Loading...
HomeMy WebLinkAboutFile Documents.802 E Cooper Ave.0203.2019 (14).ARBKThe City of Aspen These plans must be kept at the building site or inspection delays may occur. Construction shall conform to these plans. All changes shall be approved by the building official. Field Plan Set Must Be Printed In Color SEPARATE PERMITS ARE REQUIRED FOR ELECTRICAL, PLUMBING, MECHANICAL, OR FIRE SPRINKLER WORK 11/12/2019 SEE NOTES #1 PLANS SMOKE ALARMS AND CARBON MONOXIDE DETECTORS REQUIRED THROUGHOUT DWELLING UNIT PER CITY OF ASPEN MUNICIPAL CODE 8.15 FIRE SPRINKLERS REQUIRED SPECIAL INSPECTION REQUIRED: -Structural steel welding: Shop Special inspection is required per 2015 IBC section 1704. Inspector to verify that copy of agreement for inspection program to be on the job site prior to performing any inspections. A copy of all Special Inspector field reports to be on the job site for inspectors' review if requested. Failure to comply may result in denial of inspection. READ THIS OR FAIL YOUR INSPECTION! Furred & Dropped Ceilings, Soffits, and Walls 20015 IBC 803.13 This applies to the attachment of finishes or furring to any assemblies that are required to be either fire-rated or non-combustible and is separate from the fire-rated assembly requirement. Walls, Ceilings & Soffits: If furred 1 ¾ inches or less, do one of the following: 4.Fill spaces with Class A material. 5.Fill spaces with inorganic or non-combustible material. 6.Fire block 8 feet in all directions. Walls: If set out (furred) greater than 1 ¾ inches, do one of the following: 4.Use a Class A finish material (such as drywall). 5.Use non-combustible framing. 6.Protect both sides with fire sprinklers. Ceilings & Soffits: If dropped (furred) greater than 1 ¾ inches: Framing members, hangers, and other assembly members must be non-combustible. You may not use wood. In Type III and V construction only, you may use fire retardant treated wood or non-combustible framing. Dwelling Separation Required - 2015 IBC -708 Fire Partitions, 711 Horizontal Assemblies: Walls and floor/ceilings separating dwelling units shall have a fire-resistance rating of at least 1 hour. Walls shall extend from the top of the floor assembly below to the underside of the floor or roof slab or deck above or to the fire-resistance-rated floor/ceiling assembly above. -714: Penetrations must be protected by a through-penetration firestop system. Recessed fixtures shall not reduce the required fire resistance by use of a listed fixture, a listed firehood, or a drywall assembly meeting the required fire resistance. Exhaust fans require ceiling radiation damper. -1207 Sound Transmission: Separating walls and floor/ceilings shall have an STC rating of at least 50. Floor/ceilings shall have an IIC rating of at least 50. FIRE RATED HATS REQUIRED Where floor/ceiling or roof/ceiling assemblies are required to have a fire-resistive rating, recessed fixtures shall be installed such that the required fire resistance will not be reduced (IBC 714.4.2) FIRE DAMPERS REQUIRED Ducts and air transfer openings in fire resistive floor/ceiling or roof/ceiling assemblies shall be protected with approved fire dampers installed in accordance with their listing (IBC 717.5.2 & 717.5.4) Code Editions Fire Sprinkler System Type Of Construction Fire Alarms Installed Required Special Inspections Energy Code Compliance Exterior Energy Use Total Approved On-Site Snowmelt________ Spa_______ Pool _________ Building Type/Occupancy Group COMMUNITY DEVELOPMENT DEPARTMENT BUILDING DESCRIPTION FORM - IRC & IBC CITY OF ASPEN 130 S. GALENA ST | ASPEN, CO 81611 BUILDING CODE INFORMATION 2015 IRC Existing?NFPA 13 NFPA 13 R High-Strength Bolting Epoxy Anchors Structual Steel Welding Permanent Micropiles Other _____________ Prescriptive Table UNIT DESCRIPTION AS PROPOSED # Stories Above Grade ______ # Stories Below Grade _______ Parking Spaces ______ Parking Spaces ______ Parking Spaces ______ # Bedrooms ______ # Full Baths ______ Deck Area ______ # 3/4 Baths ______ # 1/2 Baths ______ # Kitchens ______ # Wood Fireplaces ______ # Gas Appliances ______ # Gas Logs______ NFPA 13 D RESCheck UA Alternative Yes No One Family Two Family Townhouse Reviewed By: _____________________Date:__________ BUILDING ROOMS AND USES BY LEVEL AS PROPOSED (Include Mechanical & Storage) Basement ___________________________________________________________________________________ ___________________________________________________________________________________________ Main Level __________________________________________________________________________________ ____________________________________________________________________________________________ 2nd Floor ___________________________________________________________________________________ __________________________________________________________________________________________ 3rd Floor ___________________________________________________________________________________ ___________________________________________________________________________________________ Additional ___________________________________________________________________________________ ___________________________________________________________________________________________ Attached Garage Detached Garage Carport Is there an ADU? # Living Rooms_____# Kitchens _____# Full Baths _____# 3/4 Baths _____# 1/2 Baths _____# Bedrooms _____ # Other Rooms (List)____________ ADU BUILDING DESCRIPTION YesNo PERMIT NUMBER: _______________________________ (As Adopted and Amended) Other (Please Explain) _________________ _________________ VA VB IV IIIA IIIB IIA IIB IA IB Sprayed Fire-Resistants COMCheck UA Alternative (Existing + New) A__BB (A <50)F__H__I __ E R__S__ U M IRC IBC 2015 IBC (As Adopted and Amended) YesNo Required?YesNo Type January 2018 2015 IEBC (As Adopted and Amended) Other _____________ Gross Area of Building: __________ Gross Area of Unit: __________ Occupant Load: ___________ n n n n n 4,104 sq ftN/A 2 n 1 1 1 1 3 3 0 1 1 4 Bedroom + Bath w/ closet Garage, guest bedroom w/ guest bathroom, master bedroom w/ master bath, living room, dining room, kitchen power room & entry/foyer NT 6/18/19 04/24/2019 2 2480 sqft x powder 12/17/19 01/ 0 6 / 2 0 2 0 nic k t RESIDENTIAL REFERENCES FROM 2015 IBC CV/CS = crawl space ventilation sec. 1203.4. 18” x 24” access required 1209.1 EE = emergency escape required sec 1030 EU = enclosed usable space under stairs shall be 1-hr construction or stair enclosure rating. No access from stair enclosure. ½” gypsum permitted for stairs inside a single dwelling unit. 1011.7.3. RV = roof and rafter ventilation required 1203.2 A = Attic Access 20” x 30” 1209.2 SA = smoke alarm (NFPA 72) required sec 907.2.11 CO = carbon monoxide detector req. per Aspen Municipal Code 8.15 SG = safety glazing required sec 2406 V = mechanical ventilation required sec 1203.1 & IMC 403 (bath fans and whole house ventilation) GR = guards, 42” min ht, 4” max opening. Guards within dwelling unit 36” min ht sec 1015 HR = handrails 34”-38” ht sec 1014 DS = Draft stopping / fire blocking 718 RD = Roof drainage 1503.4 STC = Sound transmission class not less than 50 at dwelling separations, sec 1207 SI = Stairway Illumination 1205.4 PD = protect against decay, sec 2304.12 REFERENCES FROM 2015 IMC DE = clothes dryer exhaust, sec 504. Makeup air req’d if over 200 CFM AS = access and service space for maintenance req’d, sec 306 MA = make up air required if hood exhausts greater than 400 CFM, sec 505.2 ET = exhausts terminate 3’ from prop line and openings, 10’ from intakes, 501.3.1 IT= intake openings 10’ from lot line & contaminant sources (vents, streets), 401.4 D = fasten and seal all ductwork per 603.9 REFERENCES FROM 2015 IFGC DV = direct vent req’d, sec 303.3 CA = combustion air not taken from bedrooms, bathrooms or storage sec 303.3 OD = outdoor appliances must be listed for outdoor use, sec 303.6 REFERENCES FROM 2015 IECC F = new or replacement fenestration shall not exceed 0.28 U-factor, NFRC label required, Ordinance 40, 2016 L = 75% of lamps in permanently installed lights must be high efficacy, sec R404.1 SE = Continuous air barrier required; all exterior joints, cracks, and holes to be caulked, gasketed, sealed, table R402.4.1.1 REFERENCES FROM 2014 NEC EP = electric panel 'happy space' 30"x36"x78", not in storage, sec 110.26 0203.2019.ARBK WARK 802 EAST COOPER# 1 273718228030 1 FIRE SPRINKLERS REQUIRED NFPA 13 FIRE SPRINKLER SYSTEM REQUIRED SPECIAL INSPECTION AND TESTING AGREEMENT To permit applicants of project requiring special inspection and\or testing per Section 1704 of the International Building Code (IBC). Project Address: __________________________________ Permit Number:______________________ BEFORE A PERMIT