER ANSI 804.5.3
DOOR SWING CLEAR SPACEPER ANSI TABLE 404.2.3.1
OPTION A
OPTION A
PROVIDE BLOCKING - FUTURE INSTALL
PROVIDE BLOCKING - FUTURE INSTALL
ELEV. PERANSI 407.4.1.B
DRAWING SETS:
STEVENWILSON402127STATEOFCOLORADO
LICENSEDARCHITECT
STRUCTURAL
CONSULTANTSSURVEYOR
MECHANICAL
CONTRACTOR
CIVIL
INTERIOR DESIGNER
200 South Aspen Aspen CO81611
200 S Aspen
715 West Main Street, Suite 204Aspen, Colorado 81611P: 970.279.4157 F: 866.770.5585
1/26/17
Tuttle Surveying727 Blake AveGlenwood Springs, CO 81601(970) 928-9708jeff@tss-us.com
Roaring Fork Engineering0123 Emma Road, Suite 200bBasalt, CO 81621(970) 948-7474richardg@rfeng.biz
Architectural Engineering Consultants40801 US-6 #214Avon, CO 81620(970) 748-8520taylor@aec-vail.com
Madigan + CompanyPO Box 9682Aspen, CO 81612(970) 319-2232chris@madiganco.co
KL&A215 N. 12th Street, Unit ECarbondale, CO 81623(970) 927-5174mlyons@klaa.com
dg+a interiors5401 N Central Expressway, Suite 305Dallas, TX 75205(214) 522-6716, Ext 12donna@dgainteriors.com
Provide enlargedplans and interiorelevations withdimensions of eachaccessible facility,including the skistorage. A portionmust be accessibleper 2009 IBC 1109.8.
This has been updated.
These have been provided on sheets
A-016 through A-040. Type B kitchens
are shown on sheet A-024 through
A-027.
This has been updated and shown on
A-031.
These have been provided on sheets A-029
through A-030.
This has been provided on sheet A-028.
City of Aspen
Received
7/10/17
Building Department
Page: A-018
File Name: Plan Set201701.pdf
Subject: PlanCheck
Author: nickt
Color:
Double door 203B, 204 A/B to
the game lounge/bar restroom
must allow a 32" clear opening
when only one leaf is opened
(ICC/ANSI A117.1-2003
404.2.2).
Page: A-019
File Name: Plan Set201701.pdf
Subject: PlanCheck
Author: nickt
Color:
The residence 2 shower
compartment does not comply
as a Type B Option A shower.
The 30x48 clearspace may not
overlap a water closet and a
shower enclosure may not block
access to the controls from the
clearspace. Provide the
dimensions of the shower
compartment and dimension
blocking and shower control
locations.
Page: A-019
File Name: Plan Set201701.pdf
Subject: PlanCheck
Author: nickt
Color:
Provide enlarged plans and
interior elevations with
dimensions of each accessible
facility, including the Type B unit
kitchens. Provide the dimensions
of the clear spaces, height of the
counter, width of space between
counter and opposing walls, etc
(demonstrate compliance with all
kitchen Type B accessibility
provisions). The 40" width
requirement will be measured to
the furthest projection, including
protruding ranges and fridges.
You will be required to rip it out
and fix it at final inspection if it
exceeds 40" at any point. Please
make it explicitly clear on the
plans and show your fixtures
with actual real protrusions and
dimensions.
Page: A-020
File Name: Plan Set201701.pdf
Subject: PlanCheck
Author: nickt
Color:
The roof deck facilities must be
fully accessible as they serve
more than one residential unit
(2009 IBC 1109.14.1). Provide
enlarged plans and elevations of
the lift, kitchen, pool, and spa
with all dimensions necessary to
demonstrate compliance. Detail
the pool and spa lifts and how
they fit in the space with clear
spaces.
1'-6"1'-6"
4'
3'
40" MIN CLEAR SPACE PER ANSI 804.2.1
TOILET CLEAR SPACE PER ANSI 604.3
DOOR SWING CLEAR SPACEPER ANSI TABLE 404.2.3.1
60" TURNING RADIUS INCLUDING KNEEAND TOE SPACE PER ANSI 304.3.1
CLEAR FLOOR SPACE PER ANSI 305.3
SINK CLEAR SPACE PER ANSI 305.3
TOILET CLEAR SPACE PER ANSI 604.3
CLEAR FLOOR SPACE PER ANSI 305.3
DOOR SWING CLEAR SPACEPER ANSI TABLE 404.2.3.1
REFRIGERATOR CLEAR FLOOR SPACEPER ANSI 804.5.6REFRIGERATOR CLEAR FLOORSPACE PER ANSI 804.5.6
SINK CLEAR SPACE PER ANSI 305.3
POCKET APPROACHPER ANSI TABLE 404.2.3.3
DISHWASHER CLEAR FLOOR SPACEPER ANSI 804.5.3
Double door 203B,204 A/B to the gamelounge/bar restroommust allow a 32" clearopening when onlyone leaf is opened(ICC/ANSIA117.1-2003 404.2.2).
