Subject: PlanCheck
Page Label: 3 Previous comment not resolved.
Author:justinh Provide an architectural
File Name: 0016.2019.ACBK_MEP&ENERGY BuildingComm
snowmelt plan that shows the
__
ent 1.pdf — existing and proposed snowmelt.
= — Currently what is shown on the
Color: •
revised CREMP worksheet as
proposed/new snowmelt(7600
SF)does not match the total
shown on the snowmelt
schedule in the mechanical plan
set(4742 SF). The mechanical
plans and schedule,the
architectural snowmelt plan, and
this form all need to be accurate
and consistent regarding new
snowmelt and the architectural
snowmelt plan needs to clearly
identify new snowmelt vs
existing snowmelt. Provide
documentation of the boiler
efficiency claimed on the
CREMP worksheet, cutsheet
submitted did not provide that
information.
m =-- Subject: PlanCheck
ea Page Label: 4
t The letter submitted specifically
s Author:justinh notes that the effects of applying
File Name: 0016.2019.ACBK MEP&ENERGY BuildingComm spray foam over spray applied
— — fire resistive material have not
ent_1.pdf
Color: • been investigated unless
otherwise noted in an individual
design or certification. This
alludes to it having worked on
past projects but gives no real
specifics. It also appears to be
specific to CAFCO SFRM,which
is not one of the approved
SFRMs per the UL listing you've
chosen. This document seems
to allude more to it being
possible, rather than it being
approved. Original comment
requesting documentation that
you can apply spray foam over
your spray applied fireproofing
still stands. Submit a signed and
stamped report from a fire
protection engineer which states
how this assembly can be
constructed without
compromising the integrity of the
SFRM. Attached is an example
of such a report he had
submitted for a similar situation
on a past project.
Subject: PlanCheck
Page Label: 4 Acknowledged, comment
Author:justinh unresolved currently.
File Name: 0016.2019.ACBK_MEP&ENERGY_BuildingComm Technically you can have
-- ent_1.pdf thermal bridging, but areas with
{ the bridges must be accounted
?IT ET wm� u Color: • for in your envelope ComCheck
as wall,floor, or roof area with
zero insulation.
COMcheck Envelope.425 Rio Grande Place.2019.06.21.pdf(4)
Subject: PlanCheck
�•�«�;���u„ Pa a Label: 1 I question these roof square E�._�Mom....w..,,., g
Author:justinh footages for roof. I'm measuring
-__ -••----••-°_ •°~° File Name: COMcheck Envelope.425 Rio Grande approximately 5700 SF of roof
`m"' Place.201 9.06.21.pdf on the roof level and 7500 SF of
�
_._.- = -
Color: • roof on the upper level (which I
assume correspond to what you
have as roof 1 and 2 on the
report), but I do not see where
-- _ -• _ the square footage for roof 3
(10580 SF)is coming from. The
round 1 comment regarding the
skylight/roof percentage being
over 3% is still relevant as far as
I can tell. It might be helpful to
have a quick meeting prior to
resubmitting to make sure we're
all in agreement regarding the
areas we're counting for the
various envelope elements.
Subject: PlanCheck
_- --� Page Label: 1 Only floors that make up the
_m:, Nt, ET Author:justinh thermal envelope should be
- File Name: COMcheck Envelope.425 Rio Grande entered in the ComCheck(just
-- Place.2019.06.21.pdf areas that project out over
Color: • unconditioned space, slab on
-- = grade less than 24"from finished
grade, and your floor over the
unconditioned crawlspace).
These seem to be all floors in
the building, please revise.
Subject: PlanCheck
- - Page Label: 3 Provide a spec on the Bendheim
Author:justinh channel glass system that shows
,_ File Name: COMcheck Envelope.425 Rio Grande it will achieve a U value of.30.
= - Place.2019.06.21.pdf Unless I'm misunderstanding the
Color: • assembly I do not think you can
-• °- take credit for both the window
ENNESEMNIMEnt system and a steel wall
W M om assembly of the same area.
Please revise or justify what is
entered in the ComCheck, be
sure to revise all areas using the
channel glass if revisions are
necessary.
Subject: PlanCheck
Page Label: 5 I am finding several instances
Author:justinh where walls are being entered
-_ 7 I,... ,,,, File Name: COMcheck Envelope.425 Rio Grande incorrectly. For example,walls
=-__ i J Place.2019.06.21.pdf 12 and 16 on the main level are
== -_ Color: • CMU walls with 4"of rigid
insulation for a R20 value(per
e what is shown on A0.10/A9.1).
