Loading...
HomeMy WebLinkAboutFile Documents.210 W Main St.0064-2020-BCHO (3)0064-2020-BCHO_BuildingComments_1 Subject: Group Page: 1 Page Index: 1 Author: nickt Color: File Name: 90. Architectural Plans 20201030.pdf Revise A1.14.B and associated details to provide a 1 hour horizontal assembly at the floor/ceiling under the exit passageway. 90. Architectural Plans 20201030.pdf (7) Subject: PlanCheck Page: 1 Page Index: 1 Author: nickt Color: File Name: 90. Architectural Plans 20201030.pdf Provide an updated lower level floor plan. The most recent one that I have is dated 11/15/19 and does not match the backgrounds of the mechanical drawings which you claim are up to date. Subject: PlanCheck Page: 1 Page Index: 1 Author: nickt Color: File Name: 90. Architectural Plans 20201030.pdf Is the accessible parking space no longer moving to the center? Your change order letter says it moves to the center. Please confirm. Subject: PlanCheck Page: 1 Page Index: 1 Author: nickt Color: File Name: 90. Architectural Plans 20201030.pdf Provide a full set of architecturals. Compare it to the approved master permit set (dated 11/15/19) and cloud EVERY change. Subject: PlanCheck Page: 1 Page Index: 1 Author: nickt Color: File Name: 90. Architectural Plans 20201030.pdf You have changed to a tub. Cloud the change. Update ADA bath plans to fully detail and dimension all accessibility requirements. Scale: AS NOTED ISSUE SCHEMATIC DESIGN PERMIT SUBMITTAL COMMENTS 1 COMMENTS 2 HPC APPROVAL WINDOW HPC APPROVAL CHANGE ORDER 1 KING LOUISE HOUSING 210 WEST MAIN STREET ASPEN, CO 81611 1" ACTUALIF THE ABOVE DIMENSION DOESNOT MEASURE ONE INCH (1")EXACTLY, THIS DRAWING WILLHAVE BEEN ENLARGED ORREDUCED, AFFECTING ALLLABELED SCALES. ALL DESIGNS, IDEAS ARRANGEMENTSAND PLANS INDICATED BY THESEDRAWINGS AND SPECIFICATIONS ARETHE PROPERTY AND COPYRIGHT OF KIMRAYMOND ARCHITECTS, INC. ANDSHALL NEITHER BE USED ON ANY OTHERWORK NOR BE USED BY ANY OTHERPERSON FOR ANY USE WHATSOEVERWITHOUT WRITTEN PERMISSION.WRITTEN DIMENSIONS SHALL TAKEPRECEDENCE OVER SCALEDDIMENSIONS AND SHALL BE VERIFIED ATTHE SITE. ANY DIMENSIONALDISCREPANCY SHALL BE BROUGHT TOTHE ATTENTION OF THE ARCHITECTPRIOR TO COMMENCEMENT OF WORK. DATE 11/22/18 KIM RAYMOND ARCHITECTS, INC. | 300 E. HYMAN AVENUE, SUITE 100 | | www.kimraymondarchitects.com | | 970-925-2252 | 03/05/19 07/01/19 09/16/19 04/21/20 