Loading...
HomeMy WebLinkAboutFile Documents.210 W Main St.0064-2020-BCHO (2)0064-2020-BCHO_BuildingComments_1 Subject: Group Page: A.2.06 PROPOSED MAIN LEVEL PLAN Page Index: 1 Author: nickt Color: File Name: 90.Architectural Plans.09092020.pdf Revise A1.14.B and associated details to provide a 1 hour horizontal assembly at the floor/ceiling under the exit passageway. 90.Architectural Plans.09092020.pdf (1) Subject: PlanCheck Page: 1 Page Index: 1 Author: nickt Color: File Name: 9001_MPE-all_09-25-20_stamped-signed.pdf Revise mechanical drawings to cloud all changes. 9001_MPE-all_09-25-20_stamped-signed.pdf (5) Subject: PlanCheck Page: 1 Page Index: 1 Author: nickt Color: File Name: 9001_MPE-all_09-25-20_stamped-signed.pdf The backgrounds in the basement do not match the approved architecturals. Subject: PlanCheck Page: 2 Page Index: 2 Author: nickt Color: File Name: 9001_MPE-all_09-25-20_stamped-signed.pdf Revise the mechanical drawings to show the routing of the boiler flues correctly on each floor. The various stories appear to show conflicting routing locations. Scale: AS NOTED ISSUE SCHEMATIC DESIGN PERMIT SUBMITTAL COMMENTS 1 COMMENTS 2 HPC APPROVAL WINDOW HPC APPROVAL CHANGE ORDER 1 KING LOUISE HOUSING 210 WEST MAIN STREET ASPEN, CO 81611 1" ACTUALIF THE ABOVE DIMENSION DOESNOT MEASURE ONE INCH (1")EXACTLY, THIS DRAWING WILLHAVE BEEN ENLARGED ORREDUCED, AFFECTING ALLLABELED SCALES. ALL DESIGNS, IDEAS ARRANGEMENTSAND PLANS INDICATED BY THESEDRAWINGS AND SPECIFICATIONS ARETHE PROPERTY AND COPYRIGHT OF KIMRAYMOND ARCHITECTS, INC. ANDSHALL NEITHER BE USED ON ANY OTHERWORK NOR BE USED BY ANY OTHERPERSON FOR ANY USE WHATSOEVERWITHOUT WRITTEN PERMISSION.WRITTEN DIMENSIONS SHALL TAKEPRECEDENCE OVER SCALEDDIMENSIONS AND SHALL BE VERIFIED ATTHE SITE. ANY DIMENSIONALDISCREPANCY SHALL BE BROUGHT TOTHE ATTENTION OF THE ARCHITECTPRIOR TO COMMENCEMENT OF WORK. DATE 11/22/18 KIM RAYMOND ARCHITECTS, INC. | 300 E. HYMAN AVENUE, SUITE 100 | | www.kimraymondarchitects.com | | 970-925-2252 | 03/05/19 07/01/19 09/16/19 04/21/20 05/20/20 08/28/20 6 9 1/4" 12345678910111213141516 101-01 101-02 101-04 101-05 101-06 101-01 101-03 103-04 103-05 103-01 102-06 102-05 102-01 102-02 102-03 102-01 102-04 102-07 101-10 101-08 101-04 102-02102-03 103-07 103-08 103-06 103-02 101-02 103-01 103-02 103-03 101-09 103-05 103-04 00-12 103-03 101-07 101-06 101-04A RG F F D F W W D DW DW DW RG 1A.6.06 2A.6.06 #DrgID#LayID 1 1 49'-3" 80'-11" 6'-4" 15'-7" 5'-0" 2'-10" 13'-8" 5'-10" 12'-9 1/2"24'-2 1/2"5'-0"16'-8 1/2"22'-2 1/2" 4 1/2" 5'-0" /2" 5'-0" 3 1/2" 1/2" 12'-8" 5 1/2" 8'-1 1/2" 3 1/2" 3 1/2"11'-4"5 1/2"5'-9 1/2"5 1/2"8'-5 1/2"3 1/2"10'-1" 3 1/2"11'-11 1/4"3 1/2"9'-4 3/4" 4 1/2"5'-0" 3 1/2" 3 1/2"18'-1" 3 1/2" 2'-8"3 1/2"5'-3"5 1/2"3'-3 1/4"3 1/2" 3 1/2" 3 1/2"4'-4"3 1/2" 4'-0" 2'-6" 4 1/2" 3 1/2"3'-1 1/4" 3'-1 1/4" 5'-0" 2'-0 3/4" 5'-0" 9'-1" 1/2" 9'-1 1/2" 3 1/2"2'-1"3 1/2" 4'-0" 