HomeMy WebLinkAboutFile Documents.200 S Aspen St.0007.2017 (42).ACBKCOMcheck Software Version 4.0.7.1
Interior Lighting Compliance Certificate
Project Title:
2015 IECC
Project Type:New Construction
Construction Site:
200 S Aspen St
Aspen, CO 81611
Owner/Agent:Designer/Contractor:
Aaron Humphrey
Alpenglow Lighting Design, Inc
4341 CR 113
Carbondale, CO 81623
970-948-2637
aaron@alpenglowinc.com
Project Information
Energy Code:
Hotel Lenado
Reduced interior lighting power. Requirements are implicitly enforced within interior lighting allowance calculations.
Additional Efficiency Package
Allowed Interior Lighting Power
A
Area Category
B
Floor Area
(ft2)
C
Allowed
Watts / ft2
D
Allowed Watts
(B X C)
1-Hotel 18425 0.78 14427
14427Total Allowed Watts =
Proposed Interior Lighting Power
E
(C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
1-Hotel
LED 1: L1: RECESSED DOWNLIGHT: LED Other Fixture Unit 16W:1 160 18 2880
LED 1 copy 1: L1: RECESSED DOWNLIGHT: LED Other Fixture Unit 16W:1 45 18 Exempt
Exemption:Sleeping Unit Lighting
LED 3: L3: RECESSED SHOWER LIGHT: LED Other Fixture Unit 13W:1 9 12 108
LED 5: L5: LINEAR LED COVE/UNDERCAB SYSTEM: LED Other Fixture Unit 103W:1 3 100 300
LED 6: L5A: LINEAR LED COVE SYSTEM: LED Other Fixture Unit 103W:1 22 100 2200
LED 6 copy 2: L5A: LINEAR LED COVE SYSTEM: LED Other Fixture Unit 103W:1 28 60 Exempt
Exemption:Sleeping Unit Lighting
LED 6 copy 1: L5A: LINEAR LED COVE SYSTEM: LED Other Fixture Unit 103W:1 19 60 Exempt
Exemption:Furniture-mounted Supplemental Task Lighting
LED 7: L6: 6" SURFACE SHALLOW: LED Other Fixture Unit 13W:1 14 14 Exempt
Exemption:Sleeping Unit Lighting
LED 8: L7: LED LINEAR LED COVE SYSTEM: LED Other Fixture Unit 103W:1 10 60 Exempt
Exemption:Sleeping Unit Lighting
LED 10: L9: 9" SURFACE SHALLOW: LED Other Fixture Unit 16W:1 55 17 935
LED 11: L10: ELEVATOR PIT LIGHT: LED Other Fixture Unit 40W:1 3 32 96
LED 12: L11: LINEAR INDUSTRIAL: LED Other Fixture Unit 40W:1 21 43 903
LED 13: L12: ADA SCONCE: LED Other Fixture Unit 46W:1 6 25 150
LED 14: L13: STEPLIGHT (POWER SUPPLY): LED Other Fixture Unit 28W:1 1 30 30
LED 15: L14: LINER SLOT (PER FOOT): LED Linear 8W:1 80 7 560
Project Title:
Data filename:
Hotel Lenado
C:\Users\stock\CloudStation\Active Projects\Forum Phi\200 S. Aspen St\Design\Calcs\Hotel Lenado
Lighting 110717.cck
11/09/17Report date:
91 ofPage
11/27/17
12/19
/
2
0
1
7
nickt
E
(C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
LED 17: L15A: DECORATIVE PENDANT: LED Other Fixture Unit 125W:1 1 160 160
LED 19 copy 1: L16: downlight: LED Other Fixture Unit 16W:1 43 10 430
LED 19: L17: DECORATIVE PENDANT: LED Other Fixture Unit 16W:1 5 50 250
LED 20: L18: FLOOR LAMP: LED Other Fixture Unit 16W:1 10 18 180
LED 21: L19: MINI BOLLARD: LED Other Fixture Unit 6.5W:1 5 9 45
LED 22: L20: READING LIGHT: LED Other Fixture Unit 13W:1 24 9 Exempt
Exemption:Sleeping Unit Lighting
LED 23: L21: DOWNLIGHT: LED Other Fixture Unit 28W:1 4 2 6
LED 24: L22: DECORATIVE: LED Other Fixture Unit 16W:1 6 10 60
LED 26: L24: LED TAPE: LED Other Fixture Unit 13W:1 8 50 Exempt
Exemption:Sleeping Unit Lighting
LED 27: L25: PENDANT: LED Other Fixture Unit 13W:1 2 30 60
LED 30: D: DECORATIVE: LED A Lamp 13W:1 28 14 392
LED 30: X1: EXIT: LED Other Fixture Unit 6.5W:1 18 6 Exempt
Exemption:Exit Signs, Safety or Emergency Lighting
9745Total Proposed Watts =
Interior Lighting Compliance Statement
Compliance Statement: The proposed interior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed interior lighting systems have been
designed to meet the 2015 IECC requirements in COMcheck Version 4.0.7.1 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist.
