HomeMy WebLinkAboutFile Documents.200 S Aspen St.0007.2017 (28).ACBKMarkup Summary RevisedPlan Set.2017.04 5-19-2017 Page Label: B-02 Author: mikeh Date: 5/17/2017 9:47:34 AM File Name: RevisedPlan Set.2017.04.pdf A cut greater than 4' in height is proposed near the north east corner of the shoring system according to the profile. Section B-B depicts excavation extending almost to the property line, which is well into the dripline of the existing trees. Preserving these trees is a requirement of the development and no excavation will be allowed beyond the building limits. Please adjust plans. RevisedPlan Set.2017.04.pdf (26) Page Label: B-03 Author: mikeh Date: 5/17/2017 1:21:40 PM File Name: RevisedPlan Set.2017.04.pdf No excavation is allowed on the north side of the building in order to preserve the existing trees. Please adjust the plans. Page Label: B-03 Author: mikeh Date: 5/17/2017 9:52:45 AM File Name: RevisedPlan Set.2017.04.pdf Excavation is not allowed within the alley ROW. Please adjust plans to eliminate any excavation within alley ROW. Page Label: B-03 Author: mikeh Date: 5/17/2017 10:28:57 AM File Name: RevisedPlan Set.2017.04.pdf Excavation extends into the park. Permission from City of Aspen Parks Department must be obtained and provided in a written letter or excavation must be contained within the property limits. Please obtain permission or adjust the design. Page Label: C-103 Author: mikeh Date: 5/18/2017 4:47:31 PM File Name: RevisedPlan Set.2017.04.pdf Please verify that 100 yr storm depth does not exceed 12" as required in Section 4.4 of the URMP. K 7 E H G F J 6 A cut greater than 4' in height is proposed near the north eastcorner of the shoring system according to the profile. Section B-Bdepicts excavation extending almost to the property line, which iswell into the dripline of the existing trees. Preserving these trees isa requirement of the development and no excavation will beallowed beyond the building limits. Please adjust plans. No excavation is allowed on the north side of the building in order to preserve the existing trees. Please adjust the plans. Excavation is not allowed within the alleyROW. Please adjust plans to eliminate any excavation within alley ROW. Excavation extends into the park. Permission from City of Aspen Parks Department must be obtained and provided in a written letter or excavation must be contained within the property limits. Please obtain permission or adjust the design. Please verify that 100 yr storm depth does not exceed 12" as required in Section 4.4 of the URMP. The ROW analysis of the cur, gutter and curb inlet has been re-done using the 100 year peak event. This section was not shown correctly and has been corrected. This section was not shown correctly and has been corrected. This section was not shown correctly and has been corrected. This has been adjusted. City of Aspen Received 6/27/17 Building Department Page Label: C-104 Author: mikeh Date: 5/18/2017 9:48:20 AM File Name: RevisedPlan Set.2017.04.pdf The URMP requires a linear that extends 10' from the foundation to prevent infiltration and deterioration of the foundation. Please include the required liner in the plans. Page Label: C-104 Author: mikeh Date: 5/17/2017 12:56:55 PM File Name: RevisedPlan Set.2017.04.pdf Truncated domes must be parallel with traffic in order to provide direction to the visually impaired. Please adjust plans so that truncated domes are perpendicular to pedestrian flow. Page Label: C-108 Author: mikeh Date: 5/18/2017 10:11:15 AM File Name: RevisedPlan Set.2017.04.pdf This area of sidewalk and landscape buffer must drain to Aspen St in order to reduce runoff reaching the infrastructure at the intersection of Aspen and Hopkins. Page Label: C-108 Author: mikeh Date: 5/17/2017 1:04:18 PM File Name: RevisedPlan Set.2017.04.pdf As noted in the last round of comments, a low point is not allowed in the sidewalk. In this design, public infrastructure depends on the function of private infrastructure. Please adjust plans so no low point exists. Page Label: C-108 Author: mikeh Date: 5/18/2017 10:12:08 AM File Name: RevisedPlan Set.2017.04.pdf This area of sidewalk and landscape buffer must drain to Aspen St in order to reduce runoff reaching the infrastructure at the intersection of Aspen and Hopkins. The URMP requires a linear that extends 10' from the foundation to prevent infiltration and deterioration of the foundation. Please include the required liner in the plans. Truncated domes must be parallel withtraffic in order to provide direction to thevisually impaired. Please adjust plans sothat truncated domes are perpendicularto pedestrian flow. This area of sidewalk and landscapebuffer