HomeMy WebLinkAboutFile Documents.612 W Francis St.0079-2020-BCHO (19)The City of Aspen
These plans must be kept at the
building site or inspection
delays may occur. Construction
shall conform to these plans. All
changes shall be approved by
the building official.
Field Plan Set Must Be Printed In Color
SEPARATE PERMITS ARE
REQUIRED FOR ELECTRICAL,
PLUMBING, MECHANICAL, OR
FIRE SPRINKLER WORK
0079-2020-BCHO
WESTEND 2019 LLC
612 W FRANCIS
273512409015
R311.7 Stairways.
R311.7.1 Width. Stairways shall be not less than 36
inches (914 mm) in clear width at all points above the per-
mitted handrail height and below the required headroom
height. Handrails shall not project more than 41/2 inches
(114 mm) on either side of the stairway and the clear
width of the stairway at and below the handrail height,
including treads and landings, shall be not less than 311/2
inches (787 mm) where a handrail is installed on one side
and 27 inches (698 mm) where handrails are provided on
both sides.
Exception: The width of spiral stairways shall be in
accordance with Section R311.7.10.1.
R311.7.2 Headroom. The headroom in stairways shall be
not less than 6 feet 8 inches (2032 mm) measured verti-
cally from the sloped line adjoining the tread nosing or
from the floor surface of the landing or platform on that
portion of the stairway.
Exceptions:
1. Where the nosings of treads at the side of a flight
extend under the edge of a floor opening through
which the stair passes, the floor opening shall be
allowed to project horizontally into the required
headroom not more than 43/4 inches (121 mm).
2. The headroom for spiral stairways shall be in
accordance with Section R311.7.10.1.
R311.7.3 Vertical rise. A flight of stairs shall not have a
vertical rise larger than 147 inches (3734 mm) between
floor levels or landings.
R311.7.4 Walkline. The walkline across winder treads
shall be concentric to the curved direction of travel
through the turn and located 12 inches (305 mm) from the
side where the winders are narrower. The 12-inch (305
mm) dimension shall be measured from the widest point
of the clear stair width at the walking surface of the
winder. If winders are adjacent within the flight, the point
of the widest clear stair width of the adjacent winders shall
be used.
R311.7.5 Stair treads and risers. Stair treads and risers
shall meet the requirements of this section. For the pur-
poses of this section, dimensions and dimensioned sur-
faces shall be exclusive of carpets, rugs or runners.
R311.7.5.1 Risers. The riser height shall be not more
than 73/4 inches (196 mm). The riser shall be measured
vertically between leading edges of the adjacent treads.
The greatest riser height within any flight of stairs shall
not exceed the smallest by more than 3/8 inch (9.5 mm).
Risers shall be vertical or sloped from the underside of
the nosing of the tread above at an angle not more than 30
degrees (0.51 rad) from the vertical. Open risers are per-
mitted provided that the openings located more than 30
inches (762 mm), as measured vertically, to the floor or
grade below do not permit the passage of a 4-inch-diam-
eter (102 mm) sphere.
Exceptions:
1. The opening between adjacent treads is not
limited on spiral stairways.
2. The riser height of spiral stairways shall be in
accordance with Section R311.7.10.1.
R311.7.5.2 Treads. The tread depth shall be not less
than 10 inches (254 mm). The tread depth shall be mea-
sured horizontally between the vertical planes of the
foremost projection of adjacent treads and at a right
angle to the tread’s leading edge. The greatest tread
depth within any flight of stairs shall not exceed the
smallest by more than 3/8 inch (9.5 mm).
R311.7.5.2.1 Winder treads. Winder treads shall
have a tread depth of not less than 10 inches (254
mm) measured between the vertical planes of the
foremost projection of adjacent treads at the intersec-
tions with the walkline. Winder treads shall have a
tread depth of not less than 6 inches (152 mm) at any
point within the clear width of the stair. Within any
flight of stairs, the largest winder tread depth at the
walkline shall not exceed the smallest winder tread
by more than 3/8 inch (9.5 mm). Consistently shaped
winders at the walkline shall be allowed within the
same flight of stairs as rectangular treads and do not
have to be within 3/8 inch (9.5 mm) of the rectangular
tread depth.
Exception: The tread depth at spiral stairways
shall be in accordance with Section R311.7.10.1.
R311.7.5.3 Nosings. The radius of curvature at the nos-
ing shall be not greater than 9/16 inch (14 mm). A nosing
projection not less than 3/4 inch (19 mm) and not more
than 11/4 inches (32 mm) shall be provided on stairways
with solid risers. The greatest nosing projection shall
not exceed the smallest nosing projection by more than
3/8 inch (9.5 mm) between two stories, including the
nosing at the level of floors and landings. Beveling of
nosings shall not exceed 1/2 inch (12.7 mm).
