Loading...
HomeMy WebLinkAboutFile Documents.754 Moore Dr.0034.2018 (95).ARBK z Copyright 2016 The Cable Connection, Carson City, Nevada. All Rights Reserved. Engineering Analysis of Sphere Pass-Through Requirement of International Building Code The 2015 International Building Code (IBC) and 2015 International Residential Code (IRC) require that guardrail intermediate railings be spaced so as to prevent a 4.0 in. diameter sphere from passing through them. (IBC 1015.4/IRC R312.1.3) However, the code does not state that a load is to be applied to the 4.0 in. sphere. While the absence of that load specification is not critical to solid railing members, it may be important for wire rope railing infill, since it is flexible. Therefore, in the absence of IBC/CBC guidelines, a rational load requirement has been developed based on the following: The 2015 IRC Section R301.5 does address a requirement for railing infill by stating that railing infill must withstand a load of 50 lb applied over a 1.0 square foot area, applied horizontally and perpendicular to the railing plane. Applying that pressure over the projected area of a 4.0 in. diameter sphere, the resulting load on the sphere is calculated as follows: F= 50 lb/sq ft x 144 sq in/sq ft x p x (4.0 in) 2 = 4.36 lb 4 To allow for dynamic/impact loading, a conservative safety factor of 2.0 is applied: FMAX = 4.36 x 2.0 = 8.72 lb Therefore, 8.7 lb is used as the standard force applied to a 4.0 in. diameter sphere, which cable railing infill must not allow to pass in order to be IBC/CBC compliant. The railing infill case to be analyzed is for: .125 in. diameter, 1x19 construction, 316 stainless cables 48.0 in. unsupported cable span 3.125 in. cable spacing, center to center This represents the thinnest cable in our Ultra-tecy line, hence the largest space between cables, given our standard center to center cable spacing of 3.125 in. The 48 in. cable unsupported span was chosen to be convenient for both design and installation of the railing system. 09/18/2018 Page 2 of 10 The geometry of two adjacent cables, the cable guides, and the 4.0 inch test sphere are shown in Fig. 1. D = Sphere Diameter Sc = Center-Center Cable Spacing d = Cable Diameter LCG = Cable Unsupported Span Fig. 1 The deflection due to the sphere having been forced between the two cables is shown in Fig. 2. (Deflection shown at maximum.) Note that the cables are not fixed to the cable guides, but that they pass freely through them, and are ultimately fixed at a total cable length of LCT. D = Deflection of one Cable Fig. 2 09/18/2018 Page 3 of 10 The force that a cable exerts against the sphere is then calculated based on the deflection of the cables. The cables exert no force on the sphere until they are deflected from their rest position. Once deflected, the force of a cable on the sphere is calculated by trigonometry. The geometry and associated forces of one half of one cable are shown in Fig. 3 Fig. 3 A Mathcad worksheet was created to analyze the cable forces as a function of the cable deflection, D. The relationship of cable force on the sphere, P, to deflection, D, is described by: Eq. 1 Where: T = Cable Tension P = Force of One Cable on Sphere The vertical component of T acting on the sphere is proportional to the sine of the cable angle from horizontal, which is calculated by the term within the parentheses of Eq. 1. Since the cable tension acts on the sphere on either side, the net force of the cable on the sphere is double the vertical component of T. P ()2T  2 LCG 2   2     09/18/2018 Page 4 of 10 The cable tension increases as the sphere deflects and stretches the cable. The increase of cable tension with respect to deflection is calculated below: Eq. 2 LCT is the entire length of the cable between fixed ends. E125 is the effective Young’s Modulus of .125” diameter, 1x19 construction, type 316 stainless steel cable, which was determined by pull testing such cable and recording its elongation vs. applied tension. It is designated as an effective modulus since is it calculated based on the cross sectional area of a smooth rod of the same diameter as the nominal diameter of the stranded cable tested. Doing so then allows the cable to be treated as a solid rod for simplified calculation of its extension under load. The term within the parentheses calculates the strain imparted by the stretching of one half of the cable between the cable guides, which is then multiplied by the cable area and the effective modulus to give the tension increase imparted by the deflection. The resulting tension increase per deflection, Ti(Δ), is added to the cable’s installed tension, T, for the following calculations. Calculate Tension Increase Due to Cable Deflection, Δ Ti ()2 2 .5 LCG2 .5 .5 LCG LCT   d()2 4E125 09/18/2018 Page 5 of 10 Fig. 3 shows a free-body diagram of the sphere and the forces acting on it. The cable contact points are at the tips of the force vectors, P. Fig. 3 For simplicity, it is assumed that the cables move only in the vertical plane. 