Please depict the area of "no
construction equipment" on the
plans.
Plan Set.2017.01.pdf (66)
Page Label: B-02
Author: mikeh
Date: 3/2/2017 10:39:52 AM
File Name: Plan Set.2017.01.pdf
Plan calls for dewatering. Where
will water be discharged? Please
provide more information on
dewatering the site.
Page Label: B-02
Author: mikeh
Date: 3/2/2017 10:23:07 AM
File Name: Plan Set.2017.01.pdf
Please provide stationing in plan
view.
Page Label: B-02
Author: mikeh
Date: 3/2/2017 10:15:51 AM
File Name: Plan Set.2017.01.pdf
Limits of excavation appear to
be 9' from shoring. Excavation
extends well into driplines of
existing trees. Please adjust
plans to minimize excavation on
north side of building.
Page Label: B-03
Author: mikeh
Date: 3/2/2017 10:20:06 AM
File Name: Plan Set.2017.01.pdf
Retaining wall part of temporary
shoring design? The retaining
wall is not depicted on plans.
Please provide more information
and design on retaining wall.
Please depict the area of "no
construction equipment" on the plans.
Plan calls for dewatering. Where will
water be discharged? Please provide
more information on dewatering the site.
E
H
G
F
J
Please provide stationing in plan view.
756
Limits of excavation appear to be 9' from
shoring. Excavation extends well into
driplines of existing trees. Please adjust
plans to minimize excavation on north
side of building.
Retaining wall part of temporary shoring
design? The retaining wall is not
depicted on plans. Please provide more
information and design on retaining wall.
This area has been
added.
De-watering is not
planned for this site per
Soils Report.
Stationing is for reference only and is not
utilized for layout. It is not added to plan view,
however dimensions to column lines are
clarified on plan view.
The line referenced in Comment 4 is the
property line, not a limit of excavation. This
has been clarified on the plan view.
The retaining wall is not considered in the
temporary shoring design. It is an existing
wall that is to remain in place.
City of Aspen
Received
4/24/17
Building Department
Page Label: B-03
Author: mikeh
Date: 3/2/2017 10:32:21 AM
File Name: Plan Set.2017.01.pdf
Soils report doesn't mention a
maximum cut slope. The 1:1
slope must be verified. Please
provide evidence that a 1:1
slope is stable in the soils on
location.
Page Label: B-03
Author: mikeh
Date: 3/2/2017 10:34:56 AM
File Name: Plan Set.2017.01.pdf
Traffic loads in the alley must be
accounted for in design.
Southern wall does not appear
to be any different than any of
the other sides. Please verify
that traffic loading is designed
for.
Page Label: B-03
Author: mikeh
Date: 3/2/2017 10:35:16 AM
File Name: Plan Set.2017.01.pdf
Property lines must be depicted
on all sections. Please adjust
plans.
Page Label: B-04
Author: mikeh
Date: 3/2/2017 10:36:56 AM
File Name: Plan Set.2017.01.pdf
How will utility installation
penetrate shoring? Please
provide more information on how
utilities will be installed in
regards to the shoring.
Page Label: C-101
Author: mikeh
Date: 2/27/2017 4:51:16 PM
File Name: Plan Set.2017.01.pdf
Please see drainage report for
drainage report comments.
Soils report doesn't mention a maximum
cut slope. The 1:1 slope must be
verified. Please provide evidence that a
1:1 slope is stable in the soils on
location.
Traffic loads in the alley must be
accounted for in design. Southern wall
does not appear to be any different than
any of the other sides. Please verify that
traffic loading is designed for.
Job No.:
Dwg. No.:
General Contractor:
Drawn By:
Scale:
Date:
BERKEL & COMPANYCONTRACTORS, INC.Owner:
200 SOUTH ASPEN STREET
ASPEN, COLORADO
REGIONAL OFFICE - (502) 225-0053
01/12/2017
Property lines must be depicted on allsections. Please adjust plans.
How will utility installation penetrate
shoring? Please provide more
information on how utilities will be
installed in regards to the shoring.
Please see drainage report for drainage
report comments.
Temporary slope has been
modified to 1.5H : 1V
Verified. Traffic loading is included
on all 4 sides of the excavation.
Property lines have been added to all
sections.
The lagging boards may be
removed during installation of the
near surface utilities.
