Loading...
HomeMy WebLinkAboutFile Documents.230 E Hopkins Ave.0089.2018 (3).ACBK0089-2018-ACBK_BuildingComments_2 Page: 1 File Name: 230 E. Hopkins_ComCheck_Mech_2019-04-18.pdf Subject: PlanCheck Author: nickt Color: Revise the COMcheck to include the owner/agent. 230 E. Hopkins_ComCheck_Mech_2019-04-18.pdf (1) Page: [1] A2.3 File Name: 230 E. Hopkins_Drawings_Architecture_2019-04-18.pdf Subject: PlanCheck Author: nickt Color: Provide pool design drawings and documentation demonstrating compliance with 2015 ISPSC (including barrier and deck requirements) and APSC-15. Fill out and submit the APSC-15 compliance information sheet available here: https://apsp.org/portals/0/FileDo wnloads/APSP-15%20Complian ce%20Information%20Sheet.pdf 230 E. Hopkins_Drawings_Architecture_2019-04-18.pdf (23) Page: A0.5z FIRE SEPARATION & THERMAL ENVELOPE DIAGRAMS File Name: 230 E. Hopkins_Drawings_Architecture_2019-04-18.pdf Subject: PlanCheck Author: nickt Color: 1/2 hour (30 minute) rating required for corridor walls serving dwellings. 2015 IBC 1020.1 Page: A0.5z FIRE SEPARATION & THERMAL ENVELOPE DIAGRAMS File Name: 230 E. Hopkins_Drawings_Architecture_2019-04-18.pdf Subject: PlanCheck Author: nickt Color: The entire floor structure on floor 1 and floor 2 throughout the entire building must be 1 hour fire rated to maintain dwelling separation fire partition continuity (2015 IBC 708.4). Page: A2.1 PROPOSED LEVEL ONE FLOOR PLAN File Name: 230 E. Hopkins_Drawings_Architecture_2019-04-18.pdf Subject: PlanCheck Author: nickt Color: Include interior elevations and dimensioned plan to demonstrate accessibility for Comm 1 Bathroom as you have done for other bathrooms on A9.1. Also provide a clearspace beyond the door swing. COMcheck Software Version 4.1.1.0 Mechanical Compliance Certificate Project Title: 90.1 (2013) Standard Project Type:Alteration Location:Aspen, Colorado Climate Zone:7 Construction Site: 200-234 E. HOPKINS ASPEN, CO 81611 Owner/Agent:Designer/Contractor: David Denio AEC Avon, CO 970-748-8520 david@aec-vail.com Project Information Energy Code: MOUNTAIN FORGE REMODEL Mechanical Systems List Quantity System Type & Description Heating: 1 each - Duct Furnace, Gas, Capacity = 26 kBtu/h Proposed Efficiency = 95.00% Ec, Required Efficiency: 80.00 % Ec Cooling: 1 each - Split System, Capacity = 16 kBtu/h, Air-Cooled Condenser Proposed Efficiency = 15.50 SEER, Required Efficiency: 13.00 SEER Fan System: F-1 -- Compliance (Motor nameplate HP method) : Passes Fans: FAN 1 Supply, Constant Volume, 705 CFM, 0.3 motor nameplate hp, 0.0 fan efficiency grade SYSTEM VERIFICATION REQUIRED. 1 F-1 / CU-1 Heating: 1 each - Duct Furnace, Gas, Capacity = 26 kBtu/h Proposed Efficiency = 95.00% Ec, Required Efficiency: 80.00 % Ec Cooling: 1 each - Split System, Capacity = 29 kBtu/h, Air-Cooled Condenser 1 F-2 / CU-2 Revise the COMcheck to include the owner/agent. ELEVATOR 6:12 12:12 12:12 6:12 12 : 1 2 12: 1 2 20'-0" SETBACK FOR 10'-0" OVERRUN FORELEVATOR & STAIR 15'-0" SETBACK FOR6'-0" MECHANICAL EQUIPMENT DN MEMBRANE ROOF MEMBRANE ROOF ME M B R A N E R O O F MODULAR GREENROOF DN RD OD DS DN DNDN RD OD DN DN 20 ' - 0 " S E T B A C K F O R 10' - 0 " O V E R R U N F O R EL E V A T O R & S T A I R 15' - 0 " S E T B A C K F O R 6'- 0 " M E C H A N I C A L EQ U I P M E N T RD OD DN DN DN DN 10-0" SETBACK FORPERMANENT ROOFTOP AMENITIES - 5' HEIGHT 10- 0 " S E T B A C K F O R PE R M A N E N T R O O F T O P AM E N I T I E S - 5 ' H E I G H T RD OD WHy WHy DS DN RD OD DN DN RIVER ROCK BALLASTAROUND DRAINS DN U/C REF U/CREF DN RD OD DN DNDN DN RD OD DN DNDN RD OD PLANTERPLANTERPLANTERPLANTERPLANTER PLANTERPLANTER BE N C H UP UP UP 7" PLANTER PLANTER 18" 18" 12" E2 A4.2CD F GB 6'-1 0 " 17 ' - 1 1 1 / 4 " 6'-7 1 / 4 " 15 ' - 0 3 / 4 " 17 ' - 1 1 1 / 4 " 6'-1 0 " 100'-0" 10'-5 1/4"18'-8"26'-4 3/4"14'-8 1/2"24'-1 3/8" PRO P E R T Y L I N E PRO P E R T Y L I N E PROPERTY LINE SETBACK LINE SE T B A C K L I N E SETBACK LINE SET B A C K L I N E HO P K I N S A V E N U E AL L E Y 2 A5.2 5'- 5 3 / 8 " 5'- 5 3 / 8 " 60' - 0 " 6'-7 1 / 4 " 15 ' - 0 3 / 4 " 8'-1 3 / 8 " 8'-1 3 / 8 " 5'-8 1/8" EXISTING ADDITION 1 A5.2A EXI S T I N G AD D I T I O N EXI S T I N G AD D I T I O N 1 A5.3 LEVEL TWODECK BELOW METAL ROOF METAL ROOF METAL ROOF MECHVENT ROOFDECK301 T. O. DECK "A"121'-11 3/8" T. O. PARAPET126'-7" ROOF BELOW LEVEL TWODECK BELOW ROOF BELOW ROOF BELOW 4 & 5A6.21T. O. PARAPET126'-7" W-14 A7.02 W-14 A7.02 W-13A7.02 FIRE RESISTANCE LEGEND 1-HOUR RATED FIR 1-HOUR RATED FIR 1-HOUR RATED EXT 20 MIN. RATED FIRE 2A6.11 GAS F.P.FLUE T.O. SHEATHING122'-9 3/8" T.O. SHEATHING121'-3 3/8" T.O. (E) SHEATHING121'-3 3/8" T.O. (E) SHEATHING121'-3 3/8" T. O. PARAPET123'-4" T. O. PARAPET126'-7" GENERAL PLAN NOTES: 1.INTERIOR PARTITIONS ARE TYPE W7 2.DIMENSIONS ARE TO FACE OF FRAM MARKED AS "CLR" OR "FIN", DIMENS FINISH.3.WHERE NO DIMENSIONS ARE GIVEN OPENINGS, THE EXISTING ROUGH O REMAIN AND WILL BE INFILLED WITH OR DOOR.4.G.C. TO FIELD VERIFY EXISTING CON CONFIRM WALL LAYOUTS WORK AS ARCHITECT OF DISCREPANCIES. OUTDOORKITCHEN 302 STAIR 1303 4A6.25 1/303SNOW FENCE GUTTER GUTTER GUTTER GUTTER 4'-9 1/2"4'- 7 3 / 8 " 6'-7 1 / 2 " 18 ' - 1 1 5 / 8 " 14 ' - 1 " 6'-8 3 / 8 " 21 ' - 6 5 / 8 " 8'-4 1/4"9'-3"18'-9 3/4" GA S F I R E P I T GRILL 5A7.12 1A6.27 2A6.27 9'-6 1/2" T. O. PARAPET126'-7" "SUN DECK" 3R @ 6" 3R @ 6" SPA RESISTANCE POOL ACCESSHATCH TOPOOL MECH.BELOW HANDRAIL @ 36"ABOVE NOSING 5R @ 6"GUA R D @ 3 6 " A F F 6" CMU WALL BELOW - TYP.@ POOL PERIMETER 19'-4" 7'- 0 " 7'-0" 7'-0 " T. O. FINISH 123'-5 3/8" T. O. FINISH124'-11 3/8" ROOF DRAINSBELOW LEVELPAVER DECK, TYP. 3'- 6 " 4'-0" 6'-0" Provide pool design drawings and documentationdemonstrating compliance with 2015 ISPSC (including barrier and deck requirements) and APSC-15. Fill out and submit the APSC-15 compliance information sheet available here: https://apsp.org/portals/0/FileDownloads/APSP-15%20Compliance%20Information%20Sheet.pdf W FDFD BrassFaucetsStillnessK-T948-4 DN UP UP UP FD FEC WHy FD FD FD FD FD UP FD AIR LEAKAGE COMPLIANCE TABLE COMPONENT PER COMPONENTS LISTED IN IECC R402.4.1.1 GENERALREQUIREMENTS A CONTINUOUS AIR BARRIER SHALL BE INSTALLED IN THE BUILDING ENVELOPE. THEEXTERIOR THERMAL ENVELOPE SHALL CONTAIN A CONTINUOUS AIR BARRIER. BREAKSOR JOINTS IN THE AIR BARRIER SHALL BE SEALED. AIR BARRIER CRITERIA CEILING / ATTIC 1/2" MIN. GWB WITH ALL JOINTS TAPED AND SEALED. ALL ATTIC ACCESS DOORS, WHERETHEY OCCUR, SHALL BE GASKETED. WALLS 1/2" MIN. GWB WITH ALL JOINTS TAPED AND SEALED. SILL SEALER BETWEEN SILL PLATES AND FOUNDATIONS ARE REQUIRED. TOP PLATES AT THE TOP OF EXTERIOR WALLS SHALL BE SEALED. WINDOWS, SKYLIGHTS, ANDDOORS ALL SHIM SPACES AND CAVITIES AROUND THE INSIDE OF EXTERIOR DOORS, WINDOWS, AND SKYLIGHTS SHALL BE AIR-SEALED WITH BACKER ROD AND SEALANT OR CLOSEDCELL LOW-EXPANSION FOAM IF ALLOWED BY LISTED ASSEMBLY. RIM JOISTS RIM JOISTS SHALL BE AIR SEALED. JOINTS BETWEEN RIM JOISTS AND TOP PLATES,FLOOR AND ROOF SHEATHING, AND INTERSECTING RIM JOISTS SHALL BE SEALED. FLOORS (INCL.ABOVE GARAGEAND CANTILEVERED FLOORS) THE AIR BARRIER SHALL BE INSTALLED AT ANY EXPOSED EDGE OF INSULATION. AIRBARRIER MAY INCLUDE CLOSED-CELL SPRAY FOAM INSULATION APPLIED TIGHT TO THEUNDERSIDE OF FLOOR SHEATHING AND AT PERIMETER RIM JOISTS IF ALLOWED BY LISTED ASSEMBLY. CRAWL SPACEWALLS WHERE IT OCCURS, EXPOSED EARTH IN UNVENTED CRAWL SPACES SHALL BECOVERED WITH A CLASS I VAPOR RETARDER WITH OVERLAPPING, TAPED JOINTS. SHAFTS, PENETRATIONS ALL PENETRATIONS THROUGH THE EXTERIOR ENVELOPE SHALL BE SEALED WITH COMPATIBLE SEALANTS, GASKETS, BOOTS, ETC. PENETRATIONS THROUGH THE GWB AIR BARRIER SHALL BE SEALED WITH COMPATIBLE SEALANT, PUTTY, MUD /TAPE ASAPPLICABLE. GARAGE SEPARATION GARAGE INTERIOR SHALL BE FULLY SHEATHED IN GWB AND TAPED/SEALED, TYP. RECESSEDLIGHTING FIXTURES RECESSED INTO THE BUILDING THERMAL ENVELOPE SHALL BE IC RATED ANDSEALED TO THE GWB AIR BARRIER PLUMBING AND WIRING DEVICES/FIXTURES SET INTO THE EXTERIOR BUILDING THERMAL ENVELOPE SHALL BE AIR SEALED. SHOWER/TUB ONEXTERIOR WALL SHOWERS AND TUBS LOCATED AT EXTERIOR WALLS SHALL BE SEPARATED BY AN AIRBARRIER. MIN. 1/2" CEMENT BOARD WITH JOINTS SEALED WITH WATERPROOFINGMEMBRANE OR SIM. REQUIRED. ELECTRICAL/PHONE AIR BARRIER SHALL BE INSTALLED BEHIND BOXES OR AIR-SEALED BOXES SHALL BE FIRE SEPARATION LEGEND 20 MINUTE FIRE PARTITION DWELLING UNIT ACOUSTIC SEPARATION (MIN. 50 STC PER IBC 1207.2) THERMAL BARRIER 1 HOUR FIRE-RATED ASSEMBLY NOTE: REFER TO FLOOR PLANS, SHEETS A2.X, AND BUILDING SECTIONS, SHEETS A5.X, FOR DETAILED WALL AND FLOOR FIRE RESISTANCE DESIGNATIONS. SCALE: BASEMENT LEVEL FIRE SEPARATION DIAGRAM 1/16" = 1'-0" 1 A0.5z R2 - RESIDENTIAL B - BUSINESS B - BUSINESS B - BUSINESS 1/2 hour (30 minute) rating required for corridor walls servingdwellings. 2015 IBC 1020.1 1 2 3 4 5 6 7 7 6 5 4 3 SCALE: TRANSVERSE SECTION FIRE SEPARATION DIAGRAM 1/16" = 1'-0" 7 A0.5z SCALE: TRANSVERSE SECTIO FIRE SEPARATION DIA 1/16" = 1'-0" 8 A0.5z R2 - RESIDENTIAL R2 - RES. B - BUSINESS B - BUSINESS B - BUSINESS B - BUSINESS R R2 - R U - UTILITY R2 - RESIDENTIALNOTE: SAME UNIT The entire floor structure on floor 1 and floor 2 throughout the entire building must be 1 hour fire rated to maintain dwelling separation fire partition continuity (2015 IBC 708.4). H L W L TR. P GMEM 4 1 E 4 1A4.21A4.1 2A4.2CD F G 2 2 66 5 B 60' - 0 " 6'-1 0 " 17'- 1 1 1 / 4 " 6'-7 1 / 4 " 15'- 0 3 / 4 " 17'- 1 1 1 / 4 " 6'-1 0 " 100'-0" 100'-0" 10'-5 1/4"18'-8"26'-4 3/4"14'-8 1/2"24'-1 3/8" 26'-4 3/4"14'-8 1/2" 3 3 5 PROPERTY LINE PR O P E R T Y L I N E PROPERTY LINE PR O P E R T Y L I N E PROPERTY LINE 5'-8 1/8" SETBACK LINE SET B A C K L I N E SETBACK LINE SET B A C K L I N E MONARCH STREET HOP K I N S A V E N U E ALL E Y 2A5.2 2A5.1 2A5.1 7 5'-5 3 / 8 " 7 5'-5 3 / 8 " 60' - 0 " 6'-7 1 / 4 " 15'- 0 3 / 4 " 8'-1 3 / 8 " 8'-1 3 / 8 " 10'-5 1/4"18'-8" 5'-8 1/8" 24'-1 3/8" EXISTING ADDITION EXISTING ADDITION 1 A5.1 1 A5.1 1A5.2A EX I S T I N G AD D I T I O N EX I S T I N G AD D I T I O N 1 1A5.3 K-692ClairetteFaucetsBrass 105sf 52sf DN DN DN SLOPEDNUP FEC WHy WHy DW REF ELEL E C . METE R S MDP TRUENORTH SCALE: PROPOSEDLEVEL ONE FLOOR PLAN 3/16" = 1'-0" 1 A2.1 PLANNORTH SUBGRADECOURTYARDBELOW TRASH/RECYCLINGMETERS NEWMECHCHASE COMM.UNIT 1100 COMM.UNIT 2108 GARAGE103 COMM. 1BATHROOM 101 ENTRYLOBBY109 STAIR #1104 RESTROOM106 AHU102 AHUWINDOW WELL OPEN TO BELOW TR A S H / R E C Y C L I N G COMM.UNIT 3107 NEW K I T C H E N L A Y O U T 115 124 1/100 1/101 1/102 1/103 1/104 2/104 1/107 2/1071/108 1/109 2/108 1/106 ELEVATOR1 2/103103 101 103 103 ABV. 106 107 108 109 111 112 113 114 122121120119118117116 123 ABV. 125 126ABV. 101 T. O. PLY.100'-0" (E) T. O. PLY.(E)100'-0" T. O. PLY.100'-0" T. O. PLY.99'-6" T. O. TOPPING SLAB99'-6" 2A6.21 T. O. TOPPING SLAB100'-0" W14A7.02 W14A7.02 W15 SIM.A7.02 2A6.25 W8FA7.01 W15 SIM. A7.02 W10A7.01 W8FA7.01 W8A7.01 W8A7.01 W8A7.01 W8A7.01 W12A7.01 W12A7.01 FIRE RESISTANCE LEGEND: 1-HOUR RATED FIRE BARRIER 1-HOUR RATED FIRE PARTITION 1-HOUR RATED EXTERIOR WALL 20 MIN. RATED FIRE PARTITION T. O. PLY. (E)100'-0" T. O. STRUCT. SLAB99'-3" 3A6.23 W8A7.01 W3A7.01 W3A7.01 W3A7.01 W7A7.01 W7A7.01 HALL105 W6A7.01 GENERAL PLAN NOTES: 1.INTERIOR PARTITIONS ARE TYPE W7/A7.01, U.N.O.2.DIMENSIONS ARE TO FACE OF FRAMING, TYP. WHEREMARKED AS "CLR" OR "FIN", DIMENSIONS ARE TOFINISH.3.WHERE NO DIMENSIONS ARE GIVEN FOR EXTERIOROPENINGS, THE EXISTING ROUGH OPENING IS TOREMAIN AND WILL BE INFILLED WITH A NEW WINDOWOR DOOR.4.G.C. TO FIELD VERIFY EXISTING CONDITIONS ANDCONFIRM WALL LAYOUTS WORK AS PLANNED. NOTIFYARCHITECT OF DISCREPANCIES. PROPERTY LINE NEIGHBORING BUILDING EXISTING WALLEXISTING SETBACK ENCROACHMENT NEIGHBORING BUILDING W7A7.01 1A6.23 114 ABV.6A7.10 SIM.SIM. W3A7.01 FAC P T. O. SLAB100'-0" RAISED PLANTER - RE: LANDSCAPE &CIVIL 3'- 6 1 / 8 " 18'-9 3/4"5'-3 5/8"9'-3" 9'- 4 1 / 2 " 14'- 3 9 / 1 6 " 12'- 5 1 3 / 1 6 " 5'-6 1 / 2 " 4'-0 1/8"8'-2 3/4"7'-3 3/8"4'-7 1/8" 5'-5 1/2" EQ . EQ . EQ . EQ . EQ . A CLR EQ . A CLR 2A7.10 2A7.10 NEW WINDOWS IN EXISTING OPENINGS 2'-3 1 / 8 " 7'-1 " ADDEDFURRINGWALL FORRECESSEDELEC. PANEL EVCS LOCATION- RE:ELECTRICAL 3/104 AREA MARKED TO REMAIN CLEARFOR TRASH / RECYCLING ACCESSAND EMERGENCY EGRESS WASTE RECEPTACLES - EACHSHALL BE LESS THAN 1YD (200GALLON) CAPACITY, TYP. PER IFC304.3.4 WASTE RECEPTACLES - EACHSHALL BE LESS THAN 1YD (200GALLON) CAPACITY, TYP. PER IFC304.3.4 W10A7.01SIM. 3A6.22 EXISTCOLUMN 1A6.27 2A6.27 2A7.12 2X8 FRAMING FOR MOMENTFRAME CLEARANCE - HOLD EXT.FACE OF FRAMING, TYP. 4" STEP 2/100 3A6.26 ntati o n \ 0 1 _ D r a w i n g s \ 2 1 7 1 8 _ A 2 - 1 . d w g Revision: Issue: SHEET TITLE PROJECT NO: DWG FILE: SCALE: 21718_A2-1.dwg MTN FORGE RENOVATION AND ADDITION 230-234 E. HOPKINS A ASPEN, CO 81611 21718 11.16.2017P+Z FINAL HEARING 1 denve 3 500 w main staspen, co 81611970.544.9006 rowland+brougarchitecture / urban design / inte 08.02.2018CONSTRUCTION DOCUMENT 08.28.201880% PRICING 02.08.2019CD/PRICING SET 04.18.2019CONSTRUCTION DOCUMENT 03.08.2019ASI-001 3/16"=1'-0" PROPOSEDLEVEL ONEFLOOR PLAN Include interior elevations and dimensioned plan todemonstrateaccessibility for Comm1 Bathroom as youhave done for otherbathrooms on A9.1. Also provide aclearspace beyond thedoor swing. Page: A2.2 PROPOSED LEVEL TWO FLOOR PLAN File Name: 230 E. Hopkins_Drawings_Architecture_2019-04-18.pdf Subject: PlanCheck Author: nickt Color: The service sink required by 2015 IBC 2902.1 is only accessible to Commerical unit 8. It must be accessible to all Group B occupancies. Page: A2.2 PROPOSED LEVEL TWO FLOOR PLAN File Name: 230 E. Hopkins_Drawings_Architecture_2019-04-18.pdf Subject: PlanCheck Author: nickt Color: 1/2 hour (30 minute) rating required for corridor walls serving dwellings. 