You have them both entered as
_-=______ •:.:: steel framed walls and use R10
cavity with R8 continuous for
wall 12 (these are insulation
values from a different type wall)
and R22 continuous for wall 16
(correct insulation type but you
cannot take credit for the R
value of the wall components
like CMU and gypsum,
ComCheck already builds these
types of things in when you
select the wall type,only the R
value of the actual insulation
should be used). Please go
through the ComCheck report to
make sure you are using the
correct insulation values from
the correct assemblies, currently
about 50% of the wall
assemblies I've spot checked on
this report have not matched the
relevant assembly detailed on
A9.1 per the wall tags called out
on A0.10.
Comcheck Lighting.425 Rio Grande Place.2019.06.21.pdf(1)
Subject: PlanCheck
,,�l� Page Label: 1 This floor area is greater than
n Interi Lighting lo Author:justinh what is shown on the envelope
I I v „a. File Name: Comcheck Lighting.425 Rio Grande ComCheck or the gross area
Place.2019.06.21.pdf sheet for interior building area.
•%:,i i °•- All three should match as we're
_�_. N.°.. Color: •
°`"°..° °"°' dealing with the same gross floor
area for the entire building.
Please revise.
Plan Set.Arch.425 Rio Grande Place.2019.06.21.pdf(4)
■moo =, o Subject: PlanCheck doors and shaft
■M1— Page Label: A2.9 MAIN LEVEL PARTIAL FLOOR PLAN Elevatorconstiture the thermal envelope
l \ o -AREA C in this location (main level),
a� �,_ Author:justinh
revise ComCheck report and
I■�- - File Name: Plan Set.Arch.425 Rio Grande
IIff/M o plan sheet to incorporate this
o r Place.2019.06.21.pdf p
® area as well.
® w Color: •
i
Subject: PlanCheck
d \ Elevator shaft and doors
Page Label:A2.15 UPPER LEVEL PARTIAL FLOOR PLAN
-AREA C constitute the thermal envelope/i "°°"` Author:justinh on the upper level, include them
,j2i
� File Name: Plan Set.Arch.425 Rio Grande
in the ComCheck report and
I /�!� � '® Place.2019.06.21.pdf plan.
_II�ilim—ii _ Color: ■
®IUIIIIIOIIIIR ®-�
II
Subject: PlanCheck
Page Label:A9.1 ROOF, WALL,AND FLOOR ASSEMBLIES Several of the wall assemblies
® Author:justinh are titled with an R value that is
.. [iI � File Name: Plan Set.Arch.425 Rio Grande not what is actually shown for
Place.2019.06.21.pdf example W5 is called out as R10
Irvr - Color: • but the 1.5"of rigid insulation
would only be R7.5, and W2 is
called R18 but the detail shows
R8 continuous and R24 batt
0 insulation which would be R32.
Several of these inconsistencies
seem to have made it into the
Envelope ComCheck as well,for
example, Main Level west wall
1.2 is W2 and is shown on the
ComCheck as R8 continuous
and R10 cavity as the detail title
suggests, but that is not what the
detail actually shows. Please be
sure that all insulation values
shown/called out are correct and
that the correct values are being
used in the ComCheck.
MT IS—,, Subject: PlanCheck Please remove the R values for
u..aW o Page Label:A9.1 ROOF, WALL,AND FLOOR ASSEMBLIES items like gypsum wall board
<w Author:justinh and CMU from this detail.
w -°.A , O 2e File Name: Plan Set.Arch.425 Rio Grande
Z e Place.2019.06.21.pdf ComCheck already builds these
Color: • types of items into what it
Q-� °a„ assumes your assembly is when
iii °° you select wall types. Only R
a values of actual insulation
I- I�'I ASSEMBLS
should be called out.
Plan Set.Mechanical.425 Rio Grande Place.2019.06.21.pdf(2)
.°,.0 Subject: PlanCheck
.uwo a „o," _.m;, Page Label: M0.01 MECHANICAL, PLUMBING, FIRE Please add a general note
PROTECTION COVER SHEET stating that the system
�EWL
°°�.M�° •°°°° •�TM°T�°°g°a..° ,:::,= °° Author:justinh commissioning plan will be due
Ee` File Name: Plan Set.Mechanical.425 Rio Grande prior to final
mechanical/electrical inspections
Place.2019.06.21.pdf
Color: • at tenant finish per IECC
C408.2.1. Final commissioning
reports shall be due prior to
building final inspection at tenant
finish.
Subject: PlanCheck
-__---_---_®, Page Label: M8.02 MECHANICAL SCHEDULES Revised mechanical and
plumbing sets are not stamped.
Author:justinh
File Name: Plan Set.Mechanical.425 Rio Grande
" Place.2019.06.21.pdf
I` Color: ■
n
r iiaarnl=
u.
Trim=1 r i Cta