DN DN
1'-6"1'-6"
TOILET CLEAR SPACE PER ANSI 604.3
SINK CLEAR SPACE PER ANSI 305.3
40
POCKET APPROACHPER ANSI TABLE 404.2.3.3
S
R
OPTION A
PROVIDE BLOCKING - FUTURE INSTALL
The residence 2
shower compartmentdoes not comply as aType B Option A
shower. The 30x48clearspace may notoverlap a water closet
and a showerenclosure may notblock access to the
controls from the
clearspace. Providethe dimensions of theshower compartment
and dimensionblocking and showercontrol locations.
DN
UP
W/DW/D
F
DN
DW
1'-6"1'-6"
3'-5"
3'-71/8"
3'-2"
3'
F
DW
F
DW
7'-327/32"
3'-61/4"
3'-111/32"
3'-6"3'-6"
3'-61/4"
SPACE PER ANSI 804.2.1
40" MIN CLEAR SPACE PER ANSI 804.2.1REFRIGERATOR CLEAR FLOOR SPACE PER ANSI 804.5.6
SINK CLEAR FLOOR SPACE PER ANSI 305.3DISHWASHER CLEAR FLOOR SPACE PER ANSI 804.5.3
OVEN CLEAR FLOOR SPACE PER ANSI 804.5.5
DOOR SWING CLEAR SPACE PER ANSI TABLE 404.2.3.1
04.3.3
R CLEAR FLOOR SPACE PER ANSI 804.5.6
OOR SPACE PER ANSI 305.3
LOOR SPACE PER ANSI 804.5.5
CLEAR FLOOR SPACE PER ANSI 305.3
40" MIN CLEAR SPACE PER ANSI 804.2.1
PER ANSI 304.3.1
SINK CLEAR FLOOR SPACE PER ANSI 305.3
REFRIGERATOR CLEAR FLOOR SPACE PER ANSI 804.5.6
CLEAR FLOOR SPACE PER ANSI 804.5.3
OPTION A
STALL
DISHWASHER CLEAR FLOOR SPACE PER ANSI 804.5.3
ELEV. PERANSI 407.4.1.B
NUPPER LEVEL 3/16" = 1'-0"1 4 8 16
DRAWING SETS:NAMEPERMIT SUBMITTAL ID IS
STRUCTURAL
MECHANICAL
COPYRIGHT
CONTRACTOR
CIVIL
INTERIOR DESIGNER
PROJECT NO:DRAWN BY:LG, CF, ESFORUM PH
PARCEL ID # 273707337001LEGAL DESCRIPTIONCITY AND TOWNSITE OF ASPEN Block:Lot: Thru C
ZONE DISTRICT Mixed Use
1404
DATE OF PUBLICATION
A-019
UPPER LEVACCESIBILITY
Tuttle Surveying727 Blake AveGlenwood Springs, CO 81601(970) 928-9708jeff@tss-us.com
Roaring Fork Engineering0123 Emma Road, Suite 200bBasalt, CO 81621(970) 948-7474richardg@rfeng.biz
Architectural Engineering Consultants40801 US-6 #214Avon, CO 81620(970) 748-8520taylor@aec-vail.com
Madigan + CompanyPO Box 9682Aspen, CO 81612(970) 319-2232chris@madiganco.co
KL&A215 N. 12th Street, Unit ECarbondale, CO 81623(970) 927-5174mlyons@klaa.com
1/26/17
dg+a interiors5401 N Central Expressway, Suite 305Dallas, TX 75205(214) 522-6716, Ext 12donna@dgainteriors.com
Provide enlarged plans and interior elevationswith dimensions of each accessible facility,including the Type B unit kitchens. Provide thedimensions of the clear spaces, height of thecounter, width of space between counter andopposing walls, etc (demonstrate compliance withall kitchen Type B accessibility provisions). The40" width requirement will be measured to thefurthest projection, including protruding rangesand fridges. You will be required to rip it out andfix it at final inspection if it exceeds 40" at anypoint. Please make it explicitly clear on the plansand show your fixtures with actual realprotrusions and dimensions.
DN
3'-5"3'-5"
3'-5"
3'-2"
F
F
UP
F
F
60" MIN CLEAR SPACE PER ANSI 804.2.1
CLEAR FLOOR SPACE PER ANSI 305.3
DOOR SWING CLEAR SPACE PER ANSI TABLE 404.2.3.1SINK CLEAR FLOOR SPACE PER ANSI 305.3
CLEAR FLOOR SPACE PER ANSI 410.2.1
PORTABLE POOL LIFT PERICC A117.1 SECTION 1109.2
PORTABLE POOL LIFT PERICC A117.1 SECTION 1109.2
REFRIGERATOR CLEAR FLOOR SPACE PER ANSI 804.5.6
REFRIGERATOR CLEAR FLOOR SPACE PER ANSI 804.5.6REFRIGERATOR CLEAR FLOOR SPACE PER ANSI 804.5.6REFRIGERATOR CLEAR FLOOR SPACE PER ANSI 804.5.6
ELEV. PERANSI 407.4.1.B
DRAWING SETS:NAMEPERMIT SUBMITTAL ID
STEVENWILSON402127
STATEOFCOLORA
LICENSEDARCHITE
STRUCTURAL
CONSULTANTSSURVEYOR
MECHANICAL
CONTRACTOR
CIVIL
INTERIOR DESIGNER
200 South Aspen As81611
200 S Asp
1/26/17
Tuttle Surveying727 Blake AveGlenwood Springs, CO 81601(970) 928-9708jeff@tss-us.com
Roaring Fork Engineering0123 Emma Road, Suite 200bBasalt, CO 81621(970) 948-7474richardg@rfeng.biz
Architectural Engineering Consultants40801 US-6 #214Avon, CO 81620(970) 748-8520taylor@aec-vail.com
Madigan + CompanyPO Box 9682Aspen, CO 81612(970) 319-2232chris@madiganco.co
KL&A215 N. 12th Street, Unit ECarbondale, CO 81623(970) 927-5174mlyons@klaa.com
dg+a interiors5401 N Central Expressway, Suite 305Dallas, TX 75205(214) 522-6716, Ext 12donna@dgainteriors.com
The roof deck facilitiesmust be fullyaccessible as theyserve more than oneresidential unit (2009IBC 1109.14.1).Provide enlargedplans and elevationsof the lift, kitchen,pool, and spa with alldimensions necessaryto demonstratecompliance. Detail thepool and spa lifts andhow they fit in thespace with clearspaces.