2015 IBC 1020.1 Page: A2.2 PROPOSED LEVEL TWO FLOOR PLAN File Name: 230 E. Hopkins_Drawings_Architecture_2019-04-18.pdf Subject: PlanCheck Author: nickt Color: Include interior elevations and dimensioned plan to demonstrate accessibility for Restroom 222 as you have done for other bathrooms on A9.1. Also provide a clearspace beyond the door swing. Page: A5.2 PROPOSED BUILDING SECTIONS File Name: 230 E. Hopkins_Drawings_Architecture_2019-04-18.pdf Subject: PlanCheck Author: nickt Color: To maintain dwelling separation continuity, assembly R2/A7.03 must be a listed 1 hour fire rated assembly. Revise R2/A7.03 to indicate a listing. Page: A5.2 PROPOSED BUILDING SECTIONS File Name: 230 E. Hopkins_Drawings_Architecture_2019-04-18.pdf Subject: PlanCheck Author: nickt Color: In order to avoid needing a parapet at the exterior wall, the 1 hour rated roof must have all supporting construction also be 1 hour fire rated. Indicate all locations with this requirement. 2015 IBC 705.11 exception 4.2 DN UP OV REFDRWS FR. REF. U/CREF MW PTRY. U/CWINE FEC RD OD OVERFLOWSCUPPER RD DN DN DNDN DN DN DNDN RD OD DN RD OD DN RD OD DN DN FLA T C E I L I N G RID G E A B O V E STRGBELOW MECHEQ ACCESSPANEL RD ODDNDN DNOD RD DN 4 1 E 4 1A4.21 2A4.2CD F G 2 2 66 5 B 60'- 0 " 6'-1 0 " 17'- 1 1 1 / 4 " 6'- 7 1 / 4 " 15 ' - 0 3 / 4 " 17'- 1 1 1 / 4 " 6'-1 0 " 100'-0" 10'-5 1/4"18'-8"26'-4 3/4"14'-8 1/2"24'-1 3/8" 3 3 5 PROPERTY LINE PRO P E R T Y L I N E PROPERTY LINE PR O P E R T Y L I N E PROPERTY LINE SETBACK LINE SET B A C K L I N E SETBACK LINE SET B A C K L I N E HO P K I N S A V E N U E ALL E Y 2A5.2 1 2A5.1 7 5'-5 3 / 8 " 7 5'-5 3 / 8 " 60'- 0 " 6'- 7 1 / 4 " 15 ' - 0 3 / 4 " 8'- 1 3 / 8 " 8'- 1 3 / 8 " 5'-8 1/8" EXISTING ADDITION 1 1A5.1 1A5.2A EXI S T I N G AD D I T I O N EXI S T I N G AD D I T I O N 1 1A5.3 EXISTING ROOF BELOW PROPOSEDDECK RESIDENCEGREAT ROOM204 COMM.UNIT 8214 STAIR #1217 COMM.UNIT 7221 GUESTSUITE219 CORRIDOR 2216 RO O F O V E R H A N G RESIDENCEKITCHEN 202 EXISTINGDECK MECH. 3 218 JANITORCLOSET213 1/203 1/201 1/210 1/221 1/217 1/213 1/219 TWO-SIDED GASFIREPLACE APPLIANCE ELEVATOR 1 201ABV. 202 203 1/218 204 205 207 208 209 210 212211 213 214 215 218 220 220 220 221 222 223 223 224225226 1/215 T. O. PLY.111'-1 3/8" T. O. PLY.111'-1 3/8" 3A6.21 RESTROOM222 1/208 RESIDENCEDINING 203 3A6.25 RESIDENCECLOSET 211 1/207 1/222 WC210a RESIDENCEFOYER 201 1A6.11 W12 A7.01 W8FA7.01 W8A7.01 W12A7.01SIM.W12A7.01 ROOF CANOPY BELOWW8A7.01 W8A7.01 W8A7.01 W14A7.02 W8FA7.01W8FA7.01 W8A7.01 SUITEENTRY206 HALL208 BENCH RESIDENCECLOSET 209 2/219 RESIDENCESTUDY207 GUESTSUITE 212 GAS FIREPLACEAPPLIANCE ROOF CANOPY BELOW RES.BATH210 W10A7.01 W10A7.01 W10A7.01 W10A7.01 W8A7.01 GENERAL PLAN NOTES: 1.INTERIOR PARTITIONS ARE TYPE W7/A7.01, U.N.O.2.DIMENSIONS ARE TO FACE OF FRAMING, TYP. WHEREMARKED AS "CLR" OR "FIN", DIMENSIONS ARE TOFINISH.3.WHERE NO DIMENSIONS ARE GIVEN FOR EXTERIOROPENINGS, THE EXISTING ROUGH OPENING IS TOREMAIN AND WILL BE INFILLED WITH A NEW WINDOW OR DOOR.4.G.C. TO FIELD VERIFY EXISTING CONDITIONS ANDCONFIRM WALL LAYOUTS WORK AS PLANNED. NOTIFYARCHITECT OF DISCREPANCIES. 3A6.13 204 204 206ABV.207206ABV. 217216 ABV.ABV.ABV. 219 SHOWER210b 1A7.11 2X4 FURRING 3A7.04 1'-4 1 / 8 " 5'- 1 1 1 / 8 " 9'- 9 1 / 4 " 7'-8 1 / 4 " 13'- 2 1 / 4 " 5'-9 1 / 8 " 4'- 0 1 / 2 " 18'-9 3/4"5'-3 5/8"9'-3" 5'-3 5/8" 3 1 / 2 " 3'-1 " 8'- 7 1 1 / 1 6 " EQ . EQ . 4'-4 5/8"10'-4 3/4"4'-9 3/8"4'-9 3/8"4'-4 5/16"8'-10 11/16"4'-5 5/16"8'-10 11/16"4'-5 3/8"4'-5 3/8"12'-8 1/2"3'-9 3/4"2'-3 1/2" NEW WINDOW - EXIST.OPENING 7 1 / 8 " 9" 5'-1 1 1 / 1 6 " 1'-1 0 " ALIGNS WITHBELOW - RE:ELEVATIONS EQ . A CL R EQ . A CLR WINDOWS ALIGN WITH BELOW EXIST. OPENINGS - VIF - RE: ELEVATIONS 2'-9 3/16"2'-10 5/16" 1/209 1/211 W10A7.01SIM.W10A7.01SIM. W10A7.01SIM. FIRE RESISTANCE LEGEND: 1-HOUR RATED FIRE BARRIER 1-HOUR RATED FIRE PARTITION 1-HOUR RATED EXTERIOR WALL 20 MIN. RATED FIRE PARTITION 1/206 3A6.22 1A6.27 2A6.27 NEW WINDOW - EXIST. OPENING EXIST. PARAPET 2X8 FRAMING FOR MOMENTFRAME CLEARANCE - HOLD EXT.FACE OF FRAMING, TYP. 1 A6.26 Revision: Issue: MTN FOR RENOVA AND ADD 230-234 E. H ASPEN, CO 11.16.2017P+Z FINAL HEAR 500 w main staspen, co 81611970.544.9006 rowlandarchitecture / urb 08.02.2018CONSTRUCTION 08.28.201880% PRICING 02.08.2019CD/PRICING SET 04.18.2019CONSTRUCTION 03.08.2019ASI-001 The service sinkrequired by 2015 IBC2902.1 is onlyaccessible toCommerical unit 8. Itmust be accessible toall Group Boccupancies. DN UP F G 6 15 ' - 0 3 / 4 " 14'-8 1/2"24'-1 3/8" 5 PROPERTY LINE SETBACK LINE 7 5'- 5 3 / 8 " 1A5.1 1 A5.3 STAIR #1 217 COMM.UNIT 7 221 1/217 222 223 223 RESTROOM 1/222 W8F A7.01 W8A7.01 W14 A7.02 GENERAL PLAN NOTES: 1.INTERIOR PARTITIONS ARE TYPE W7/A7.01, U.N.O.2.DIMENSIONS ARE TO FACE OF FRAMING, TYP. WHEREMARKED AS "CLR" OR "FIN", DIMENSIONS ARE TOFINISH.3.WHERE NO DIMENSIONS ARE GIVEN FOR EXTERIOROPENINGS, THE EXISTING ROUGH OPENING IS TOREMAIN AND WILL BE INFILLED WITH A NEW WINDOWOR DOOR.4.G.C. TO FIELD VERIFY EXISTING CONDITIONS AND CONFIRM WALL LAYOUTS WORK AS PLANNED. NOTIFY ARCHITECT OF DISCREPANCIES. 1'- 4 1 / 8 " 5'- 1 1 1 / 8 " 9'-9 1 / 4 " 18'-9 3/4"5'-3 5/8"9'-3" 7 1 / 8 " 9" FIRE RESISTANCE LEGEND: 1-HOUR RATED FIRE BARRIER 1-HOUR RATED FIRE PARTITION 1-HOUR RATED EXTERIOR WALL 20 MIN. RATED FIRE PARTITION Revision: Issue: 11.16.2017P+Z FINAL HEARING 1830 blake stdenver, co 80202303.308.1373 500 w main staspen, co 81611970.544.9006 rowland+broughton architecture / urban design / interior design 08.02.2018CONSTRUCTION DOCUMENTS 08.28.2018 80% PRICING 02.08.2019CD/PRICING SET 04.18.2019CONSTRUCTION DOCUMENTS 03.08.2019ASI-001 1/2 hour (30 minute) rating required forcorridor walls serving dwellings. 2015 IBC 1020.1 DN UP OV REFDRWS FR. REF. U/CREF MW PTRY. U/CWINE FEC RD OD OVERFLOWSCUPPERRD DN DN DNDN DN DN DNDN RD OD DN RD OD DN RD OD DN DN FLA T C E I L I N G RID G E A B O V E STRGBELOW MECHEQ ACCESSPANEL RD ODDNDN DNOD RDDN E 4 1A4.2 2A4.2CD F G 2 6 B 60'- 0 " 6'-1 0 " 17'- 1 1 1 / 4 " 6'-7 1 / 4 " 15' - 0 3 / 4 " 17'- 1 1 1 / 4 " 6'-1 0 " 100'-0" 100'-0" 10'-5 1/4"18'-8"26'-4 3/4"14'-8 1/2"24'-1 3/8" 26'-4 3/4"14'-8 1/2" 3 5 PROPERTY LINE PRO P E R T Y L I N E PROPERTY LINE PRO P E R T Y L I N E PROPERTY LINE 5'-8 1/8" SETBACK LINE SET B A C K L I N E SETBACK LINE SET B A C K L I N E MONARCH STREET HOP K I N S A V E N U E ALL E Y 2A5.2 2A5.1 7 5'-5 3 / 8 " 5'-5 3 / 8 " 6'-7 1 / 4 " 15' - 0 3 / 4 " 8'-1 3 / 8 " 8'-1 3 / 8 " 10'-5 1/4"18'-8" 5'-8 1/8" 24'-1 3/8" EXISTING ADDITION EXISTING ADDITION 1A5.1 1A5.2A EXI S T I N G ADD I T I O N EXI S T I N G ADD I T I O N 1 1A5.3 TRUENORTHSCALE: PROPOSEDLEVEL TWO FLOOR PLAN3/16" = 1'-0"1A2.2 PLANNORTH EXISTING ROOF BELOW PROPOSEDDECK RESIDENCEGREAT ROOM204 COMM.UNIT 8214 STAIR #1 217 COMM.UNIT 7221 GUESTSUITE219 CORRIDOR 2 216 RO O F O V E R H A N G RESIDENCEKITCHEN202 EXISTINGDECK MECH. 3218 JANITORCLOSET213 1/203 1/201 1/210 1/221 1/217 1/213 1/219 TWO-SIDED GASFIREPLACE APPLIANCE ELEVATOR1 201ABV. 202 203 1/218 204 205 207 208 209 210 212211 213 214 215 218 220 220 220 221 222 223 223 224225226 1/215 T. O. PLY.111'-1 3/8" T. O. PLY.111'-1 3/8" 3A6.21 RESTROOM222 1/208 RESIDENCEDINING203 3A6.25 RESIDENCECLOSET211 1/207 1/222 WC210a RESIDENCEFOYER201 1A6.11 W12A7.01 W8FA7.01 W8A7.01 W12A7.01SIM.W12A7.01 ROOF CANOPYBELOWW8A7.01 W8A7.01 W8A7.01 W14A7.02 W8FA7.01W8FA7.01 W8A7.01 SUITEENTRY206 HALL208 BENCH RESIDENCECLOSET209 2/219 RESIDENCESTUDY207 GUESTSUITE212 GAS FIREPLACEAPPLIANCE ROOF CANOPYBELOW RES.BATH210 W10A7.01 W10A7.01 W10A7.01W10A7.01 W8A7.01 GENERAL PLAN NOTES: 1.INTERIOR PARTITIONS ARE TYPE W7/A7.01, U.N.O.2.DIMENSIONS ARE TO FACE OF FRAMING, TYP. WHEREMARKED AS "CLR" OR "FIN", DIMENSIONS ARE TOFINISH.3.WHERE NO DIMENSIONS ARE GIVEN FOR EXTERIOROPENINGS, THE EXISTING ROUGH OPENING IS TOREMAIN AND WILL BE INFILLED WITH A NEW WINDOWOR DOOR.4.G.C. TO FIELD VERIFY EXISTING CONDITIONS ANDCONFIRM WALL LAYOUTS WORK AS PLANNED. NOTIFYARCHITECT OF DISCREPANCIES. 3A6.13 204 204 206ABV.207206ABV. 217216ABV.ABV.ABV.219 SHOWER210b 1A7.11 2X4 FURRING 3A7.04 1'-4 1 / 8 " 5'-1 1 1 / 8 " 9'-9 1 / 4 " 7'-8 1 / 4 " 13'- 2 1 / 4 " 5'-9 1 / 8 " 4'-0 1 / 2 " 18'-9 3/4"5'-3 5/8"9'-3" 5'-3 5/8" 3 1 / 2 " 3'-1 " 8'-7 1 1 / 1 6 " EQ . EQ. 4'-4 5/8"10'-4 3/4"4'-9 3/8"4'-9 3/8"4'-4 5/16"8'-10 11/16"4'-5 5/16"8'-10 11/16"4'-5 3/8"4'-5 3/8"12'-8 1/2"3'-9 3/4"2'-3 1/2" NEW WINDOW - EXIST.OPENING 7 1/ 8 " 9" 5'-1 1 1 / 1 6 " 1'-1 0 " ALIGNS WITHBELOW - RE:ELEVATIONS EQ . A CLR EQ. A CLR WINDOWS ALIGN WITH BELOW EXIST. OPENINGS - VIF - RE: ELEVATIONS 2'-9 3/16"2'-10 5/16" 1/209 1/211 W10A7.01SIM.W10A7.01SIM. W10A7.01SIM. FIRE RESISTANCE LEGEND: 1-HOUR RATED FIRE BARRIER 1-HOUR RATED FIRE PARTITION 1-HOUR RATED EXTERIOR WALL 20 MIN. RATED FIRE PARTITION 1/206 3A6.22 1A6.27 2A6.27 NEW WINDOW -EXIST. OPENING EXIST. PARAPET 2X8 FRAMING FOR MOMENTFRAME CLEARANCE - HOLD EXT.FACE OF FRAMING, TYP. 1A6.26 Revision: Issue: SHEET TITLE PROJECT NO: DWG FILE: SCALE: 21718_A2-2.dwg MTN FORGERENOVATION AND ADDITION 230-234 E. HOPKINS AVENUEASPEN, CO 81611 21718 11.16.2017P+Z FINAL HEARING 1830 blake stdenver, co 80202303.308.1373 500 w main staspen, co 81611970.544.9006 rowland+broughtonarchitecture / urban design / interior design 08.02.2018CONSTRUCTION DOCUMENTS 08.28.201880% PRICING 02.08.2019CD/PRICING SET 04.18.2019CONSTRUCTION DOCUMENTS 03.08.2019ASI-001 A2.2 3/16"=1'-0" PROPOSEDLEVEL TWOFLOOR PLAN Include interiorelevations anddimensioned plan todemonstrateaccessibility forRestroom 222 as youhave done for otherbathrooms on A9.1.Also provide aclearspace beyond thedoor swing. SCALE: PROPOSEDBUILDING SECTION 3/16" = 1'-0" 1 A5.2 T.O. PLYLEVEL ONE (E)100'-0" T.O. PLYLEVEL TWO (E)111'-1 3/8" T.O. CONC.BASEMENT (E)88'-10 5/8" T.O. PLYROOF (IN FOREGROUND)121'-3 3/8" 11 ' - 1 3 / 8 " 11'- 1 3 / 8 " 10' - 2 " T.O. PLATEAT GABLE122'-6" T.O. PARAPET(IN FOREGROUND)126'-7" 1 2 3 4 5 6 7 60'-0" 5'-5 3/8"15'-0 3/4"6'-7 1/4"8'-1 3/8"17'-11 1/4"6'-10" 1A5.12A5.1 12 12 12 12 R2A7.03F2A7.02 MONARCHSTREET F2A7.02 F6A7.02F6A7.02 F2A7.02F2A7.02 5A7.10 SIM. O.H. W5A7.01 EXIST. CMU WALLS EXIST. FOUNDATION F8A7.02 F1A7.02 F1A7.02 RESIDENCEGREAT RM 204 RESIDENCEDINING 203 COMM.UNIT 1100 ENTRYLOBBY109 COMM.UNIT 2108 SE T B A C K PR O P E R T Y L I N E PR O P E R T Y L I N E SE T B A C K EXIST. SETBACKENCROACHMENT R1A7.03 R1A7.03 COMM.UNIT 4016 COMM.UNIT 4001 COURTYARD 000 LINE OF PROPOSEDGRADE - RE: CIVIL GUARDRAIL BEYOND 2A7.10 W3A7.02SIM. F4A7.02 2A7.11SIM. OH 6A7.11 W17FA7.02 MICROPILE WALL -RE: SHORINGDESIGN EXIST. BEAM - SIZEVARIES - RE:STRUCT. EXIST. BEAM - SIZEVARIES - RE:STRUCT. STEEL BEAM - SIZEVARIES - RE:STRUCT. 5'-3 5 / 8 " T.O. PLYROOF121'-3 3/8" T.O. ROOFDECK "A"121'-11 3/8" T.O. PARAPET126'-7" 1 2 3 4 5 6 7 60'-0" 5'-5 3/8"15'-0 3/4"6'-7 1/4"8'-1 3/8"17'-11 1/4"6'-10" 1A5.12A5.1 PARAPET ROOF BEYOND ROOF BEYONDPARAPET EXIST. BEAMBEYONDBEAM - RE:STRUCT. EXIST. ROOFFRAMING R3A7.03 EXIST. BEAMBEYOND SE T B A C K PR O P E R T Y L I N E PR O P E R T Y L I N E SE T B A C K GLASS SAFETYGUARD GLASS SAFETY GUARD @ MIN.18" ABOVE POOL COPING 12' - 7 " C L R . PER M F R . 