05/20/20 08/28/20 6 9 1/4" 12345678910111213141516 101-01 101-02 101-04 101-05 101-06 101-01 101-03 103-04 103-05 103-01 102-06 102-05 102-01 102-02 102-03 102-01 102-04 102-07 101-10 101-08 101-04 102-02102-03 103-07 103-08 103-06 103-02 101-02 103-01 103-02 103-03 101-09 103-05 103-04 00-12 103-03 101-07 101-06 101-04A RG F F D F W W D DW DW DW RG 1A.6.06 2A.6.06 #DrgID#LayID 1A.6.14 1 1 1 49'-3" 80'-11" 6'-4" 15'-7" 5'-0" 2'-10" 13'-8" 5'-10" 12'-9 1/2"24'-2 1/2"5'-0"16'-8 1/2"22'-2 1/2" 4 1/2" 5'-0" 1/2" 5'-0" 3 1/2" 3 1/2" 12'-8" 5 1/2" 8'-1 1/2" 3 1/2" 3 1/2"11'-4"5 1/2"5'-9 1/2"5 1/2"8'-5 1/2"3 1/2"10'-1" 3 1/2"11'-11 1/4"3 1/2"9'-4 3/4" 4 1/2"5'-0" 3 1/2" 3 1/2"18'-1" 3 1/2" 2'-8"3 1/2"5'-3"5 1/2"3'-3 1/4"3 1/2" 3 1/2" 3 1/2"4'-4"3 1/2" 4'-0" 2'-6" 4 1/2" 3 1/2"3'-1 1/4" 3'-1 1/4" 5'-0" 2'-0 3/4" 5'-0" 9'-1" 3 1/2" 9'-1 1/2" 3 1/2"2'-1"3 1/2" 4'-0" 2'-6" 4'-0" 2'-6" 3'-8"3 1/2"6'-4 1/2"7'-4 1/2"3 1/2"3'-8" 3'-4"5'-10 3/4"2'-0" 3 1/2" 14'-11 1/2" 3 1/2" 3'-4 1/2" 3 1/2"10'-8 1/2" 2'-8"3 1/2"3 1/2" 4'-1" 8'-0 1/4"3 1/2"3'-4 1/2"3'-4 1/2"3 1/2"7'-11" 3 1/2"2'-1" 2'-7 1/2" 5'-7 3/4" 2'-0 3/4"1'-1" 5'-2 3/4" 3 1/2" 3 1/2" 5'-4 1/2"2'-10 1/2" 2'-5" 3'-11 1/2" 7'-1 1/2" 4'-2" 15'-3" 6'-8"8'-0"3'-5" 4'-0" 3'-1" 2'-5" 1'-8 1/2" 1'-8 1/2"1'-6 1/2" 11'-9 1/4" 5'-0" 10'-4 1/2" 3'-2" 5'-2 1/4" 8'-2 1/2" 8'-6 1/4" 3'-2" 3'-7 1/4" 4'-1" 3 1/2" 11'-10" 10'-11" 5'-1 3/4" 3 1/2" 6'-2 1/2" 3 1/2" 8'-0"3 1/2"3'-3"3 1/2" 12'-7" 3 1/2"2'-3"3 1/2" 5'-11" 3 1/2" 3 1/2" 1'-1 1/2"2'-10 1/4" 2'-0 3/4" 3 1/2"11'-8" 1'-1 1/2" 6" 2'-8 3/4" 2'-0" 5'-2 1/4" 7"5'-0 1/2" 7" 8'-0" 7'-10" 2'-8 1/2"3 1/2" 7"8'-2 1/4"7'-10"6'-6 1/4"3'-9 1/2" 2'-0" 3'-0" 10'-4 1/4" 4'-1 3/4" 1'-6 1/4" 7'-1 3/4" 3'-4"2'-6"2'-6 1/4" 3 1/2" 3'-11 3/4" 3 1/2" 3 1/2"2'-5 1/2" 3 1/2"7'-2 1/2" 5'-1 1/4"1'-9 3/4"3 1/2" 7'-2 1/2" C= 7'-6" C= 7' 2A 3.1 1 HR FIRE WALL 1H EXTERIORWALL ASSEMBLY CONTROL JOINT CONTROL JOINT CONTROLJOINT 1H FIRE WALLASSEMBLY CEILING TO BEFIRE RATED ONEXIT HALLWAY &CANTILEVEREDROOF INSULATED WALL, SEERESCHECK'S WALL 13 INSULATED WALL, SEERESCHECK'S WALL 3 INSULATED WALL, SEERESCHECK'S WALL 2 INSULATED WALL, SEERESCHECK'S WALL 1 HEIGHT TO MATCHWINDOW SILL NOTE: 8" B VENTS STACK ASTHEY RUN HORIZONTALACROSS THE STORAGE ROOMCEILING, IN A 1 HR HORIZ. SHAFTSEE SHT. A.6.14GA FILE NO. WP 7008 1 HR FIRE SHAFTSEE SHEET A.6.14 BOILER VENTS COME FROM BOILERNEXT TO EACH