Name - Title Signature Date
Interior Lighting PASSES: Design 32% better than code
Project Title:
Data filename:
Hotel Lenado
C:\Users\stock\CloudStation\Active Projects\Forum Phi\200 S. Aspen St\Design\Calcs\Hotel Lenado
Lighting 110717.cck
11/09/17Report date:
92 ofPage
Aaron J. Humphrey, President 11/09/17
11/27/17
12/19
/
2
0
1
7
nickt
COMcheck Software Version 4.0.7.1
Exterior Lighting Compliance Certificate
Project Title:
2015 IECC
Project Type:New Construction
Construction Site:
200 S Aspen St
Aspen, CO 81611
Owner/Agent:Designer/Contractor:
Aaron Humphrey
Alpenglow Lighting Design, Inc
4341 CR 113
Carbondale, CO 81623
970-948-2637
aaron@alpenglowinc.com
Project Information
Energy Code:
Hotel Lenado
2 (Neighborhood business district)Exterior Lighting Zone
Allowed Exterior Lighting Power
A
Area/Surface Category
B
Quantity
C
Allowed
Watts / Unit
D
Tradable
Wattage
E
Allowed Watts
(B X C)
SIDEWALK (Walkway < 10 feet wide)2590 ft of 0.7 Yes 1813
ROOF DECK (Special feature area)1445 ft2 0.14 Yes 202
Total Tradable Watts (a) =
Total Allowed Watts =
Total Allowed Supplemental Watts (b) =
2015
2015
600
(a)Wattage tradeoffs are only allowed between tradable areas/surfaces.
(b)A supplemental allowance equal to 600 watts may be applied toward compliance of both non-tradable and tradable areas/surfaces.
Proposed Exterior Lighting Power
E
(C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
SIDEWALK ( Walkway < 10 feet wide 2590 ft of walkway length): Tradable Wattage
LED 1: L13: LED STEPLIGHT (POWER SUPPLY): LED Other Fixture Unit 46W:1 1 30 30
LED 5: L21: FRAME LIGHT (POWER SUPPLY): LED Other Fixture Unit 103W:1 7 100 700
LED 6: L2: RECESSED DOWNLIGTH: LED Other Fixture Unit 6.5W:1 1 12 12
LED 7: L23: SCONCE: LED Other Fixture Unit 95W:1 3 100 300
ROOF DECK ( Special feature area 1445 ft2): Tradable Wattage
LED 1 copy 1: L13: LED STEPLIGHT (POWER SUPPLY): LED Other Fixture Unit 46W:1 1 30 30
LED 3: L18: FLOOR LAMP: LED Other Fixture Unit 16W:1 6 18 108
LED 4: L19: MINI BOLLARD: LED Other Fixture Unit 6.5W:1 2 9 18
1198Total Tradable Proposed Watts =
Project Title:
Data filename:
Hotel Lenado
C:\Users\stock\CloudStation\Active Projects\Forum Phi\200 S. Aspen St\Design\Calcs\Hotel Lenado
Lighting 110717.cck
11/09/17Report date:
93 ofPage
11/27/17
12/19
/
2
0
1
7
nickt
Exterior Lighting Compliance Statement
Compliance Statement: The proposed exterior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed exterior lighting systems have been
designed to meet the 2015 IECC requirements in COMcheck Version 4.0.7.1 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist.
Name - Title Signature Date
Exterior Lighting PASSES: Design 54% better than code
Project Title:
Data filename:
Hotel Lenado
C:\Users\stock\CloudStation\Active Projects\Forum Phi\200 S. Aspen St\Design\Calcs\Hotel Lenado
Lighting 110717.cck
11/09/17Report date:
94 ofPage
Aaron J. Humphrey, President 11/09/17
11/27/17
12/19
/
2
0
1
7
nickt
Inspection Checklist
Requirements: 100.0% were addressed directly in the COMcheck software
COMcheck Software Version 4.0.7.1
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Energy Code: 2015 IECC
Section
#
& Req.ID
Plan Review Complies?Comments/Assumptions
C103.2
[PR4]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the interior lighting
and electrical systems and equipment
and document where exceptions to
the standard are claimed. Information
provided should include interior
lighting power calculations, wattage of
bulbs and ballasts, transformers and
control devices.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C103.2
[PR8]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the exterior lighting
and electrical systems and equipment
and document where exceptions to
the standard are claimed. Information
provided should include exterior
lighting power calculations, wattage of
bulbs and ballasts, transformers and
control devices.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C406
[PR9]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the additional energy
efficiency package options.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Hotel Lenado
C:\Users\stock\CloudStation\Active Projects\Forum Phi\200 S. Aspen St\Design\Calcs\Hotel Lenado
Lighting 110717.cck
11/09/17Report date:
95 ofPage
X
X
X 11/27/17
12/19
/
2
0
1
7
nickt
Section
#
& Req.ID
Rough-In Electrical Inspection Complies?Comments/Assumptions
C405.2.1
[EL15]1
Lighting controls installed to uniformly
reduce the lighting load by at least
50%.