Exception: A nosing projection is not required where
the tread depth is not less than 11 inches (279 mm).
R311.7.5.4 Exterior plastic composite stair treads.
Plastic composite exterior stair treads shall comply
with the provisions of this section and Section R507.3.
R311.7.6 Landings for stairways. There shall be a floor
or landing at the top and bottom of each stairway. The
width perpendicular to the direction of travel shall be not
less than the width of the flight served. Landings of shapes
other than square or rectangular shall be permitted pro-
vided that the depth at the walk line and the total area is
not less than that of a quarter circle with a radius equal to
the required landing width. Where the stairway has a
straight run, the depth in the direction of travel shall be not
less than 36 inches (914 mm).
Exception: A floor or landing is not required at the top
of an interior flight of stairs, including stairs in an
enclosed garage, provided that a door does not swing
over the stairs.
R311.7.7 Stairway walking surface. The walking surface
of treads and landings of stairways shall be sloped not
steeper than one unit vertical in 48 inches horizontal (2-per-
cent slope).
R311.7.8 Handrails. Handrails shall be provided on not
less than one side of each continuous run of treads or flight
with four or more risers.
R311.7.8.1 Height. Handrail height, measured verti-
cally from the sloped plane adjoining the tread nosing, or
finish surface of ramp slope, shall be not less than 34
inches (864 mm) and not more than 38 inches (965 mm).
Exceptions:
1. The use of a volute, turnout or starting easing
shall be allowed over the lowest tread.
2. Where handrail fittings or bendings are used to
provide continuous transition between flights,
transitions at winder treads, the transition from
handrail to guard, or used at the start of a flight,
the handrail height at the fittings or bendings
shall be permitted to exceed 38 inches (956
mm).
R311.7.8.2 Continuity. Handrails for stairways shall
be continuous for the full length of the flight, from a
point directly above the top riser of the flight to a point
directly above the lowest riser of the flight. Handrail
ends shall be returned or shall terminate in newel posts
or safety terminals. Handrails adjacent to a wall shall
have a space of not less than 11/2 inches (38 mm)
between the wall and the handrails.
Exceptions:
1. Handrails shall be permitted to be interrupted
by a newel post at the turn.
2. The use of a volute, turnout, starting easing or
starting newel shall be allowed over the lowest
tread.
R311.7.8.3 Grip-size. Required handrails shall be of
one of the following types or provide equivalent grasp-
ability.
1. Type I. Handrails with a circular cross section
shall have an outside diameter of not less than 11/4
inches (32 mm) and not greater than 2 inches (51
mm). If the handrail is not circular, it shall have a
perimeter dimension of not less than 4 inches (102
mm) and not greater than 61/4 inches (160 mm)
with a cross section of dimension of not more than
21/4 inches (57 mm). Edges shall have a radius of
not less than 0.01 inch (0.25 mm).
2. Type II. Handrails with a perimeter greater than
61/4 inches (160 mm) shall have a graspable finger
recess area on both sides of the profile. The finger
recess shall begin within a distance of 3/4 inch (19
mm) measured vertically from the tallest portion
of the profile and achieve a depth of not less than
5/16 inch (8 mm) within 7/8 inch (22 mm) below the
widest portion of the profile. This required depth
shall continue for not less than 3/8 inch (10 mm) to
a level that is not less than 13/4 inches (45 mm)
below the tallest portion of the profile. The width
of the handrail above the recess shall be not less
than 11/4 inches (32 mm) and not more than 23/4inches (70 mm). Edges shall have a radius of not
less than 0.01 inch (0.25 mm).
R311.7.8.4 Exterior plastic composite handrails.
Plastic composite exterior handrails shall comply with
the requirements of Section R507.3.
R311.7.9 Illumination. Stairways shall be provided with
illumination in accordance with Section R303.7.
SECTION R312
GUARDS AND WINDOW FALL PROTECTION
R312.1 Guards. Guards shall be provided in accordance
with Sections R312.1.1 through R312.1.4.
R312.1.1 Where required. Guards shall be located along
open-sided walking surfaces, including stairs, ramps and
landings, that are located more than 30 inches (762 mm)
measured vertically to the floor or grade below at any
point within 36 inches (914 mm) horizontally to the edge
of the open side. Insect screening shall not be considered
as a guard.
R312.1.2 Height. Required guards at open-sided walking
surfaces, including stairs, porches, balconies or landings,
shall be not less than 36 inches (914 mm) in height as
measured vertically above the adjacent walking surface or
the line connecting the leading edges of the treads.