10'- 0 " M A X . O V E R R U N R4A7.03SIM. T.O. CONCRETE135'-7" 6A6.24 ELEVATORSHAFT 9'-0 " 7A7.10 TYP. 9A7.10 8A7.12 WATER FEATURE SPA BEYOND 1'- 8 " G U A R D 3'-6 " R3FA7.03 POOLR8A7.03 Revision: Issue: MTN FORGE RENOVATION AND ADDITION 230-234 E. HOPKINS AVENUE ASPEN, CO 81611 11.16.2017P+Z FINAL HEARING 1830 blake stdenver, co 80202303.308.1373 500 w main staspen, co 81611970.544.9006 rowland+broughtonarchitecture / urban design / interior design 08.02.2018CONSTRUCTION DOCUMENTS 08.28.201880% PRICING 02.08.2019CD/PRICING SET 04.18.2019CONSTRUCTION DOCUMENTS 03.08.2019ASI-001 To maintain dwelling separation continuity,assembly R2/A7.03must be a listed 1 hourfire rated assembly.Revise R2/A7.03 toindicate a listing. SCALE: PROPOSEDBUILDING SECTION3/16" = 1'-0"1A5.2 T.O. PLYLEVEL ONE (E)100'-0" T.O. PLYLEVEL TWO (E)111'-1 3/8" T.O. CONC.BASEMENT (E)88'-10 5/8" T.O. PLYROOF (IN FOREGROUND)121'-3 3/8" 11'-1 3 / 8 " 11'-1 3 / 8 " 10'-2 " T.O. PLATEAT GABLE122'-6" T.O. PARAPET(IN FOREGROUND)126'-7" 1 2 3 4 5 6 760'-0" 5'-5 3/8"15'-0 3/4"6'-7 1/4"8'-1 3/8"17'-11 1/4"6'-10" 1A5.12A5.1 1212 1212 R2A7.03F2A7.02 MONARCHSTREET F2A7.02 F6A7.02F6A7.02 F2A7.02F2A7.02 5A7.10SIM. O.H. W5A7.01 EXIST. CMU WALLS EXIST. FOUNDATION F8A7.02 F1A7.02 F1A7.02 RESIDENCEGREAT RM204 RESIDENCEDINING203 COMM.UNIT 1100 ENTRYLOBBY109 COMM.UNIT 2108 SET B A C K PRO P E R T Y L I N E PRO P E R T Y L I N E SET B A C K EXIST. SETBACKENCROACHMENT R1A7.03 R1A7.03 COMM.UNIT 4016 COMM.UNIT 4001 COURTYARD000 LINE OF PROPOSEDGRADE - RE: CIVIL GUARDRAIL BEYOND 2A7.10 W3A7.02SIM. F4A7.02 2A7.11SIM. OH 6A7.11 W17FA7.02 MICROPILE WALL -RE: SHORINGDESIGN EXIST. BEAM - SIZEVARIES - RE:STRUCT. EXIST. BEAM - SIZEVARIES - RE:STRUCT.STEEL BEAM - SIZEVARIES - RE:STRUCT. SCALE: PROPOSEDBUILDING SECTION3/16" = 1'-0"2A5.2 MONARCHSTREET 5'-3 5 / 8 " T.O. PLYLEVEL ONE100'-0" T.O. PLYLEVEL TWO111'-1 3/8" T.O. CONC.BASEMENT88'-10 5/8" T.O. PLYROOF121'-3 3/8" 11'- 1 3 / 8 " 11'- 1 3 / 8 " 10'- 2 " T.O. ROOFDECK "A"121'-11 3/8" T.O. PARAPET126'-7" 1 2 3 4 5 6 7 60'-0"5'-5 3/8"15'-0 3/4"6'-7 1/4"8'-1 3/8"17'-11 1/4"6'-10" 1A5.12A5.1 EXIST. CMU WALLS NEWEGRESSWELL PARAPET ROOF BEYOND ROOF BEYONDPARAPET EXIST. BEAMBEYONDBEAM - RE:STRUCT. EXIST. FOUNDATION EXIST. ROOFFRAMING EXIST. AREAWELLWALL - TOP CUTDOWN BELOWGRADE NEW EGRESS WELLWALL F1A7.02 8'-8" R3A7.03 R2A7.03F2A7.02 F2A7.02 EXIST. BEAMBEYOND 8'-1 0 " 8'-0" RES.BATH210 HALL208 RESIDENCECLOSET211 CORR. 2216 COMM.UNIT 8214 COMM.UNIT 1100 HALL105 COMM.UNIT 3107RAISED PLANTER &WATER QUALITYCAPTURE - RE:LANDSCAPE & CIVIL F2A7.02 W4A7.01 COMM. 1BATHROOM101 BEDROOM002 COMM.UNIT 5007 W6A7.01 BEAM - RE:STRUCT. RESTROOM012 SET B A C K PRO P E R T Y L I N E PRO P E R T Y L I N E SET B A C K MICROPILE WALL -RE: SHORINGDESIGN CORRIDOR017 GLASS SAFETYGUARD GLASS SAFETY GUARD @ MIN.18" ABOVE POOL COPING 4'-0" P I T PER M F R . 12'- 7 " C L R . PER M F R . 10'-0 " M A X . O V E R R U N R4A7.03SIM. T.O. CONCRETE135'-7" F2A7.02 6A7.10BEYOND 6A6.24 ELEVATORSHAFT ELEVATORSHAFT 9'-0" W3A7.02SIM. EXIST. SETBACKENCROACHMENT F4A7.02 7A7.10TYP. 9A7.10 8A7.12 WATER FEATURE SPA BEYOND 1'-8" G U A R D 3'-6" W17FA7.02 R3FA7.03 POOLR8A7.03 File Pa t h : P : \ P r o j - 2 0 1 7 \ 2 1 7 1 8 . 0 0 _ M t n F o r g e \ 0 6 _ D o c u m e n t a t i o n \ 0 1 _ D r a w i n g s \ 2 1 7 1 8 _ A 5 - 1 . d w g Plot Dat e / T i m e : A p r i l 1 8 , 2 0 1 9 - 1 0 : 3 9 a m COPYRIGHT 2019 ROWLAND+BROUGHTON ARCHITECTURE AND URBAN DESIGNTHE INFORMATION AND DESIGN INTENT CONTAINED ON THIS DOCUMENT ISTHE PROPERTY OF ROWLAND+BROUGHTON ARCHITECTURE AND URBANDESIGN. NO PART OF THIS INFORMATION MAY BE USED WITHOUT THE PRIORWRITTEN PERMISSION OF ROWLAND+BROUGHTON ARCHITECTURE AND URBANDESIGN. ROWLAND+BROUGHTON ARCHITECTURE AND URBAN DESIGN SHALLRETAIN ALL COMMON LAW STATUTORY AND OTHER RESERVED RIGHTS,INCLUDING COPYRIGHT THERETO. Revision: Issue: SHEET TITLE PROJECT NO: DWG FILE: SCALE: 21718_A5-1.dwg MTN FORGERENOVATION AND ADDITION 230-234 E. HOPKINS AVENUEASPEN, CO 81611 21718 11.16.2017P+Z FINAL HEARING 1830 blake stdenver, co 80202303.308.1373 500 w main staspen, co 81611970.544.9006 rowland+broughtonarchitecture / urban design / interior design 08.02.2018CONSTRUCTION DOCUMENTS08.28.201880% PRICING 02.08.2019CD/PRICING SET 04.18.2019CONSTRUCTION DOCUMENTS 03.08.2019ASI-001 A5.2 3/16" = 1'-0" PROPOSEDBUILDINGSECTIONS In order to avoidneeding a parapet atthe exterior wall, the 1hour rated roof musthave all supportingconstruction also be 1hour fire rated. Indicateall locations with thisrequirement. 2015 IBC705.11 exception 4.2 Page: A6.14 ROOF TOP FIREPIT & PLANTERS File Name: 230 E. Hopkins_Drawings_Architecture_2019-04-18.pdf Subject: PlanCheck Author: nickt Color: I have not received installation instructions for the gas fire pit detailing required clearances. Provide instructions and revise plans to clearly show compliance with manufacturer's requirements for clearances. Page: A6.22 SECTION AT MAIN STAIR File Name: 230 E. Hopkins_Drawings_Architecture_2019-04-18.pdf Subject: PlanCheck Author: nickt Color: The hall extension to the exit enclosure must be built as an exit passageway. This requires 1 hour fire barriers. Fire barriers must be continuous to the underside of floor sheathing above with no structural interruption. Thoroughly detail in architecturals and structurals to show compliance. 2015 IBC 707.5 Page: A6.22 SECTION AT MAIN STAIR File Name: 230 E. Hopkins_Drawings_Architecture_2019-04-18.pdf Subject: PlanCheck Author: nickt Color: Ceilings dropped below rated assemblies must be framed with non-combustible or fire resistant treated materials. 2015 IBC 803.4 Page: A6.22 SECTION AT MAIN STAIR File Name: 230 E. Hopkins_Drawings_Architecture_2019-04-18.pdf Subject: PlanCheck Author: nickt Color: Clearly identify all structure that supports the fire barriers and protect with 1 hour fire rating. Columns must be individually encapsulated with 1 hour fire rating. Beams that support more than a floor and a roof or more than two floors must also be individually encapsulated with 1 hour rating. 2015 IBC 704. Page: A6.26 MECH. SHAFT DRAWINGS File Name: 230 E. Hopkins_Drawings_Architecture_2019-04-18.pdf Subject: PlanCheck Author: nickt Color: Clearly identify all structure that supports the fire barriers and protect with 1 hour fire rating. Columns must be individually encapsulated with 1 hour fire rating. Beams that support more than a floor and a roof or more than two floors must also be individually encapsulated with 1 hour rating. 2015 IBC 704. UP 5'-2 " 2'-10" VENT PIPE ROUTING IN CHASEBELOW BENCH TO TERMINATIONWALL VENT. INSTALL PER MFRREQ'S. AND SPECIFICATIONS VERTICAL PENETRATIONTHROUGH ROOF DECK. RE: MECH. ENG. PLANS FOR DETAILS E F PLANTER (A)PLANTER (A)PLANTER (A)PLANTER (A)PLANTER (B) 12" THK. CORTEN SHEETSTEEL PLANTER BED, TYP. 6" H. GLASS FIRE PIT SCREEN.HIGH TEMPERATURE, TEMPERED GLAZING, CLEAR FINISH.GAP 12" ABV. FIN. STONE 2" THK. ONE PIECE SANDSTONESLAB. PROVIDE SANDSTONESEALER TO ALL EXPOSED FACES/EDGES OF STONE DECORATIVE LINEAR STAINLESSSTEEL FIRE-PIT TROUGH & BURNERRE: MANUF. SPECIFICATIONS 3'-8" 8 1/2"1'-10"1'-1 1/2" 5'-0 " 5" 5" 4'-2 " 7'-4 " SE A T I N G / B E N C H T O A L L O W F O R C H A S E 5'-5 1 / 4 " 3'-8 3/4"5'-11" (TYP.) 3'-0 " ( T Y P . ) 3'-0"8 3/4" WOOD SLAT BENCH, TOP ANDFRONT FACE, TO MATCH ADJ. PARAPET WALL SIDING, SIZE,FINISH AND COLOR. SAND & SEAL 2" SQ. SLAT WOOD SEAT. SANDSMOOTH AND SEAL. PROVIDE (QTY 8) 14" THK. RUBBER FEET TOUNDERSIDE FOR CUSHIONING 12" THK. CORTEN SHEETSTEEL PLANTER BED, TYP. 12" APPROX. GAP BETWEENPLANTER BEDS, TYP.1/2" 8 1/2"2'-1" NOTES: 1.LINEAR FIRE-PIT 36" AUTO IGNITION STAINLESS STEEL LINEAR TROUGH AND BURNER BY "HEARTH PRODUCTS CONTROLS CO"WITH TUMBLED SMOOTH LAVA ROCK.5 MINS. TO 1 HR AUTOMATIC TIMER (SPEC. AS APPROVED BY OWNER)2.6"H x 12" THK GLASS SCREEN:HIGH TEMPERATURE, TEMPERED GLAZING, HEAT SHIELD,CLEAR FIN. (COLOR AS APPROVED BY OWNER)3.GLASS SUPPORT POSTS:1.75"SQ BRUSHED STAINLESS STEEL TUBE LEGS. & GLAZING CLIPS. 4.SANDSTONE FINISH:LIGHT TAN COLOR,SEAL ALL EXPOSED FACES/EDGES,(COLOR AS APPROVED BY OWNER) 5.12" CORTEN STEEL FINISH: RUST FINISH, BURNT RED/ORANGE(COLOR AS APPROVED BY OWNER)6.SLAT BENCH FINISH:HARDWOOD, COLOR TO MATCH ADJACENT PARAPET SIDING & SIZE.(COLOR AS APPROVED BY OWNER)7.BENCH SEAT FINISH:TROPICAL HARDWOOD(COLOR AS APPROVED BY OWNER) 1/2" GAP TYP. 5A6.14 2 A6.14 3A6.14 2A6.14 ENCH AND PLANTER ELEVATION = 1'-0" 38" GAP 2" SQ. SLAT WOOD SEAT. WOOD SLAT BENCH, TO MATCHADJ. PARAPET WALL SIDING, SIZE,FINISH AND COLOR. 12" THK. CORTEN SHEETSTEEL,TYP. 2 3'- 0 " 1'-2 " 4" P PARAPET WALL WOOD SIDING METAL CAP FLASHING OD SIDING FULLY WELDED CORNER EDGE OF CORTEN STEELAT PARAPET WALL SLOPE TO DRAIN 1/4" PER FT. MIN. SCALE: TYPICAL PLANTER SECTION 1" = 1'-0" 5 A6.14 2" RIGID INSULATION, ADHEREDTO CORTEN STEEL 12" THK. CORTEN SHEET STEELPLANTER BED RE: LANDSCAPE PLANS FORSPECIFIC PLANTINGS/FILL, TYP. LIQUID RUBBER,WATERPROOFSEALANT OVER 1/2:" EXT. GRADE PLY, ADHERED TO INSUL. 5" OF MED. GRANULAR FILL GEOTEXTILE FABRIC ON 2" DRAINAGE CELL WALL MAT 12" x 4" SQ. WELDED CORTEN STL.PLATE. AT CNR'S AND 12" O.C.AROUND INT. PERIM. OF PLANTER. 3'-0 " 2'-8 " RAISED CONC. PAVER DECKING 2'-0 " M A X . P E R S T U C T . 1" THK. EXT. GRADE PLY 2" DIA. SCHEDULE 40 DRAIN PIPE ADJUSTABLE PEDESTALS AT 24" O.C.TO MATCH PAVER PEDESTALS. (2) 2x6 CONT. EXT. GRADE WOOD BLOCKING, TYP. 3'-0" SCALE: TYPICAL BENCH SECTION 1" = 1'-0" 4 A6.14 VENT PIPE ROUTING BELOW BENCH TOTERMINATION WALL VENT. INSTALL PER MFR REQ'S. AND SPECIFICATIONS OOTH 14" THK.ER FEET VERTICAL PENETRATIONTHROUGH ROOF DECK. RE: MECH. ENG. PLANSFOR DETAILS 1'- 6 1 / 2 " 1'-2 " ( A F F ) FACE, DING,SEAL C. 2'-9 1/2" 4" 2'-1" 1'-5" PROVIDE BLOCKING INPARAPET WALL, TYP. 4"4" FLUSHE PIT 1'-2 " 4" T.O.DECK 8 1/2" HEIGHTFLAME S. TIMER Revision: Issue: SHEET TITLE PROJECT NO: DWG FILE: 21718_A6-11.dwg MTN FORGE RENOVATION AND ADDITION 230-234 E. HOPKINS AVENUE ASPEN, CO 81611 21718 11.16.2017P+Z FINAL HEARING 1830 blake stdenver, co 80202303.308.1373 500 w main staspen, co 81611970.544.9006 rowland+broughton architecture / urban design / interior design 08.02.2018CONSTRUCTION DOCUMENTS 08.28.201880% PRICING 02.08.2019CD/PRICING SET 04.18.2019CONSTRUCTION DOCUMENTS 03.08.2019ASI-001 ROOF TOP FIREPIT & PLANTERS I have not received installation instructions for the gas fire pit detailing requiredclearances. Provideinstructions and reviseplans to clearly showcompliance withmanufacturer'srequirements forclearances. 5 A6 STAIR #1010 STAIR #1104 STAIR #1212 ROOFDECK301 10R @ 6 - 1 1 / 1 6 " = 5 ' - 6 1 1 / 1 6 " 7'-4" CLR 7'-4" CLR. 7'-4" CLR. 10 R @ 6 - 1 1 / 1 6 " = 5 ' - 6 1 1 / 1 6 " 7'-4" CLR. 8'-0 1 / 4 " 10R @ 6 - 1 3 / 1 6 " = 5 ' - 8 " 3'-6 " 3'-6 " 3'-6 " 3'-0 "3'-6 " HANDRAILEXTENSION HANDRAILBEYOND R3A7.03 F1A7.02 W-15A7.02 W-15A7.02 W-14A7.02 STAI 30 CORR. 2216 HALL105 COMM. 3CORRIDOR017 F2A7.02 F2A7.02 8A7.05 AT DOOR DOOR HEADBEYOND DOOR HEADBEYOND SCALE: SECTION THROUGH EXIT ENCLOSURE 1/2" = 1'-0" 3 A6.22 W17FA7.02 765 STAIR #1104 EXIT ENCLOSURE EXTERIOR EXIT ENCLOSURE EXIT DISCHARGE W8FA7.01 F6A7.02F2A7.02 MECH. 2011 COMM. 3CORRIDOR017 R5A7.03F6A7.02 F2A7.02 F6A7.02 W10A7.01SIM. 1-HOUR HORIZONTALFLOOR/CEILING ASSEMBLY 1-HOUR FIRE BARRIER FIRE BARRIERSUPPORTED ONSEPARATE BEAM - RE: STRUCTURAL 1-HOUR HORIZONTALFLOOR/CEILING ASSEMBLY 1-HOUR FIRE BARRIER FLOOR FRAMING SUPPORTED ON CMU /CAST IN PLACE CONCRETE FIREBARRIERS EACH SIDE - RE: STRUCTURAL LINE OF T.O. CMU WALLBEYOND - RE: STRUCTURAL LINE OF CONCRETEELEVATOR SHAFTBEYOND - RE: STRUCTURAL LINE OF CONCRETE ELEVATOR SHAFTBEYOND - RE:STRUCTURAL BLOCKING BETWEENBEAMS F6A7.02 JANITORCLOSET 213 UTILITY 215 W8FA7.01 W10A7.01SIM. PR O P E R T Y L I N E PR O P E R T Y L I N E (BE Y O N D MICROPILE WALL - RE:SHORING DESIGNER F10A7.03 5A7.10SIM.1-HOUR HORIZONTALFLOOR/CEILING ASSEMBLY1-HOUR HORIZONTALFLOOR/CEILING ASSEMBLY 1-HOUR RATED WALL DROPPED CEILING DOOR BEYOND T.O. PLYLEVEL ONE (E)100'-0" T.O. PLYLEVEL TWO (E)111'-1 3/8" T.O. CONC.BASEMENT88'-10 5/8" DOOR HEAD BEYOND DROPPED SOFFIT - RE:ELEVATIONS FOR ALIGNMENT EXTERIOR F4A7.02 EXISTING PORTION OFBUILDING (BEYOND) -EXISTING SETBACK ENCROACHMENT 2A6.22 3A6.22 NOTE: FLOOR JOISTS BEYONDARE FRAMED INTO LVL BEAMWHICH IS POSTED DOWN TO CMU WALL BELOW - RE:STRUCTURAL STAIR #1104 EXIT ENCLOSURE MECH. 2011 JANITORCLOSET213 F6A7.02 F6A7.02 SCALE: SECTION THROUGH EXIT ENCLOSURE 1/2" = 1'-0" 2 A6.22 W15 SIM.A7.02W18 SIM.A7.02 1-HOUR FIRE BARRIER 1-HOUR FIRE BARRIER 1-HOUR HORIZONTALFLOOR/CEILINGASSEMBLY 1-HOUR HORIZONTALFLOOR/CEILING ASSEMBLY F4A7.02 RE: STRUCTURAL FOR FOOTING DETAILS FULLY GROUTED CMU WALL -RE: STRUCTURAL CAST IN PLACE CONCRETEWALLS - RE: STRUCTURAL 12A7.05 SIM. 3A7.05SIM. File P a t h : P : \ P r o j - 2 0 1 7 \ 2 1 7 1 8 . 0 0 _ M t n F o r g e \ 0 6 _ D o c u m e n t a t i o n \ 0 1 _ D r a w i n g s \ 2 1 7 1 8 _ A 6 - 2 1 . d w g Plot D a t e / T i m e : A p r i l 1 8 , 2 0 1 9 - 1 0 : 4 7 a m The hall extension tothe exit enclosure mustbe built as an exit passageway. Thisrequires 1 hour firebarriers. Fire barriers must be continuous tothe underside of floorsheathing above with no structuralinterruption.Thoroughly detail inarchitecturals andstructurals to showcompliance. 