This has been updated to be a one leaf
sliding door to provide for the 32" clear
opening.
This has been revised and shown on sheet
A-037.
This has been provided on sheets A-032,
A-033 and A-035. We will maintain the 40"
width requirement.
This has been provided on sheets A-038
through A-040.
City of Aspen
Received
7/10/17
Building Department
Page: A-021
File Name: Plan Set201701.pdf
Subject: PlanCheck
Author: nickt
Color:
The employee restroom control
location cannot be more than 27"
from the seat wall (measured
from the wall, not the seat).
ICC/ANSI A117.1-2003 section
608.5.2
Page: A-021
File Name: Plan Set201701.pdf
Subject: PlanCheck
Author: nickt
Color:
The employee restroom shower
enclosure door must not obstruct
controls or transfer onto the seat
(ICC/ANSI A117.1-2003 section
608.8).
Page: A-023
File Name: Plan Set201701.pdf
Subject: PlanCheck
Author: nickt
Color:
Note the blocking requirement
where you have dashes in the
interior elevations for the Type
B accessible units.
Page: A-025
File Name: Plan Set201701.pdf
Subject: PlanCheck
Author: nickt
Color:
Provide all Type B accessible
dimensions for the residence 1
bathroom on both the drawings
provided and additional enlarged
plans and interior elevations of
the lavatory. Show and
dimension all clear spaces,
blocking locations, and tub
dimensions.
Page: A-026
File Name: Plan Set201701.pdf
Subject: PlanCheck
Author: nickt
Color:
Provide all Type B accessible
dimensions for the residence 1
bathroom on both the drawings
provided and additional enlarged
plans and interior elevations of
the lavatory. Show and
dimension all clear spaces,
blocking locations, and tub
dimensions.
30" MIN4" MAX
38" MIN
48" MAX
6" MAX 1'-8"
10"
16"
36" MAX
3" MIN18" MIN
FOLDING SEAT
CL
SHOWER DIMSPER ANSI 608
40"6" MAX
38" MIN
16" MIN 27" MAX
36" MAX
1'-4"
3" MIN18" MIN
FOLDING SEAT
CL
SHOWER DIMSPER ANSI 608
4 EMPLOYEE RR E5EMPLOYEE RR N
The employeerestroom controllocation cannot bemore than 27" fromthe seat wall(measured from thewall, not the seat).ICC/ANSIA117.1-2003 section608.5.2
36" MAX
12" MAX 42" MIN
3'-3"
16"
36" MAXFOLDING SEAT
3'36" MIN 6"
40" MAX
34" MAX
36" MAX
007B
1A-0212A-0213A-021
4A-021
5A-021
EMPLOYEE RR008
B10'-6"FLAT
1 EMPLOYEE RR N2EMPLOYEE RR W 1/2" = 1'-0"EMPLOYEE RR S
006 EMPLOYEE RR PLAN 1/2" = 1'-0"006 EMPLOYEE RR RCP 1/2" = 1'-0"
DRAWING SETS:
NAMEPERMIT SUBMITTAL
COPYRIGHT
CONTRACTOR
INTERIOR DESIGN
PROJECT NO:
DRAWN BY:
PARCEL ID # 2737073370LEGAL DESCRIPTIONCITY AND TOWNSITE OFLot: Thru C
ZONE DISTRICT Mixed Us
DATE OF PUBLICATION
A-0
ACCESELEVA
Madigan + CompanyPO Box 9682Aspen, CO 81612(970) 319-2232chris@madiganco.co
dg+a interiors5401 N Central ExpresswaDallas, TX 75205(214) 522-6716, Ext 12donna@dgainteriors.com
The employeerestroom showerenclosure door mustnot obstruct controlsor transfer onto theseat (ICC/ANSIA117.1-2003 section608.8).
A
8'-6"FLAT
34" MAX
20" MAX
40" MAX
34" MAX
9"2'-3"6"1'-3"
2'-9"
6"
1'-9"
34" MAX
20" MAX3'-6"263/64"
2'-9"
6"
7F
34" MAX
3"3'-6"
40" MAX
2'-9"
6"
1'-3"6"2'-3"9"
2'-9"
6"
1'-9"
34" MAX
20" MAX
211 AH 1 POWDER RCP 1/2" = 1 AH 1 POWDER N 1/2" = 1'-0"2 AH 1 POWDER W3AH 1 POWDER S 1/2" = 1'-0"4 AH 1 POWDER E
212-214 AH 1 AH 2 POWDER N2AH 2 POWDER W1/2" = 1'-0"3 AH 2 POWDER S4AH 2 POWDER E1/2" = 1'-0"
Note the blockingrequirement where youhave dashes in theinterior elevations forthe Type B accessibleunits.
