232 E. Main St.
Aspen, Colorado
List of Special Inspections and Tests - IBC 2015
09.05.18
Dear Building Official,
The following is a list of the required special inspections and tests for the construction of the
new building and site improvements for the Core and Shell building located at 305-307 South
Mill St.. The General Contractor is responsible to become familiar with all requirements of
Chapter 17 of the 2015 International Building Code.
Certificates of compliance for the fabrication of structural, load-bearing or lateral load-resisting
members or assemblies on the premises of a registered and approved fabricator in accordance
with Section 1704.2.5.1.
Reports of material properties verifying compliance with the requirements of
AWS D1.4 for weldability as specified in Section 26.6.4 of ACI 318 for
reinforcing bars in concrete complying with a standard other than ASTM A706 that
are to be welded
Special inspections and nondestructive testing of structural steel
elements in buildings, structures and portions thereof shall be in
accordance with the quality assurance inspection requirements of AISC 360.
Special inspections and qualification of welding special inspectors for
cold-formed steel floor and roof deck shall be in accordance with the quality
assurance inspection requirements of SDI QA/QC.
modif. architecture 1200 west lake street suite 200 chicago, il 60607 312.288.2009
12/26/2018
Special inspections of welding and qualifications of special
inspectors for reinforcing bars shall be in accordance with the requirements
of AWS D1.4 for special inspection and of AWS D1.4 for special inspector
qualification.
Special inspections and tests of masonry construction shall be performed
in accordance with the quality assurance program requirements of TMS 402/ACI
530/ASCE 5 and TMS 602/ACI 530.1/ASCE 6.
Special inspections and tests of existing site soil conditions, fill
placement and load-bearing requirements shall be performed in accordance with
this section and Table 1705.6. The approved geotechnical report and the
construction documents prepared by the registered design professionals
shall be used to determine compliance. During fill placement, the special
inspector shall verify that proper materials and procedures are used in
accordance with the provisions of the approved geotechnical report.
modif. architecture 1200 west lake street suite 200 chicago, il 60607 312.288.2009
12/26/2018
Periodic special inspection is required for fastening of the following
systems and components:
1. Roof covering, roof deck and roof framing connections.
2. Exterior wall covering and wall connections to roof and floor diaphragms and
Framing.
Special inspections for seismic resistance shall be required as specified
in Sections 1705.12.1 through 1705.12.9, unless exempted by the exceptions of
Section 1704.2.
Special inspections of structural steel in the seismic force resisting
systems of buildings and structures assigned to Seismic Design Category
B, C, D, E or F shall be performed in accordance with the quality assurance
requirements of AISC 341.
Special inspections of structural steel elements in the seismic
Force resisting systems of buildings and structures assigned to Seismic Design
Category B, C, D, E or F other than those covered in Section 1705.12.1.1,
including struts, collectors, chords and foundation elements, shall be performed
in accordance with the quality assurance requirements of AISC 341.
modif. architecture 1200 west lake street suite 200 chicago, il 60607 312.288.2009
12/26/2018
For the seismic force-resisting systems of structures assigned to Seismic
Design Category C, D, E or F:
1. Continuous special inspection shall be required during field gluing
operations of elements of the seismic force-resisting system.
2. Periodic special inspection shall be required for nailing, bolting,
anchoring and other fastening of elements of the seismic force-resisting system,
including wood shear walls, wood diaphragms, drag struts, braces, shear panels
and hold-downs.
1705.12.3 Cold-formed steel light-frame construction. For the seismic force-resisting systems of
structures assigned to Seismic Design Category C, D, E or F, periodic special inspection shall
be required:
1. For welding operations of elements of the seismic force-resisting system; and
2. For screw attachment, bolting, anchoring and other fastening of elements of
the seismic force-resisting system, including shear walls, braces, diaphragms,
collectors (drag struts) and hold-downs.
Periodic special inspection of plumbing, mechanical and electrical
components shall be required for the following:
1. Anchorage of electrical equipment for emergency and standby power systems in
structures assigned to Seismic Design Category C, D, E or F.
2. Installation and anchorage of vibration isolation systems in structures
assigned to Seismic Design Category C, D, E or F where the approved
construction documents require a nominal clearance of 1/4
inch (6.4 mm) or less between the equipment support frame and restraint.
Nondestructive testing of structural steel in the seismic force resisting systems
of buildings and structures assigned to Seismic Design Category B, C, D,
E or F shall be performed in accordance with the quality assurance requirements
of AISC 341.
Special inspections and tests of sprayed fire-resistant materials applied
to floor, roof and wall assemblies and structural members shall be performed in
accordance with Sections 1705.14.1 through 1705.14.6. Special inspections
shall be based on the fire-resistance design as designated in the approved
construction documents. The tests set forth in this section shall be based
on samplings from specific floor, roof and wall assemblies and structural
members. Special inspections and tests shall be performed after the rough
installation of electrical, automatic sprinkler, mechanical and plumbing systems
and suspension systems for ceilings, where applicable.
modif. architecture 1200 west lake street suite 200 chicago, il 60607 312.288.2009
12/26/2018
Inspections of penetration firestop systems that are tested and listed <in
accordance with Sections 714.3.1.2 and 714.4.2 shall be conducted by an
approved agency in accordance with ASTM E2174.
Inspection of fire-resistant joint systems that are tested and listed in
accordance with Sections 715.3 and 715.4 shall be conducted by an approved
agency <in accordance with ASTM E2393.
End of list.
*************