2'-6" 4'-0" 2'-6" 3'-8"3 1/2"6'-4 1/2"7'-4 1/2"3 1/2"3'-8" 3'-4" 5'-10 3/4"2'-0" 3 1/2" 14'-11 1/2" 3 1/2" 3'-4 1/2" 3 1/2"10'-8 1/2" 2'-8"3 1/2"3 1/2" 4'-1" 8'-0 1/4"3 1/2"3'-4 1/2"3'-4 1/2"3 1/2"7'-11" 3 1/2"2'-1" 3'-0 3/4" 2'-7 1/2" 5'-7 3/4" 2'-0 3/4"1'-1" 5'-2 3/4" 3 1/2" 3 1/2" 8'-0" 5'-4 1/2"2'-10 1/2" 2'-5" 3'-11 1/2" 7'-1 1/2" 4'-2" 15'-3" 6'-8"8'-0"3'-5" 4'-0" 3'-1" 2'-5" 1'-8 1/2" 1'-8 1/2"1'-6 1/2" 11'-9 1/4" 5'-0" 10'-4 1/2" 3'-2" 5'-2 1/4" 8'-2 1/2" 8'-6 1/4" 3'-2" 3'-7 1/4" 4'-1" 3 1/2" 11'-10" 10'-11" 5'-1 3/4" 3 1/2" 6'-2 1/2" 3 1/2" 8'-0"3 1/2"3'-3"3 1/2" 12'-7" 3 1/2"2'-3"3 1/2" 5'-11" 3 1/2" 3 1/2" 1'-1 1/2" 2'-10 1/4" 2'-0 3/4" 3 1/2"11'-8" 1'-1 1/2" 6" 2'-8 3/4" 2'-0" 5'-2 1/4" 7"5'-0 1/2" 7" 8'-0" 7'-10" 2'-8 1/2"3 1/2" 7"8'-2 1/4"7'-10"6'-6 1/4"3'-9 1/2" 2'-0" 3'-0" 10'-4 1/4" 4'-1 3/4" 1'-6 1/4" 7'-1 3/4" 3'-4"2'-6"2'-6 1/4" 3 1/2" 3'-11 3/4" 3 1/2" 3 1/2"2'-5 1/2" 3 1/2"7'-2 1/2" 5'-1 1/4"1'-9 3/4"3 1/2" 7'-2 1/2" C= 7'-6" C= 7' 2A 3.1 1 HR FIRE WALL 1H EXTERIORWALL ASSEMBLY CONTROL JOINT CONTROL JOINT CONTROLJOINT 1H FIRE WALLASSEMBLY CEILING TO BEFIRE RATED ONEXIT HALLWAY &CANTILEVEREDROOF INSULATED WALL, SEERESCHECK'S WALL 13 INSULATED WALL, SEERESCHECK'S WALL 3 INSULATED WALL, SEERESCHECK'S WALL 2 INSULATED WALL, SEERESCHECK'S WALL 1 HEIGHT TO MATCHWINDOW SILL SIDEWALK LIVING DINING KITCHEN PORCH DINING HALL BEDROOM 2 BEDROOM 1 BATH 1 LAUNDRY LIVING KITCHEN PORCH BEDROOM 2BEDROOM 1 LIVING DINING KITCHEN BATH(ADA TYPE B,OPTION B) PANTRY UNITSTORAGE UNITSTORAGE TRASH HALL UP POWDER BATH 2(ADA TYPE B,OPTION B) * NOTE:CLOSET DOOR TO HAVE 31 3/4"DOOR CLEARANCE * NOTE:CLOSET DOOR TO HAVE 31 3/4"DOOR CLEARANCE * NOTE:CLOSET DOOR TO HAVE 31 3/4" DOORCLEARANCE NOTE:CLOSET DOOR TO HAVE 31 3/4" DOOR CLEARANCE UPDN 30"X48" 30"X48" 3 00-14 00-15 00-13 F 2 A 5 B C D G E 41 1A.4.03 2A.4.03 4A.4.04 2A.4.03 RG 1/2" 1/2" 2'-3" 3'-6 1/2" 5'-1 1/2" 4'-1" 6'-0 1/2" 3 1/2" 11'-9 3/4" 3 1/2"2'-2"3 1/2" 9'-4 1/4" 5 1/2" 14'-5 1/4" 3 1/2" 9'-10 1/4" 7'-4 1/2" 7'-7 1/2" 3 1/2" 3'-6 1/4" 6'-0 1/2" C= 7'C= 7' C= 7' C= 7' 5A.4.05 6A.4.05 7A.4.05 2A 3.1MAIL BOXES ETBACK LINE PROPERTY LINE ATIO/BALCONY SETBACK LINE (HPC RESOLUTION #12 OF 2018) UNIT 102 UNIT 103(TYPE B UNIT) UNIT 101(TYPE B UNIT) ST-101 ST-103 GARBAGE(SPRINKLED) SETBACK LINEN #12 OF 2018):SECTION 2 1 Revise A1.14.B andassociated details to provide a 1 hourhorizontal assembly atthe floor/ceiling underthe exit passageway. UNIT 203UNIT 102 UNIT 103UNIT 102 5 SCALE: 3/32" = 1'-0"6 SECTION 6-FIRE ASSEMBLY Revise mechanical drawings to cloud all changes. The backgrounds inthe basement do notmatch the approvedarchitecturals. Revise the mechanical drawings to show the routing of the boiler flues correctly on each floor. The various stories appear to show conflicting routing locations. Subject: PlanCheck Page: 2 Page Index: 2 Author: nickt Color: File Name: 9001_MPE-all_09-25-20_stamped-signed.pdf