Provide all Type B accessible dimensions for the residence 1bathroom on both the drawings provided and additional enlargedplans and interior elevations of the lavatory. Show and dimension allclear spaces, blocking locations, and tub dimensions.
Provide all Type B accessible dimensions for the residence 1bathroom on both the drawings provided and additional enlargedplans and interior elevations of the lavatory. Show and dimension allclear spaces, blocking locations, and tub dimensions.
This has been updated on sheets A-025,
A-027, A-034 and A-037.
This has been revised and shown on A-021.
This has been revised and shown on A-021.
This has been provided and shown on
A-034.
This has been provided and shown on
A-037.
City of Aspen
Received
7/10/17
Building Department
Page: A-102
File Name: Plan Set201701.pdf
Subject: PlanCheck
Author: nickt
Color:
Van accessible space must be
11' wide or have an 8' access
aisle (ICC/ANSI A117.1-2003
section 502.2).
Page: A-104
File Name: Plan Set201701.pdf
Subject: PlanCheck
Author: nickt
Color:
Provide a seating plan for the
game lounge/bar, delineate exit
access pathways between tables
and chairs. Show accessible
seating locations in accordance
with 2009 IBC 1108.2.9.
Calculate your occupant load
based on the seating plan.
Page: A-104
File Name: Plan Set201701.pdf
Subject: PlanCheck
Author: nickt
Color:
Door 203A to the game
lounge/bar must have at least
one leaf that when open on its
own provides 32" clear opening.
(ICC/ANSI A117.1-2003 404.2.1)
Page: A-105
File Name: Plan Set201701.pdf
Subject: PlanCheck
Author: nickt
Color:
Detail how you will maintain the
1 hour dwelling separation fire
rating at the dumbwaiter and
provide sheet A-419. The
provided dumbwaiter spec does
not discuss fire rating.
Page: A-301
File Name: Plan Set201701.pdf
Subject: PlanCheck
Author: nickt
Color:
Provide a detail of F-4 (called
out on A-301 above the open to
the exterior garage 217). Detail
21/A-510 suggests it has no
insulation. Account for any
thermal bridging at detail
21/A-510 in COMcheck.
002A
018B
018A
34'-81/2"6"5'-11/2"1'
6"5'-71/4"6"
6
8'-6"8'-6"8'-6"5'
18'
LOBBY 2002
LOBBY 1001
E1A-407
1
15/8"
9'-53/4"
6"
14'-11"
6"
VAN ACCESSIBLE
151515 14
Van accessible spacemust be 11' wide or
have an 8' accessaisle (ICC/ANSI
A117.1-2003 section502.2).
R
5
101/4"15/8"8"15/8"14'-8"15/8"
15/8"
8"
15/8"
11'-41/2"
6"
21'-107/8"
4'-101/4"
Provide a seating plan for the game
lounge/bar, delineate exit access
pathways between tables and chairs.
Show accessible seating locations in
accordance with 2009 IBC 1108.2.9.
Calculate your occupant load based on
the seating plan.
204A204B
203B
203A
SA-4
11/4"35/8"1'-111/2"35/8"11/4"
HALL 2205
ET
WATER CLOSET WATER CLOSET
ATH
GAME LOUNGE / BAR RR204
GAME LOUNGE/ BAR203
207A
1'-7"
6"
7'-37/8"
6"
5'-117/8"
/4"35/8"1'6"16'-27/8"35/8"2'-2"35/8"15'-101/4"
6"5'-11/4"35/8"5'-43/8"35/8"5'-11/4"6"1'-91/4"35/8"6'-105/8"6"
1'5'-31/2"
35/8"3'-11/8"
15/8"
6'-43/8"
15/8"
8"
15/8"
11'-41/2"
6"35/8"4'-41/2"16'-23/8"
6"
5'-117/8"
9'-1/2"
3'-
25'-7"15/8"103/8"15/8"8'-13/4
31
36
Door 203A to thegame lounge/bar musthave at least one leafthat when open on itsown provides 32" clearopening. (ICC/ANSIA117.1-2003 404.2.1)
2728
293031323334353637383940414243444546474849505152535455
GUARDRAIL PER IRC 312, MIN HEIGHT 34"GUARDRAIL PER IBC 1012, MIN HEIGHT 42"