City of Aspen
Received
4/24/17
Building Department
Page Label: C-102
Author: mikeh
Date: 2/27/2017 10:32:41 AM
File Name: Plan Set.2017.01.pdf
Sawcut must be perpendicular to
the travel way. Please adjust
plans.
Page Label: C-103
Author: mikeh
Date: 3/2/2017 9:47:16 AM
File Name: Plan Set.2017.01.pdf
Benches will not be allowed
within the ROW. Please adjust
the plans.
Page Label: C-103
Author: mikeh
Date: 2/27/2017 1:25:16 PM
File Name: Plan Set.2017.01.pdf
Excavation for sidewalk may
negatively affect the health of
the existing tree. Please verify
with the Parks Department that
sidewalk excavation is allowed
that close to the tree trunk.
Page Label: C-103
Author: mikeh
Date: 3/8/2017 10:42:45 AM
File Name: Plan Set.2017.01.pdf
Please include the areas of
floating sidewalk on this plan on
both Hopkins and Aspen.
Page Label: C-103
Author: mikeh
Date: 3/2/2017 9:48:27 AM
File Name: Plan Set.2017.01.pdf
Snowmelt cannot drain onto
sidewalk. No drainage from
impervious area will be allowed
to reach ROW without treatment.
Please adjust plans.
Sawcut must be perpendicular to the
travel way. Please adjust plans.
Benches will not be
allowed within the
ROW. Please adjust
the plans.
Excavation for sidewalk may negatively
affect the health of the existing tree.
Please verify with the Parks Department
that sidewalk excavation is allowed that
close to the tree trunk.
Please include the areas of floating
sidewalk on this plan on both Hopkins
and Aspen.
Snowmelt cannot drain onto sidewalk.
No drainage from impervious area will be
allowed to reach ROW without
treatment. Please adjust plans.
The saw cut has
been altered to be
perpendicular to
the travel way.
Staff has discussed
these feature with
the architect and
landscape architects.
A 2' set back has been noted within the civil plan set. The sidewalk alignment and grading has also been
altered to accommodate this. Parks is aware of this tree and they have required a floating sidewalk in this
area.
The floating sidewalk has been
depicted with a hatch on this
sheet.
The front entry way surface has been changed to permeable
pavers and the grading has been altered to slope drainage
onto the property where inlets will convey the storm water to
the COA storm system.
City of Aspen
Received
4/24/17
Building Department
Page Label: C-106
Author: mikeh
Date: 2/27/2017 10:38:08 AM
File Name: Plan Set.2017.01.pdf
Low point on sidewalk. Drainage
design must provide conveyance
in order to prevent puddling.
Please adjust plans.
Page Label: C-106
Author: mikeh
Date: 2/27/2017 10:30:32 AM
File Name: Plan Set.2017.01.pdf
2% maximum cross slope for
sidewalk as well as alley
crossing. These point elevations
create an incorrect cross slope
direction as well as a greater
than the maximum 2%. Please
adjust plans.
Page Label: C-106
Author: mikeh
Date: 2/27/2017 1:50:52 PM
File Name: Plan Set.2017.01.pdf
Cross section numbers do not
match what is labeled in plan
view. Please adjust cross
section numbering to match the
plan view.
Page Label: C-106
Author: mikeh
Date: 2/27/2017 10:35:17 AM
File Name: Plan Set.2017.01.pdf
Slope arrows appear to point in
an incorrect direction. Roadway
must be crowned and direct
runoff to curb and gutter. Please
adjust plans and also verify
cross slopes.
Page Label: C-106
Author: mikeh
Date: 3/7/2017 10:02:11 AM
File Name: Plan Set.2017.01.pdf
Wings for sidewalk ramps is
required. Please adjust plans
and details to include winged
ADA ramps.
Low point on sidewalk. Drainage design
must provide conveyance in order to
prevent puddling. Please adjust plans.
2% maximum cross slope for sidewalk
as well as alley crossing. These point
elevations create an incorrect cross
slope direction as well as a greater than
the maximum 2%. Please adjust plans.
Cross section numbers
do not match what is
labeled in plan view.
Please adjust cross
section numbering to
match the plan view.
Slope arrows appear to point in an
incorrect direction. Roadway must be
crowned and direct runoff to curb and
gutter. Please adjust plans and also
verify cross slopes.
Wings for sidewalk ramps is required.
Please adjust plans and details to
include winged ADA ramps.