CAN BE ISSUED: The owner, or the engineer or architect of record, acting as the owner’s agent, shall complete two copies of this agreement and the attached Special-inspection and Testing Schedule, including the required acknowledgments. A pre-construction conference with the parties involved may be required to review the special-inspection requirements and procedures. APPROVAL OF SPECIAL INSPECTORS: Special inspectors may have no financial interest in the projects for which they provide special inspections. Special inspectors shall be approved by the building department prior to performing any duties. Special inspectors shall submit their qualifications and are subject to personal interviews for pre-qualification. Special inspectors shall display approved identification, as stipulated by the building official, when performing the function of special inspector. Special inspection and testing shall meet the minimum requirements of the International Building Code Section 1704. The following conditions are also applicable: A. Duties and Responsibilities of the Special Inspector 1. Signify presence at job site. Special inspectors should notify contractor personnel of their presence and responsibilities at the job site. If required by the building official, they shall sign in on the appropriate form posted with the building permit. Observe assigned work. The special inspector shall observe assigned work for conformance with the building department approved (stamped) design drawings, specifications, and applicable workmanship provisions of the International Building Code. Architect\engineer-reviewed shop drawings may be used only as an aid to inspection. For continuous special-inspection, the special inspector shall be on site at all times observing the work requiring special inspection. Periodic inspections, if any, must have prior approval based on a separate written plan reviewed and approved by the building department and the engineer or architect of record. 3. Report nonconforming items. The special inspector shall bring nonconforming items to the immediate attention of the contractor and note all such items in the daily report. If any item is not resolved in a timely manner or is about to be incorporated in the work, the special inspector shall immediately notify the building department by telephone or in person, notify the engineer or architect, and post a discrepancy notice. Provide timely reports. The special inspector shall complete written inspection reports for each inspection visit and provide the reports on a timely basis determined by the building official. The special inspector or inspection agency shall furnish these reports directly to the building official, engineer or architect of record, and others as designated. [IBC Sec. 1704.1.2] These reports should be organized on a daily format and may be submitted weekly at the option of the building official. These reports should include: a. Description of daily inspections and tests made with applicable locations, b. Listing of nonconforming items, c. Report on how nonconforming items were resolved or unresolved as applicable, d. Itemized changes authorized by the architect, engineer, and building official if not included in nonconforming items. 2. 4. 1 830 E Cooper #1 0088.2019.ARBK 5. Provide Final Inspection Report. The special inspector shall submit a written final report documenting required special inspections and correction of any discrepancies noted in the inspections prior to the final building inspection. B. Owner Responsibilities. The project owner, the engineer or architect or record, or an agent of the owner is responsible for employing special-inspection services. The special inspector\agency shall not be in the employ of the contractor, subcontractor or material supplier. [IBC Sec 1704.1] In case of an owner\contractor, the special inspector\agency shall be employed as specified by the building official. C. Engineer or Architect of Record Responsibilities 1. Prepare special inspection program. The engineer or architect of record shall list the items for which special inspection is required; and shall indicate any items for which the IBC or the building official approves periodic inspection and the frequency of such inspections. Respond to field discrepancies. The engineer or architect of record shall respond to uncorrected field discrepancies in design, material, or workmanship observed by the special inspector. Review shop drawings and submit design changes. The engineer or architect of record shall acknowledge and review for conformance with the construction drawings those shop drawings that may detail structural information, shall submit to the building official and to the special-inspection agency written documentation of any verbally authorized deviations from the approved construction documents, and shall submit revised documents for building official approval as required. 