HomeMy WebLinkAboutFile Documents.232 E Main St.0132.2018 (116).ACBK 232 E. Main St. Aspen, Colorado Non-Vented Roof Assembly Dew Point Calculation 09.05.18 The calculation must show that the temperature of the condensing surface (T interface) is greater than 41 degrees F at 35% relative humidity. T(interface) = R(exterior) / R(total) x [T(inside) – T(outside)] + T(outside) Where: T(interface) = temperature at the sheathing/insulation interface or the temperature of the first condensing surface. Must be greater than 41 deg F. R(exterior) = the R-value of the exterior sheathing R(total) = the total R-value of the entire assembly T(inside) = 70 deg F T(outside) = 19.8 deg F (mean daily temp) Wood Shingle Roof Assembly: Thickness:Component:R-Value: Outside air layer 0.17 5/8”Wood Shingle 1.6 40 mil Ice and Water Shield 0.15 3/4“Plywood Sheathing 0.94 4”Rigid insulation 20 - - - - - - - - - - -condensing surface - - - - - - - - - 3/4“Plywood Sheathing 0.94 Inside air layer 0.65 R(exterior) = 0.17 + 1.6 + 0.15 + 0.94 + 20 = 22.86 R(total) = 22.86 + 0.94 + 0.65 = 24.45 T(inside) = 70 deg F T(outside) = 19.8 deg F T(interface) = R(exterior) / R(total) x [T(inside) – T(outside)] + T(outside) T(interface) = 22.86/24.45 x [70 - 19.8] + 19.8 T(interface) = 66.92 deg F modif. architecture 1200 west lake street suite 200 chicago, il 60607 312.288.2009 12/26/2018 ACM Roof Assembly: Thickness:Component:R-Value: Outside air layer 0.17 6mm ACM Panel 0.86 4”Rigid insulation 20 - - - - - - - - - - -condensing surface - - - - - - - - - 40 mil Ice and Water Shield 0.15 5/8”Dens Deck 0.67 2”Metal Decking 0.00 Inside air layer 0.65 R(exterior) = 0.17 + 0.86 + 20 = 21.03 R(total) = 21.03 + 0.15 + 0.67 + 0.00 + 0.65 = 22.5 T(inside) = 70 deg F T(outside) = 19.8 deg F T(interface) = R(exterior) / R(total) x [T(inside) – T(outside)] + T(outside) T(interface) = 21.03/22.5 x [70 - 19.8] + 19.8 T(interface) = 66.52 deg F modif. architecture 1200 west lake street suite 200 chicago, il 60607 312.288.2009 12/26/2018