OTHER, IN THE VERTICAL SHAFTTHAT STARTS AT THIS FLOOR NOTE: 8" B VENTS TURN BACK UPAT THIS POINT, THIS SHOWS WHERETHE VENTS ARE RISING UP THROUGHTHE CEILING IN THIS LOCATION UP FROM BELOW SIDEWALK LIVING DINING KITCHEN PORCH DINING HALL BEDROOM 2 BEDROOM 1 BATH 1 LAUNDRY LIVING KITCHEN PORCH BEDROOM 2BEDROOM 1 LIVING DINING KITCHEN BATH(ADA TYPE B,OPTION B) PANTRY UNITSTORAGE UNITSTORAGE TRASH HALL UP POWDER BATH 2(ADA TYPE B,OPTION B) * NOTE:CLOSET DOOR TO HAVE 31 3/4"DOOR CLEARANCE * NOTE:CLOSET DOOR TO HAVE 31 3/4"DOOR CLEARANCE * NOTE:CLOSET DOOR TO HAVE 31 3/4" DOORCLEARANCE NOTE:CLOSET DOOR TO HAVE 31 3/4" DOOR CLEARANCE UPDN 30"X48" 30"X48" 3 00-14 00-15 00-13 F 2 A 5 B C D G E 4 1A.4.03 2A.4.03 4A.4.04 2A.4.03 RG 3 1/2" 3 1/2" 2'-3" 3'-6 1/2" 5'-1 1/2" 4'-1" 6'-0 1/2" 3 1/2" 11'-9 3/4" 3 1/2"2'-2"3 1/2" 9'-4 1/4" 5 1/2" 14'-5 1/4" 3 1/2" 9'-10 1/4" 7'-4 1/2" 7'-7 1/2" 3 1/2" 3'-6 1/4" 6'-0 1/2" C= 7'C= 7' C= 7' C= 7' 5A.4.05 6A.4.05 7A.4.05 2A 3.1MAIL BOXES SETBACK LINE PROPERTY LINE PATIO/BALCONY SETBACK LINE (HPC RESOLUTION #12 OF 2018) UNIT 102 UNIT 103 (TYPE B UNIT) UNIT 101(TYPE B UNIT) ST-101 ST-103 GARBAGE(SPRINKLED) NE NE18):SECTION 2 1 Revise A1.14.B andassociated details to provide a 1 hourhorizontal assembly atthe floor/ceiling underthe exit passageway. UNIT 203UNIT 102 UNIT 103UNIT 102 5 SCALE: 3/32" = 1'-0"6 SECTION 6-FIRE ASSEMBLY 103-09 103-08103-11 103-10 1" 16'-8 1/2" 3 1/2"11'-4"3 1/2"10'-4"3 1/2"4'-0"2'-11 1/2"4'-4 1/2"4'-4 1/2"2'-11 1/2"3'-0"6'-1 3 11'-9 1/4" 2 3.1 MEC VEN * NOTE:CLOSET DOOR TO HAVE 31 3/4"DOOR CLEARANCE 54 7A.4.05 Provide an updated lower level floor plan. The most recent one that I have is dated 11/15/19 and does not match the backgrounds of the mechanical drawings which you claim are up to date. 9 1/4" 101-09 101-08 101-10 101-08 101-04 101-09 101-07 101-06 101-04A F W D RG 2A.6.06 1 49'-3" 12'-9 1/2"24'-2 1/2" 3 1/2" 2'-0 3/4" 9'-1" 4'-0" 2'-6" 8'-0 1/4"3 1/2"3'-4 1/2"3'-4 1/2"3 1/2"7'-11" 5'-7 3 33'-9 3/4" 5'-11 1/2"5'-8 3/4"5'-11 1/4"5'-8 1/2" 5'-4 1/2"4 1/2" 6'-4" 15'-7" 5'-0" 8'-8 1/2" 5'-0"3'-8 1/2" 3'-2" 5'-2 1/4" 11'-8 1/4"3 1/2"11'-7 3/4" 3 1/2" 3'-11 3/4" 3 1/2" 3 1/2"2'-5 1/2" 3 1/2"7'-2 1/2" 5'-1 1/4"1'-9 3/4"3 1/2" 7'-2 1/2" 5'-2 1/2" 11'-0" 8'-6"C= 7'-6" 2A 3.1 1 HR FIRE WALL CONTROL JOINT INSULATED WALL, SEERESCHECK'S WALL 13 INSULATED WALL, SEERESCHECK'S WALL 3 