Exceptions:
1.Guards on the open sides of stairs shall have a
height not less than 34 inches (864 mm) mea-
sured vertically from a line connecting the lead-
ing edges of the treads.
2. Where the top of the guard serves as a handrail on
the open sides of stairs, the top of the guard shall be
not less than 34 inches (864 mm) and not more than
38 inches (965 mm) as measured vertically from a
line connecting the leading edges of the treads.
R312.1.3 Opening limitations. Required guards shall not
have openings from the walking surface to the required
guard height that allow passage of a sphere 4 inches (102
mm) in diameter.
Exceptions:
1. The triangular openings at the open side of stair,
formed by the riser, tread and bottom rail of a
guard, shall not allow passage of a sphere 6
inches (153 mm) in diameter.
2.Guards on the open side of stairs shall not have
openings that allow passage of a sphere 43/8inches (111 mm) in diameter.
SMOKE ALARMS AND
CARBON MONOXIDE
DETECTORS REQUIRED
THROUGHOUT DWELLING
UNIT PER CITY OF ASPEN
MUNICIPAL CODE 8.15
Memorandum
Page 1 of 2
KL&A, Inc.
215 N. 12th Street, Unit E
Carbondale, Colorado 81623
Telephone: (970) 927-5174
Job Name: 612 W Francis
Job Number: B0647.000
To: Email: Company:
Joel Hocknell joelhocknell@gmail.com Cyr and
Company
From: Brett McElvain, P.E.
Date: July 1, 2020
Pages Including Cover: 2
re: 612 W Francis Header Modifications for Shade Pockets
Cc: Dana Ellis (Rowland+Broughton)
Comments:
Joel,
I have reviewed the photos you sent for the modifications that were made to the existing
headers and windowsills to accommodate the addition of the shade pockets. The modifications
appear to be in compliance with the details below and our conversation regarding the
placement of the A34 clips.
10/21/202006/08/2022
Memorandum
Page 2 of 2
If you have any questions or need clarifications, please call.
07/01/2020
10/21/202006/08/2022
SPECIAL INSPECTION REQUIRED:
-Structural steel welding: Field & Shop
-High strength bolting
-Epoxy anchors
-Intumescent paint
-Spray applied fire resistive materials
-Permanent micropiles
Special inspection is required per 2015 IBC
section 1704. Inspector to verify that copy of
agreement for inspection program to be on
the job site prior to performing any
inspections. A copy of all Special Inspector
field reports to be on the job site for
inspectors' review if requested. Failure to
comply may result in denial of inspection.
SEE NOTES #1 PLANS
07/22/2022
justinh
GLASS IN GUARDS AND HANDRAILS
Glass in guards and handrails shall be two plies equal thickness
laminated glass. Tempered glass is only permitted where not
above a walking surface and when a top rail that is either
self-supported (glass infill panels) or is supported by a minimum of
three panes of glass. IRC 308.7/IBC 2407.
External Energy Use Approved
RREMP CREMP
PERMIT #:_______________DATE:________
SNOWMELT:_____________________________
POOL: _____________________________
SPA: _____________________________
OFFSET:________________________________
REMP SHEET: __________________________
REVIEWED BY: _________________________
SNOWMELT SYSTEM AND EQUIPMENT MANDATORY REQ’S.
All snowmelt systems shall meet the following:
-Any portions in the Right of Way must be on a separate zone. A ROW
permit and Permanent Encroachment License are required.
-R10 insulation shall be installed under the area to be snow melted or R5
insulation shall be installed under and at the slab edges. (Ordinance 11
Series 2011)
-Automatic controls installed for system shut off when pavement
temperature is above 50°F and no precipitation is falling. (2009 IECC
Sec. 403.8 & 503.2.4.5)
-Automatic or manual controls installed for system shut off when outdoor
temperature is above 40°F. (2009 IECC Sec. 403.8 & 503.2.4.5)
-Inspection by testing hydrostatically at 1½ times max system design
pressure, but not less than 100psi, for 15minutes. (2009 IMC Sec.
1208.1)
MINIMUM BOILER AFUE: _________________
x
MASTER PERMIT 0108.2019.ARBK
0079-2020-BCHO 7/22/22
485 SQ.FT. TOTAL
A1.1
95%
NONE
JH
bobn
07/25/2022ZONING
REVIEWED BY ZONING
07/25/2022 bobn
It should be known that this review shall
not relieve the applicant of theirresponsibility to comply with therequirements of the City of Aspen. Thereview and approval by the City isoffered only to assist the applicant's
understanding of the applicable LandUse Code requirements. The issuanceof a permit based on constructiondocuments and other data shall notprevent the City of Aspen from
requiring the correction of errors in theconstruction documents and otherdata.