The grass buffer and sidewalk now slope toward the
pervious pavers at the entry way. Inlets are provided at low
points on the property.
The grading in this are has been changed
to satisfy the 2% cross-slope requirement.
The numbering has been corrected for the
cross-sections. They now match in plan
view and profile view.
The slope arrow style has been changed so
they only point in the direction of flow. The
road way slopes toward the curb and
gutter.
Wings have been added to the sidewalk
ADA ramps and conform with the COA
design standards. This can be seen on all
applicable sheets.
City of Aspen
Received
4/24/17
Building Department
Page Label: C-106
Author: mikeh
Date: 2/28/2017 5:45:18 PM
File Name: Plan Set.2017.01.pdf
Grading within park must be
approved by Parks Department.
Please verify Parks is allowing
such grading.
Page Label: C-106
Author: mikeh
Date: 3/7/2017 9:47:45 AM
File Name: Plan Set.2017.01.pdf
More spot elevations are
required in this area to ensure
overflow reaches grated lid of
manhole. Please provide a more
detailed design in this area.
Page Label: C-106
Author: mikeh
Date: 2/27/2017 10:56:47 AM
File Name: Plan Set.2017.01.pdf
7900' proposed contour doesn't
work. Please adjust plans.
Page Label: C-106
Author: mikeh
Date: 2/27/2017 10:31:24 AM
File Name: Plan Set.2017.01.pdf
Landscape buffer must have a
maximum cross slope of 5%.
Please adjust plans.
Page Label: C-106
Author: mikeh
Date: 2/23/2017 10:10:58 AM
File Name: Plan Set.2017.01.pdf
Cross slopes greater than 2%.
Maximum ADA ramp cross slope
is 2%. Curb profile calls out 2%
slope for ramps. Please adjust
the plans to have a maximum
cross slope of 2%.
Grading within park must be approved
by Parks Department. Please verify
Parks is allowing such grading.
More spot elevations are required in this
area to ensure overflow reaches grated
lid of manhole. Please provide a more
detailed design in this area.
7900' proposed contour doesn't work.
Please adjust plans.
Landscape buffer must have a maximum
cross slope of 5%. Please adjust plans.
Cross slopes greater than 2%. Maximum ADA
ramp cross slope is 2%. Curb profile calls out 2%
slope for ramps. Please adjust the plans to have
a maximum cross slope of 2%.
Discussions with the parks department
have taken place and proposed grading
has been agreed upon.
A 5 scale grading view has been added to
the set on sheet C-108. Additional spot
elevations and cross-sections have been
provided.
A sidewalk ramp has been added to this
area. The re-grading is shown on the new
sheet C-108.
The grass buffer slope has been reduced to
less than 5%. The re-grading is shown on
the new sheet C-108.
Re-grading of the ADA ramps has been
performed. The re-grading is shown on the
new sheet C-108.
City of Aspen
Received
4/24/17
Building Department
Page Label: C-106
Author: mikeh
Date: 3/9/2017 2:58:39 PM
File Name: Plan Set.2017.01.pdf
Steep grade directly off sidewalk
will not be allowed. Please bring
design up to standard.
Page Label: C-106
Author: mikeh
Date: 2/27/2017 1:48:07 PM
File Name: Plan Set.2017.01.pdf
Entire manhole must be located
within property. Please depict
the outer limits of the manhole,
not just the lid, on the plans to
ensure the manhole is on private
property.
Page Label: C-106
Author: mikeh
Date: 2/27/2017 1:54:06 PM
File Name: Plan Set.2017.01.pdf
Re-grading of alley pushes
runoff onto neighboring property
to south. The alley must convey
runoff to Aspen St, not the
neighbors to the south of the
alley. Please adjust the grading
design.
Page Label: C-106
Author: mikeh
Date: 3/7/2017 9:46:31 AM
File Name: Plan Set.2017.01.pdf
Please depict existing curb and
gutter to ensure proper tie in.
Page Label: C-107
Author: mikeh
Date: 2/27/2017 5:07:07 PM
File Name: Plan Set.2017.01.pdf
How will curb inlet be placed on
curve of curb & gutter? Please
adjust plans to include
installation description.
Steep grade directly off sidewalk will not
be allowed. Please bring design up to
standard.
Entire manhole must be located within
property. Please depict the outer limits of
the manhole, not just the lid, on the
plans to ensure the manhole is on
private property.