2015 IBC707.5 R D D B D B W17FA7.02 765 STAIR #1 104 EXIT ENCLOSURE EXTERIOR EXIT ENCLOSURE EXIT DISCHARGE W8F A7.01 F6A7.02F2A7.02 MECH. 2 011 COMM. 3CORRIDOR 017 R5A7.03F6A7.02 F2A7.02 F6A7.02 W10 A7.01SIM. 1-HOUR HORIZONTAL FLOOR/CEILING ASSEMBLY 1-HOUR FIRE BARRIER FIRE BARRIERSUPPORTED ONSEPARATE BEAM - RE:STRUCTURAL 1-HOUR HORIZONTALFLOOR/CEILING ASSEMBLY 1-HOUR FIRE BARRIER FLOOR FRAMING SUPPORTED ON CMU /CAST IN PLACE CONCRETE FIREBARRIERS EACH SIDE - RE: STRUCTURAL LINE OF T.O. CMU WALLBEYOND - RE: STRUCTURAL LINE OF CONCRETEELEVATOR SHAFTBEYOND - RE:STRUCTURAL LINE OF CONCRETE ELEVATOR SHAFT BEYOND - RE:STRUCTURAL BLOCKING BETWEEN BEAMS F6A7.02 JANITORCLOSET 213 UTILITY 215 W8F A7.01 W10A7.01SIM. PRO P E R T Y L I N E PRO P E R T Y L I N E (BE Y O N D MICROPILE WALL - RE:SHORING DESIGNER F10A7.03 5A7.10SIM.1-HOUR HORIZONTAL FLOOR/CEILING ASSEMBLY 1-HOUR HORIZONTAL FLOOR/CEILING ASSEMBLY 1-HOUR RATED WALL DROPPED CEILING DOOR BEYOND T.O. PLYLEVEL ONE (E)100'-0" T.O. PLYLEVEL TWO (E)111'-1 3/8" DOOR HEAD BEYOND DROPPED SOFFIT - RE:ELEVATIONS FOR ALIGNMENT EXTERIOR EXISTING PORTION OF BUILDING (BEYOND) - EXISTING SETBACKENCROACHMENT 2A6.22 3A6.22 NOTE: FLOOR JOISTS BEYOND ARE FRAMED INTO LVL BEAM WHICH IS POSTED DOWN TO CMU WALL BELOW - RE: STRUCTURAL STAIR #1 104 EXIT ENCLOSURE MECH. 2 011 JANITORCLOSET 213 F6A7.02 F6A7.02 W15 SIM.A7.02W18 SIM.A7.02 1-HOUR FIRE BARRIER 1-HOUR FIRE BARRIER 1-HOUR HORIZONTALFLOOR/CEILINGASSEMBLY 1-HOUR HORIZONTALFLOOR/CEILING ASSEMBLY RE: STRUCTURAL FOR FULLY GROUTED CMU WALL -RE: STRUCTURAL CAST IN PLACE CONCRETEWALLS - RE: STRUCTURAL 12A7.05 SIM. 3A7.05SIM. wg Ceilings droppedbelow rated assemblies must beframed withnon-combustible or fire resistant treatedmaterials. 2015 IBC803.4 STAIR #1 010 STAIR # 104 212 10R @ 6 - 1 1 / 1 6 " = 5 ' - 6 1 1 / 1 6 " 7'-4" CLR 10R @ 6 - 1 1 / 1 6 " = 5 ' - 6 1 1 / 1 6 " 7'-4" CLR 10R @ 6 - 1 3 / 1 6 " = 5 ' - 8 " 3'-6 " 3'-6 " 3'-6 " F1A7.02 W-15A7.02 216 HALL 105 COMM. 3CORRIDOR017 F2A7.02 F2A7.02 SCALE: SECTION THROUGH EXIT ENCLOSURE 1/2" = 1'-0" 3 A6.22 W17FA7.02 765 STAIR #1104 EXIT ENCLOSURE EXTERIOR EXIT ENCLOSURE EXIT DISCHARGE W8F A7.01 F6A7.02F2A7.02 MECH. 2011 COMM. 3CORRIDOR017 R5A7.03F6A7.02 F2A7.02 F6A7.02 W10 A7.01SIM. 1-HOUR HORIZONTALFLOOR/CEILING ASSEMBLY 1-HOUR FIRE BARRIER FIRE BARRIERSUPPORTED ONSEPARATE BEAM - RE:STRUCTURAL 1-HOUR HORIZONTALFLOOR/CEILING ASSEMBLY 1-HOUR FIRE BARRIER FLOOR FRAMING SUPPORTED ON CMU /CAST IN PLACE CONCRETE FIREBARRIERS EACH SIDE - RE: STRUCTURAL LINE OF T.O. CMU WALLBEYOND - RE: STRUCTURAL LINE OF CONCRETEELEVATOR SHAFTBEYOND - RE:STRUCTURAL LINE OF CONCRETEELEVATOR SHAFT BEYOND - RE:STRUCTURAL BLOCKING BETWEENBEAMS F6A7.02 JANITORCLOSET 213 UTILITY 215 W8FA7.01 W10 A7.01SIM. PR O P E R T Y L I N E PR O P E R T Y L I N E (BE Y O N D MICROPILE WALL - RE:SHORING DESIGNER F10A7.03 5A7.10SIM.1-HOUR HORIZONTALFLOOR/CEILING ASSEMBLY1-HOUR HORIZONTALFLOOR/CEILING ASSEMBLY 1-HOUR RATED WALL DROPPED CEILING DOOR BEYOND T.O. PLYLEVEL ONE (E)100'-0" T.O. PLYLEVEL TWO (E)111'-1 3/8" T.O. CONC.BASEMENT88'-10 5/8" DOOR HEAD BEYOND DROPPED SOFFIT - RE:ELEVATIONS FOR ALIGNMENT EXTERIOR F4A7.02 EXISTING PORTION OFBUILDING (BEYOND) -EXISTING SETBACKENCROACHMENT 2A6.22 3A6.22 NOTE: FLOOR JOISTS BEYONDARE FRAMED INTO LVL BEAM WHICH IS POSTED DOWN TOCMU WALL BELOW - RE:STRUCTURAL STAIR #1104 EXIT ENCLOSURE MECH. 2011 JANITORCLOSET213 F6A7.02 F6A7.02 SCALE: SECTION THROUGH EXIT ENCLOSURE 1/2" = 1'-0" 2 A6.22 W15 SIM.A7.02W18 SIM.A7.02 1-HOUR FIRE BARRIER 1-HOUR FIRE BARRIER 1-HOUR HORIZONTALFLOOR/CEILINGASSEMBLY 1-HOUR HORIZONTALFLOOR/CEILING ASSEMBLY F4A7.02 RE: STRUCTURAL FORFOOTING DETAILS FULLY GROUTED CMU WALL -RE: STRUCTURAL CAST IN PLACE CONCRETEWALLS - RE: STRUCTURAL 12A7.05SIM. 3A7.05SIM. File P a t h : P : \ P r o j - 2 0 1 7 \ 2 1 7 1 8 . 0 0 _ M t n F o r g e \ 0 6 _ D o c u m e n t a t i o n \ 0 1 _ D r a w i n g s \ 2 1 7 1 8 _ A 6 - 2 1 . d w g Plot D a t e / T i m e : A p r i l 1 8 , 2 0 1 9 - 1 0 : 4 7 a m Clearly identify allstructure that supportsthe fire barriers andprotect with 1 hour firerating. Columns mustbe individuallyencapsulated with 1 hour fire rating. Beamsthat support more thana floor and a roof ormore than two floors must also beindividuallyencapsulated with 1hour rating. 2015 IBC 704. SCALE: SECTION AT MECHANICAL SHAFT 1/2" = 1'-0" 5 A6.26 T.O. PLYLEVEL ONE (E)100'-0" T.O. PLYLEVEL TWO (E)111'-1 3/8" T.O. CONC.BASEMENT88'-10 5/8" T.O. PLYROOF (E)121'-3 3/8" MECH. 1CHASE / EQUIP. RM.008 COMM.UNIT 1 100 MECH. 3218 SCALE: LEVEL TWO ENLARGED PLAN - MECHANICAL SHAFT 1/2" = 1'-0" 1 A6.26 SCALE: LEVEL ONE ENLARGED PLAN - MECHANICAL SHAFT 1/2" = 1'-0" 3 A6.26 R4FA7.03R3FA7.03 R7A7.03 ROOFDECK301 T.O. PARAPET126'-7" T.O. PLYLEVEL ONE ADU99'-6" AHU 102 COMM.UNIT 7009 W10A7.01 W10A7.01 F2A7.02 F2A7.02 F6A7.02 F6A7.02 F4A7.02F1A7.02 GUESTSUITE219W9A7.01 FD SCALE: BASEMENT ENLARGED PLAN - MECHANICAL SHAFT 1/2" = 1'-0" 4 A6.26 W16A7.02 SHAFTENCLOSURE NOTE: DUCTSRUNNING UP INTOSHAFT ENCLOSURESHALL BEPROTECTED BY FIREDAMPERS AT THISLEVEL PER IBC713.11.3. PROVIDEDRAFTSTOPPING ATSHAFT OPENING SHAFTENCLOSURE OVERFRAMED CURBABOVE SHAFT SLOPE1/2":12" FLUE & COMBUSTION AIR &VENT PIPE TERMINATIONSABOVE - RE: MEP DUCTS PENETRATINGTHE SHAFTENCLOSURE SHALLBE PROTECTED BYDAMPERS ASREQUIRED BY CODE -RE: MECHANICALDOCUMENTATION SCALE: ROOF - ENLARGED PLAN - MECHANICAL SHAFT 1/2" = 1'-0" 2 A6.26 F F 5A6.26 5A6.26 5A6.26 5A6.26 3 3 4 3 4 3 OBSCURE GLASS VISION SHIELDPARAPETMECH. 3218 GUESTSUITE219 COMM.UNIT 1 100 AHU 102 MECH. 1CHASE / EQUIP. RM.008 COMM.UNIT 7009 W10A7.01 W10A7.01 W10A7.01 W16A7.02 W10A7.01 W10A7.01SIM. W9A7.01 W9A7.01 W9A7.01 W9A7.01 W9A7.01 W9A7.01 FURRING WALL INFRONT OF RATEDASSEMBLY FURRING WALL INFRONT OF RATEDASSEMBLY 1-HOUR HORIZONTALFLOOR/CEILINGASSEMBLY 1-HOUR FIRE BARRIER 1-HOUR FIRE BARRIER 1-HOURHORIZONTALFLOOR/CEILINGASSEMBLY 1-HOUR HORIZONTALFLOOR/CEILINGASSEMBLY 1-HOUR HORIZONTALROOF/CEILINGASSEMBLY 1-HOUR HORIZONTALROOF/CEILINGASSEMBLY F1A7.02F4A7.02 W16A7.02 F6A7.02SIM.F2A7.02 W6A7.01 W10A7.01 MECH. 1CHASE / EQUIP. RM.008 SCALE: SECTION AT MECHANICAL SHAFT 1/2" = 1'-0" 6 A6.26 COMM.UNIT 1 100 SHAFTENCLOSURE DUCTS PENETRATINGTHE SHAFTENCLOSURE SHALLBE PROTECTED BYDAMPERS ASREQUIRED BY CODE -RE: MECHANICALDOCUMENTATION CORRIDOR017 W10A7.01 W10A7.01 1-HOURHORIZONTALFLOOR/CEILINGASSEMBLY 1-HOUR FIREBARRIER1-HOUR FIREBARRIER 1-HOUR FIREBARRIER 1-HOUR FIREBARRIER 1-HOURHORIZONTALFLOOR/CEILINGASSEMBLY 1-HOUR FIREBARRIER F2A7.02 GUESTSUITE212CORRIDOR 2216 W10A7.01 6A6.26 6A6.26 SHAFTENCLOSURE R3FA7.03R3FA7.03 R7A7.03 1-HOUR HORIZONTALROOF/CEILINGASSEMBLY 1-HOUR FIREBARRIER F2A7.02 NOTE: DUCTSRUNNING UP INTOSHAFT ENCLOSURESHALL BEPROTECTED BY FIREDAMPERS AT THISLEVEL PER IBC713.11.3. PROVIDEDRAFTSTOPPING ATSHAFT OPENINGREFER TO MEP FOREQUIPMENT LAYOUT COMM. UNITELECTRICAL PANEL SETIN FURRING WALL - RE:ELECTRICAL - DO NOTPENETRATE SHAFTASSEMBLY 1-HOUR FIRE BARRIERASSEMBLY W10A7.01 SURFACE MOUNT SURFACE MOUNT COPYRIGHT 2019 ROWLAND+BROUGHTON ARCHITECTURE AND URBAN DESIGNTHE INFORMATION AND DESIGN INTENT CONTAINED ON THIS DOCUMENT ISTHE PROPERTY OF ROWLAND+BROUGHTON ARCHITECTURE AND URBANDESIGN. NO PART OF THIS INFORMATION MAY BE USED WITHOUT THE PRIORWRITTEN PERMISSION OF ROWLAND+BROUGHTON ARCHITECTURE AND URBANDESIGN. ROWLAND+BROUGHTON ARCHITECTURE AND URBAN DESIGN SHALLRETAIN ALL COMMON LAW STATUTORY AND OTHER RESERVED RIGHTS,INCLUDING COPYRIGHT THERETO. Revision: Issue: SHEET TITLE PROJECT NO: DWG FILE: SCALE: 21718_A6-21.dwg MTN FORGE RENOVATION AND ADDITION 230-234 E. HOPKINS AVENUE ASPEN, CO 81611 21718 11.16.2017P+Z FINAL HEARING 1830 blake stdenver, co 80202303.308.1373 500 w main staspen, co 81611970.544.9006 architecture / urban design / interior design 08.02.2018CONSTRUCTION DOCUMENTS 08.28.201880% PRICING 02.08.2019CD/PRICING SET 04.18.2019CONSTRUCTION DOCUMENTS 03.08.2019ASI-001 A6.26 1/2" = 1'-0" MECH. SHAFT DRAWINGS Clearly identify allstructure that supportsthe fire barriers andprotect with 1 hour firerating. Columns mustbe individuallyencapsulated with 1hour fire rating. Beamsthat support more thana floor and a roof ormore than two floorsmust also beindividuallyencapsulated with 1hour rating. 2015 IBC704. Page: A6.26 MECH. SHAFT DRAWINGS File Name: 230 E. Hopkins_Drawings_Architecture_2019-04-18.pdf Subject: PlanCheck Author: nickt Color: With the shaft unenclosed at the bottom, the mechanical room must essentially become part of the shaft using 1 hour fire barriers. Fire barriers must be continuous to the underside of the floor sheathing above. 2015 IBC 707.5 Page: A6.26 MECH. SHAFT DRAWINGS File Name: 230 E. Hopkins_Drawings_Architecture_2019-04-18.pdf Subject: PlanCheck Author: nickt Color: The mechanical shaft must be built as a fire barrier. The walls may not be interrupted by any structure other than floor or roof sheathing. Walls must be continuous to the underside of the floor/roof sheathing. 2015 IBC 707.5 Page: A7.03 BUILDING ASSEMBLIES File Name: 230 E. Hopkins_Drawings_Architecture_2019-04-18.pdf Subject: PlanCheck Author: nickt Color: Any assembly that claims a fire or sound rating must reference a listed assembly that you include in the plans. Revise to treat similarly to how you have done the wall assemblies. Page: A8.2 DOOR SCHEDULE File Name: 230 E. Hopkins_Drawings_Architecture_2019-04-18.pdf Subject: PlanCheck Author: nickt Color: Doors 1/010, 3/104, and 1/217 are shown to have hardware group D which refers to an interior pocket lockset. These are swinging doors which serve an exit stair enclosure. Locking prohibited unless you can demonstrate compliance with one of the exceptions of 2015 IBC 1010.1.9.11. Page: A8.2 DOOR SCHEDULE File Name: 230 E. Hopkins_Drawings_Architecture_2019-04-18.pdf Subject: Group Author: nickt Color: Door 1/213 serves an employee work area per your response and therefore must provide 32" clear measured from the face of the door leaf opened at 90 degrees to the face of the doorstop. A 2'-10" (34") door will typically only provide 31 3/4" of clearance. Revise door schedule to demonstrate compliance. (2015 IBC 1010.1.1) SCALE:SECTION AT MECHANICAL SHAFT1/2" = 1'-0"5A6.26 F T.O. PLYLEVEL ONE (E)100'-0" T.O. PLYLEVEL TWO (E)111'-1 3/8" T.O. CONC.BASEMENT88'-10 5/8" T.O. PLYROOF (E)121'-3 3/8" MECH. 1CHASE / EQUIP. RM.008 COMM.UNIT 1100 MECH. 3218 SCALE:LEVEL TWO ENLARGED PLAN - MECHANICAL SHAFT1/2" = 1'-0" 1A6.26 SCALE:LEVEL ONE ENLARGED PLAN - MECHANICAL SHAFT1/2" = 1'-0" 3A6.26 R4FA7.03R3FA7.03 R7A7.03 ROOFDECK301 T.O. PARAPET126'-7" T.O. PLYLEVEL ONE ADU99'-6" AHU102 COMM.UNIT 7009 W10A7.01 W10A7.01 F2A7.02 F2A7.02 F6A7.02 F6A7.02 F4A7.02F1A7.02 GUESTSUITE219W9A7.01 FD SCALE:BASEMENT ENLARGED PLAN - MECHANICAL SHAFT1/2" = 1'-0" 4A6.26 W16A7.02 SHAFTENCLOSURE NOTE: DUCTSRUNNING UP INTOSHAFT ENCLOSURESHALL BEPROTECTED BY FIREDAMPERS AT THISLEVEL PER IBC713.11.3. PROVIDEDRAFTSTOPPING ATSHAFT OPENING SHAFTENCLOSURE OVERFRAMED CURBABOVE SHAFT SLOPE1/2":12" FLUE & COMBUSTION AIR &VENT PIPE TERMINATIONSABOVE - RE: MEP DUCTS PENETRATINGTHE SHAFTENCLOSURE SHALLBE PROTECTED BYDAMPERS ASREQUIRED BY CODE -RE: MECHANICALDOCUMENTATION SCALE:ROOF - ENLARGED PLAN - MECHANICAL SHAFT1/2" = 1'-0" 2A6.26 F F F 5A6.26 5A6.26 5A6.26 5A6.26 4 3 4 3 4 3 4 3 OBSCURE GLASS VISION SHIELDPARAPETMECH. 3218 GUESTSUITE219 COMM.UNIT 1100 AHU102 MECH. 1CHASE / EQUIP. RM.008 COMM.UNIT 7009 WHy W10A7.01 W10A7.01 W10A7.01 W16A7.02 W10A7.01 W10A7.01SIM. W9A7.01 W9A7.01 W9A7.01 W9A7.01 W9A7.01 W9A7.01 FURRING WALL INFRONT OF RATEDASSEMBLY FURRING WALL INFRONT OF RATEDASSEMBLY 1-HOUR HORIZONTALFLOOR/CEILINGASSEMBLY 1-HOUR FIRE BARRIER 1-HOUR FIRE BARRIER 1-HOURHORIZONTALFLOOR/CEILINGASSEMBLY 1-HOUR HORIZONTALFLOOR/CEILINGASSEMBLY 1-HOUR HORIZONTALROOF/CEILINGASSEMBLY 1-HOUR HORIZONTALROOF/CEILINGASSEMBLY 4 3 7A7.12SIM F1A7.02F4A7.02 W16A7.02 F6A7.02SIM.F2A7.02 W6A7.01 W10A7.01 MECH. 1CHASE / EQUIP. RM.008 SCALE:SECTION AT MECHANICAL SHAFT1/2" = 1'-0" 6A6.26 COMM.UNIT 1100 SHAFTENCLOSURE DUCTS PENETRATINGTHE SHAFTENCLOSURE SHALLBE PROTECTED BYDAMPERS ASREQUIRED BY CODE -RE: MECHANICALDOCUMENTATION CORRIDOR017 W10A7.01 W10A7.01 1-HOURHORIZONTALFLOOR/CEILINGASSEMBLY 1-HOUR FIREBARRIER1-HOUR FIREBARRIER 1-HOUR FIREBARRIER 1-HOUR FIREBARRIER 1-HOURHORIZONTALFLOOR/CEILINGASSEMBLY 1-HOUR FIREBARRIER F2A7.02 GUESTSUITE212CORRIDOR 2216 W10A7.01 6A6.266A6.26 6A6.26 6A6.26 SHAFTENCLOSURE R3FA7.03R3FA7.03 R7A7.03 1-HOUR HORIZONTALROOF/CEILINGASSEMBLY 1-HOUR FIREBARRIER F2A7.02 6A6.265A6.26 NOTE: DUCTSRUNNING UP INTOSHAFT ENCLOSURESHALL BEPROTECTED BY FIREDAMPERS AT THISLEVEL PER IBC713.11.3. PROVIDEDRAFTSTOPPING ATSHAFT OPENINGREFER TO MEP FOREQUIPMENT LAYOUT COMM. UNITELECTRICAL PANEL SETIN FURRING WALL - RE:ELECTRICAL - DO NOTPENETRATE SHAFTASSEMBLY 1-HOUR FIRE BARRIERASSEMBLY W10A7.01 SURFACE MOUNT SURFACE MOUNT File Pat h : P : \ P r o j - 2 0 1 7 \ 2 1 7 1 8 . 