HANDRAIL PER IRC 312, MIN HEIGHT 34"HANDRAIL PER IBC 1012, MIN HEIGHT 42"GAS FIREPLACE APPLIANCEDRYER FLUE VENTEXHAUST FLUE VENT
FRESH AIR INTAKESEWAGE EJECTOR ACCESS LOCATIONBOILER FLUESBUILT IN MILLWORKOMIT
ROOF MEMBRANE
METAL FACIAMETAL CAPMETAL RAILINGVERTICAL WOOD SIDINGHORIZONTAL WOOD SIDING
BRICK VENEER
WOOD W/IN 6" OF GRADE TO BE NATURALLY DURABLEOR PRESERVATIVE-TREATED PER IBC 2304.11.2.6OMITOMITHOSE BIBB
OMITFLAT ROOF, SLOPED 1/4" PER 1' FOR DRAINAGESNOW FENCEDOWNSPOUTGUTTER
STANDING SEAM METAL ROOFING
DRAWING SETS:NAMEPERMIT SUBMITTAL
STEWIL402
STATEOF
LICENSED
STRUCTURAL
CONSULTANTSSURVEYOR
MECHANICAL
COPYRIGHT
CONTRACTOR
CIVIL
INTERIOR DESIGNE
PROJECT NO:DRAWN BY:
PARCEL ID # 27370733700LEGAL DESCRIPTION
1/2
CITY AND TOWNSITE OF ALot: Thru C
ZONE DISTRICT Mixed Use
DATE OF PUBLICATION
Tuttle Surveying727 Blake AveGlenwood Springs, CO 816(970) 928-9708jeff@tss-us.com
Roaring Fork Engineering0123 Emma Road, Suite 20Basalt, CO 81621(970) 948-7474richardg@rfeng.biz
Architectural Engineering C40801 US-6 #214Avon, CO 81620(970) 748-8520taylor@aec-vail.com
Madigan + CompanyPO Box 9682Aspen, CO 81612(970) 319-2232chris@madiganco.co
KL&A215 N. 12th Street, Unit ECarbondale, CO 81623(970) 927-5174mlyons@klaa.com
dg+a interiors5401 N Central ExpresswayDallas, TX 75205(214) 522-6716, Ext 12donna@dgainteriors.com
PROPOSE
DN
UP
W/DW/D
F
313A
322BC 322A
310C
310B
312
311
307A
302A 303A
309A
DW
F9A-417
F8A-416
3A-203
320C 320B 320A321A321B
83'-6"
5'-63/8"
3'-21/8"
4'-11/2"
14'-111/2"
13'-43/4"
7'-51/8"
6'-111/2"
13'
8"4'-103/8"6"
6'-95/8"
8"
14'-31/2"
6"
12'-43/4"
6"
7'-51/8"
6"
6'-51/2"
6"
67/8"
10'-105/
5'-55/16"
2'-95/8"
3'-77/8"
6'-23/8"
6'-23/8"
6'-33/4"
7'-113/4"
4'-5/8"
3'-117/8"
15'-41/4"8'-51/4"12'-23/4"17'-81/8"8'-25/8"14'-41/4"6"8'-51/4"8"10'-103/4"8"17'-1/8"8"7'-85/8"6"4'-61/4"3'-23/8"10'-83/8"6'-33/4"5'-53/8"5'-53/8"4'-93/8"3'-77/8"3/4"8'-101/2"
14'-41/4"35/8"
15/8"41/4"
6"4'-3"
6"
14'-2"6"4'-91/4"35/8"1'-43/4"35/8"8'-11/2"8"21'-8"
7"
7'-7"
15/8"
7'-93/8"
35/8"
14'-107/8"
SLAB = 121'
T.O. SLAB = 120'-9"
2
2
2
24
44
DECKDECK
HALL 3307
RESIDENCE 2 KITCHEN310
RESIDENCE 2 DINING312
RESIDENCE 2 CLOSET316
STAIR 1309
ELEV308
RESIDENCE 2 SITTING311
RESIDENCE 1 ENTRY302
DECK
RESIDENCE 1 BEDROOM303
RESIDENCE 2 BEDROOM313
F
DW
F
DW 314B
314A
314C
315 D
E
C
F
G
CA-303
DA-304
B
A
307B
317A
317B
317C
317D
316
319D 319C 319B 319A318
E1A-407
DW1A-418
17'-63/8"6"7'-71/2"1'5'-9"1'18'-45/8"
15'-61/4"
6"3'-41/4"15/8"3'-83/4"
15/8"3'-83/8"
1'
7'-101/4"
1'
4'-71/8"6"
6'-5/8"
35/8"
25'-115/8"35/8"1'-1/2"35/8"12'-15/8"6'-9"17'-63/4"
"26'-75/8"15/8"1'-117/8"43/8"15/8"2'-11/2"26'-6"
11'-5/8"
15/8"3'-31/4"15/8"2'-1"6"5'-6"6"3'-1/2"15/8"
3'-73/8"15/8"47/8"15/8"
7'-51/4"
35/8"
7'-93/8"
15/8"
7'-7"
6"
2'-61/4"15/8"2'-63/4"6"
7'-3/4"
15/8"4'-103/8"
6"
6'-5/8"
8"
16'-23/4"6"95/8"6"1'-11"15/8"17'-101/2"6"4'-4"35/8"6'-51/4"35/8"6'-103/8"6"
27'-5/8"
91/4"
8'-97/8"
35/8"4'-67/8"
6"
51/16"15/8"
16'-11/4"35/8"8'-79/16"3'-21/16"7'-17/8"35/8"2'-77/8"15/8"
24
31
31
37
37
37
37
37
37
42
42
42
42
42
422
27
27
51
44
RANGE HOOD
RESIDENCE 1 LIVING/KITCHEN301
RESIDENCE 2 BAR317
Detail how you willmaintain the 1 hourdwelling separationfire rating at thedumbwaiter andprovide sheet A-419.The provideddumbwaiter spec doesnot discuss fire rating.