Re-grading of alley pushes runoff onto
neighboring property to south. The alley
must convey runoff to Aspen St, not the
neighbors to the south of the alley.
Please adjust the grading design.
Please depict existing curb and gutter to
ensure proper tie in.
How will curb inlet be placed on curve of
curb & gutter? Please adjust plans to
include installation description.
The grading behind the proposed landscape benches has
been altered to eliminate steep slopes. This is shown on
sheet C-108 with a zoomed 5 scale view of the proposed
grading.
The new proposed storm inlet is now a 24"
diameter nyloplast pvc inlet placed completely
on the property. This is large enough for
spacing of all the pipe connection and satisfies
the URMP capacity calculations.
The alley grading has been altered to provide
positive drainage away from the neighboring
property. This can be seen on the new
grading sheet C-107.
The existing curb and gutter layer from the
survey has been turned on.
Station Offset labels have been added to corners of the inlet box on
the curb and gutter alignment sheet C-111. The inlet will be placed first
using this control. The curb and gutter will be installed second. The
deviation from the alignment for each corner of the inlet is negligible >
0.25" and the curb and gutter concrete will be field adjusted to make up
for this gap.
City of Aspen
Received
4/24/17
Building Department
Page Label: C-107
Author: mikeh
Date: 2/27/2017 5:15:26 PM
File Name: Plan Set.2017.01.pdf
Needs more separation??.
Please adjust plans. Please
have pipe split the difference
between the building and the
transformer.
Page Label: C-107
Author: mikeh
Date: 2/27/2017 5:05:04 PM
File Name: Plan Set.2017.01.pdf
What degree bend is this?
Please adjust plans to note all
bends.
Page Label: C-107
Author: mikeh
Date: 2/28/2017 3:46:09 PM
File Name: Plan Set.2017.01.pdf
No detail for manhole is depicted
within the plan set. Please
include a manhole detail that
includes the grated lid.
Page Label: C-107
Author: mikeh
Date: 2/23/2017 10:04:34 AM
File Name: Plan Set.2017.01.pdf
Storm pipe cannot run that close
to trunk of existing tree. Please
adjust plans.
Page Label: C-107
Author: mikeh
Date: 2/27/2017 1:19:32 PM
File Name: Plan Set.2017.01.pdf
Please fade back existing pipe to
be demoed or remove it from
this plan for clarity.
Needs more separation??. Please adjust
plans. Please have pipe split the
difference between the building and the
transformer.
What degree bend is this? Please adjust
plans to note all bends.
No detail for manhole is depicted within
the plan set. Please include a manhole
detail that includes the grated lid.
Storm pipe cannot run that close to trunk
of existing tree. Please adjust plans.
Please fade back existing pipe to be
demoed or remove it from this plan for
clarity.
The storm pipe has been re-aligned to split
the distance between the structure and the
transformer. See sheet C-109
This portion of the storm system has been re-
designed. A proposed inlet has been placed
in the low point of this area. See sheet C-109.
Details have been provided for the new
nyloplast inlets vs. the concrete manhole.
See sheet C-119.
This tree has been added the the removal
list.
This existing pipe has been faded back or
turned off. I believe it is conduit for
communications that will be demolished.
City of Aspen
Received
4/24/17
Building Department
Page Label: C-108
Author: mikeh
Date: 2/27/2017 4:42:47 PM
File Name: Plan Set.2017.01.pdf
Sanitary sewer service line
needs to be depicts to ensure
proper crossing and separation.
Please depict the sanitary
Page Label: C-108
Author: mikeh
Date: 2/23/2017 10:12:42 AM
File Name: Plan Set.2017.01.pdf
Water line must be depicted on
profile. Label separation
between water line and storm
line. Please adjust plans.
Page Label: C-108
Author: mikeh
Date: 3/7/2017 2:21:09 PM
File Name: Plan Set.2017.01.pdf
Manholes are required to have
a minimum of a 0.2' drop. 2' of
sump is excessive. Please limit
sump to 0.2'. Please adjust
plans.
Page Label: C-108
Author: mikeh
Date: 2/27/2017 4:40:41 PM
File Name: Plan Set.2017.01.pdf
Top of soil elevations needs to
be depicted on profile. Please
provide top of soil elevations.