0 0 _ M t n F o r g e \ 0 6 _ D o c u m e n t a t i o n \ 0 1 _ D r a w i n g s \ 2 1 7 1 8 _ A 6 - 2 1 . d w g Plot Date/ T i m e : A p r i l 1 8 , 2 0 1 9 - 1 0 : 4 4 a m COPYRIGHT 2019 ROWLAND+BROUGHTON ARCHITECTURE AND URBAN DESIGNTHE INFORMATION AND DESIGN INTENT CONTAINED ON THIS DOCUMENT ISTHE PROPERTY OF ROWLAND+BROUGHTON ARCHITECTURE AND URBANDESIGN. NO PART OF THIS INFORMATION MAY BE USED WITHOUT THE PRIORWRITTEN PERMISSION OF ROWLAND+BROUGHTON ARCHITECTURE AND URBANDESIGN. ROWLAND+BROUGHTON ARCHITECTURE AND URBAN DESIGN SHALLRETAIN ALL COMMON LAW STATUTORY AND OTHER RESERVED RIGHTS,INCLUDING COPYRIGHT THERETO. Revision: Issue: SHEET TITLE PROJECT NO: DWG FILE: SCALE: 21718_A6-21.dwg MTN FORGERENOVATION AND ADDITION 230-234 E. HOPKINS AVENUEASPEN, CO 81611 21718 11.16.2017P+Z FINAL HEARING 1830 blake stdenver, co 80202303.308.1373 500 w main staspen, co 81611970.544.9006 rowland+broughtonarchitecture / urban design / interior design 08.02.2018CONSTRUCTION DOCUMENTS 08.28.201880% PRICING02.08.2019CD/PRICING SET 04.18.2019CONSTRUCTION DOCUMENTS 03.08.2019ASI-001 A6.26 1/2" = 1'-0" MECH. SHAFTDRAWINGS With the shaftunenclosed at thebottom, themechanical room mustessentially becomepart of the shaft using1 hour fire barriers.Fire barriers must becontinuous to theunderside of the floorsheathing above. 2015IBC 707.5 SCALE: SECTION AT MECHANICAL SHAFT 1/2" = 1'-0" 5 A6.26 F T.O. PLYLEVEL ONE (E)100'-0" T.O. PLYLEVEL TWO (E)111'-1 3/8" T.O. CONC.BASEMENT88'-10 5/8" T.O. PLYROOF (E)121'-3 3/8" MECH. 1CHASE / EQUIP. RM.008 COMM.UNIT 1100 MECH. 3218 SCALE:LEVEL TWO ENLARGED PLAN - MECHANICAL SHAFT1/2" = 1'-0" 1A6.26 SCALE:LEVEL ONE ENLARGED PLAN - MECHANICAL SHAFT1/2" = 1'-0" 3A6.26 R4FA7.03R3FA7.03 R7A7.03 ROOFDECK301 T.O. PARAPET126'-7" T.O. PLYLEVEL ONE ADU99'-6" AHU102 COMM.UNIT 7009 W10A7.01 W10A7.01 F2A7.02 F2A7.02 F6A7.02 F6A7.02 F4A7.02F1A7.02 GUESTSUITE219W9A7.01 FD SCALE: BASEMENT ENLARGED PLAN - MECHANICAL SHAFT 1/2" = 1'-0" 4 A6.26 W16A7.02 SHAFTENCLOSURE NOTE: DUCTSRUNNING UP INTOSHAFT ENCLOSURESHALL BEPROTECTED BY FIREDAMPERS AT THISLEVEL PER IBC713.11.3. PROVIDEDRAFTSTOPPING ATSHAFT OPENING SHAFTENCLOSURE OVERFRAMED CURBABOVE SHAFT SLOPE1/2":12" FLUE & COMBUSTION AIR &VENT PIPE TERMINATIONSABOVE - RE: MEP DUCTS PENETRATINGTHE SHAFTENCLOSURE SHALLBE PROTECTED BYDAMPERS ASREQUIRED BY CODE -RE: MECHANICALDOCUMENTATION SCALE:ROOF - ENLARGED PLAN - MECHANICAL SHAFT1/2" = 1'-0" 2A6.26 F F F 5A6.26 5A6.26 5A6.26 5A6.26 4 3 4 3 4 3 4 3 OBSCURE GLASS VISION SHIELDPARAPETMECH. 3218 GUESTSUITE219 COMM.UNIT 1100 AHU102 MECH. 1CHASE / EQUIP. RM.008 COMM.UNIT 7009 WHy W10A7.01 W10A7.01 W10A7.01 W16A7.02 W10A7.01 W10A7.01SIM. W9A7.01 W9A7.01 W9A7.01 W9A7.01 W9A7.01 W9A7.01 FURRING WALL INFRONT OF RATEDASSEMBLY FURRING WALL INFRONT OF RATEDASSEMBLY 1-HOUR HORIZONTALFLOOR/CEILINGASSEMBLY 1-HOUR FIRE BARRIER 1-HOUR FIRE BARRIER 1-HOURHORIZONTALFLOOR/CEILINGASSEMBLY 1-HOUR HORIZONTALFLOOR/CEILINGASSEMBLY 1-HOUR HORIZONTALROOF/CEILINGASSEMBLY 1-HOUR HORIZONTALROOF/CEILINGASSEMBLY 4 3 7A7.12SIM F1A7.02F4A7.02 W16A7.02 F6A7.02SIM.F2A7.02 W6A7.01 W10A7.01 MECH. 1CHASE / EQUIP. RM.008 SCALE: SECTION AT MECHANICAL SHAFT 1/2" = 1'-0" 6 A6.26 COMM.UNIT 1100 SHAFTENCLOSURE DUCTS PENETRATINGTHE SHAFTENCLOSURE SHALLBE PROTECTED BYDAMPERS ASREQUIRED BY CODE -RE: MECHANICALDOCUMENTATION CORRIDOR017 W10A7.01 W10A7.01 1-HOURHORIZONTALFLOOR/CEILINGASSEMBLY 1-HOUR FIREBARRIER1-HOUR FIREBARRIER 1-HOUR FIREBARRIER 1-HOUR FIREBARRIER 1-HOURHORIZONTALFLOOR/CEILINGASSEMBLY 1-HOUR FIREBARRIER F2A7.02 GUESTSUITE212CORRIDOR 2216 W10A7.01 6A6.266A6.26 6A6.26 6A6.26 SHAFTENCLOSURE R3FA7.03R3FA7.03 R7A7.03 1-HOUR HORIZONTALROOF/CEILINGASSEMBLY 1-HOUR FIREBARRIER F2A7.02 6A6.265A6.26 NOTE: DUCTSRUNNING UP INTOSHAFT ENCLOSURESHALL BEPROTECTED BY FIREDAMPERS AT THISLEVEL PER IBC713.11.3. PROVIDEDRAFTSTOPPING ATSHAFT OPENINGREFER TO MEP FOREQUIPMENT LAYOUT COMM. UNITELECTRICAL PANEL SETIN FURRING WALL - RE:ELECTRICAL - DO NOTPENETRATE SHAFTASSEMBLY 1-HOUR FIRE BARRIERASSEMBLY W10A7.01 SURFACE MOUNT SURFACE MOUNT File Path : P : \ P r o j - 2 0 1 7 \ 2 1 7 1 8 . 0 0 _ M t n F o r g e \ 0 6 _ D o c u m e n t a t i o n \ 0 1 _ D r a w i n g s \ 2 1 7 1 8 _ A 6 - 2 1 . d w g Plot Date/T i m e : A p r i l 1 8 , 2 0 1 9 - 1 0 : 4 4 a m COPYRIGHT 2019 ROWLAND+BROUGHTON ARCHITECTURE AND URBAN DESIGNTHE INFORMATION AND DESIGN INTENT CONTAINED ON THIS DOCUMENT ISTHE PROPERTY OF ROWLAND+BROUGHTON ARCHITECTURE AND URBANDESIGN. NO PART OF THIS INFORMATION MAY BE USED WITHOUT THE PRIORWRITTEN PERMISSION OF ROWLAND+BROUGHTON ARCHITECTURE AND URBANDESIGN. ROWLAND+BROUGHTON ARCHITECTURE AND URBAN DESIGN SHALLRETAIN ALL COMMON LAW STATUTORY AND OTHER RESERVED RIGHTS,INCLUDING COPYRIGHT THERETO. Revision: Issue: SHEET TITLE PROJECT NO: DWG FILE: SCALE: 21718_A6-21.dwg MTN FORGERENOVATION AND ADDITION 230-234 E. HOPKINS AVENUEASPEN, CO 81611 21718 11.16.2017P+Z FINAL HEARING 1830 blake stdenver, co 80202303.308.1373500 w main staspen, co 81611970.544.9006 rowland+broughtonarchitecture / urban design / interior design 08.02.2018CONSTRUCTION DOCUMENTS08.28.201880% PRICING02.08.2019CD/PRICING SET 04.18.2019CONSTRUCTION DOCUMENTS 03.08.2019ASI-001 A6.26 1/2" = 1'-0" MECH. SHAFTDRAWINGS The mechanical shaftmust be built as a firebarrier. The walls maynot be interrupted byany structure otherthan floor or roofsheathing. Walls mustbe continuous to theunderside of thefloor/roof sheathing.2015 IBC 707.5 SCALE: ROOF ASSEMBLYSLOPED ROOF WITH STANDING SEAM METAL1 1/2" = 1'-0"R-49 MIN.R1A7.03 FRAMING - RE: STRUCTURAL 5/8" TYPE X GWB SHEATHING - RE:STRUCTURAL INTERIOR EXTERIOR SCALE: ROOF ASSEMBLY (EXISTING ROOFS)LOW-SLOPE ROOF WITH MEMBRANE1 1/2" = 1'-0"R-49 MIN.R2A7.03 EXISTING FRAMING - RE:STRUCTURAL EXISTING PLYWOOD SHEATHING(TO REMAIN, TYP.) INTERIOR EXTERIOR INTERIOR FINISH - RE: SCHEDULE SPRAY APPLIED CLOSED-CELLFOAM INSULATION (R-49 MIN.)- SEAL ALL AIR GAPS IC RATED RECESSED LIGHTHOUSING (WHERE OCCURS) PREFINISHED METALSTANDING SEAMROOFINGCLASS-A ROOFINGUNDERLAYMENT -VERSASHIELD ORAPPROVED EQ.HIGH-TEMPERATURESELF-ADHEREDICE&WATER BARRIER,TYP. FOR ENTIRE ROOF EXIST . T O R E M A I N RE: S T R U C T U R A L TAPERED RIGID INSULATION - 2"MIN. THICKNESS. R-10 MIN. VARIE S - R E : R C P S 1/4" DENS DECK CLASS AROOFING UNDERLAYMENT FULLY ADHERED SINGLE-PLYROOFING MEMBRANE SPRAY APPLIED CLOSED-CELLFOAM INSULATION (R-39 MIN.)- SEAL ALL AIR GAPS 5/8" TYPE X GWBINTERIOR FINISH - RE: SCHEDULE DROPPED CEILING - VARIES - RE:RCPS CEILING FRAMING AS REQUIREDMECH. SPACE SCALE: ROOF ASSEMBLY (EXISTING & NEW ROOFS)LOW-SLOPE ROOF WITH MEMBRANE & PEDESTAL DECK1 1/2" = 1'-0"R-49 MIN.R3(F)A7.03 EXISTING FRAMING - RE:STRUCTURAL EXISTING PLYWOOD SHEATHING(TO REMAIN, TYP.)AT NEW ROOF, RE: STRUCTURALFOR SHEATHING INTERIOR EXTERIOR EXIST . T O R E M A I N RE: S T R U C T U R A L TAPERED RIGID INSULATION - 2"MIN. THICKNESS. R-10 MIN. B.O. EXISTING OR NEW FRAMING- RE: STRUCTURAL VARIE S - R E : R C P S 1/4" DENS DECK CLASS AROOFING UNDERLAYMENT FULLY ADHERED SINGLE-PLYROOFING MEMBRANE SPRAY APPLIED CLOSED-CELLFOAM INSULATION (R-39 MIN.)- SEAL ALL AIR GAPS 5/8" TYPE X GWBINTERIOR FINISH - RE: SCHEDULE DROPPED CEILING - VARIES - RE:RCPS CEILING FRAMING AS REQUIREDMECH. SPACE SCALE: ROOF ASSEMBLY (NEW ROOFS)LOW-SLOPE ROOF WITH MEMBRANE1 1/2" = 1'-0"R-49 MIN.R4(F)A7.03 FRAMING - RE: STRUCTURAL SHEATHING - RE: STRUCTURAL INTERIOR B.O. FRAMING TAPERED RIGID INSULATION - 2"MIN. THICKNESS. R-10 MIN. VARIE S - R E : R C P S 1/4" DENS DECK CLASS AROOFING UNDERLAYMENT FULLY ADHERED SINGLE-PLYROOFING MEMBRANE SPRAY APPLIED CLOSED-CELLFOAM INSULATION (R-39 MIN.)- SEAL ALL AIR GAPS 5/8" TYPE X GWBINTERIOR FINISH - RE: SCHEDULE DROPPED CEILING - VARIES - RE:RCPS CEILING FRAMING AS REQUIREDMECH. SPACE EXTERIOR VARIE S RE: RO O F P L A N ADJUSTABLE PEDESTAL SYSTEMPAVER SLOPE TO DRAIN1/4" PER FT. MIN.SLOPE TO DRAIN1/4" PER FT. MIN.SLOPE TO DRAIN1/4" PER FT. MIN. AT "R4F" : 2-LAYERS 5/8" TYPE "X"GWB APPLIED PER GA-610 FOR1-HOUR RATING. AT "R4" -1-LAYER 1/2" MIN. TYPE X GWB SCALE: ROOF ASSEMBLY (NEW ROOFS)LOW-SLOPE ROOF WITH MEMBRANE & PAVERS1 1/2" = 1'-0"R-49 MIN.R5A7.03 FRAMING - RE: STRUCTURAL SHEATHING - RE: STRUCTURAL B.O. FRAMING TAPERED RIGID INSULATION - 2"MIN. THICKNESS. R-10 MIN. 1/4" DENS DECK CLASS AROOFING UNDERLAYMENT HOT FLUID APPLIEDWATERPROOFING SPRAY APPLIED CLOSED-CELLFOAM INSULATION (R-39 MIN.)- SEAL ALL AIR GAPS EXTERIORSLOPE TO DRAIN1/4" PER FT. MIN. SCALE: FLOOR ASSEMBLY (NEW FLOORS)SNOWMELTED STAIR TREADS AND RISERS1 1/2" = 1'-0"F9A7.03 PORCELAIN PAVER STAIR TREADSAND RISERS SNOWMELT TUBING - RE: MEP REINFORCED CONCRETESUB-STRUCTRE - RE: STRUCTURAL EXTERIOR COMPACTED BASE PER GEOTECH 2" HIGH-DENSITY SUB-SLAB RIGIDINSULATION - R-10 MIN. RE: S T A I R DRAW I N G RE: STAIRDRAWING SCALE: FLOOR ASSEMBLY (NEW FLOORS)SNOWMELTED CONCRETE WALKWAY1 1/2" = 1'-0"F10A7.03 EXTERIOR REINFORCED CONCRETE SLAB - RE:CIVIL & LANDSCAPE 2" HIGH-DENSITY SUB-SLAB RIGIDINSULATION - R-10 MIN. COMPACTED BASE PER GEOTECH RADIANT SNOWMELT TUBING TIED TOREBAR AS REQUIRED - RE: MEP -PROVIDE TUBING COVERAGE PERMANUFACTURERSLOPE PER CIVIL RE: M F R . RE: MEP RE: MEP RE: LANDSCAPE FOR SURFACETEXTURE AND JOINTING, TYP. THERMA-HEXX THERMA-PANELSNOWMELT PANEL HIGH-COMPRESSION DRAINAGEMAT NON-SHRINK THICK-SET MUD BEDRADIANT SNOWMELT TUBING TIED TOSLAB AS REQUIRED - RE: MEP EXTERIOR PAVERS INTERIOR DROPPED CEILING - VARIES - RE:RCPS CEILING FRAMING AS REQUIREDMECH. SPACE 5/8" TYPE X GWBVARIE S - R E : R C P S RAT E D A S S E M B L Y ICC- E S R - 3 2 0 7 AT "SIM." - ADD DECORATIVERIVER ROCK BALLAST R2 "SI M . " O N L Y B.O. EXISTING OR NEW FRAMING- RE: STRUCTURAL NOTE:AT "R4 SIM." OMIT DROPPED CEILING SCALE: ROOF ASSEMBLY (EXISTING ROOFS)LOW-SLOPE ROOF WITH MEMBRANE - MODULAR GREEN ROOF1 1/2" = 1'-0"R-49 MIN.R6A7.03 EXISTING FRAMING - RE:STRUCTURAL EXISTING PLYWOOD SHEATHING(TO REMAIN, TYP.) INTERIOR EXTERIOR EXIST. T O R E M A I N RE: ST R U C T U R A L TAPERED RIGID INSULATION - 2"MIN. THICKNESS. R-10 MIN. VARIE S - R E : R C P S 1/4" DENS DECK CLASS AROOFING UNDERLAYMENT FULLY ADHERED SINGLE-PLYROOFING MEMBRANE SPRAY APPLIED CLOSED-CELLFOAM INSULATION (R-39 MIN.)- SEAL ALL AIR GAPS 5/8" TYPE X GWBINTERIOR FINISH - RE: SCHEDULE DROPPED CEILING - VARIES - RE:RCPS CEILING FRAMING AS REQUIREDMECH. SPACE SLOPE MEMBRANE TO DRAIN1/4" PER FT. MIN. B.O. EXISTING OR NEW FRAMING- RE: STRUCTURAL 1/2" TYPE X GWB THERMAL &IGNIITION BARRIER SLIP-SHEET PER GREEN ROOFMODULE MFR'S SPECS MODULAR GREEN ROOFPANEL SYSTEM -LiveRoof STANDARDSYSTEM OR APPROVEDEQUAL 4 1/4" LiveRoof ENGINEEREDSOIL & PLANTS AT "R3F" : 2-LAYERS 5/8" TYPE "X"GWB APPLIED PER GA-610 FOR1-HOUR RATING. AT "R3" -1-LAYER 1/2" MIN. TYPE X GWB SCALE: ROOF ASSEMBLY (NEW ROOFS)OVERFRAMED ROOF & CURB WITH MEMBRANE1 1/2" = 1'-0"R-49 MIN.R7A7.03 FRAMING - RE: STRUCTURAL SHEATHING - RE: STRUCTURAL SHAFT ENCLOSURE B.O. FRAMING TAPERED RIGID INSULATION - 2"MIN. THICKNESS. R-10 MIN. 1/4" DENS DECK CLASS AROOFING UNDERLAYMENT FULLY ADHERED SINGLE-PLYROOFING MEMBRANE BLOWN OR BATT INSULATION(R-39 MIN.) EXTERIOR SLOPE TO DRAIN1/2" PER FT. MIN. 2-LAYERS 5/8" TYPE "X" GWBAPPLIED PER GA-610 FOR1-HOUR RATING OVERFRAMING AS REQUIRED SHEATHING - RE: STRUCTURAL 1-HOUR FIRE RATED ASS'YICC-ESR-3207STC 60-61IIC 56-57 2-LAYERS 5/8" TYPE C GWBAPPLIED PER LISTED ASSEMBLY 78" 20 GA.DRYWALL FURRINGCHANNEL. 24" MAX. O.C. PERLISTING KINETICS WAVE HANGER @ 48"MAX. OC, INSTALLED PER LISTING 2-LAYERS 5/8" TYPE "X" GWBAPPLIED PER GA-610 FOR1-HOUR RATING NON-SHRINK THICK-SET MUD BED SCALE: ROOF ASSEMBLY (NEW ROOFS)CONCRETE POOL SUB-SLAB1 1/2" = 1'-0"R-49 MIN.R8A7.03 EXISTING/NEW FRAMING - RE:STRUCTURAL EXISTING PLYWOOD SHEATHING(TO REMAIN, TYP.)AT NEW ROOF, RE: STRUCTURALFOR SHEATHING INTERIOR EXTERIOR EXIST. T O R E M A I N RE: ST R U C T U R A L RIGID INSULATION - 2"THICKNESS. R-10 MIN. B.O. EXISTING OR NEW FRAMING- RE: STRUCTURAL VARIE S - R E : R C P S SPRAY APPLIED CLOSED-CELLFOAM INSULATION (R-39 MIN.)- SEAL ALL AIR GAPS 5/8" TYPE X GWBINTERIOR FINISH - RE: SCHEDULE DROPPED CEILING - VARIES - RE:RCPSCEILING FRAMING AS REQUIRED MECH. SPACE RE ST R U C T . REINFORCED CONCRETE &METAL DECK SLAB - RE:STRUCTURAL HYDROTECH MONOLITHICMEMBRANE 6125-FR FABRICREINFORCED SYSTEM APPLIEDPER MFR. REQUIREMENTS 2-LAYERS 5/8" TYPE C GWBAPPLIED PER LISTED ASSEMBLY 78" 20 GA.DRYWALL FURRINGCHANNEL. 