must drain to Aspen St in order toreduce runoff reaching the infrastructureat the intersection of Aspen and Hopkins. As noted in the last round of comments,a low point is not allowed in thesidewalk. In this design, public infrastructure depends on the function ofprivate infrastructure. Please adjustplans so no low point exists. This area of sidewalk andlandscape buffer must drain toAspen St in order to reduce runoffreaching the infrastructure at theintersection of Aspen and Hopkins. A 30 mil PVC liner has been called out in plan view for the pavers under the entry. It will extend to the property line. These truncated domes have been removed. The sidewalk and front entry has been re- graded. The sidewalk drains toward The grass buffer. The sidewalk doesn't drain into the on site infrastructure. The longitudanal slope of the sidewalk has been changes so there is no low point. Flow will follow the west side of the sidewalk until it flow to the curb and gutter near the east to west ADA ramp at the intersection. City of Aspen Received 6/27/17 Building Department Page Label: C-109 Author: mikeh Date: 5/17/2017 11:17:45 AM File Name: RevisedPlan Set.2017.04.pdf Should perforated under drain be connected to orifice plate? Design is unclear. Please adjust plans. Page Label: C-109 Author: mikeh Date: 5/17/2017 11:16:55 AM File Name: RevisedPlan Set.2017.04.pdf Outfall orifice is well below grade and doesn't tie into any storm water infrastructure. Should orifice tie into perforated PVC pipe? Please verify design and depict on plans properly. Page Label: C-109 Author: mikeh Date: 5/18/2017 9:16:32 AM File Name: RevisedPlan Set.2017.04.pdf No under drain is depicted on plans, only in this detail. If under drain is proposed, please include on all necessary sheets. Page Label: C-110 Author: mikeh Date: 5/18/2017 9:26:42 AM File Name: RevisedPlan Set.2017.04.pdf With stormwater pipes invert out below the bioretention media the runoff does not receive any treatment before reaching the COA stormwater system as required. The screened rock bed is not an infiltration BMP, therefore the runoff must receive treatment before the rock bed. Please have all runoff infiltrate through the bioretention media. Past comments apply with infiltration rate of media to ensure all runoff is treated for the WQCV. Page Label: C-111 Author: mikeh Date: 5/19/2017 8:40:53 AM File Name: RevisedPlan Set.2017.04.pdf If centerline is not accurate, then sawcut must be adjusted to extend to the centerline of Aspen St. Should perforated under drain beconnected to orifice plate? Design isunclear. Please adjust plans. Outfall orifice is well below grade and doesn't tie into any storm water infrastructure. Should orifice tie into perforated PVC pipe? Please verify design and depict on plans properly. No under drain is depicted on plans, onlyin this detail. If under drain is proposed,please include on all necessary sheets. With stormwater pipes invert out below the bioretention media the runoff does not receive any treatment before reaching the COAstormwater system as required. The screened rock bed is not aninfiltration BMP, therefore the runoff must receive treatment before the rock bed. Please have all runoff infiltrate through thebioretention media. Past comments apply with infiltration rate ofmedia to ensure all runoff is treated for the WQCV. If centerline is not accurate, then sawcutmust be adjusted to extend to the centerline of Aspen St. The perforated under drain is connected to the second orifice plate. The orifice plate is now attached to the perforated under drain. Below this under drain is PVC liner which also directs runoff to the perforated under drain. The perforated under drain is called out in plan view and on the storm drain profiles. This detail has been changes to show the orifice plate. These storm drains now daylight above the medium. The infiltration rate of the medium is not needed as the bio-pond/ swales/plater have enough capcity above the finished grade surface and the bottom of the weirs for the WQCV. Additional survey was obtained to determine the expect location of the crown and center line. The center line and crown have been shown and the saw cut line adjusted. City of Aspen Received 6/27/17 Building Department Page Label: C-111 Author: mikeh Date: 5/18/2017 3:50:57 PM File Name: RevisedPlan Set.2017.04.pdf Are these dimensions correct? Where the road is full width one side is 28' and the other is 21', even with the same parking alignment on each side of the street. Please verify as the 13.6' dimension is tight for a bike and vehicle lane. Page Label: C-112 Author: mikeh Date: 5/18/2017 9:10:33 AM File Name: RevisedPlan Set.2017.04.pdf