10111213141516171819202122232425
26
27
28
29
303132333435363738394041424344454647484950
51
52
53
5455
HOT TUBS, POOLS, WA5.mOMITENERGY EFFICIENT & EQUIPMENT PER 26.57DRAINAGE & STORMW26.575.020.E.5.LPAINTED LINE FOR PAWHEEL STOPOMITOMITOMITOMIT
LIGHT WELL FOR LIGHWINDOW WELL PANELREQUIRE NO MORE THEGRESS SILL 32" AFF PATIO, SNOWMELT PEDECK, SNOWMELTED,DRAINAGEOMIT
OMIT
GUARDRAIL PER IRC 3
GUARDRAIL PER IBC 1
HANDRAIL PER IRC 31
HANDRAIL PER IBC 10
GAS FIREPLACE APPLDRYER FLUE VENTEXHAUST FLUE VENTFRESH AIR INTAKESEWAGE EJECTOR ACBOILER FLUESBUILT IN MILLWORKOMIT
ROOF MEMBRANE
METAL FACIA
METAL CAP
METAL RAILING
VERTICAL WOOD SIDIN
HORIZONTAL WOOD S
BRICK VENEER
WOOD W/IN 6" OF GRAOR PRESERVATIVE-TR
OMITOMITHOSE BIBB
OMITFLAT ROOF, SLOPED 1SNOW FENCEDOWNSPOUTGUTTER
STANDING SEAM META
E D C B A
SETBACK LINE PROPERTY LINE@ SOUTH
DROPPED STRUCTURET.O. SLAB = 109'-4 1/2"110'-6"T.O. SLAB @ PARK LEVEL
135'-4"T.O. SLAB @ UPPER ROOF DECK
121'-0"T.O. SLAB @ SOUTH PENTHOUSE
131'-2 1/2"T.O. SLAB @ LOWER ROOF DECK
145'-4"T.O. ROOF
DROPPED STRUCTURET.O. SLAB = 120'-9"
R-1
R-3
2
6
5252
51
28
2851
33
R-6F-4
F-5
W-44 W-25
W-25
W-41 W-41
W-44
R-4
RESIDENCE 2 BEDROOM313HEN
HALL 2205
RESIDENCE 2CLOSET316 DECK
LODGE 9 BATH223 GARAGE217LODGE9 BED222
36A-513
22A-510
10
34A-512 34A-512
21A-510
9A-508
33A-512 32A-512
4 31
W-25
W-25
W-41 W-41
W-44
Provide a detail of F-4(called out on A-301above the open to theexterior garage 217).Detail 21/A-510suggests it has noinsulation. Account forany thermal bridgingat detail 21/A-510 inCOMcheck.
This has been updated and provided on
sheet A-016 and A-101.
This door size has been updated and will
provide a 32" clear opening.
Seating plan has been added on A-013. Exit pathways
have been adjusted around the furniture. Per 1108.2.9,
all furniture must be accessible. Occupant load was
adjusted based on third party reviewer comment
regarding A-2 occupancy as 97 occupants, which is
more restrictive.
The shaft and the doors will be 1 hour rated.
This has been noted on the details on sheet
A-409. Please note that the Zoning Dept
has requested we remove the opening from
Res 1. So, the dumbwaiter is now
accessible from Res 2 only.
Thermal bridging has been accounted for on
the revised COMcheck. This particular
location does have insulation. The graphic
representation has been corrected.
City of Aspen
Received
7/10/17
Building Department
Page: A-406
File Name: Plan Set201701.pdf
Subject: PlanCheck
Author: nickt
Color:
Roof top deck stair handrails
must have extensions.
Page: A-411
File Name: Plan Set201701.pdf
Subject: PlanCheck
Author: nickt
Color:
Verify 98" headroom at garage
door header
Page: A-501
File Name: Plan Set201701.pdf
Subject: PlanCheck
Author: nickt
Color:
Print all fire rated assemblies on
the plans, including IBC 720 and
721 assemblies.
W-21, W-26, W-43, W-44, W-45,
and W-46 all reference the
concrete assemblies section of
IBC 721 but these are all steel
stud walls. F-3 references
721.2.1.1 which is for walls only,
not floor/ceilings.
Choose other assemblies and
print the assemblies on the
plans.
Page: A-502
File Name: Plan Set201701.pdf
Subject: PlanCheck
Author: nickt
Color:
Dwelling separation walls (walls
that separate dwellings other
dwellings, other occupancies,
other rooms and hallways, etc)
must have a listed STC rating of
50 or greater.
Dwelling separation floors and
ceilings must have both an STC
and IIC rating of 50 or greater.
Provide listed and tested
assemblies at each situation.
(2009 IBC 1207)
Page: A-508
File Name: Plan Set201701.pdf
Subject: PlanCheck
Author: nickt
Color:
Detail 9/A-508 shows a thermal
break from Garage 217 to the
interior. Account for this and any
other areas like it in COMcheck
but entering a portion of roof or
wall with zero insulation.
11"
61/8"
3'-0"
3'-0"HANDRAIL PER IRC 311
131'-2 1/2"T.O. SLAB @ LOWER ROOF DECK
135'-4"T.O. SLAB @ UPPER ROOF DECK135'-4"T.O. SLAB @ UPPER ROOF DECK
131'-2 1/2"T.O. SLAB @ LOWER ROOF DECK
GUARDRAIL PER IRC 312
Roof top deck stairhandrails must haveextensions.