Complies
Does Not
Not Observable
Not Applicable
Exception: Lighting that is related to means of egress in
stairways, ramps, corridors, or emergency routes.
C405.2.1
[EL18]1
Occupancy sensors installed in
required spaces.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C405.2.1,
C405.2.2.
3
[EL23]2
Independent lighting controls installed
per approved lighting plans and all
manual controls readily accessible and
visible to occupants.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C405.2.2.
1
[EL22]2
Automatic controls to shut off all
building lighting installed in all
buildings.
Complies
Does Not
Not Observable
Not Applicable
Exception: Lighting controlled by occupancy sensors.
C405.2.3
[EL16]2
Daylight zones provided with
individual controls that control the
lights independent of general area
lighting.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C405.2.3,
C405.2.3.
1,
C405.2.3.
2
[EL20]1
Primary sidelighted areas are
equipped with required lighting
controls.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C405.2.3,
C405.2.3.
1,
C405.2.3.
3
[EL21]1
Enclosed spaces with daylight area
under skylights and rooftop monitors
are equipped with required lighting
controls.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C405.2.4
[EL4]1
Separate lighting control devices for
specific uses installed per approved
lighting plans.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C405.2.4
[EL8]1
Additional interior lighting power
allowed for special functions per the
approved lighting plans and is
automatically controlled and
separated from general lighting.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C405.2.5
[EL25]null
Automatic lighting controls for exterior
lighting installed. Controls will be
daylight controlled, set based on
business operation time-of-day, or
reduce connected lighting > 30%.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C405.3
[EL6]1
Exit signs do not exceed 5 watts per
face.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Hotel Lenado
C:\Users\stock\CloudStation\Active Projects\Forum Phi\200 S. Aspen St\Design\Calcs\Hotel Lenado
Lighting 110717.cck
11/09/17Report date:
96 ofPage
X
X
X
X
X
X
X
X
X
X
X
11/27/17
12/19
/
2
0
1
7
nickt
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Hotel Lenado
C:\Users\stock\CloudStation\Active Projects\Forum Phi\200 S. Aspen St\Design\Calcs\Hotel Lenado
Lighting 110717.cck
11/09/17Report date:
97 ofPage
11/27/17
12/19
/
2
0
1
7
nickt
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
C303.3,
C408.2.5.
2
[FI17]3
Furnished O&M instructions for
systems and equipment to the
building owner or designated
representative.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C405.4.1
[FI18]1
Interior installed lamp and fixture
lighting power is consistent with what
is shown on the approved lighting
plans, demonstrating proposed watts
are less than or equal to allowed
watts.
Complies
Does Not
Not Observable
Not Applicable
See the Interior Lighting fixture schedule for values.
C405.5.1
[FI19]1
Exterior lighting power is consistent
with what is shown on the approved
lighting plans, demonstrating
proposed watts are less than or equal
to allowed watts.
Complies
Does Not
Not Observable
Not Applicable
See the Exterior Lighting fixture schedule for values.
C408.2.5.
1
[FI16]3
Furnished as-built drawings for
electric power systems within 90 days
of system acceptance.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.3
[FI33]1
Lighting systems have been tested to
ensure proper calibration, adjustment,
programming, and operation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Hotel Lenado
C:\Users\stock\CloudStation\Active Projects\Forum Phi\200 S. Aspen St\Design\Calcs\Hotel Lenado
Lighting 110717.cck
11/09/17Report date:
98 ofPage
X
X
X
X
X
11/09/17 Comments/Revisions:
1. Removed egress lighting exemption from interior common space fixtures.
2. Revised interior fixture counts to remove fixtures from AHU residential units.
3. Revised interior exemptions for sleeping unit lighting.
4. Moved certain exterior fixtures previously exempted as egress lighting on interior
count to exterior count.
11/27/17
12/19
/
2
0
1
7
nickt
Project Title:
Data filename:
Hotel Lenado
C:\Users\stock\CloudStation\Active Projects\Forum Phi\200 S. Aspen St\Design\Calcs\Hotel Lenado
Lighting 110717.cck
11/09/17Report date:
99 ofPage
11/27/17
12/19
/
2
0
1
7
nickt