2. 3. D. Contractor Responsibilities 1. Notify the special inspector. The contractor is responsible for notifying the special inspector or agency regarding individual inspections for items listed on the attached schedule and as noted on the building department approved plans. Adequate notice shall be provided so the special inspector has time to become familiar with the project. Provide access to approved plans. The contractor is responsible for providing the special inspector access to approved plans. Retain special inspection records. Upon request, the contractor is also responsible for retaining, at the job site, all special inspection records completed by the special inspector. 2. 3. E. Inspection of Fabricators 1. Fabrication of structural assemblies and members. Where fabrication of structural load-bearing members and assemblies is being performed on the premises of a fabricator’s shop, IBC Section 1704.2 shall require special inspection of the fabricated items. Fabrication and implementation procedures. The special inspector shall verify that the fabricator maintains detailed fabrication and quality control procedures that provide a basis for inspection control of the workmanship and the fabricator’s ability to conform to approved construction documents and reference standards. The special inspector shall review the procedures for completeness and adequacy relative to code requirements for fabricator’s scope of work. 2. F. Approved Fabricator Responsibilities 1. Fabrication exempt inspections. Special inspections are not required where work is done on the premise of a fabricator registered and approved to perform such work without special inspection. 2 G. Project Address: Special Inspection Agency: Owner: Rick Wark Engineer/ Architect: Kim Raymond Architects Contractor: Adam Rothberg Approved Fabricator: Inspected Fabricator: (circle one) CITY OF ASPEN PITKIN COUNTY: Printed Name: al offabricator. Approval shall be based upon review ofthe fabricator's written and quality control manuals and periodic auditing of fabrication practices by ana ed special inspection agency, 3. Com shal1 of fabrication. Upon completion of fabrication, the approved fabricator it certificate of compliance to the building official stating that the work was in accordance with the approved construction documents. Building rtment Responsibilities l. Ap,p special-inspection prrogram. The building department shall approve all inspectors and special- inspection requirements. En ins special inspection. Work requiring special inspection and the building shall monitor the performance of special inspectors, His\ller approval, in to that of the special inspector, must be obtained prior to placement of concl'ete, of structural steel. or other similar materials. inspection reports. The building official should review special-inspection ss and final reports. final inspection. The building official should perform the final inspection and for a project [IBC Sec, 109.3.1] after the final special-inspection report has been and approved. East Cooper Avenue, Unit 1 Permit Number: oo88'2019'ARBK ACKNOWLEDGMENTS read and agree to comply with the conditions of this agreement. Printed Name:Date: Printed Name Date Printed Name: Kim Raymond Date: 1214119 Printed Name: Printed Name:Date: Printed Name:Date: 2. Approval of fabricator. Approval shall be based upon review of the fabricator's written procedural and quality control manuals and periodic auditing of fabrication practices by an approved special inspection agency. 3. Completion of fabrication. Upon completion of fabrication, the approved fabricator shall submit certificate of compliance to the building official stating that the work was performed in accordance with the approved construction documents. G. Building Department Responsibilities 1. Approve special-inspection program. The building department shall approve all special inspectors and special-inspection requirements. 