24" MAX. O.C. PERLISTING KINETICS WAVE HANGER @ 48"MAX. OC, INSTALLED PER LISTING HYDROTECH SURFACECONDITIONER HYDROTECHHYDROFLEX 30PROTECTION COURSE PREFABRICATED POOLSTRUCTURE SCALE: ROOF ASSEMBLY CONCRETE SUB-SLAB WITH SNOWMELTED PAVER FINISH1 1/2" = 1'-0"R-49 MIN.R9A7.03 EXISTING/NEW FRAMING - RE:STRUCTURAL EXISTING PLYWOOD SHEATHING(TO REMAIN, TYP.)AT NEW ROOF, RE: STRUCTURALFOR SHEATHING INTERIOR EXTERIOR EXIST . T O R E M A I N RE: S T R U C T U R A L RIGID INSULATION B.O. EXISTING OR NEW FRAMING- RE: STRUCTURAL VARIE S - R E : R C P S SPRAY APPLIED CLOSED-CELLFOAM INSULATION (R-39 MIN.)- SEAL ALL AIR GAPS 5/8" TYPE X GWBINTERIOR FINISH - RE: SCHEDULE DROPPED CEILING - VARIES - RE:RCPS CEILING FRAMING AS REQUIRED MECH. SPACE RE ST R U C T . REINFORCED CONCRETE &METAL DECK SLAB - RE:STRUCTURAL HYDROTECH MONOLITHICMEMBRANE 6125-FR FABRICREINFORCED SYSTEM APPLIEDPER MFR. REQUIREMENTS 2-LAYERS 5/8" TYPE C GWBAPPLIED PER LISTED ASSEMBLY 78" 20 GA.DRYWALL FURRINGCHANNEL. 24" MAX. O.C. PERLISTING KINETICS WAVE HANGER @ 48"MAX. OC, INSTALLED PER LISTING HYDROTECHHYDROFLEX 30PROTECTION COURSESECUROCK ROOFSUBSTRATE BOARD TAPERED RIGID INSULATION ASREQUIRED TO CREATE 1/4" PERFT SLOPE HYDRODRAIN SETTING BEDRADIANT SNOWMELT TUBING EXTERIOR PAVERSSLOPE TO DRAIN1/4" PER FT. MIN. SCALE: DECK ASSEMBLYPAVERS OVER STAINLESS STEEL POOL SHELL1 1/2" = 1'-0"R10A7.03 GALVANIZED METAL LATH PERLATICRETE SYSTEM DETAILSTEEL SHELL SUBSTRATE BY POOL MFR.STEEL FRAMING BY POOL MFR. LATICRETE 3701 FORTIFIED MORTAR PERSYSTEM DETAIL LATICRETE HYDRO BANLATICRETE 254 PLATINUM EXTERIOR PORCELAIN TILE / PAVER - RE:FINISH SCHEDULE LATICRETE SPECTRALOCK PROPREMIUM GROUT SLOPE TO DRAIN1/8" PER FT. MIN. File Path: P : \ P r o j - 2 0 1 7 \ 2 1 7 1 8 . 0 0 _ M t n F o r g e \ 0 6 _ D o c u m e n t a t i o n \ 0 1 _ D r a w i n g s \ 2 1 7 1 8 _ A 7 - 0 1 - A S S E M . d w g Plot Date/Tim e : A p r i l 1 7 , 2 0 1 9 - 4 : 5 3 p m COPYRIGHT 2019 ROWLAND+BROUGHTON ARCHITECTURE AND URBAN DESIGNTHE INFORMATION AND DESIGN INTENT CONTAINED ON THIS DOCUMENT ISTHE PROPERTY OF ROWLAND+BROUGHTON ARCHITECTURE AND URBANDESIGN. NO PART OF THIS INFORMATION MAY BE USED WITHOUT THE PRIORWRITTEN PERMISSION OF ROWLAND+BROUGHTON ARCHITECTURE AND URBANDESIGN. ROWLAND+BROUGHTON ARCHITECTURE AND URBAN DESIGN SHALLRETAIN ALL COMMON LAW STATUTORY AND OTHER RESERVED RIGHTS,INCLUDING COPYRIGHT THERETO. Revision: Issue: SHEET TITLE PROJECT NO: DWG FILE: SCALE: 21718_A7-01-ASSEM.dwg MTN FORGERENOVATION AND ADDITION 230-234 E. HOPKINS AVENUEASPEN, CO 81611 21718 11.16.2017P+Z FINAL HEARING 1830 blake stdenver, co 80202303.308.1373500 w main staspen, co 81611970.544.9006 rowland+broughtonarchitecture / urban design / interior design 08.02.2018CONSTRUCTION DOCUMENTS08.28.201880% PRICING02.08.2019CD/PRICING SET 04.18.2019CONSTRUCTION DOCUMENTS 03.08.2019ASI-001 A7.03 AS NOTED BUILDINGASSEMBLIES Any assembly thatclaims a fire or soundrating must referencea listed assembly thatyou include in theplans. Revise to treatsimilarly to how youhave done the wallassemblies. SCALE:DOOR TYPE A1/2" = 1'-0" SCALE:DOOR TYPE B1/2" = 1'-0" BA8.2 SCALE:DOOR TYPE C1/2" = 1'-0" CA8.2 SCALE:DOOR TYPE D1/2" = 1'-0" DA8.2 SCALE:DOOR TYPE E1/2" = 1'-0" SCALE:DOOR TYPE F1/2" = 1'-0" FA8.2 ERIOR SWING - GLAZED RE: SCHEDULE TEMPEREDINSULATEDGLAZING 2"5 1/2" 10" MIN . A D A ALUMINUMCLAD WOODDOOR " RE: PLANSFOR SWINGORIENTATION INTERIOR SWING - SOLID RE: SCHEDULE RE: S C H E D U L E 3'-0 " VER I F Y 2 3/4" SOLID COREWOODDOOR PANELDETAIL TBD RE: PLANSFOR SWINGORIENTATION DOORFINISH TBD INTERIOR SWING - SOLID (AHU) RE: SCHEDULE RE: S C H E D U L E 3'-0 " VER I F Y 2 3/4" SOLID COREWOODDOOR FLUSHPANEL RE: PLANSFOR SWINGORIENTATION PAINTEDFINISH RE: SCHEDULE " SOLID COREWOODDOOR FLUSHPANEL BYPASSDOORS PAINTEDFINISH 2 3/4" TOP TRACK FLOOR MOUNTGUIDES, TYP. INTERIOR SWING - SOLID - RATED RE: SCHEDULE RE: S C H E D U L E 3'-0 " VER I F Y 2 3/4" SOLID CORERATEDWOOD DOOR PANELDETAIL TBD RE: PLANSFOR SWINGORIENTATION DOORFINISH TBD INTERIOR DOUBLE SWING - SOLID RE: SCHEDULE RE: S C H E D U L E 3'-0 " VER I F Y 2 3/4" SOLID COREWOODDOOR PANELDETAIL TBD RE: PLANSFOR SWINGORIENTATION DOORFINISH TBD 2 3/4" 10" MIN . A D A 10" MIN . A D A 10" MIN . A D A NTERIOR BYPASS - SOLID (AHU) SCALE:DOOR TYPE G1/2" = 1'-0" GA8.2 BUILDING ENTRY DOOR - EXTERIOR SWING - GLAZED RE: SCHEDULE RE: S C H E D U L E TEMPEREDINSULATEDGLAZING 5 1/2"5 1/2" 10" MIN . A D A ALUMINUMCLAD WOODDOOR 3'-0 " VER I F Y 2 3/4" RE: PLANSFOR SWINGORIENTATION SCALE:DOOR TYPE H1/2" = 1'-0" ERIOR SWING - FLUSH PANEL - RATED RE: SCHEDULE PAINTEDSTEEL FLUSHDOOR " RE: PLANSFOR SWINGORIENTATION SCALE:DOOR TYPE J1/2" = 1'-0" JA8.2 INTERIOR SWING - GLAZED RE: SCHEDULE RE: S C H E D U L E 3'-0 " VER I F Y 2 3/4" SOLID COREWOODDOOR PANELDETAIL TBD DOORFINISH TBD 10" MIN . A D A RE: PLANSFOR SWINGORIENTATION TEMPEREDGLAZING SCALE:DOOR TYPE K1/2" = 1'-0" KA8.2 RE: SCHEDULE RE: S C H E D U L E 3'-0 " VER I F Y 10" MIN . A D A RE: PLANSFOR SWINGORIENTATION2 3/4"2 3/4" EXTERIOR SWING - GLAZED - CENTER MULLION ALUMINUMCLAD WOODDOOR CENTERMULLION TEMPEREDINSULATEDGLAZING TEMPEREDINSULATEDGLAZING SCALE:DOOR TYPE L1/2" = 1'-0" EXTERIOR - OVERHEADECTIONAL GARAGE DOOR RE: SCHEDULE SCALE:DOOR TYPE M1/2" = 1'-0" MA8.2 EXTERIOR - SLIDING GLAZED DOORS RE: SCHEDULE RE: S C H E D U L E TEMPEREDINSULATEDGLAZING TEMPEREDINSULATEDGLAZING TEMPEREDINSULATEDGLAZING FIXED PANEL EQ EQ EQ BY M F R - V E R I F Y CL CL CL SCALE:DOOR TYPE N1/2" = 1'-0" NA8.2 INTERIOR POCKET - SOLID RE: SCHEDULE RE: S C H E D U L E 3'-0" VER I F Y 2 3/4" SOLID COREWOODDOOR PANELDETAIL TBD RE: PLANS FORPOCKETORIENTATION DOORFINISH TBD 10" MIN. A D A VERIFYBACKSET W/POCKETDOORHARDWARE GC TO COORDINATE LEAFEXTENSION ON POCKET SIDE METAL CLADDING OVERINSULATED CORE, RE:ELEVATIONS AND DETAILS DOOR HARDWARE GROUPS: GROUP: AFUNCTION:EXTERIOR SWING LOCKSETHANDLE:TBDDEADBOLT:TBDFINISH:TBD GROUP: BFUNCTION: INTERIOR SWING LOCKSETHANDLE: TBDDEADBOLT:TBDFINISH: TBD GROUP: CFUNCTION:INTERIOR SWING PASSAGEHANDLE:TBDFINISH:TBD GROUP: DFUNCTION:INTERIOR POCKET LOCKSETHANDLE:TBDFINISH: TBD GROUP: EFUNCTION: INTERIOR POCKET PASSAGEHANDLE:TBDFINISH: TBD GROUP: GFUNCTION:INTERIOR SWING PRIVACYHANDLE:TBDFINISH:TBD GROUP: HFUNCTION: ELEVATOR SWING INTERLOCKHANDLE: TBDFINISH: TBD GROUP: IFUNCTION:INTERIOR SWING FRAMELESSHANDLE:TBDFINISH:TBD GROUP: JFUNCTION:EXTERIOR SWING SELF-RELEASING*HANDLE:TBDFINISH:TBD(1)EGRESS SIDE SHALL BE SELF RELEASING, OPPOSITE SIDESHALL BE LOCKABLE - COMPLIANT W/ IBC 1010.1.9.11 EX. 1(2)EGRESS SIDE SHALL BE SELF RELEASING, OPPOSITE SIDESHALL BE LOCKABLE, PROVIDE ELECTRONIC CONTROLLEDLATCH RELEASE - COMPLIANT W/ IBC 1010.1.9.11 EX. 3 GROUP: HFUNCTION:INTERIOR SWING JIBHANDLE:TBDFINISH:TBD COPYRIGHT 2019 ROWLAND+BROUGHTON ARCHITECTURE AND URBAN DESIGNTHE INFORMATION AND DESIGN INTENT CONTAINED ON THIS DOCUMENT ISTHE PROPERTY OF ROWLAND+BROUGHTON ARCHITECTURE AND URBANDESIGN. NO PART OF THIS INFORMATION MAY BE USED WITHOUT THE PRIORWRITTEN PERMISSION OF ROWLAND+BROUGHTON ARCHITECTURE AND URBANDESIGN. ROWLAND+BROUGHTON ARCHITECTURE AND URBAN DESIGN SHALLRETAIN ALL COMMON LAW STATUTORY AND OTHER RESERVED RIGHTS,INCLUDING COPYRIGHT THERETO. Revision: Issue: SHEET TITLE PROJECT NO: DWG FILE: SCALE: 21718_A8-1.dwg MTN FORGE RENOVATION AND ADDITION 230-234 E. HOPKINS AVENUEASPEN, CO 81611 21718 11.16.2017P+Z FINAL HEARING 1830 blake stdenver, co 80202303.308.1373 500 w main staspen, co 81611970.544.9006 rowland+broughtonarchitecture / urban design / interior design 08.02.2018CONSTRUCTION DOCUMENTS08.28.201880% PRICING02.08.2019CD/PRICING SET 04.18.2019CONSTRUCTION DOCUMENTS 03.08.2019ASI-001 DOORSCHEDULE AS NOTED A8.2 Doors 1/010, 3/104, and 1/217 areshown to have hardware group Dwhich refers to an interior pocketlockset. These are swinging doorswhich serve an exit stair enclosure.Locking prohibited unless you candemonstrate compliance with one ofthe exceptions of 2015 IBC1010.1.9.11. SCALE: DOOR TYPE A 1/2" = 1'-0" A A8.2 SCALE: DOOR TYPE B 1/2" = 1'-0" B A8.2 SCALE: DOOR TYPE C 1/2" = 1'-0" C A8.2 SCALE: DOOR TYPE D 1/2" = 1'-0" D A8.2 SCALE: DOOR TYPE E 1/2" = 1'-0" E A8.2 SCALE: DOOR TYPE F 1/2" = 1'-0" F A8.2 EXTERIOR SWING - GLAZED 10 MIN . A INTERIOR SWING - SOLID INTERIOR SWING - SOLID (AHU) RE: SCHEDULE RE : S C H E D U L E 3'- 0 " VER I F Y 2 3/4" SOLID CORE WOODDOOR FLUSHPANEL BYPASSDOORS PAINTEDFINISH 2 3/4" TOP TRACK FLOOR MOUNTGUIDES, TYP. INTERIOR SWING - SOLID - RATED INTERIOR DOUBLE SWING - SOLID RE: SCHEDULE RE : S C H E D U L E 3'- 0 " VER I F Y 2 3/4" SOLID CORE WOODDOOR PANELDETAIL TBD RE: PLANSFOR SWINGORIENTATION DOORFINISH TBD 2 3/4" 10 MIN . A 10 MIN . A 10 " MIN . A D A INTERIOR BYPASS - SOLID (AHU) SCALE: DOOR TYPE G 1/2" = 1'-0" G A8.2 BUILDING ENTRY DOOR - EXTERIOR SWING - GLAZED RE: SCHEDULE RE : S C H E D U L E TEMPEREDINSULATEDGLAZING 5 1/2"5 1/2" 10 " MIN . A D A ALUMINUMCLAD WOODDOOR 3'- 0 " VER I F Y 2 3/4" RE: PLANS FOR SWINGORIENTATION SCALE: DOOR TYPE H 1/2" = 1'-0" H A8.2 EXTERIOR SWING - FLUSH PANEL - RATED RE: SCHEDULE RE: S C H E D U L E PAINTED STEEL FLUSH DOOR 3'-0 " VE R I F Y 2 3/4" RE: PLANSFOR SWINGORIENTATION SCALE: DOOR TYPE J 1/2" = 1'-0" J A8.2 INTERIOR SWING - GLAZED RE: SCHEDULE RE: S C H E D U L E 3'-0 " VE R I F Y 2 3/4" SOLID COREWOODDOOR PANELDETAIL TBD DOOR FINISH TBD 10" MIN . A D A RE: PLANS FOR SWING ORIENTATION TEMPERED GLAZING SCALE: DOOR TYPE K 1/2" = 1'-0" K A8.2 RE: SCHEDULE RE: S C H E D U L E 3'-0 " VE R I F Y 10" MIN . A D A RE: PLANS FOR SWING ORIENTATION2 3/4"2 3/4" EXTERIOR SWING - GLAZED - CENTER MULLION ALUMINUM CLAD WOOD DOOR CENTERMULLION TEMPEREDINSULATEDGLAZING TEMPEREDINSULATEDGLAZING SCALE: DOOR TYPE L 1/2" = 1'-0" L A8.2 EXTERIOR - OVERHEADSECTIONAL GARAGE DOOR RE: SCHEDULE RE: S C H E D U L E SCALE: DOOR TYPE M 1/2" = 1'-0" M A8.2 EXTERIOR - SLIDING GLAZED DOORS RE: SCHEDULE RE: S C H E D U L E TEMPEREDINSULATED GLAZING TEMPEREDINSULATED GLAZING TEMPEREDINSULATED GLAZING FIXED PANEL EQ EQ EQ BY M F R - V E R I F Y CLCL CL CL SCALE: DOOR TYPE N 1/2" = 1'-0" N A8.2 INTERIOR POCKET - SOLID RE: SCHEDULE RE : S C H E D U L E 3'-0 " VER I F Y 2 3/4" SOLID CORE WOODDOOR PANELDETAIL TBD RE: PLANS FORPOCKETORIENTATION DOORFINISH TBD 10 " MIN . A D A VERIFYBACKSET W/POCKETDOORHARDWARE GC TO COORDINATE LEAFEXTENSION ON POCKET SIDE METAL CLADDING OVERINSULATED CORE, RE:ELEVATIONS AND DETAILS DOOR HARDWARE GROUPS: GROUP: A FUNCTION:EXTERIOR SWING LOCKSETHANDLE:TBDDEADBOLT:TBDFINISH:TBD GROUP: B FUNCTION: INTERIOR SWING LOCKSETHANDLE: TBDDEADBOLT:TBDFINISH: TBD GROUP: CFUNCTION:INTERIOR SWING PASSAGEHANDLE:TBDFINISH:TBD GROUP: DFUNCTION:INTERIOR POCKET LOCKSETHANDLE:TBDFINISH: TBD GROUP: E FUNCTION: INTERIOR POCKET PASSAGEHANDLE:TBDFINISH: TBD GROUP: G FUNCTION:INTERIOR SWING PRIVACYHANDLE:TBDFINISH:TBD GROUP: HFUNCTION: ELEVATOR SWING INTERLOC HANDLE: TBDFINISH: TBD GROUP: IFUNCTION:INTERIOR SWING FRAMELESS HANDLE:TBDFINISH:TBD GROUP: JFUNCTION:EXTERIOR SWING SELF-RELE HANDLE:TBD FINISH:TBD(1)EGRESS SIDE SHALL BE SELF RELE SHALL BE LOCKABLE - COMPLIANT (2)EGRESS SIDE SHALL BE SELF RELE SHALL BE LOCKABLE, PROVIDE ELE LATCH RELEASE - COMPLIANT W/ IB GROUP: HFUNCTION:INTERIOR SWING JIBHANDLE:TBD FINISH:TBD Door 1/213 serves an employee work area per yourresponse and therefore mustprovide 32" clear measuredfrom the face of the door leafopened at 90 degrees to the face of the doorstop. A 2'-10" (34") door will typically only provide 31 3/4" of clearance. Revise door schedule todemonstrate compliance.(2015 IBC 1010.1.1) Page: A8.2 DOOR SCHEDULE File Name: 230 E. Hopkins_Drawings_Architecture_2019-04-18.pdf Subject: PlanCheck Author: nickt Color: Just to be clear, this is the roof deck door and the egress side is from the roof, so it may not be locked from the outside. Also, specify hardware that will unlock without unlatching and specify the location of the signal to unlock (fire access command panel in the entry). 2015 IBC 1010.1.9.11 ex 3. Page: A8.2 DOOR SCHEDULE File Name: 230 E. Hopkins_Drawings_Architecture_2019-04-18.pdf Subject: PlanCheck Author: nickt Color: Door 1/215 requires a 20 minute fire rating due to being in a 1/2 hour rated corridor. 