ERV intakes are less than 10' from property line (2015 IMC 401.4). This building site is constrained by the historic district on the front façade, the alley parking in back, narrow setbacks on each side, and an exterior exit stair in the middle; all of which practically prevent a fully code compliant location for the eight intakes. The current neighbors do not have hazardous exhausts nearby and any future development will not be able to locate hazardous exhausts within 10’ of their property line or the intakes in question. The intakes are serving as whole house ventilation, which is a City of Aspen above code program to provide ventilation that would normally be provided by operable windows, which are allowed to be located 5’ from the property line. As such, the location of these intakes does not pose a hazard and is a reasonable accommodation of the constraints of this site so they may remain as located 5’ from side lot property lines. Subject: PlanCheck Page: 2 Page Index: 2 Author: nickt Color: File Name: 9001_MPE-all_09-25-20_stamped-signed.pdf Revise the architectural drawings to clearly detail a shaft enclosure for the boiler flues. Include sheet A6.14 and revise it to show the actual proposed design. Show it connecting 4 stories, which requires a 2 hour fire rating. Show the horizontal portion and provide a listed horizontal shaft assembly. Revise the vertical shaft assemblies to separate the shaft from the rest of the building construction on all four sides. 2015 IBC 713. ERV intakes are less than 10' from property line (2015 IMC 401.4). This building site is constrained by the historic district on the front façade, the alley parking in back, narrow setbacks on each side, and an exterior exit stair in the middle; all of which practically prevent a fully code compliant location for the eight intakes. The current neighbors do not have hazardous exhausts nearby and any future development will not be able to locate hazardous exhausts within 10’ of their property line or the intakes in question. The intakes are serving as whole house ventilation, which is a City of Aspen above code program to provide ventilation that would normally be provided by operable windows, which are allowed to be located 5’ from the property line. As such, the location of these intakes does not pose a hazard and is a reasonable accommodation of the constraints of this site so they may remain as located 5’ from side lot property lines. Revise the architectural drawings to clearly detail a shaft enclosure for the boiler flues. Include sheet A6.14 and revise it to show the actual proposed design. Show it connecting 4 stories, which requires a 2 hour fire rating. Show the horizontal portion and provide a listed horizontal shaft assembly. Revise the vertical shaft assemblies to separate the shaft from the rest of the building construction on all four sides. 2015 IBC 713.