2. Enforce special inspection. Work requiring special inspection and the building inspector shall monitor the performance of special inspectors. HisVHer approval, in addition to that of the special inspector, must be obtained prior to placement of concrete, covering of structural steel, or other similar materials. 3. Review inspection reports. The building official should review special-inspection progress and final reports. 4. Perform final inspection. The building official should perform the final inspection and approval for a project [IBC Sec. 109.3.1] after the final special-inspection report has been reviewed and approved. Project Address: 802 East Cooper Avenue. Unit 1 Perinit Number: 0088.2019.ARBK ACKNOWLEDGMENTS 1 have read and agree to comply with the conditions of this agreement. Special Inspection Agency: Signature/y^^/^/?^--- ^yPrinted Name: Date: ^ffffr^f^^A^f-—*}.Owner: Rick Wark Signature: Engineer/ Architect: Signature: Kim Raymond Architects ^ Contractor: Adam Rothberg Approved Fabricator: Signature: Signature: Printed Name Printed Name: Kim Raymond Printed Name: Printed Name: Date Date: 12/4/19 Date: Date: Inspected Fabricator:Signature:Printed Name:Date: (circle one) CITY OF ASPEN PITKIN COUNTY: Signature:Printed Name:Date: Nick Thompson 1/6/20 01/ 0 6 / 2 0 2 0 nic k t AI R S E A L I N G D E T A I L S U S I N G DR Y W A L L A N D F R A M I N G The City of Aspen Behind tub at exterior wall Behind fireplace at exterior wall Seal all penetrations of air barrier including: Recessed cans Receptacles Outlets Vents Wiring Pipes Intersection of Interior Partition Wall and Ceiling Window Jamb with Trim Window Jamb with Drywall Returns Cantilevered Floor using Spray FoamCantilevered Floor using Floor Sheathing Soffit Intersection Dwelling Separation Wall Intersection with Exterior Wall Chase Intersection with Exterior Wall Rim Joist using Spray Foam Wall Section using Drywall and Framing Rim Joist with Double Plate Important areas to seal: Between double sill plates Between sill plate and floor sheathing Rim joist areas Seal gyp to window and door openings Kitchen soffits above wall cabinets Sheath and seal behind bathtubs, fireplaces, and chases along the exterior wall. Gaps between HVAC registers and drywall Weatherstrip attic access hatches Spray Foam in Un-vented Roof Double plate sealed together and to subfloor Drywall sealed to top plate Drywall sealed to bottom plate Bottom plate sealed to subfloor Subfloor sealed to rim joist/rim closure Rim joist/rim closure sealed to top plate Drywall sealed to top plate Drywall sealed to bottom plate Bottom plate sealed to subfloor Subfloor sealed to rim joist/rim closure Rim joist/rim closure sealed to top plate Wall and ceiling drywall sealed Double plate sealed together and to subfloor Spray extends over gyp joint Drywall sealed to top plate Drywall sealed to bottom plate Bottom plate sealed to subfloor Subfloor sealed to rim joist/rim closure Rim joist/rim closure sealed to top plate Drywall sealed to top plate Drywall sealed to second plate Drywall sealed to bottom plate Bottom plate sealed to subfloor Plates sealed toward each other and sheathing Plates sealed to subfloor Top plate sealed to sheathing Drywall sealed to top plate Drywall sealed to framing Framing sealed to thin profile sheathing Drywall sealed to framing Framing sealed to exterior drywall Fireplace Unit Exterior Wall Seal around air intake penetrations Gyp spanning behind the fireplace Plates sealed together Seal bottom plate to foundation Drywall sealed to bottom plate Bottom plate sealed to subfloor Subfloor sealed to rim joist/rim closure Rim joist/rim closure sealed to top plate Plates sealed together Seal bottom plate to foundation Gasket for capillary break is NOT an adequate seal Drywall sealed to bottom plate Bottom plate sealed to subfloor Plates sealed to subfloor Top plate sealed to sheathing Drywall sealed to top plate Joist sealed to subfloor Top plate sealed to joist Sheathing sealed to bottom plate Bottom plate sealed to subfloor Subfloor sealed to rim joist/rim closure Rim joist/rim closure sealed to top plate Plates sealed together Seal bottom plate to foundation Seal gyp and sheathing to blocking Bath Unit Seal window