121'-0"T.O. SLAB @ NORTH PENTHOUSE
110'-6"T.O. SLAB @ PARK LEVEL
5"
8'-6"
8"
111/8"
Verify 98" headroom atgarage door header
NON RATEDD
Print all fire rated assemblies on the plans, includingIBC 720 and 721 assemblies.
W-21, W-26, W-43, W-44, W-45, and W-46 all
reference the concrete assemblies section of IBC 721
but these are all steel stud walls. F-3 references721.2.1.1 which is for walls only, not floor/ceilings.
Choose other assemblies and print the assemblies
on the plans.
Dwelling separation walls (walls that separate
dwellings other dwellings, other occupancies,
other rooms and hallways, etc) must have a
listed STC rating of 50 or greater.
Dwelling separation floors and ceilings must
have both an STC and IIC rating of 50 or
greater.
Provide listed and tested assemblies at each
situation.
(2009 IBC 1207)
F-3A-502FINISHED FLOORPER PLANS
110'-6"T.O. SLAB @ PARK LEVEL
METAL FLASHING
BEAM BEYOND
CONDITIONEDSPACE EXTERIOR
SLOPE PERPLANS
F-5A-502
W-25A-501
DECK SUPPORT ANGLE
DOOR STOP
1 1/2-2" THICK 18"X36" STONEPAVERS. RUNNING BOND PATTERN.PER LANDSCAPE
LIGHT GUAGE METAL RUNNER
NON SHRINK GROUT
Detail 9/A-508 showsa thermal break fromGarage 217 to theinterior. Account forthis and any otherareas like it in
COMcheck but
entering a portion of
roof or wall with zero
insulation.
This has been updated.
This has been noted in Section B on A-302,
as well as the car lift detail on sheet A-411.
This has been updated in the COMcheck.
Charts for IBC 720 and 721 are on Sheet
A-009.
W-21, 26, 43, 45 and 46 all reference table
721.2.1.4(2), gyp board thicknesses.
F-3 - this reference has been updated.
Dwelling separation walls - listed assembly has
been provided (U425) and testing report has
been provided. (W-43 and W-44 on A-502)
Dwelling separation floors and ceilings - F-3 has
been updated and testing report has been
provided. (F-3 is now on A-503)
City of Aspen
Received
7/10/17
Building Department
Page: A-510
File Name: Plan Set201701.pdf
Subject: PlanCheck
Author: nickt
Color:
Details 18, 19, 22, and 23 on
A-510 show thermal bridges.
Account for them in COMcheck.
Page: CVR
File Name: Plan Set201701.pdf
Subject: PlanCheck
Author: nickt
Color:
Provide the original copy of a
state demo license (not the
approved application form but
the license).
Page: GX-002
File Name: Plan Set201701.pdf
Subject: PlanCheck
Author: nickt
Color:
GSHP plans say not for
construction. Revise. Submitted
plans may not be conceptual.
Page: LIGHT-100
File Name: Plan Set201701.pdf
Subject: PlanCheck
Author: nickt
Color:
Provide an exterior lighting
COMcheck
Page: LIGHT-102
File Name: Plan Set201701.pdf
Subject: PlanCheck
Author: nickt
Color:
You have provided two interior
lighting COMchecks. One is
labeled hotel only, the other is
labeled entire building. Both
show only 'hotel' as an area
category. Submit only one
COMcheck for all interior lighting
for the entire building. The
insides of dwelling and sleeping
units are exempt per 2009 IECC
505.1 but 50% of lamps must be
high efficacy (note that on
plans). For both interior and
exterior comchecks, provide cut
sheets for all light fixture types.
Highlight the maximum fixture
wattage on the cut sheet; it must
match the comcheck. Also
highlight the nationally
recognized testing lab listing on
each cut sheet.
F-5A-502
RIGID INSULATION BOARDCOMPACT FILLLINE OF TEMPORARY SHORING
19
CONDITIONEDSPACE
EXTERIOR
SLOPE PERPLANS
W-1A-501
LIGHT GUAGE METALRUNNER CHANNEL
GROUT JOINTS SOLID
DECK SUPPORT ANGLE
1 1/2-2" THICK 18"X36" STONEPAVERS. RUNNING BOND PATTERN.PER LANDSCAPE
ON GRADE PER LANDSCAPE PLANS5" (MIN) CONCRETE SLAB WITHSNOWMELTED TUBING ANDWELDED WIRE FABRIC
4" COMPACTED ROAD BASE, CLASS6, PER CIVIL
PROVIDE CONTROL JOINT ATASSEMBLY SEPARATIONR-5A-502 F-3A-502 FINISHED FLOORPER PLANS121'-0"T.O. SLAB @ NORTH PENTHOUSE
LIGHT GUAGE METAL RUNNERCHANNEL
INSULATE BEAM
METAL FLASHING
20
EXTERIOR
CONDITIONEDSPACE
CONDITIONEDSPACE
SLOPE PERPLANS
W-25A-501
F-3A-502 F-4A-502 FINISHED FLOORPER PLANS121'-0"T.O. SLAB @ SOUTH PENTHOUSE
INSULATE BEAMLIGHT GUAGE METAL RUNNERCHANNEL
21
CONDITIONEDSPACE EXTERIOR
CONDITIONEDSPACE
W-25A-501
DECK SUPPORT ANGLE
R-6A-502F-4A-502
121'-0"T.O. SLAB @ NORTH PENTHOUSE LIGHT GUAGE METAL RUNNERCHANNEL
INSULATE BEAM
FLEX FLASHING
WINDOW PER SCHEDULE
METAL FLASHINGFOAM BACKER ROD AND SEALANTFINISHED FLOORPER PLANS
22
EXTERIOR
SLOPE PERPLANSCONDITIONEDSPACE EXTERIOR
F-3A-502 F-5A-502FINISHED FLOOR PER PLANS110'-6"T.O. SLAB @ PARK LEVEL METAL FLASHING
18
EXTERIORCONDITIONEDSPACE
CONDITIONEDSPACE
W-22A-501
DECK SUPPORT ANGLE
DOOR STOP1 1/2-2" THICK 18"X36" STONEPAVERS. RUNNING BOND PATTERN.PER LANDSCAPE
NON SHRINK GROUT
R-6A-502F-4A-502
LIGHT GUAGE METAL RUNNERCHANNEL
FLEX FLASHING
WINDOW PER SCHEDULE
METAL FLASHING
FOAM BACKER ROD AND SEALANT121'-0"T.O. SLAB @ SOUTH PENTHOUSE
23
SLOPE PERPLANSCONDITIONEDSPACE EXTERIOR
19 1" = 1'-0"20 1" = 1'-0"
21 1" = 1'-22 1" = 1'-0"
18 1" = 1'-
23 1" = 1'-0"
Details 18, 19, 22, and23 on A-510 showthermal bridges.Account for them inCOMcheck.