This low spot within the sidewalk is not allowed. Please adjust the plans. Page Label: C-117 Author: mikeh Date: 5/18/2017 9:58:19 AM File Name: RevisedPlan Set.2017.04.pdf Please include note that contractor not to disturb soil behind the thrust block while excavating for storm line. Page Label: C-117 Author: mikeh Date: 5/17/2017 4:15:59 PM File Name: RevisedPlan Set.2017.04.pdf 7' of cover is required throughout the line. Current design has the 4" service line raise roughly 1' over the 45', which decreases the cover at the building. Please adjust plans to ensure 7' of cover. Page Label: C-117 Author: mikeh Date: 5/17/2017 4:17:00 PM File Name: RevisedPlan Set.2017.04.pdf Profile must include thrust block locations. Please adjust plans. Are these dimensions correct? Where theroad is full width oneside is 28' and theother is 21', even withthe same parkingalignment on each sideof the street. Please verify as the 13.6' dimension is tight for a bike and vehicle lane. This low spot within the sidewalk is notallowed. Please adjust the plans. Please include note that contractor not to disturb soil behind the thrust block while excavating for storm line. 7' of cover is required throughout the line. Current design has the 4" service line raiseroughly 1' over the 45', which decreases the cover at the building. Please adjust plans to ensure 7' of cover. Profile must include thrust block locations. Please adjust plans. With the new additional survey these dimension where verified. The longitudinal slope of the sidewalk no longer has a low point. A note has been added to the utility sheet as well as the storm layout sheet. The water service depth is over 7' and a note has been added specifying a 7' min. depth. Thrust block have been added to the bend call outs on the profile. City of Aspen Received 6/27/17 Building Department Page Label: C-117 Author: mikeh Date: 5/18/2017 9:07:58 AM File Name: RevisedPlan Set.2017.04.pdf If tie rods are incorporated into the design, please include minimum lengths, rod thickness, direction, and other pertinent information with regards to the tie rods. Page Label: C-117 Author: mikeh Date: 5/17/2017 4:10:45 PM File Name: RevisedPlan Set.2017.04.pdf No thrust block or second form of restraint is included for the tee. Please include a restraint design for the tee. Page Label: C-117 Author: mikeh Date: 5/17/2017 3:33:04 PM File Name: RevisedPlan Set.2017.04.pdf Penetration detail including restraint must be included in the plan set. Please include penetration detail. Page Label: C-117 Author: mikeh Date: 5/18/2017 9:55:45 AM File Name: RevisedPlan Set.2017.04.pdf Please provide letter from Quest allowing the lid to be relocated and the logistics of the work. Page Label: C-117 Author: mikeh Date: 5/19/2017 8:57:13 AM File Name: RevisedPlan Set.2017.04.pdf 8" C900 is very close to the communications vault. If in the field the pipe needs to be re-routed then a change order will be required. If tie rods are incorporated into the design, please include minimum lengths, rod thickness, direction, and other pertinent information with regards to the tie rods. No thrust block or second form ofrestraint is included for the tee. Pleaseinclude a restraint design for the tee. Penetration detail including restraint must be included in the plan set. Please include penetration detail. Please provide letter from Quest allowing the lid to be relocated and the logistics of the work. 8" C900 is very close to thecommunications vault. If in the field thepipe needs to be re-routed then a change order will be required. Information regarding the tie rods has been added to plan view on the utility sheet. Tie rods will extend back 20' to mid-span restrainsts or to the next bell with bell restrants added. A trust block has been shown for the tee in plan and profile view. The mechanical consultant has provided a detail. A letter from Qwest will be added to the comment response submittal. If the vault posses a conflict during exploratory excavation then a change order will be submitted to re-rout the 8" C900 pipe. City of Aspen Received 6/27/17 Building Department Page Label: C-118 Author: mikeh Date: 5/17/2017 4:22:20 PM File Name: RevisedPlan Set.2017.04.pdf No excavation is allowed for the sidewalk. 10" excavation will not be allowed within the vicinity of the trees.. Please adjust the detail to exclude excavation.No excavation is allowed for thesidewalk. 10" excavation will not be allowed within the vicinity of the trees..Please adjust the detail to exclude excavation. The excavation call out has been removed from this detail and a note has been added saying no excavation is allow. City of Aspen Received 6/27/17 Building Department