frame to wall frame Seal wall frame to gyp Seal wall frame to gyp Seal wall frame to gyp Seal soffit blocking penetrations of gyp Seal soffit blocking to gyp Seal wall gyp to soffit gyp Sheathing as draft stop Sheathing as draft stop Thin profile sheathing behind tub 01/ 0 6 / 2 0 2 0 nic k t AI R S E A L I N G D E T A I L S U S I N G EX T E R I O R S H E A T H I N G The City of Aspen Sheathing/rigid insulation to spray foam roof Alternate: Sheathing to foundation Window Jamb with J-trim Window Jamb with Wood Trim Wall Section using Exterior Sheathing and Ceiling Drywall Extend sheathing past sheathing and seal to foundation Detail: Sheathing to Sill Plate Seal all penetrations of air barrier including: Structural projections Exterior Receptacles Exterior Outlets Vents Wiring Pipes Important areas to seal: Install per manufacturer's instructions Tape/seal all sheathing joints Use appropriate fasteners Seal sheathing to top plates and bottom plates (or foundation) Seal sheathing to window and door openings Sealed joints in exterior sheathing Exterior sheathing sealed to sill plate Sill plate sealed to foundation Ice+watershield sealed to roof framing Exterior sheathing sealed to sill plate Sill gasket is NOT adequate air sealing Sill Plate sealed to foundation Spray extends over sheathing Tape over window flange Window flange Seal sheathing to framing 01/ 0 6 / 2 0 2 0 nic k t Important areas to seal: -Install per manufacturer's instructions -Lap and tape all housewrap joints -Tape all tears and holes in housewrap. Large holes may require shingling in patched pieces of housewrap. -Use appropriate fasteners per manufacturer's instructions; typically this requires cap fasteners or taped staples -All joints, openings, and penetrations must be taped and sealed. -The bottom course of housewrap must be sealed to the foundation or sill plate (and then the sill plate sealed to the foundation). -The top course of housewrap must be sealed to the sheathing or top plate. AI R S E A L I N G D E T A I L S U S I N G HO U S E W R A P The City of Aspen Housewrap to spray foam roof Wall Section using Housewrap and Ceiling Drywall Alternate: Housewrap to foundation Detail: Housewrap under Sill Plate Bottom course of housewrap sealed to the foundation Lap and tape house wrap over pre-wrapped house wrap Pre-wrap a course of housewrap under the sill plate with sill sealer Spray foam against top plate Spray foam hard to reach cavities before they are closed up Seal housewrap to sheathing Spray foam against sheathing Housewrap to spray foam to housewrap Housewrap to drywall ceiling to housewrap Seal recessed cans Housewrap Pre-install housewrap Lap and seal upper housewrap to pre-installed housewrap Seal housewrap to plates Seal plates to continuous blocking Continuous blocking sealed on all sides Seal drywall to blockingSeal drywall to top plate Seal housewrap to top plate Seal all penetrations of air barrier including: Structural projections Exterior Receptacles Exterior Outlets Vents Wiring Pipes Housewrap with taped joints Vented Attic Spray over ceiling drywall Seal housewrap to top plate Housewrap sealed to sheathing Housewrap wrapped around and sealed to ice+watershield 01/ 0 6 / 2 0 2 0 nic k t AI R S E A L I N G D E T A I L S U S I N G SP R A Y F O A M The City of Aspen Sealant to be applied along the full length of double plates and stud packs. Foundation gasket Spray foam hard to reach cavities before they are closed up Seal between double plates Seal between double plates Seal between double plates Spray foam all cavities Spray foam rim joist Spray foam all cavities Seal between double plates Seal between plate and floor sheathing Spray foam rim joist Gasket sill plate to foundation Important areas to seal: -Caulk/glue/seal along the full length of double plates and stud packs. -Seal between all framing members not encapsulated with spray foam -Apply spray foam in hard to reach areas before they are covered up or provide access holes to allow spraying Seal all penetrations of air barrier including: Structural projections Exterior Receptacles Exterior Outlets Vents Wiring Pipes Wall Section using Spray Foam Seal studs to plates where notcovered with spray foam Detail of Foundation Connection Isometric showing areas to add sealant in addition to spray foam Seal between plate and floor sheathing 01/ 0 6 / 2 0 2 0 nic k t