Provide the original copy
of a state demo license
(not the approved
application form but the
license).
6 HEADER MANIFOLD DETAIL
NOT TO SCALE
GSHP plans say not
for construction.Revise. Submittedplans may not beconceptual.
Provide an exterior
lighting COMcheck
You have provided two interior lighting COMchecks.
One is labeled hotel only, the other is labeled entirebuilding. Both show only 'hotel' as an area category.
Submit only one COMcheck for all interior lighting for
the entire building. The insides of dwelling and
sleeping units are exempt per 2009 IECC 505.1 but
50% of lamps must be high efficacy (note that onplans). For both interior and exterior comchecks,
provide cut sheets for all light fixture types. Highlightthe maximum fixture wattage on the cut sheet; it must
match the comcheck. Also highlight the nationallyrecognized testing lab listing on each cut sheet.
This was hand delivered to Denis by Chris
Madigan. Garrett has record of this.
This has been updated.
This has been updated in the COMcheck.
This was provided on sheet 3-4 in the
comcheck document.
You can disregard the hotel only Comcheck.
The whole building comcheck has be
provided again for clarity with this submittal.
100% of the lamps are high efficacy. In
addition, the lighting specs have been
provided again but with all wattage and lab
testing information circled.
City of Aspen
Received
7/10/17
Building Department
Page: S-001
File Name: Plan Set201701.pdf
Subject: PlanCheck
Author: nickt
Color:
The special inspection
agreement must be signed by a
special inspector and by an
inspected fabricator. Myers may
inspect their own work only for
work done in their shop. Items
that require special inspection by
third party inspector include field
welds, high strength bolting, and
expansion/epoxy anchors.
Page: S-001
File Name: Plan Set201701.pdf
Subject: PlanCheck
Author: nickt
Color:
Provide a special inspection
program listing all items needing
special inspection and noting
periodic vs continuous
inspection per the agreement.
STRUCTURAL DESIGN CRITERIA
The special inspection agreement must be
signed by a special inspector and by an
inspected fabricator. Myers may inspect their
own work only for work done in their shop.
Items that require special inspection by third
party inspector include field welds, high
strength bolting, and expansion/epoxy
anchors.
undations consist of
crete slabs onmes and ordinary
ed by a specialty
is responsible forwell as for all
wings on the
project withoutnts.cies, omissions,ttention of theed before affected
Wind Loading
Basic Wind Speed
Exposure Category
GCpi
Wind Base Shear
Wind Design Pressure Componen
East/West
North/South
Local Jurisdiction: City of Aspen
Building Code: 2015 International B
Interior Roof Zone (Zone 1)
STRUCT
Risk Category: II
SPECIAL INSPECTION1. Special inspection and testing shall be performed as required by the local jurisdiction, thebuilding code and the construction documents. See quality assurance section of the generalnotes.2. Coordinate and schedule inspection and testing prior to the start of work requiringinspection and testing while providing special inspection reasonable notice.3. All deficiencies shall be corrected for acceptance by the testing agency.4. Inspections performed by the local jurisdiction do not replace inspection or testing requiredby the owners testing agency.5. Special inspection and testing is required for the items shown in the special inspections andtesting table.
SUBMITTALS1. See Material sections of these General Notes for required shop drawings.2. Submit one (1) copy of the required information (Manufacturers Data, Shop Drawings, etc)via electronic media (PDF or similar).3. Reproducible copies of contract documents shall not be used.4. Submittals shall be sent directly to the Architect for review and distribution.5. Submittals shall be reviewed by Contractor and Subcontractor prior to submission.
Provide a specialinspection programlisting all itemsneeding specialinspection and notingperiodic vs continuousinspection per theagreement.
This has been signed and provided.
This has been provided.
City of Aspen
Received
7/10/17
Building Department