HomeMy WebLinkAboutFile Documents.430 W Hallam St.0291.2017 (107).ARBKJOB NAME 430 West Hallam
DATE 4/1/2023
MODEL#TBW120AGD00BOBS
SERIAL#214611573
Cooling
STAGE 1 236 9.3 amps
GEO IN 49 degrees F 38 PSI
GEO OUT 54 degrees F 30 PSI
LOAD IN 57 degrees F 24 PSI
LOAD OUT 53 degrees F 18 PSI
STAGE 2 237 19.6 amps
GEO IN 51 degrees F 38 PSI
GEO OUT 60 degrees F 30 PSI
LOAD IN 53 degrees F 24 PSI
LOAD OUT 46 degrees F 18 PSI
Heating
STAGE 1 236 14.2 amps
GEO IN 51 degrees F 38 PSI
GEO OUT 48 degrees F 30 PSI
LOAD IN 82 degrees F 20 PSI
LOAD OUT 86 degrees F 16 PSI
STAGE 2 237 24.8 amps
GEO IN 50 degrees F 38 PSI
GEO OUT 43 degrees F 30 PSI
LOAD IN 82 degrees F 20 PSI
LOAD OUT 90 degrees F 16 PSI