Page Label: C-108
Author: mikeh
Date: 2/27/2017 1:00:02 PM
File Name: Plan Set.2017.01.pdf
Design must include prevention
of water infiltration on the south
side of the bio-retention area
near the transformer. Please
include an infiltration prevention
measure on south side of rock
bed and bio planting media.
Sanitary sewer service line needs to be
depicts to ensure proper crossing and
separation. Please depict the sanitary
Water line must be depicted on profile.
Label separation between water line and
storm line. Please adjust plans.
Manholes are required to have a
minimum of a 0.2' drop. 2' of sump is
excessive. Please limit sump to 0.2'.
Please adjust plans.
Top of soil elevations needs to be depicted on
profile. Please provide top of soil elevations.
Design must include prevention of water infiltration on the
south side of the bio-retention area near the transformer.
Please include an infiltration prevention measure on south
side of rock bed and bio planting media.
The sanitary sewer service connection
has been added to the profile. See sheet
C-110
The water line has been added to the
storm pipe profile. See sheet C-110.
This storm manhole has been adjust to
limit the sump and implement a 0.2' drop
between inv. in and out. See Sheet
C-110.
Top soil elevations have been added.
See sheet C-110.
Another site wall has been added just to
the north of the transformer where PVC
liner will be attached.
City of Aspen
Received
4/24/17
Building Department
Page Label: C-108
Author: mikeh
Date: 2/23/2017 10:29:51 AM
File Name: Plan Set.2017.01.pdf
Profile must depict water service
line to ensure proper separation.
Please depict the water service
line crossing on the profile and
label the separation.
Page Label: C-109
Author: mikeh
Date: 3/8/2017 10:37:49 AM
File Name: Plan Set.2017.01.pdf
Tree must have 2' of separation
from sidewalk. Please adjust the
shape of the sidewalk to provide
adequate separation.
Page Label: C-109
Author: mikeh
Date: 2/27/2017 10:43:57 AM
File Name: Plan Set.2017.01.pdf
Sidewalks are allowed to have a
greater than 5% longitudinal
slope if the roadway has a slope
greater than 5%, but the
sidewalk longitudinal slope
cannot exceed the slope of the
road. Please adjust the plans so
that sidewalk is not steeper than
the road.
Page Label: C-110
Author: mikeh
Date: 3/9/2017 2:46:39 PM
File Name: Plan Set.2017.01.pdf
Please include measurements
from the centerline on Hopkins
and Aspen to ensure enough
space exists for both vehicle and
bike lanes.
Page Label: C-110
Author: mikeh
Date: 2/27/2017 10:49:04 AM
File Name: Plan Set.2017.01.pdf
Alley directs runoff to low point
on sidewalk. Puddling will occur
at north side of alley crossing.
Please adjust plans to prevent
puddling.
Profile must depict water service line to
ensure proper separation. Please depict
the water service line crossing on the
profile and label the separation.
Tree must have 2' of separation from
sidewalk. Please adjust the shape of the
sidewalk to provide adequate separation.
Sidewalks are allowed to have a greater
than 5% longitudinal slope if the roadway
has a slope greater than 5%, but the
sidewalk longitudinal slope cannot
exceed the slope of the road. Please
adjust the plans so that sidewalk is not
steeper than the road.
Please include measurements from the
centerline on Hopkins and Aspen to
ensure enough space exists for both
vehicle and bike lanes.
Alley directs runoff to low point on
sidewalk. Puddling will occur at north
side of alley crossing. Please adjust
plans to prevent puddling.
The water service line has been added to
the North Swale to 24" Catch Basin
Profile on sheet C-110
The sidewalk has been moved to
accommodate this 2' set back.
The sidewalk slope was reduced as much as
possible but due to the tree just north of the
alley the sidewalk elevation was required to
be raised to limit disturbance to the roots.
Dimension have been added to sheet C-111
A sidewalk ramp has been added which
slope up from the alley. This directs runoff
back to the curb and gutter. The low point is
now the flow line of the alley cross pan. See
sheet C-108 for detailed grading.
City of Aspen
Received
4/24/17
Building Department
Page Label: C-110
Author: mikeh
Date: 3/7/2017 9:27:20 AM
File Name: Plan Set.2017.01.pdf
Low point with no conveyance.
Even with inlet in landscaping
area, during the winter months
puddling and icing will be a huge
issue. Excess infrastructure
within the ROW will not be
allowed. No low point will be
allowed on the sidewalk. Please
adjust plans.
