These plans must be kept at the
building site or inspection
delays may occur. Construction
shall conform to these plans. All
changes shall be approved by
the building official.
Field Plan Set Must Be Printed In Color
SEPARATE PERMITS ARE
REQUIRED FOR ELECTRICAL,
PLUMBING, MECHANICAL, OR
FIRE SPRINKLER WORK
07/16/2019
07/09/2019
SMOKE ALARMS AND
CARBON MONOXIDE
DETECTORS REQUIRED
THROUGHOUT DWELLING
UNIT PER CITY OF ASPEN
MUNICIPAL CODE 8.15
FIRE
SPRINKLERS
REQUIRED
RESIDENTIAL REFERENCES FROM 2015 IBC
CV/CS = crawl space ventilation sec. 1203.4. 18” x 24” access required
1209.1
EE = emergency escape required sec 1030
EU = enclosed usable space under stairs shall be 1-hr construction or stair
enclosure rating. No access from stair enclosure. ½” gypsum permitted for
stairs inside a single dwelling unit. 1011.7.3.
RV = roof and rafter ventilation required 1203.2
A = Attic Access 20” x 30” 1209.2
SA = smoke alarm (NFPA 72) required sec 907.2.11
CO = carbon monoxide detector req. per Aspen Municipal Code 8.15
SG = safety glazing required sec 2406
V = mechanical ventilation required sec 1203.1 & IMC 403 (bath fans and
whole house ventilation)
GR = guards, 42” min ht, 4” max opening. Guards within dwelling unit 36” min
ht sec 1015
HR = handrails 34”-38” ht sec 1014
DS = Draft stopping / fire blocking 718
RD = Roof drainage 1503.4
STC = Sound transmission class not less than 50 at dwelling separations, sec
1207
SI = Stairway Illumination 1205.4
PD = protect against decay, sec 2304.12
REFERENCES FROM 2015 IMC
DE = clothes dryer exhaust, sec 504. Makeup air req’d if over 200 CFM
AS = access and service space for maintenance req’d, sec 306
MA = make up air required if hood exhausts greater than 400 CFM, sec 505.2
ET = exhausts terminate 3’ from prop line and openings, 10’ from intakes,
501.3.1
IT= intake openings 10’ from lot line & contaminant sources (vents, streets),
401.4
D = fasten and seal all ductwork per 603.9
REFERENCES FROM 2015 IFGC
DV = direct vent req’d, sec 303.3
CA = combustion air not taken from bedrooms, bathrooms or
storage sec 303.3
OD = outdoor appliances must be listed for outdoor use, sec 303.6
REFERENCES FROM 2015 IECC
F = new or replacement fenestration shall not exceed 0.28 U-factor, NFRC
label required, Ordinance 40, 2016
L = 75% of lamps in permanently installed lights must be high efficacy, sec
R404.1
SE = Continuous air barrier required; all exterior joints, cracks, and holes to be
caulked, gasketed, sealed, table R402.4.1.1
REFERENCES FROM 2014 NEC
EP = electric panel 'happy space' 30"x36"x78", not in storage, sec 110.26
Dwelling Separation Required - 2015 IBC
-708 Fire Partitions, 711 Horizontal Assemblies:
Walls and floor/ceilings separating dwelling units shall have a fire-resistance
rating of at least 1 hour. Walls shall extend from the top of the floor assembly
below to the underside of the floor or roof slab or deck above or to the
fire-resistance-rated floor/ceiling assembly above.
-714: Penetrations must be protected by a through-penetration firestop
system. Recessed fixtures shall not reduce the required fire resistance by use
of a listed fixture, a listed firehood, or a drywall assembly meeting the required
fire resistance. Exhaust fans require ceiling radiation damper.
-1207 Sound Transmission: Separating walls and floor/ceilings shall have an
STC rating of at least 50. Floor/ceilings shall have an IIC rating of at least 50.
External Energy Use Approved
RREMP CREMP
PERMIT #:_______________DATE:________
SNOWMELT:_____________________________
POOL: _____________________________
SPA: _____________________________
OFFSET:________________________________
REMP SHEET: __________________________
REVIEWED BY: _________________________
SNOWMELT SYSTEM AND EQUIPMENT MANDATORY REQ’S.
All snowmelt systems shall meet the following:
-Any portions in the Right of Way must be on a separate zone. A ROW
permit and Permanent Encroachment License are required.
-R10 insulation shall be installed under the area to be snow melted or R5
insulation shall be installed under and at the slab edges. (Ordinance 11
Series 2011)
-Automatic controls installed for system shut off when pavement
temperature is above 50°F and no precipitation is falling. (2009 IECC
Sec. 403.8 & 503.2.4.5)
-Automatic or manual controls installed for system shut off when outdoor
temperature is above 40°F. (2009 IECC Sec. 403.8 & 503.2.4.5)
-Inspection by testing hydrostatically at 1½ times max system design
pressure, but not less than 100psi, for 15minutes. (2009 IMC Sec.
1208.1)
MINIMUM BOILER AFUE: _________________
X
0177.2019.arbk 8/22/19
0
0
0
NA
NA
NA
TF
08/23/2019
07/09/2019
07/09/2019
07/09/2019
300 sq. ft.
0177.2019.ARBK
X PL 7.12.19
X
X
X
X
X
X
1,535.63
162.50
218.40
162.50
2,362.50
37.50
CC
BN 7.16.19
0
0
0
0
0
SW
CS
0177.2019.ARBK
MICHAEL ABBOTT
434 E MAIN ST # 201
273707327005
CHASE WALLS, WOOD FRAMED
GA FILE NO. WP 5510 GENERIC 1 HOUR
FIRE
55 to 59 STC
SOUND
Thickness:10"
Approx. Weight:9 psf
Fire Test:See WP 3341
(FM WP-147, 1-2-69);
UL R4024, 10-31-68
Sound Test:G&H BW-32ST, 4-22-68
GYPSUM WALLBOARD, WOOD STUDS
Base layer 1/4" gypsum wallboard applied parallel to each side of double row of 2 x 4 wood
studs 16" o.c. on separate plates spaced 11/2" apart with 4d coated nails, 11/2" long,
0.099" shank, 1/4" heads, 12" o.c. Joints staggered 16" on opposite sides. Face layer 1/2"
type X plain or predecorated gypsum wallboard or gypsum veneer base applied parallel
to each side with 3/8" beads of adhesive 16" o.c. and 5d coated nails, 1¾" long, 0.099"
shank, 1/4" heads, 16" o.c. at top and bottom plates. 4d finish nails, 11/2" long, 0.072"
shank, 0.1055" heads, driven at a 45° angle 16" o.c. horizontally and 24" o.c. vertically.
Joints offset 24" from base layer joints.
Sound tested with 11/2" mineral fiber insulation in stud space. Horizontal bracing required
at mid-height. (LOAD-BEARING)
if dimensional lumber
use this one
if it is TJI 's use this
one
DAM 8/23/19
DAM 8/23/19TF
TF 8/23/19
8/23/19
8/23/19