2015 IBC 1020.1. Page: A8.4 LIGHTING SCHEDULE File Name: 230 E. Hopkins_Drawings_Architecture_2019-04-18.pdf Subject: PlanCheck Author: nickt Color: I have not received cutsheets for the light fixtures; please provide. The cutsheets should have the maximum wattage highlighted (and this should match the comcheck) and listing by a nationally recognized testing lab highlighted. Page: A9.1 PROPOSED INTERIOR ELEVATIONS File Name: 230 E. Hopkins_Drawings_Architecture_2019-04-18.pdf Subject: PlanCheck Author: nickt Color: Show and dimension a 30"x48" clear space clear of the door swing. ICC A117.1-2009 section 603.2.2 exception 2. Page: [7] C5.1 Detailed Grading Plan File Name: 230 E. Hopkins_Drawings_Civil_2019-04-18.pdf Subject: PlanCheck Author: nickt Color: Verify that the slope and cross slope at this portion of the means of egress to the public way comply with 2015 IBC ch 10. 230 E. Hopkins_Drawings_Civil_2019-04-18.pdf (1) SOLID CORE WOOD DOOR PANEL DETAIL TBD RE: PLANS FOR POCKETORIENTATION DOOR FINISH TBD VERIFYBACKSET W/ POCKET DOORHARDWARE GC TO COORDINATE LEAF EXTENSION ON POCKET SIDE DOOR HARDWARE GROUPS: GROUP: A FUNCTION:EXTERIOR SWING LOCKSET HANDLE:TBD DEADBOLT:TBD FINISH:TBD GROUP: B FUNCTION: INTERIOR SWING LOCKSETHANDLE: TBD DEADBOLT:TBDFINISH: TBD GROUP: CFUNCTION:INTERIOR SWING PASSAGE HANDLE:TBD FINISH:TBD GROUP: DFUNCTION:INTERIOR POCKET LOCKSET HANDLE:TBD FINISH: TBD GROUP: EFUNCTION: INTERIOR POCKET PASSAGE HANDLE:TBD FINISH: TBD GROUP: G FUNCTION:INTERIOR SWING PRIVACY HANDLE:TBDFINISH:TBD GROUP: H FUNCTION: ELEVATOR SWING INTERLOCK HANDLE: TBDFINISH: TBD GROUP: I FUNCTION:INTERIOR SWING FRAMELESS HANDLE:TBDFINISH:TBD GROUP: JFUNCTION:EXTERIOR SWING SELF-RELEASING* HANDLE:TBD FINISH:TBD (1)EGRESS SIDE SHALL BE SELF RELEASING, OPPOSITE SIDE SHALL BE LOCKABLE - COMPLIANT W/ IBC 1010.1.9.11 EX. 1(2)EGRESS SIDE SHALL BE SELF RELEASING, OPPOSITE SIDE SHALL BE LOCKABLE, PROVIDE ELECTRONIC CONTROLLEDLATCH RELEASE - COMPLIANT W/ IBC 1010.1.9.11 EX. 3 GROUP: HFUNCTION:INTERIOR SWING JIB HANDLE:TBD FINISH:TBD COPYRIGHT 2019 ROWLAND+BROUGHTON ARCHITECTURE AND URBAN DESIGNTHE INFORMATION AND DESIGN INTENT CONTAINED ON THIS DOCUMENT ISTHE PROPERTY OF ROWLAND+BROUGHTON ARCHITECTURE AND URBANDESIGN. NO PART OF THIS INFORMATION MAY BE USED WITHOUT THE PRIORWRITTEN PERMISSION OF ROWLAND+BROUGHTON ARCHITECTURE AND URBANDESIGN. ROWLAND+BROUGHTON ARCHITECTURE AND URBAN DESIGN SHALLRETAIN ALL COMMON LAW STATUTORY AND OTHER RESERVED RIGHTS,INCLUDING COPYRIGHT THERETO. SHEET TITLE PROJECT NO: DWG FILE: SCALE: 21718_A8-1.dwg MTN FORGE RENOVATION AND ADDITION 230-234 E. HOPKINS AVENUE ASPEN, CO 81611 21718 DOOR SCHEDULE AS NOTED A8.2Just to be clear, this is the roof deck door and the egress side is from the roof, so it may not be locked from the outside. Also, specify hardware that will unlock without unlatching and specify the location of the signal to unlock (fire access command panel in the entry). 2015 IBC 1010.1.9.11 ex 3. D FOR SWING ORIENTATION 10 " MI N . A D A SCALE: DOOR TYPE G 1/2" = 1'-0" G A8.2 BUILDING ENTRY DOOR - EXTERIOR SWING - GLAZED RE : S C H E GLAZING 10 " MI N . A D A 3'- 0 " VE R I F Y 2 3/4"ORIENTATION SCALE: DOOR TYPE K 1/2" = 1'-0" RE: SCHEDULE 3'- 0 " VE R I F Y 10 " MI N . A D A RE: PLANS FOR SWING ORIENTATION 2 3/4"2 3/4" XTERIOR SWING - GLAZED - CENTER MULLION ALUMINUM CLAD WOOD DOOR CENTER MULLION TEMPERED INSULATED GLAZING TEMPERED INSULATED GLAZING Door 1/215 requires a 20 minute fire rating due to being in a 1/2 hour rated corridor. 2015 IBC 1020.1. File P a t h : P : \ P r o j - 2 0 1 7 \ 2 1 7 1 8 . 0 0 _ M t n F o r g e \ 0 6 _ D o c u m e n t a t i o n \ 0 1 _ D r a w i n g s \ 2 1 7 1 8 _ A 8 - 1 . d w g Plot D a t e / T i m e : A p r i l 1 7 , 2 0 1 9 - 4 : 4 7 p m I have not received cutsheets for the light fixtures; please provide. The cutsheets should have the maximum wattage highlighted (and this should match the comcheck) and listing by a nationally recognized testing lab highlighted. SCALE: RESTROOM 012 1/2" = 1'-0" 5 A9.1 SCALE:RESTROOM 0141/2" = 1'-0" 3A9.1 SCALE:RESTROOM 0141/2" = 1'-0" 4A9.1 1'-0"2'-0" 1'-6" 2'-10 " 3'-4" 2'-10 " 3'-6" 3'-4"4'-6" 1'-6"1'-0" 2'-8 1/4" MATERIALPRODUCTTRADENAMEMODELNUMBER MODELNUMBERTRADENAMEPRODUCTMATERIAL MODELNUMBERTRADENAMEPRODUCTMATERIAL 1'-10"5'-0" 4'-4 " 2'-10 " 6" SCALE: RESTROOM 012 1/2" = 1'-0" 6 A9.1 SCALE: RESTROOM 012 1/2" = 1'-0" 7 A9.1 SCALE:KEY PLAN1/2" = 1'-0"AA9.1 1 234A9.1 Ø5'- 0 " SCALE:KEY PLAN1/2" = 1'-0" BA9.1 GFCI 2'-3" KNEE AND TOE CLEARANCE INCOMPLIANCE WITH ANSI 117.1-2009SECTION 306 7"6" 3'-4" 9" M I N . 6" MAX. MATERIALPRODUCTTRADENAMEMODELNUMBER 8" MIN. 1'-5" MIN. 2'-3" M I N . ANSI COMPLIANT SINKAND FAUCET 36" ANSI COMPLIANTHORIZONTAL GRAB BAR 18" ANSI COMPLIANTVERTICAL GRAB BAR42" ANSI COMPLIANTHORIZONTAL GRAB BARANSI COMPLIANT TOILET HATCHED AREA INDICATES ANSICOMPLIANT REASON FORPROTRUDING DISPENSER BELOWGRAB BAR RESTROOM014 5'-0" 4'-8" 2'-6" 4'-0" PT1 PT1 PT1 PT1 B1 T6 1'-11 " 4" 7" EQ.EQ. SS2 MW2TRASH T6 2'-0"2'-6" P3 SCALE: RESTROOM 014 1/2" = 1'-0" 1 A9.1 SCALE: RESTROOM 014 1/2" = 1'-0" 2 A9.1 SCALE:RESTROOM 0121/2" = 1'-0" 8A9.1 MW2TRASH MATERIALPRODUCTTRADENAMEMODELNUMBER MODELNUMBERTRADENAMEPRODUCTMATERIAL T6 P3 PT1 SS2 4'-2 1/4" SCALE:RESTROOM 1061/2" = 1'-0" 9A9.1 SCALE:KEY PLAN1/2" = 1'-0"CA9.1 1231112A9.1 1'-0"2'-0" 1'-6" 2'-10 " SCALE: RESTROOM 106 1/2" = 1'-0" 10 A9.1 3'-4" 2'-10 "3'-4"4'-6" 1'-6"1'-0" 2'-9" SCALE: RESTROOM 106 1/2" = 1'-0" 11 A9.1 SCALE:RESTROOM 1061/2" = 1'-0" 12A9.1 Ø5'-0" MODELNUMBERTRADENAMEPRODUCTMATERIAL KNEE AND TOE CLEARANCE INCOMPLIANCE WITH ANSI 117.1 1'-10" 6" MATERIALPRODUCTTRADENAMEMODELNUMBER MODELNUMBERTRADENAMEPRODUCTMATERIAL 5'-0" 4'-0" 2'-10 " 6" DOOR CLEARANCE PER ANSI117.1 SECTION 404.2.3.2 (B) RESTROOM106 1'-0"3'-0" 36" ANSI COMPLIANTHORIZONTALGRAB BAR ANSI COMPLIANT TOILET 18" ANSI COMPLIANTVERTICAL GRAB BAR42" ANSI COMPLIANTHORIZONTAL GRAB BARHATCHED AREA INDICATES ANSICOMPLIANT REASON FORPROTRUDING DISPENSER BELOWGRAB BAR ANSI COMPLIANT SINKAND FAUCET 3'-6" 2'-6" 4'-0" 5'-0" PT1 PT1 PT1 PT1 SS2 MW2 B1 4'-8" 7 6 5 8A9.1 RESTROOM012 2'-6" 4'-0" 4'-8" 5'-0" Ø5'-0 " 3'-4" 2'-10 " 3'-6" 3'-4"4'-4" 1'-6"10" 2'-9" 18" ANSI COMPLIANTVERTICAL GRAB BAR42" ANSI COMPLIANTHORIZONTAL GRAB BARHATCHED AREA INDICATES ANSICOMPLIANT REASON FORPROTRUDING DISPENSER BELOWGRAB BAR PT1 B1 1'-0"2'-0" 1'-6" 2'-10 " 36" ANSI COMPLIANT HORIZONTALGRAB BARANSI COMPLIANT TOILET PT1 MODELNUMBERTRADENAMEPRODUCTMATERIAL KNEE AND TOE CLEARANCE INCOMPLIANCE WITH ANSI 117.1-2009SECTION 306 GFCI 2'-3" 7" 6" 1'-10" 6" 4'-4" 2'-10 " 6" ANSI COMPLIANT SINKAND FAUCET 1'-11" 4" 7" 2'-0"2'-6" 4'-0" 3'-0" GFCI 4'-0" 5'-0" TRUENORTHPLANNORTH TRUENORTHPLANNORTH TRUENORTHPLANNORTH A9.1 1/2"=1'-0" PROPOSEDINTERIORELEVATIONS File Path : P : \ P r o j - 2 0 1 7 \ 2 1 7 1 8 . 0 0 _ M t n F o r g e \ 0 6 _ D o c u m e n t a t i o n \ 0 1 _ D r a w i n g s \ 2 1 7 1 8 _ A 9 - 1 . d w g Plot Date/T i m e : A p r i l 1 7 , 2 0 1 9 - 5 : 0 8 p m COPYRIGHT 2019 ROWLAND+BROUGHTON ARCHITECTURE AND URBAN DESIGNTHE INFORMATION AND DESIGN INTENT CONTAINED ON THIS DOCUMENT ISTHE PROPERTY OF ROWLAND+BROUGHTON ARCHITECTURE AND URBANDESIGN. NO PART OF THIS INFORMATION MAY BE USED WITHOUT THE PRIORWRITTEN PERMISSION OF ROWLAND+BROUGHTON ARCHITECTURE AND URBANDESIGN. ROWLAND+BROUGHTON ARCHITECTURE AND URBAN DESIGN SHALLRETAIN ALL COMMON LAW STATUTORY AND OTHER RESERVED RIGHTS,INCLUDING COPYRIGHT THERETO. Revision: Issue: SHEET TITLE PROJECT NO: DWG FILE: SCALE: 21718_A9-1.dwg MTN FORGERENOVATION AND ADDITION 230-234 E. HOPKINS AVENUEASPEN, CO 81611 21718 11.16.2017P+Z FINAL HEARING 1830 blake stdenver, co 80202303.308.1373 500 w main staspen, co 81611970.544.9006 rowland+broughtonarchitecture / urban design / interior design 08.02.2018CONSTRUCTION DOCUMENTS 08.28.201880% PRICING02.08.2019CD/PRICING SET 04.18.2019CONSTRUCTION DOCUMENTS 03.08.2019ASI-001 Show and dimensiona 30"x48" clear spaceclear of the doorswing. ICCA117.1-2009 section603.2.2 exception 2. G E File P a t h : D : \ D r o p b o x \ P r o j e c t F i l e s \ 1 8 . 0 0 6 - 2 3 0 - 2 3 4 E a s t H o p k i n s A v e n u e , A s p e n \ P l a n s \ C 5 . 1 D e t a i l e d G r a d i n g P l a n . d w g Plot D a t e / T i m e : A p r i l 1 5 , 2 0 1 9 - 1 1 : 1 5 a m Verify that the slopeand cross slope at this portion of the meansof egress to the public way comply with 2015IBC ch 10. Page: [9] 18009 e1-E2.3 File Name: 230 E. Hopkins_Drawings_Electrical_2019-04-18.pdf Subject: PlanCheck Author: nickt Color: Receptacles used to power pool and spa must be 6' minimum from the inside walls of the pool and spa. 2017 NEC 680.22(A)(2). Section 680.8(A) refers to overhead conductors. 230 E. Hopkins_Drawings_Electrical_2019-04-18.pdf (4) Page: [9] 18009 e1-E2.3 File Name: 230 E. Hopkins_Drawings_Electrical_2019-04-18.pdf Subject: PlanCheck Author: nickt Color: Receptacles must be 6' minimum from the inside walls of the pool. 2017 NEC 680.22(A)(3) Page: [10] 18009 e1-E3.0 File Name: 230 E. Hopkins_Drawings_Electrical_2019-04-18.pdf Subject: PlanCheck Author: nickt Color: The updated lighting plans do not appear to show the occupant sensor and time switch controls required by 2015 IECC C405.2.1 and C405.2.2. Revise. Page: [13] 18009 e1-E3.3 File Name: 230 E. Hopkins_Drawings_Electrical_2019-04-18.pdf Subject: PlanCheck Author: nickt Color: Lumineres within 5' of pools and spas must comply with 2017 NEC 680.23 (A)(2) Page: 13 File Name: 230 E. Hopkins_Drawings_Structural_2019-04-18.pdf Subject: PlanCheck Author: nickt Color: Revise structure so that the mechanical room fire barrier walls are continuous to the floor sheathing without penetration by any structure. 2015 IBC 707.5 230 E. Hopkins_Drawings_Structural_2019-04-18.pdf (2) ELEVATOR 6:12 12:12 12:12 6:12 12 : 1 2 12 : 1 2 DN MEMBRANE ROOF MEMBRANE ROOF ME M B R A N E R O O F MODULAR GREEN ROOF DN RD OD DS DN DNDN RD OD DN DN RD OD DN DN DN DN RD OD WH y WHy DS DN RD OD DN DN RIVER ROCK BALLAST AROUND DRAINS UP UP UP 30" DN PL A N T E R BE N C H PLANTER PLANTER PLANTER 6" PLANTER PLANTERPLANTER U/C REF U/C REF DN RD OD DN DNDN DN RD OD DN DNDN RD OD LEVEL TWO DECK BELOW METAL ROOF METAL ROOF METAL ROOF MECHVENT ROOF BELOW LEVEL TWO DECK BELOW ROOF BELOW ROOF BELOW GAS F.P. FLUE GA S F I R E P I T ROOF DRAINS BELOW LEVEL PAVER DECK, TYP. WATER FEATUREBASIN SNOW FENCE GUTTER GUTTER GUTTER GA S F I R E T A B L E SPA 7'x7' RESISTANCE POOL 7'x19' MECHANICALVAULT BELOW GRILL "SUN DECK" 8" CONC WALL BELOW - TYP. @ POOL/SPA PERIMETER HANDRAIL @ 36" ABOVE NOSING 5R @ 6" 3R @ 6" 3R @ 6" GU A R D @ 3 6 " A F F HO P K I N S A V E N U E EXISTING ADDITION EX I S T I N G AD D I T I O N A B FDCE ROOFDECK 301 OUTDOORKITCHEN 302 STAIR 1 3031/303 EUH 6 WPGFI LED STRIPAT SHAFT WP GFI WP GFI WPGFI WPGFI WP GFI WPGFI J J J J J WP GFI AC AC AC AC PROVIDE WP GFI RECEPTACLES AT EXTERIOR KITCHEN. AT UNDERCOUNTER RECEPTACLESPROVIDE PLUGGED WP COVER. WP GFI 50A2P WP RECEPTACLEFOR SPA. HR VIA GFI. WP EUH 6 CU4 CU 5 CU 7 CU8 CU 6 CU2 CU1 CU3 AC1 WP J M M M M M M M M M J AT GUTTERS AND DOWNSPOUTS,PROVIDE (2) RUNS OF HEATTRACE AT GUTTER, ONE AT BOTTOM OF GUTTER, ONE AT TOPBUILDING SIDE OF GUTTER.ROUTE DOWN DOWNSPOUTS AND PROVIDE 3' LOOP AT OUTLET.TYPICAL. F1-2F1-4 F1-6 F1-8 F1-10 F1-12 F1-14,16 F1-18 CU9 CU 10 M M F1-17,19 F1-21,23 J HT J HT H-14PARTIAL H-34,36H-38 H-39,41 PARTIAL HT H-39,41 PARTIAL H-39,41PARTIAL H-39,41PARTIAL H-39,41PARTIAL H-40 J H-39,41PARTIAL HT HT HT HT HT #4-12,14 #3-6,8 #6-6,8 #7-6,8 #4-6,8 #1-6,8 AHU-24,26 #2-6,8 100A2P WP RECEPTACLEFOR POOL. HR VIA GFI. F1-18,20 LOCATE PER POOL EQ SHOPS J F1-22,2430A2PWATER FEATURE HT JHT JHT JHT JHT JHT Receptacles used topower pool and spamust be 6' minimumfrom the inside wallsof the pool and spa.2017 NEC680.22(A)(2). Section 680.8(A) refers to overhead conductors. ELEVATOR 12:12 6:12 12 : 1 2 12 : 1 2 DN MEMBRANE ROOF MEMBRANE ROOF ME M B R A N E R O O F MODULAR GREEN ROOF DN RD OD DS DN DNDN RD OD DN DN RD OD DN DN DN DN RD OD WH y WHy DS DN RD OD DN DN RIVER ROCK BALLAST AROUND DRAINS UP UP 30" DN CH 6" U/C REF U/CREF DN RD OD DN DNDN RD OD METAL ROOF METAL ROOF MECH VENT ROOF BELOW ROOF BELOW GAS F.P. FLUE GA S F I R E P I T ROOF DRAINS BELOW LEVEL PAVER DECK, TYP. WATER FEATURE BASIN GA S F I R E T A B L E SPA 7'x7' RESISTANCE POOL 7'x19' MECHANICALVAULT BELOW GRILL "SUN DECK" 8" CONC WALL BELOW - TYP. @ POOL/SPA PERIMETER HANDRAIL @ 36" ABOVE NOSING 5R @ 6" 3R @ 6" GU A R D @ 3 6 " A F F EXISTING ADDITION EX I S T I N G AD D I T I O N GFDCE ROOFDECK 301 OUTDOORKITCHEN 302 STAIR 1 3031/303 EUH 6 WPGFI LED STRIP AT SHAFT WPGFI WPGFI WPGFI WPGFI WPGFI WPGFI J J WP GFI AC AC AC AC PROVIDE WP GFI RECEPTACLES AT EXTERIOR KITCHEN. AT UNDERCOUNTER RECEPTACLESPROVIDE PLUGGED WP COVER. 