Page Label: C-110
Author: mikeh
Date: 3/3/2017 3:02:01 PM
File Name: Plan Set.2017.01.pdf
Sidewalk will be allowed to be 5'
wide in order to preserve trees.
Please hold the southern limit
and adjust sidewalk width to 5',
only along Hopkins.
Page Label: C-112
Author: mikeh
Date: 2/27/2017 12:45:51 PM
File Name: Plan Set.2017.01.pdf
Please provide a plan view that
depicts where each cross
section is located.
All cross sections must have
slope labels for sidewalk and
landscape buffer.
Page Label: C-112
Author: mikeh
Date: 2/27/2017 12:44:06 PM
File Name: Plan Set.2017.01.pdf
ADA ramp must be 6' wide to be
consistent with sidewalk. Please
adjust plans.
Page Label: C-114
Author: mikeh
Date: 3/7/2017 9:24:24 AM
File Name: Plan Set.2017.01.pdf
Plans call for curb stop, but the
service line is 4". A 4" line
requires the proper valve and
not a curb stop. Please adjust
the plans.
Low point with no conveyance. Even
with inlet in landscaping area, during the
winter months puddling and icing will be
a huge issue. Excess infrastructure
within the ROW will not be allowed. No
low point will be allowed on the sidewalk.
Please adjust plans.
Sidewalk will be allowed to be 5' wide in
order to preserve trees. Please hold the
southern limit and adjust sidewalk width
to 5', only along Hopkins.
Please provide a plan view that depicts
where each cross section is located.
All cross sections must have slope labels
for sidewalk and landscape buffer.
ADA ramp must be 6' wide to be
consistent with sidewalk. Please adjust
plans.
Plans call for curb stop, but the service
line is 4". A 4" line requires the proper
valve and not a curb stop. Please adjust
the plans.
This area has been re-graded. the sidewalk
profile still has a low point but due to the
cross-slope of the new alley ramp flow is
directed to the C&G. See sheet C-108.
The Hopkins sidewalk along the
cottonwoods has been reduced to a 5' width.
A side walk cross-section key sheet has
been added. See sheet C-114.
ADA ramps are now 6' wide.
The 4" water service has been redesigned
with all 4" D.I.P. parts. See sheet C-117.
City of Aspen
Received
4/24/17
Building Department
Page Label: C-114
Author: mikeh
Date: 2/28/2017 11:12:04 AM
File Name: Plan Set.2017.01.pdf
Water main crossing must be
shown on storm pipe profile.
Please adjust plans.
Page Label: C-114
Author: mikeh
Date: 3/9/2017 2:56:37 PM
File Name: Plan Set.2017.01.pdf
Demo Plan calls for the
relocation of electrical manhole.
Utility plan must depict new
location. Please adjust plans to
include new electrical manhole
location.
TM is large vault. Relocation or
abandonment must be verified
with appropriate entity. It is my
understanding City fiber runs
into vault.
Page Label: C-114
Author: mikeh
Date: 3/9/2017 2:47:33 PM
File Name: Plan Set.2017.01.pdf
Profiles for service line and
hydrant line must be provided.
Profiles must include all fittings,
bury depths, traffic flange
elevation for hydrant line, pipe
materials, and other pertinent
information. Please include
profiles in the plans.
Page Label: C-114
Author: mikeh
Date: 3/9/2017 2:54:21 PM
File Name: Plan Set.2017.01.pdf
In order to limit length of service
line and create proper
separation from storm line,
please bend the water service
closer to the water main. Also,
less fittings and bends is ideal.
Please only have one bend in
the service line.
Page Label: C-114
Author: mikeh
Date: 3/9/2017 2:02:33 PM
File Name: Plan Set.2017.01.pdf
.
Water main crossing must be shown on
storm pipe profile. Please adjust plans.
Demo Plan calls for the relocation of
electrical manhole. Utility plan must
depict new location. Please adjust plans
to include new electrical manhole
location.
TM is large vault. Relocation or
abandonment must be verified with
appropriate entity. It is my understanding
City fiber runs into vault.
Profiles for service line and hydrant
line must be provided. Profiles must
include all fittings, bury depths,
traffic flange elevation for hydrant
line, pipe materials, and other
pertinent information. Please
include profiles in the plans.