09/18/2018 Page 6 of 10 The friction force, f, of the cables against the sphere is shown for clarity, but is not used in the following equations, since the friction angle, a, is determined from the friction coefficient, m, as follows: Eq. 3 Next, angle Q, is developed as a function of deflection, D: Eq. 4 The following equations are then developed as functions of the cable deflection, D. Knowing Q and a allows the net resultant force, R, to be determined, which is the combination of the effects of cable tension and friction. Eq. 5 Next, angle F is determined from and a: Eq. 6 Which then allows RX, the horizontal component of the net force, R, to be determined: Eq. 7 Since there are two cables acting on the sphere, there are two horizontal forces, RX, resisting the force driving the sphere against the cables, F. F:= 2Rx(D) Eq. 8 atan () () ()acos .5 SC .5 D d()   R ()P () cos () () 2 () Rx ()R ()cos ()() 09/18/2018 Page 7 of 10 This final equation is then solved for several levels of cable tension over the full range of possible cable deflection, D. For the following conditions: LCG = 48.0 in. d = .125 in. SC = 3.125 in. D = 4.0 in. T = 175, 200, 225, 250, 275, 300 lb m = .285 The value for m was chosen to match the calculated push-through force for T=225 lb to that obtained by testing the actual pull-through force of a steel sphere through tensioned cables. Force Applied to Sphere vs Cable Deflection Graph 1 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.50 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Deflection, in Fo r c e , l b F300 () F275 () F250 () F225 () F200 () F175 ()  09/18/2018 Page 8 of 10 The maximum values of F are then determined for each curve plotted in Graph 1. First, the deflection, D, at which the maximum force, F, occurs is found. From the Mathcad analysis: The maximum force required to push the sphere through the cables is found using those values for Δ : F175(Δ) = 7.651 lb F250(Δ) = 10.536 lb F200(Δ) = 8.613 lb F275(Δ) = 11.502 lb F225(Δ) = 9.577 lb F300(Δ) = 12.464 lb As described earlier, the choice of value for the coefficient of friction, m, was chosen to match the peak force value to the experimental data for T = 225 lb. That value, m = .285, was then used throughout this analysis. Establish range of interest for Δ : Determine Δ at which Push-Through Force is Maximum: .3 Given .3 .5 MaximizeF175 ()0.42382MaximizeF250 ()0.4192 MaximizeF200 ()0.42197MaximizeF275 ()0.41813 MaximizeF225 ()0.42046MaximizeF300 ()0.41722 09/18/2018 Page 9 of 10 The actual forces required to push a 4.0 in. diameter sphere through .125 in. diameter, 1x19 construction, 316 stainless cables which were spaced at 3.125 in. center to center, with 48.0 in. unsupported span were tested for a fairly large number of cable tensions. The results are listed below. Each force value represents the average result of 20 trials at each tension level. T = 175 lb F = 7.88 lb T = 275 lb F = 11.67 lb T = 200 lb F = 8.74 lb T = 290 lb F = 12.04 lb T= 210 lb F= 8.61 lb T= 300 lb F= 13.02 lb T = 225 lb F = 9.58 lb T = 325 lb F = 13.43 lb T= 240 lb F= 9.95 lb T= 350 lb F= 14.27 lb T= 250 lb F= 10.59 lb T= 375 lb F= 15.76 lb T= 260 lb F= 10.69 lb T= 400 lb F= 16.65 lb The predicted pull-through force was calculated for each of the above cable tension levels and plotted against the actual forces in Graph 2. Graph 2 7 8 9 10 11 12 13 14 15 16 17 150 175 200 225 250 275 300 325 350 375 400 425 Pu l l -Th r o u g h F o r c e , l b Cable Tension, lb Test Data Calculated Values 09/18/2018 Page 10 of 10 Graph 2 shows very good correlation between the calculated values and the experimental data, which indicates that the assumptions for the analysis are reasonable. While this analysis is not strictly necessary, given that the sphere push force has been accurately determined by testing, it is useful as an aid to further understand the behavior of cable railing infill. Based on these results, it is our recommendation that our cable railing infill be installed per the following guidelines: Cable Spacing, Center to Center: 3.125 in. Maximum Unsupported Span: 48.0 in. Cable Tension: 225 lb All Ultra-tecy cable railing infill should be so installed, regardless of cable diameter. The 225 lb cable tension provides an additional margin of safety of 10% beyond the safety factor of 2.0 applied for dynamic loading. (Using the 9.58 lb avg. push force result from the test data.) Cable railing infill which is capable of resisting an 8.7 lb load to a 4.0 in sphere is more robust than the requirements of 2015 IBC/IRC, since the IBC/IRC codes only specify the size of the infill openings and make no mention of force required to expand them to a larger size. 09/18/2018