BEDROOM 2BEDROOM 1 KITCHEN BATH(ADA TYPE B,OPTION B) PANTRY UNIT STORAGE HALL CLOSET DOOR TO HAVE 31 3/4CLE NOTE:CLOSET DOOR TO HAVE 31 3/4" DOOR CLEARANCE UTILITIES 30"X48" 30"X48" PARKING SPACE VAN SIZE HANDICAP SPACE PARKING SPACE 5 ACCESS AISLE 8'-6" 00-13 F 2 D G E 1 4A.4.04 2A.4.03 3 1/2" 11'-9 3/4" 3 1/2"2'-2"3 1/2" 9'-4 1/4" 5 1/2" 3'-6 1/4" 6'-0 1/2" C= 7'C= 7' 5A.4.05 6A.4.05 SETBACK LINE PROPERTY LINE ST-101 PORCH/BALCONY SETBACK LINE(HPC RESOLUTION #12 OF 2018):SECTION 2 SCALE: 1/4" = 1'-0"1 PROPOSED GROUND LEVEL Is the accessible parking space no longer moving to the center? Your change order letter says it moves to the center. Please confirm. 102-06 102-05 102-03 102-04 RG F DW rgIDayID 1 5'-0" 2'-10" 13'-8" 5 5'-0" 3 1/2"10'-1" 3 1/2"9'-4 3/4" 3 1/2" 3'-3 1/4"3 1/2" 5'-2 3/4" 3 1/2" 3 1/2" 3'-11 1/2" 7'-1 1/2" 4'-2" 15'-3" 3 1/2" 6'-2 6" 2'-8 3/4" 2'-0" 5'-2 1/4" 7" 1H EXTERIORWALL ASSEMBLY CEILING TO BE FIRE RATED ON EXIT HALLWAY & CANTILEVEREDROOF SIDEWALK DINING KITCHEN UP 2A.4.03 2A 3.1 MAIL BOXES T 102 Provide a full set of architecturals. Compare it to the approved master permit set (dated 11/15/19) and cloud EVERY change. 9 1/4" 12345678910111213141516 101-09 101-08 103-09 103-08103-11 103-10 101-10 101-08 101-04 103-07 103-08 103-06 103-02 101-09 103-05 103-04 00-12 103-03 101-07 101-06 101-04A D F W W D DW RG 1A.6.06 2A.6.06 1 3 1/2" 3 1/2" 12'-8" 5 1/2" 8'-1 1/2" 3 1/2" 3 1/2"11'-4"3 1/2"10'-4" 3 1/2"11'-4"5 1/2"5'-9 1/2"5 1/2" 3 1/2"3 1/2" 4'-0" 2'-6" 3 1/2" 3'-1 1/4" 3'-1 1/4" 2'-0 3/4" 5'-0" 9'-1" 3 1/2" 4'-0" 2'-6" 4'-0" 2'-6" 3'-8"3 1/2"6'-4 1/2"7'-4 1/2"3 1/2"3'-8" 3 1/ 8'-0 1/4"3 1/2"3'-4 1/2"3'-4 1/2"3 1/2"7'-11" 3 1/2" 2'-1" 5'-7 3/4" 2'-0 3/4" 1'-1" 4'-0"2'-11 1/2"4'-4 1/2"4'-4 1/2"2'-11 1/2"5'-11 1/2"5'-8 3/4"5'-11 1/4"5'-8 1/2" 11'-9 1/4" 3'-2" 5'-2 1/4" 8'-2 1/2" 10'-11" 11'-8 1/4"3 1/2"11'-7 3/4"3 1/2" 12'-7" 3 1/2" 2'-3" 3 1/2" 5'-11" 3 1/2" 2'-0" 3'-0" 3'-4 3 1/2" 3'-11 3/4" 3 1/2" 3 1/2"2'-5 1/2" 3 1/2"7'-2 1/2" 5'-1 1/4"1'-9 3/4"3 1/2" 7'-2 1/2" C= 7'-6" 1 HR FIRE WALL CONTROL JOINT INSULATED WALL, SEERESCHECK'S WALL 13 INSULATED WALL, SEERESCHECK'S WALL 3 HALL BEDROOM 2 BEDROOM 1 LAUNDRY BEDROOM 2BEDROOM 1 DINING KITCHEN BATH(ADA TYPE B,OPTION B) PANTRY UNITSTORAGE TRASH HALL BATH 2(ADA TYPE B,OPTION B) * NOTE:CLOSET DOOR TO HAVE 31 3/4"DOOR CLEARANCE * NOTE:CLOSET DOOR TO HDOOR CLEARANCE * NOTE:CLOSET DOOR TO HAVE 31 3/4" DOORCLEARANCE NOTE:CLOSET DOOR TO HAVE 31 3/4" DOOR CLEARANCE UPDN UTILITIES 30"X48" 30"X48" 00-14 00-13 3 1/2" 11'-9 3/4" 3 1/2"2'-2"3 1/2" 9'-4 1/4" 5 1/2" 14'-5 1/4" 3'-6 1/4" 6'-0 1/2" C= 7'C= 7' C= 7' ST-101 ION 2 You have changed to a tub. Cloud the change. Update ADA bath plans to fully detail and dimension all accessibility requirements. 2 - A.1.14.B: Updated and clouded Detail 6 to show 1 HR. assembly. - A.2.05: Attached updated Lower Level Plan. - A.2.06: Yes... it will stay at West Side of site. Updated letter ... see attached. -A.2.06: Clouded the tub for Change Order 1. -A.6.06: Updated ADA detail for bath Unit 101 - ARCHITECTURAL SET: Compared plan sets and updated Change Order clouds. KRAI REPLY: 11/05/2020 11/17/2020 Subject: PlanCheck Page: 10 Page Index: 10 Author: nickt Color: File Name: 90. Architectural Plans 20201030.pdf Coordinate handrail return detail with contractor. What is installed must match the drawings. Subject: PlanCheck Page: 15 Page Index: 15 Author: nickt Color: File Name: 90. Architectural Plans 20201030.pdf Coordinate with contractor. What is installed must match the drawings. Subject: PlanCheck Page: M-1 BASEMENT HEATING•50AND VENTALATION PLAN Page Index: 1 Author: nickt Color: File Name: 90.MPE-all_10-29-20.pdf Compare this mechanical set to the set dated 8/25/19 and cloud everything that is different. 90.MPE-all_10-29-20.pdf (1) Scale: AS NOTED ISSUE SCHEMATIC DESIGN PERMIT SUBMITTAL COMMENTS 1 COMMENTS 2 HPC APPROVAL WINDOW HPC APPROVAL CHANGE ORDER 1 KING LOUISE HOUSING 210 WEST MAIN STREET ASPEN, CO 81611 1" ACTUAL IF THE ABOVE DIMENSION DOESNOT MEASURE ONE INCH (1")EXACTLY, THIS DRAWING WILLHAVE BEEN ENLARGED ORREDUCED, AFFECTING ALLLABELED SCALES. ALL DESIGNS, IDEAS ARRANGEMENTSAND PLANS INDICATED BY THESEDRAWINGS AND SPECIFICATIONS ARETHE PROPERTY AND COPYRIGHT OF KIMRAYMOND ARCHITECTS, INC. ANDSHALL NEITHER BE USED ON ANY OTHERWORK NOR BE USED BY ANY OTHERPERSON FOR ANY USE WHATSOEVERWITHOUT WRITTEN PERMISSION.WRITTEN DIMENSIONS SHALL TAKEPRECEDENCE OVER SCALEDDIMENSIONS AND SHALL BE VERIFIED ATTHE SITE. ANY DIMENSIONALDISCREPANCY SHALL BE BROUGHT TOTHE ATTENTION OF THE ARCHITECTPRIOR TO COMMENCEMENT OF WORK. STAIRDETAIL: DATE 11/22/18 KIM RAYMOND ARCHITECTS, INC. | 300 E. HYMAN AVENUE, SUITE 100 | | www.kimraymondarchitects.com | | 970-925-2252 | 03/05/19 07/01/19 09/16/19 04/21/20 05/20/20 08/28/20 HANDRAIL CONTINUOUSGUARDRAIL CONTINUOUSGUARDRAILW/HANDRAIL 2728293031323334 DN UP DN 3536373839404142 50 49 48 47 46 45 44 43 42 41 40 39 38 37 36 35 D05 W/D W/D C C 1 2 1 2 4'-2 1/2"13'-11"(15 TREADS @ 1')1'-0" 3'-9 3/4" 9 1/2" 2'-10 3/4" 1 1/2" 3'-2 1/2" 4'-2 1/2"13'-11"(15 TREADS @ 1')3'-0" 1'-0 1/4" 3'-0" 4'-0 1/2" 1'-0" 2'-11 1/2" 1" 4'-5" 4'-5" 1'-0"3'-2 1/2" 2"2'-10" 3'-2 1/2"1'-0" 1'-0" 1'-0" 1'-0" 1'-0" 3'-0" T GYP.109'-4"T PLY109'-2 1/2" T. FF109'-2 1/2" T. FF118'-8" HANDRAIL BATH RY Y RY D LEVEL EVEL UTILITYDECK E E 3 54 192018 DN UP 17 16 15 14 212223242526 W/DW/D C C 1 1 1 1 2 2 3'-9" 3'-4 1/4" 1'-0"5'-0 1/4" 3'-4 1/4" 3'-0" 7'-1" 1'-0" 3'-0"1'-0" 1'-0" 1'-0" 4'-2 1/2" T. SLAB89'-8" T. FF100'-0" EXTEND HANDRAIL 1',TURN AND ATTACH TOGUARDRAIL. HANDRAILEXTENDGUARDRAIL 1' HANDRAIL UNITSTORAGE HALLWAY LAUNDRY LOWER LEVEL GROUND LEVEL NOTE:18 RISERS TOGROUND FLOOR 1 2 3 56789101112 UP 131415 161718 4 E E 3 54 AIR - FLOOR PLANS REVISED 03/11/20 Coordinate handrail return detail withcontractor. What isinstalled must matchthe drawings. Scale: A HPC WIND CHAN 1" A IF THE ABOVE D NOT MEASUREXACTLY, THISHAVE BEEN REDUCED, A LABELED A.6 DET 04/21/20 05/20/20 08/28/20 SEALANT AROUNDDUCT AT PENETRATION. SEALANT AROUNDDUCT AT PENETRATIONAT INITIATION OF VERTICAL SHAFTWHICH CONNECTS ONLY 3 STORIES1 HR. FIRE RATED SHAFT REQUIRED 1 HR SHAFT WALL ASSEMBLY:- 1" USG SHAFT LINER (ATTACHED TO SHEET METAL PAN W HOLES FOR DUCTS TO START UP SHAFT)- 1" RIGID INSULATION- 1 LAYER OF TYPE "X" 5/8" GYPSUM- GA FILE NO. WP 7008 2 LAYERS OF 5/8" GWB, CONTINUOUS AT CEILING TO EXTERIOR WALL, METAL PAN AROUND VENTS 1 HR FLOORASSEMBLY: FC 5115 DUCTS ATTACH TO BOILERS CONCRETE FOUNDATION WALL EXTERIOR WALL 2X4 FRAMING W INS. 2 LAYERS OF 5/8" GWB, CONTINUOUS AT CEILING TO EXTERIOR WALL, METAL PAN AROUND VENTS 1" SHAFT LINER THROUGH FLOOR JOISTS MAIN FLOOR BASEMENT MECHANICAL ROOM 1st STORY SCALE: 1" = 1'-0"1 MECHANICAL CHASE ASSEMBLY-SECTION Coordinate with contractor. What is installed must match the drawings. Compare this mechanical set to the set dated 8/25/19 andcloud everything that is different. -A.6.14: Detail 1: Updated note to read "2 Layers of 5/8" GWP" as installed on site. -A.6.03: Updated handrail as site built. Mechanical Set was reviewed by engineer. See attached set. 11/17/2020