In order to limit length of service line and create proper
separation from storm line, please bend the water
service closer to the water main. Also, less fittings and
bends is ideal. Please only have one bend in the
service line.
The water main has been depicted on the
storm drain profiles see sheet C-110.
Separation has also been dimensioned.
Coorispondence with Qwest has taken place
and the vault was opened. The vault
dimensions are now shown on the utility plan
sheet C-117. Coordination with Qwest will
take place to relocate the lid.
Hydrant and service line profiles have been
added to sheet C-117.
There is only one bend outside of the property within the ROW. the other
bend is on the property and is the owners responsibility. Also avoiding
the large landscape benches would be wise if the line were to fail in the
future. Trees on the north side of the structure have also limited us to
entering the building from the west. Two 45 deg bends are recomended
vs. a 90 deg to enter the building perpendicular.
Valves have been moved out of the curb and
gutter. See sheet C-117.
City of Aspen
Received
4/24/17
Building Department
Page Label: C-114
Author: mikeh
Date: 2/23/2017 10:01:39 AM
File Name: Plan Set.2017.01.pdf
New locations must be depicted
on plans. Please adjust plans.
Page Label: C-114
Author: mikeh
Date: 2/27/2017 1:57:43 PM
File Name: Plan Set.2017.01.pdf
Easement must be supplied for
the transformer. Mike Horvath
can supply standard easement
language required. Please
create an easement exhibit and
agreement for review.
Page Label: C-114
Author: mikeh
Date: 3/2/2017 2:18:05 PM
File Name: Plan Set.2017.01.pdf
Electric service must be depicted
on plans and pipe profiles with
amount of storm water
infrastructure in vicinity. Primary
line must be located outside of
bio-retention area. Please adjust
plans to include location of
electrical service line.
Page Label: C-114
Author: mikeh
Date: 3/7/2017 9:24:52 AM
File Name: Plan Set.2017.01.pdf
Easterly and westerly most
valves must be located within
asphalt. The valve between
service line and hydrant line is
unnecessary and can be
removed. Please adjust the
plans.
Page Label: C-114
Author: mikeh
Date: 3/8/2017 10:43:45 AM
File Name: Plan Set.2017.01.pdf
Please also call out existing
water service line abandonment
per city standards on this sheet
as well.
New locations must be depicted on
plans. Please adjust plans.
Easement must be supplied for the
transformer. Mike Horvath can supply
standard easement language required.
Please create an easement exhibit and
agreement for review.
Electric service must be depicted on
plans and pipe profiles with amount of
storm water infrastructure in vicinity.
Primary line must be located outside of
bio-retention area. Please adjust plans to
include location of electrical service line.
Easterly and westerly most valves must
be located within asphalt. The valve
between service line and hydrant line is
unnecessary and can be removed.
Please adjust the plans.
Please also call out existing water
service line abandonment per city
standards on this sheet as well.
Relocation of the gas meter has been called
out on sheet C-117.
An easement exhibit has been provided with
the easement agreement form.
An electrical line has been shown on C-117
running from the old transformer location to
the new transformer.
Valves have been relocated out of the curb
and gutter. See sheet C-117.
Abandonment of the existing water service
has been called out. See Sheet C-117.
City of Aspen
Received
4/24/17
Building Department
Page Label: C-115
Author: mikeh
Date: 3/7/2017 2:37:14 PM
File Name: Plan Set.2017.01.pdf
No excavation is allowed for
sidewalk. 10" excavation will not
be allowed in vicinity of trees.
Please adjust the detail to
exclude excavation.
Page Label: C-116
Author: mikeh
Date: 2/28/2017 11:10:17 AM
File Name: Plan Set.2017.01.pdf
Typical Water Service Detail
does not apply to this project.
Detail is for taps 2" or smaller.
Please remove the detail from
the plan set and include relevant
detail as necessary.
Page Label: C-116
Author: mikeh
Date: 2/27/2017 4:49:05 PM
File Name: Plan Set.2017.01.pdf
No detail for the walls containing
orfices and weirs is provided.
Please provide details for the
walls of the Bio-swale areas.
Page Label: C-116
Author: mikeh
Date: 2/27/2017 4:50:12 PM
File Name: Plan Set.2017.01.pdf
More information on the
bio-media is required. Please
provide a detail for the soil
profile of the bio-media and rock
beds that complies with the
URMP.
