HomeMy WebLinkAboutFile Documents.232 E Main St.0132.2018 (115).ACBKCOMcheck Software Version 4.1.1.0
Mechanical Compliance Certificate
Project Title:
2015 IECC
Project Type:New Construction
Permit No..0132.2018.ACBK
Permit Date:2018
Location:Aspen, Colorado
Climate Zone:7
Construction Site:
232 E Main St
Aspen, CO 81611
Owner/Agent:
Brad Hribar
Centaur Construction
1200 W Lake St Suite 200
Chicago, IL 60607
3127148519
bhribar@centaurco.com
Designer/Contractor:
Bryan Urban
AEC
40801 US Hwy 6
Ste 214
Avon, CO 81620
970-748-8520
burban@aec-vail.com
Project Information
Energy Code:
232 E Main Core and Shell
Reduced interior lighting power. Requirements are implicitly enforced within interior lighting allowance calculations.
Additional Efficiency Package(s)
Mechanical Systems List
Quantity System Type & Description
Heating: 1 each - Central Furnace, Gas, Capacity = 150 kBtu/h
Proposed Efficiency = 80.00% Et, Required Efficiency: 80.00 % Et or 78% AFUE
Cooling: 1 each - Single Package DX Unit, Capacity = 73 kBtu/h, Evaporatively Cooled Condenser, Air Economizer
Proposed Efficiency = 12.80 EER, Required Efficiency: 11.90 EER + 12.1 IEER
Fan System: RTU-1 FAN -- Compliance (Brake HP method) : Passes
Fans:
RTU 1 FAN Supply, Multi-Zone VAV, 3000 CFM, 5.0 motor nameplate hp, 2.4 design brake hp (2.4 max. BHP), 80.0 fan efficiency
grade
1 RTU-1 (Multiple-Zone):
Heating: 1 each - Central Furnace, Gas, Capacity = 150 kBtu/h
Proposed Efficiency = 80.00% Et, Required Efficiency: 80.00 % Et or 78% AFUE
Cooling: 1 each - Single Package DX Unit, Capacity = 87 kBtu/h, Air-Cooled Condenser, Air Economizer
Proposed Efficiency = 13.50 EER, Required Efficiency: 11.00 EER + 12.6 IEER
Fan System: RTU-1 FAN -- Compliance (Brake HP method) : Passes
Fans:
RTU 1 FAN Supply, Multi-Zone VAV, 3000 CFM, 5.0 motor nameplate hp, 2.4 design brake hp (2.4 max. BHP), 80.0 fan efficiency
grade
1 RTU-2 (Multiple-Zone):
Heating: 1 each - Central Furnace, Gas, Capacity = 72 kBtu/h
Proposed Efficiency = 82.00% Et, Required Efficiency: 80.00 % Et or 78% AFUE
Cooling: 1 each - Single Package DX Unit, Capacity = 30 kBtu/h, Air-Cooled Condenser, Air Economizer
Proposed Efficiency = 15.50 SEER, Required Efficiency: 14.00 SEER
Fan System: RTU-3 FAN -- Compliance (Brake HP method) : Passes
Fans:
RTU 3 FAN Supply, Multi-Zone VAV, 1380 CFM, 1.5 motor nameplate hp, 0.9 design brake hp (0.9 max. BHP), 80.0 fan efficiency
grade
1 RTU-3 (Multiple-Zone):
Project Title:
Data filename:
232 E Main Core and Shell
P:\Current Projects\18029.00 - 232 East Main Street\Calculations\COMcheck\Mechanical
COMcheck.cck
12/18/19Report date:
171 ofPage12/20/2019
Quantity System Type & Description
Heating: 1 each - Central Furnace, Gas, Capacity = 72 kBtu/h
Proposed Efficiency = 82.00% Et, Required Efficiency: 80.00 % Et or 78% AFUE
Cooling: 1 each - Single Package DX Unit, Capacity = 41 kBtu/h, Air-Cooled Condenser, Air Economizer
Proposed Efficiency = 16.40 SEER, Required Efficiency: 14.00 SEER
Fan System: RTU-4 FAN -- Compliance (Brake HP method) : Passes
Fans:
RTU 4 FAN Supply, Multi-Zone VAV, 2000 CFM, 3.0 motor nameplate hp, 1.8 design brake hp (1.8 max. BHP), 80.0 fan efficiency
grade
1 RTU-4 (Multiple-Zone):
Heating: 1 each - Unit Heater (UH-1), Electric, Capacity = 3 kBtu/h
No minimum efficiency requirement applies
Fan System: None
3 UH-1 (Single Zone):
Heating: 1 each - Unit Heater (UH-2), Electric, Capacity = 5 kBtu/h
No minimum efficiency requirement applies
Fan System: None
1 UH-2 (Single Zone):
Heating: Hot Water Boiler, Capacity 1250 kBtu/h, Gas
Proposed Efficiency: 95.00 % Et, Required Efficiency: 80.00 % Et
1 Boiler-1:
Electric Storage Water Heater, Capacity: 7 gallons
Proposed Efficiency: 2.00 SL, %/h (if > 12 kW), Required Efficiency: 4.16 SL, %/h (if > 12 kW)
1 WH-1:
Mechanical Compliance Statement
Compliance Statement: The proposed mechanical design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed mechanical systems have been
designed to meet the 2015 IECC requirements in COMcheck Version 4.1.1.0 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist.
Name - Title Signature Date
Project Title:
Data filename:
232 E Main Core and Shell
P:\Current Projects\18029.00 - 232 East Main Street\Calculations\COMcheck\Mechanical
COMcheck.cck
12/18/19Report date:
172 ofPage
Bryan Urban 12/18/19
12/20/2019