Loading...
HomeMy WebLinkAboutFile Documents.232 E Main St.0132.2018 (123).ACBK 232 E. Main St. Aspen, Colorado List of Special Inspections and Tests - IBC 2015 09.05.18 Dear Building Official, The following is a list of the required special inspections and tests for the construction of the new building and site improvements for the Core and Shell building located at 305-307 South Mill St.. The General Contractor is responsible to become familiar with all requirements of Chapter 17 of the 2015 International Building Code. Certificates of compliance for the fabrication of structural, load-bearing or lateral load-resisting members or assemblies on the premises of a registered and approved fabricator in accordance with Section 1704.2.5.1. Reports of material properties verifying compliance with the requirements of AWS D1.4 for weldability as specified in Section 26.6.4 of ACI 318 for reinforcing bars in concrete complying with a standard other than ASTM A706 that are to be welded Special inspections and nondestructive testing of structural steel elements in buildings, structures and portions thereof shall be in accordance with the quality assurance inspection requirements of AISC 360. Special inspections and qualification of welding special inspectors for cold-formed steel floor and roof deck shall be in accordance with the quality assurance inspection requirements of SDI QA/QC. modif. architecture 1200 west lake street suite 200 chicago, il 60607 312.288.2009 12/26/2018 Special inspections of welding and qualifications of special inspectors for reinforcing bars shall be in accordance with the requirements of AWS D1.4 for special inspection and of AWS D1.4 for special inspector qualification. Special inspections and tests of masonry construction shall be performed in accordance with the quality assurance program requirements of TMS 402/ACI 530/ASCE 5 and TMS 602/ACI 530.1/ASCE 6. Special inspections and tests of existing site soil conditions, fill placement and load-bearing requirements shall be performed in accordance with this section and Table 1705.6. The approved geotechnical report and the construction documents prepared by the registered design professionals shall be used to determine compliance. During fill placement, the special inspector shall verify that proper materials and procedures are used in accordance with the provisions of the approved geotechnical report. modif. architecture 1200 west lake street suite 200 chicago, il 60607 312.288.2009 12/26/2018 Periodic special inspection is required for fastening of the following systems and components: 1. Roof covering, roof deck and roof framing connections. 2. Exterior wall covering and wall connections to roof and floor diaphragms and Framing. Special inspections for seismic resistance shall be required as specified in Sections 1705.12.1 through 1705.12.9, unless exempted by the exceptions of Section 1704.2. Special inspections of structural steel in the seismic force resisting systems of buildings and structures assigned to Seismic Design Category B, C, D, E or F shall be performed in accordance with the quality assurance requirements of AISC 341. Special inspections of structural steel elements in the seismic Force resisting systems of buildings and structures assigned to Seismic Design Category B, C, D, E or F other than those covered in Section 1705.12.1.1, including struts, collectors, chords and foundation elements, shall be performed in accordance with the quality assurance requirements of AISC 341. modif. architecture 1200 west lake street suite 200 chicago, il 60607 312.288.2009 12/26/2018 For the seismic force-resisting systems of structures assigned to Seismic Design Category C, D, E or F: 1. Continuous special inspection shall be required during field gluing operations of elements of the seismic force-resisting system. 2. Periodic special inspection shall be required for nailing, bolting, anchoring and other fastening of elements of the seismic force-resisting system, including wood shear walls, wood diaphragms, drag struts, braces, shear panels and hold-downs. 1705.12.3 Cold-formed steel light-frame construction. For the seismic force-resisting systems of structures assigned to Seismic Design Category C, D, E or F, periodic special inspection shall be required: 1. For welding operations of elements of the seismic force-resisting system; and 2. For screw attachment, bolting, anchoring and other fastening of elements of the seismic force-resisting system, including shear walls, braces, diaphragms, collectors (drag struts) and hold-downs. Periodic special inspection of plumbing, mechanical and electrical components shall be required for the following: 1. Anchorage of electrical equipment for emergency and standby power systems in structures assigned to Seismic Design Category C, D, E or F. 2. Installation and anchorage of vibration isolation systems in structures assigned to Seismic Design Category C, D, E or F where the approved construction documents require a nominal clearance of 1/4 inch (6.4 mm) or less between the equipment support frame and restraint. Nondestructive testing of structural steel in the seismic force resisting systems of buildings and structures assigned to Seismic Design Category B, C, D, E or F shall be performed in accordance with the quality assurance requirements of AISC 341. Special inspections and tests of sprayed fire-resistant materials applied to floor, roof and wall assemblies and structural members shall be performed in accordance with Sections 1705.14.1 through 1705.14.6. Special inspections shall be based on the fire-resistance design as designated in the approved construction documents. The tests set forth in this section shall be based on samplings from specific floor, roof and wall assemblies and structural members. Special inspections and tests shall be performed after the rough installation of electrical, automatic sprinkler, mechanical and plumbing systems and suspension systems for ceilings, where applicable. modif. architecture 1200 west lake street suite 200 chicago, il 60607 312.288.2009 12/26/2018 Inspections of penetration firestop systems that are tested and listed <in accordance with Sections 714.3.1.2 and 714.4.2 shall be conducted by an approved agency in accordance with ASTM E2174. Inspection of fire-resistant joint systems that are tested and listed in accordance with Sections 715.3 and 715.4 shall be conducted by an approved agency <in accordance with ASTM E2393. End of list. ************* Please contact me with any questions. Best regards, Stephen Coughlin, RA Owner/Architect Modif. Architecture modif. architecture 1200 west lake street suite 200 chicago, il 60607 312.288.2009 12/26/2018 Please stamp the special inspection program.