Page Label: GX-001
Author: mikeh
Date: 3/2/2017 10:48:44 AM
File Name: Plan Set.2017.01.pdf
All plans must be for
construction. Please adjust
plans.
No excavation is allowed for sidewalk.
10" excavation will not be allowed in
vicinity of trees. Please adjust the detail
to exclude excavation.
Typical Water Service Detail does not
apply to this project. Detail is for taps 2"
or smaller. Please remove the detail
from the plan set and include relevant
detail as necessary.
No detail for the walls containing orfices
and weirs is provided. Please provide
details for the walls of the Bio-swale
areas.
More information on the bio-media is
required. Please provide a detail for the
soil profile of the bio-media and rock
beds that complies with the URMP.
All plans must be for construction.
Please adjust plans.
This call out has been removed from the
detail.
This detail has been removed and the water
service profile has been added to sheet
C-117
Cross-sections through the proposed weirs
have been added. See Sheet C-109.
A cross-section / detail has also been added.
See Sheet C-109.
This has been adjusted.
City of Aspen
Received
4/24/17
Building Department
Page Label: L6.2
Author: mikeh
Date: 3/2/2017 9:50:57 AM
File Name: Plan Set.2017.01.pdf
Clearances for transformer must
be maintained. 3' on N, E, & W
sides and 10' to the South.
Please adjust landscaping plan.
jgjuhgugkuy
A
Clearances for transformer must be
maintained. 3' on N, E, & W sides and
10' to the South. Please adjust
landscaping plan.
The plants surrounding
the transformer are small
plants and shrubs.
City of Aspen
Received
4/24/17
Building Department
Markup Summary Drainage Report.2017.01 3-10-2017
Page Label: 10
Author: mikeh
Date: 2/27/2017 4:45:46 PM
File Name: Drainage Report.2017.01.pdf
Calculations must be provided
that prove the WQCV infiltrates
into the media and rock bed
before over topping the
proposed weirs separating the
bio-swale areas. Please provide
infiltration calculations to ensure
WQCV is treated.
Drainage Report.2017.01.pdf (3)
Page Label: 10
Author: mikeh
Date: 2/27/2017 4:43:59 PM
File Name: Drainage Report.2017.01.pdf
Drain time calculations need to
be supplied. The WQCV BMP
must drain within 12 hours.
Please provide drain time
calculations.
Page Label: 10
Author: mikeh
Date: 2/27/2017 4:37:38 PM
File Name: Drainage Report.2017.01.pdf
Inlet sizing calculations must be
provided for the street inlet at the
corner of Aspen and Hopkins.
Please provide capacity
calculations for the street inlet.
At the bottom of each layer of scr
to the 100yr historic peak flow wh
weir. In other words the effective
elevation when the 100 peak flow
along with section 5.8.1 of the UR
Calculations must be provided that prove
the WQCV infiltrates into the media and
rock bed before over topping the
proposed weirs separating the bio-swale
areas. Please provide infiltration
calculations to ensure WQCV is treated.
10
calculated during the 100 yr. event is shown in the appendix. This water
to size the orifice plates.
creened rock is an orifice plate. This orifice plate restricts the flow down
when the water level reached the 100yr developed elevation flow over the
e head elevation for sizing the orifice was derived from the water surface
w is flowing over the weir. Below is a table showing the values used
URMP.
Drain time calculations need to be
supplied. The WQCV BMP must drain
within 12 hours. Please provide drain
time calculations.
5.2 Inlet
Inlets were
used to siz
of 0.04’ w
was used f
will be set
selected tre
Sub Basin and Recta
Inlet ID B
S
SLOT DRAIN
ALLEY TRENCH DRAIN
Sub Basin and Circ
Inlet ID
Inlet sizing calculations must be provided
for the street inlet at the corner of Aspen
and Hopkins. Please provide capacity
calculations for the street inlet.
Roof drains and storm pipes are now piped
directly into the screened rock media below
the planting material. This way infiltration will
not be restricted by the growing media.
For the 132.37 cubic feet of WQCV to drain in
under 12 hours the flow rate through the orifice
must be greater than 11 cubic feet per hour or
0.003 cfs. The 2.81" dia orifice would need less
head than its diameter to satisfy this.
Auto CADs express tools were utilized to
simulate the proposed curb inlet at the corner of
S. Aspen St. and Hopkins. This can be seen on
sheet C-103.