50A2P WP RECEPTACLEFOR SPA. HR VIA GFI. WP EUH 6 CU4 CU5 CU7 CU8 CU6 CU 2 CU1 CU 3 AC 1 WP J M M M M M M M M M J AT GUTTERS AND DOWNSPOUTS, PROVIDE (2) RUNS OF HEAT TRACE AT GUTTER, ONE ATBOTTOM OF GUTTER, ONE AT TOPBUILDING SIDE OF GUTTER. ROUTE DOWN DOWNSPOUTS ANDPROVIDE 3' LOOP AT OUTLET.TYPICAL. F1-2F1-4 F1-6 F1-8 F1-10 F1-12 F1-14,16 F1-18 CU 9 CU 10 M M F1-17,19 F1-21,23 J HT JHT H-14PARTIAL H-34,36H-38 H-39,41PARTIAL HT H-39,41 PARTIAL H-39,41PARTIAL H-39,41PARTIAL H-40 T HT HT #4-12,14 #3-6,8 #6-6,8 #7-6,8 #4-6,8 #1-6,8 AHU-24,26 #2-6,8 100A2P WP RECEPTACLEFOR POOL. HR VIA GFI. F1-18,20 LOCATE PER POOL EQ SHOPS J F1-22,2430A2PWATER FEATURE HT JHT JHT JHT JHT Receptacles must be 6' minimum from theinside walls of the pool. 2017 NEC 680.22(A)(3) 7 6 A B C T1 The updated lighting plans do not appear to show the occupant sensor and time switch controls required by 2015 IECC C405.2.1 and C405.2.2. Revise. ELEVATOR 6:12 12:12 12:12 6:12 12: 1 2 12:1 2 DN MEMBRANE ROOF MEMBRANE ROOF MEM B R A N E R O O F MODULAR GREENROOF DN RD OD DS DN DNDN RD OD DN DN RD OD DN DN DN DN RD OD WHy WHy DS DN RD OD DN DN RIVER ROCK BALLASTAROUND DRAINS UP UP UP 30" DN PLA N T E R BEN C H PLANTER PLANTER PLANTER 6" PLANTER PLANTERPLANTER U/CREF U/CREF DN RD OD DN DNDN DN RD OD DN DNDN RD OD LEVEL TWODECK BELOW METAL ROOF METAL ROOF METAL ROOF MECHVENT ROOF BELOW LEVEL TWODECK BELOW ROOF BELOW ROOF BELOW GAS F.P.FLUE GAS F I R E P I T ROOF DRAINSBELOW LEVELPAVER DECK, TYP. WATER FEATUREBASIN SNOW FENCE GUTTER GUTTER GUTTER GUTTER GAS F I R E T A B L E SPA7'x7' RESISTANCE POOL7'x19' MECHANICALVAULTBELOW GRILL "SUN DECK" 8" CONC WALL BELOW - TYP.@ POOL/SPA PERIMETER HANDRAIL @ 36"ABOVE NOSING 5R @ 6" 3R @ 6" 3R @ 6" GU A R D @ 3 6 " A F F MONARCH STREET HO P K I N S A V E N U E ALL E Y EXISTING ADDITION EXISTING ADDITION EXI S T I N G ADD I T I O N EXI S T I N G ADD I T I O N 7 3 5 6 2 1 4 A B GFDCE B GFDCEA ROOFDECK301 OUTDOORKITCHEN302 STAIR 13031/303 a b CS1 1 SHEET DETAIL NOTES: PROVIDE MULTI SCENE CONTROLLER LUTRON GRAFIK EYE OR EQUAL.LOCATE DIMMERS INSIDE AT RESIDENCE, PROVIDE EXTERIORWEATHER PROOF DIMMER CONTROLLER. PROVIDE PHOTOCELL INPUTFOR EXTERIOR LIGHT CONTROL. PROVIDE SHOP DRAWINGS FORREVIEW PRIOR TO ROUGHIN. UP TO NEXT LEVEL LOCATE BATTERIES FOR THISEXIT AND EGRESS LIGHTWITHIN HEATED SPACE GENERAL NOTES: 1.REFERENCE PANEL SCHEDULES FOR LIGHTING CIRCUITS. 3RD FLOOR COMMON AREAS120 SF EX5EX5 R3 R3 R3 R3EX1 EX1 EX5 EGR EGR EXIT EX7 EX7 EX7 EX7EX7 EX7EX7 EX1 EX1c d c d d d d d d EX1c EX1c EX1c EX1c EX1 of ww w . a e c - v a i l . c o m a PO B o x 8 4 8 9 , 4 0 8 0 1 U S H w y 6 & 2 4 , S t e 2 1 4 , A v o n , C o l o r a d o , 8 1 6 2 0 Mec h a n i c a l , E l e c t r i c a l & L i g h t i n g D e s i g n S e r v i c e s Arc h i t e c t u r a l E n g i n e e r i n g C o n s u l t a n t s Tel e p h o n e : 9 7 0 - 7 4 8 - 8 5 2 0 ce Drawn By:Checked By: DATE:ISSUE: AEC PROJECT #: MO U N T A I N F O R G E RE M O D E L & A D D I T I O N 20 0 - 2 3 4 E . H O P K I N S AS P E N , C O L O R A D O 8 1 6 1 1 18009.00 An O f f i c e w i t h L E E D ™ A c c r e d i t e d P r o f e s s i o n a l s 07-30-18PERMIT01-23-19CONSTRUCTION COORD.01-30-19CONSTRUCTION03-08-19ASI - 001 104-18-19CD'S 51*#'% TF(.114.+)*6+0)2.#0 5%#.'žÄ ' NORTH 3rd FLOOR LIGHTING PLAN SCALE: 1/4" = 1'0" Lumineres within 5' ofpools and spas mustcomply with 2017 NEC680.23 (A)(2) A A 1 7 G G B B C C D D E E F F 2 3 4 5 6 (E) 5.125x12 GLB (E) 5.125x12 GLB (E) 5.125x12 GLB(E) 5.125x16.5 GLB 13'-4"13'-4"13'-2 5/8" 8" 60'-0" 5'-5 3/8" 15'-0 3/4" 6'-7 1/4" 8'-1 3/8" 17'-11 1/4" 6'-10" 100'-0" 10'-5 1/4"18'-8"5'-8 1/8"26'-4 3/4"14'-8 1/2"24'-1 3/8" 100'-0" 10'-5 1/4"18'-8"5'-8 1/8"26'-4 3/4"14'-8 1/2"24'-1 3/8" (E) 5.125x12 GLB (E ) 5 . 1 2 5 x 1 6 . 5 G L B CO M P O S I T E S L A B 11 7 / 8 T J I 3 6 0 @ 1 6 " O C T/SHEATHING99'-6" 5" C O M P O S I T E D E C K HSS 4x4x1/4 EBP2 HSS 4x4x 5/16 EBP2 HSS4x4x1/4HSS4x4x1/4HSS4x4x1/4 HS S4x4x1/4 BP4 HSS4x4 x5/16 BP4 1 3/4"x14" LVL@12"OC (E) 10" TJI@16"OC(E) 10" TJI@16"OC (E) 10" TJI@16"OC HS S5x5 x1/4 HS S4x4x1/4 HSS 4x4x 3/8 SLOPE SLAB 3S4.0 1 11 1 1 1S4.0 5S4.0 RE: ARCH 6S4.0 W21x44BP6 W21x44 BP6MO M E N T F R A M E 1S4.2 (2 ) 1 3 / 4 " x 9 1 / 2 " L V L (2)1 3/4"x9 1/2" LVL T/WALL98'-10" T/WALL98'-10" T/WALL100'-0" T/WALL 100'-0" T/LEDGE98'-10" A2 A2 7S4.0 T/CONC 100'-0" 0'-6" T/SHEATHING 100'-0" 1 3 1/2" HSS4x4x5/16BP4 T/SHEATHING100'-0" EXISTING A2 A2 A2 A2 8S4.0 T/SLAB100'-0" #5 @ 9 " O C #5@9"OC 8" CONC SLAB A 10 ' -9" HD1 HD1 1S4.1 (2)1 3/4"x11 7/8" LVL A2 2S4.1 LEDGE 2 1/2" 1 W8D (2)1 3/4"x11 7/8" LVL T/WALL 100'-0" (2 ) 1 3 / 4 " x 1 1 7 / 8 " L V L T/WALL102'-5 1/4" 8S4.1 6" (4)2x6 DFL No2 9S4.2 3" HSS 4x4x1/4 2 HSS4x4x5/16EBP2 T/SLAB 99'-3"T/SLAB 99'-9" 10S4.2 10S4.2 A 18'-0"HD1 HD1 12S4.2 BOTTOM BO T T O M 6" 14S4.2 9S4.0 15S4.2 15S4.2 2S4.3 3S4.3 4S4.3 8S4.3 9S4.3 T/SLAB 95'-5" HSS4x4x1/4 EBP2 (2)1 3/4"x14" LVL (2)1 3/4"x14" LVL 3 (E) W10x22 99'-9 3/4"(E) W10x22 99'-9 3/4"?(E) W10x22 99'-9 3/4" 10K W12x19 99'-11 1/4" 10K 6K W12x19 99'-11 1/4" 8K38K W12 x 4 5 99'-11 1/4" 12K 19K W12 x 3 5 99'-11 1/4" 8K (E ) W 1 2 x 2 6 99'-11 1/4" 15KW14x2699'-11 1/4"24K 12KW12x35 98'-10" 14K 9KW12x19 98'-10" 8K 5K W10 x 2 2 99'-6 3/4" 5K 15K W10 x 2 2 99'-3" 15K 6K W10 x 2 2 99'-3" 6K 16K W1 6 x 3 1 99'-9 3/4" 20K HSS4x4x1/4 102'-7 3/4"HSS4x4x1/4 102'-7 3/4"HSS4x4x1/4102'-7 3/4" (E)Pip e3XXS (E)Pipe3X XS 4'-3 1/4" 5S4.0 (2)1 3/4"x11 7/8" LVL 7S4.3 3 3/4" 6 1/4" 2 1/4" 4'-8 1/8" 2 3/4" 1'-10 1/4" T/CONC99'-9 3/4" 11S4.312S4.3 11'-10 1/4"13'-0 3/4" 6 1/4" 4 10S4.3 10S4.3 4 14 T J I 2 1 0 @ 1 6 " O C 13S4.3 (2) 1 3 / 4 " x 1 4 " L V L 14 TJI 210@16"OC 9'-5" 8'-9" 3 1/2" HSS 4x4x 3/8 T/CMU99'-9 3/4" H2 H1 H2 H2 H3 H3 H4 H10 H10 H10 H12 H12H10 H10 6"9 1 / 2 " T J I 2 1 0 @ 1 6 " O C T/CONC 99'-3 3/4" H4 H4 T/CONC 99'-9 3/4" 6" T/CONC99'-3 3/4" (2 ) 1 3 / 4 " x 1 4 " L V L T/SHEATHING 99'-6" 1 1 (2)1 3/4"x14" LVL 5 H13 H13 6K W12x22 6K 1 3/4"x11 7/8" LVL@16"OC H9 H9 H9 1 3/4"x11 7/8" LVL@16"OC (2 ) 1 3 / 4 " x 1 6 " L V L (2)1 3/4"x16" LVL (E) 12" TJI/35@12"OC 1 3/4"x9 1/2" LVL@16"OC H13 1 1. TYPICAL NEW FLOOR IS ARCHITECTURAL FINISHES OVER 3/4" T&G OSB/PLYWOOD FLOOR SHEATHING OVER WOOD FRAMING. TYPICAL FLOOR SHEATHING ATTACHMENT IS GLUE AND NAIL WITH 8d@6"OCOC AT EDGES AND @12"OC IN FIELD, UNO2. GARAGE FLOOR IS A 3" TOPPING SLAB W/ #3@9"OC EA WAY, OVER TAPERED COMPOSITE SLAB CONSTRUCTION, VARIABLE THICKNESS CONCRETE OVER 3"x16 GA COMPOSITE GALVANIZED DECK, REINFORCED W/ WWF6x6x2.1x2.1, UNO. 3. TYPICAL EXTERIOR WALL IS 1/2" OSB/PLYWOOD WALL SHEATHING ON 2x6 DFL STUD@16"OC, UNO. ATTACH WALL MAIN LEVEL PLAN NOTES: Golden ● Loveland ● Roaring Fork ● Buffalo, WY KL A, Inc.&Structural Engineers and Builders215 North 12th Street, Unit ECarbondale, Colorado 81623P: (970) 927 5174 rowland+broughton architecture / urban design / interior design 234 e hopkins ave.aspen, co 81611970.544.9006 o970.544.3473 f 1830 blake st, ste 200denver, co 80202303.308.1373 o303.308.1375 f Consultants: Issue: PROJECT NO: 11 MAY 2018DESIGN DEVELOPMENT Revision: 2 AUGUST 2018 CONSTRUCTION 5 FEBRUARY 2019 CONSTRUCTION 18 APRIL 2019 CONSTRUCTION DOCUMENTS B0551.000 MOUNTAIN FORGE RENOVATION AND ADDITION 230-234 E. HOPKINS AVENUE ASPEN, CO 81611 KEYED NOTES PLAN # DESCRIPTION 1 (E) COL TO BE REPLACED W/ STEEL HSS COLUMN2 ADDITIONAL FOOTING MAY BE REQUIRED DEPENDING ON SIZE OF(E) FOOTING 3 6" FULLY GROUTED CMU REINF W/ #4 @ 32" OC VERT & #4 @32" OC HORIZ 4 STEEL PLANTER BOX 5 1¾x9½" LVL @ 16" OC 3/16" = 1'-0"1 LEVEL ONE FLOOR FRAMING PLAN N TYP 1 08 MARCH 19ASI-001 04/15/2019 Revise structure sothat the mechanicalroom fire barrier wallsare continuous to thefloor sheathing withoutpenetration by anystructure. 2015 IBC707.5 Page: 14 File Name: 230 E. Hopkins_Drawings_Structural_2019-04-18.pdf Subject: Group Author: nickt Color: Provide a structural section and an architectural section at this location to demonstrate that the fire barriers for the exit enclosure are continuous to the underside of floor sheathing above without structural interruption. 2015 IBC 707 Page: 1 File Name: 230 E. Hopkins_RREMP_2019-04-16.pdf Subject: PlanCheck Author: nickt Color: Revise so that A1.2 and the REMP worksheet show the same thing. 230 E. Hopkins_RREMP_2019-04-16.pdf (3) Page: 1 File Name: 230 E. Hopkins_RREMP_2019-04-16.pdf Subject: PlanCheck Author: nickt Color: The latest spec submitted shows a CEC listed Flash hot tub which is exempt from REMP. Put the square footage in the New (exempt) row. Page: 1 File Name: 230 E. Hopkins_RREMP_2019-04-16.pdf Subject: PlanCheck Author: nickt Color: Fill out all of section 1 of the REMP worksheet. Page: 1 File Name: COMCHECK.pdf Subject: PlanCheck Author: nickt Color: Provide a lighting schedule and cutsheets for each fixture. The cutsheets should have the maximum wattage highlighted (and this should match the comcheck) and the listing by a nationally recognized testing lab highlighted. COMCHECK.pdf (7) 7 GBCDEF 3 4 5 6 60'-0" 5'-5 3/8" 15'-0 3/4" 6'-7 1/4" 8'-1 3/8" /4" 100'-0" 18'-8"5'-8 1/8"26'-4 3/4"14'-8 1/2"24'-1 3/8" x3 1 (E) 5.125x12 GLB(E) 5.125x12 GLB(E) 5.125x12 GLB(E) 8.75x18 GLB T/SHEATHING 111'-1 3/8" "x1 4 " L V L 14 " T J I 3 6 0 @ 1 6 " O C (2 ) 1 3 / 4 " x 1 4 " L V L H SS 4x4 x1/4 9 1/2 TJI 210@16"OC (E) 2x6@16"OC (E) 2x6@16"OC (E) 10" TJI@16"OC 9 1/2 TJI 210@16"OC (E) 10" TJI/35@16"OC H SS 4x4 x5 /1 6 HS S 4x 4x 1/4 MO M E N T F R A M E 1 H SS 4x4 x5 /1 6 W18 x 3 5 7/8 TJI 210@16"OC (2)1 3/4"x9 1/2" LVL (2 ) 1 3 / 4 " x 9 1 / 2 " L V L T/SHEATHING 111'-1 3/8" EXISTING HING /8" A 12 ' -4" HD1 HD1 A 10 ' -9" HD1 HD 1 A3 4S4.1 5S4.1 6S4.1 (2)1 3/4"x14" LVL (E) W18x65 HS S4x4x1/4 H SS 4x4 x1/4 6S4.2 6" 44 K W1 4 x 6 1 49K (E) W18x65 12K )1 3/4"x11 7/8" LVL 47K W14 x 6 1 27 K 2 2S4.22S4.2 6'-0 3/4" 9 1/2 TJI 210@16"OC 1 3/4"x9 1/2" LVL@16"OC AT FIREPLACE A2 R (E ) 1 2 " T J I / 3 5 @ 1 2 " O C HD1A18'-0" 15S4.2 16S4.3 15S4.2 1S4.3 6S4.3 3 8K W14 x 2 6 110'-11 1/8" 26K 11KW12x26 110'-11 7/8" 5K 6K W8x15 111'-0 5/8" 6K6KW8x15 111'-0 5/8" 6K 6K W8x15 110'-5 7/8" 6K 6K W8x15 110'-5 7/8" 6K HS S4x 4x1/4 (2)1 3/4"x11 7/8" LVL (3 ) 1 3 / 4 " x 1 1 7 / 8 " L V L 11 7 / 8 " T J I 2 1 0 @ 1 6 " O C 16S4.3 (2)1 3/4"x11 7/8" LVL (E) 5.125x15 GLB H4 H4 H3 H3 H2 H2 H3 H4 H10 H10 H10 H12 H12 H12 H12 (2 ) 1 3 / 4 " x 1 8 " L V L x1 / 4 ro arc 23 asp 97 97 Co Iss 11 DE Re 2 CO 5 CO 18 CO 1 08 AS Provide a structuralsection and anarchitectural section atthis location todemonstrate that thefire barriers for the exitenclosure arecontinuous to theunderside of floorsheathing abovewithout structural interruption. 2015 IBC 707 CONTACT INFORMATION : Owner: Name:City: Address:State: Email:Zip Code: Phone: Cell Phone: Owner's Representative : Name:City: Address:State: Email:Zip Code: Phone: Cell Phone: ` A.RESIDENTIAL RENEWABLE ENERGY MITIGATION PROGRAM Sheets showing snowmelt, pool, spa, and solar/GSHP information: Do you have snowmelt or a spa that has been exempted by the buiding official? Hydro Snowmelt Electric Snowmelt Pool Spa Existing To be Demoed Existing to Remain 0.00 sqft 0.00 sqft 0.00 sqft 0.00 sqft New (non-exempt)1031.00 sqft 135.00 sqft 49.00 sqft New (exempt) Total New 1031.00 sqft 0.00 sqft 135.00 sqft 49.00 sqft Total on site 1031.00 sqft 0.00 sqft 135.00 sqft 49.00 sqft Total Snowmelt on site Boiler Efficiency 98.0%100%98.0% 98.0% Mitigation Payment 18,734.69$ 8,800.00$ Total Payment for Mitigation:63,304.08$ B.ON-SITE RENEWABLE CREDITS Supplemental System REMP Credit Use PV Worksheet Photovoltaic System -$ Use Thermal Worksheet Hot Water Panels -$ Use GSHP Cert Ground Source Heat Pump -$ Other Approved System -$ Total Mitigation Credits:-$ Onsite Renewable Offsets: How many KiloWatts of PV (solar electric) would I need? 9.22 or How many square feet of SHW (solar hot water) would I need? 281.79 R-REMP Payment:63,304.08$ Amount Previously Paid on This Permit: 63,304.08$ Refund (includes minus $750): -$ C. PREPARED BY:Date: 4/16/2019 Print Name: Signature: Phone & EMail: REVIEWED:Date: dana@rowlandbroughton.com 970-748-8520 , TOTAL R-REMP PAYMENT: Dana Ellis 1031.00 sqft David Denio, PE A1.2, M-122, M-123, M-602 970-544-9006 $35,769.39 Yes (enter sqft below on the exempt row)No Revise so that A1.2 and the REMP worksheet show the same thing. PROJECT ADDRESS: Parcel ID #: Permit Number: CONTACT INFORMATION : Owner:Name:City: Address:State: Email:Zip Code: Phone: Cell Phone: Owner's Representative : Name:City: Address:State: Email:Zip Code: Phone: Cell Phone:` A.RESIDENTIAL RENEWABLE ENERGY MITIGATION PROGRAM Sheets showing snowmelt, pool, spa, and solar/GSHP information: Do you have snowmelt or a spa that has been exempted by the buiding official? Hydro Snowmelt Electric Snowmelt Pool SpaExistingTo be DemoedExisting to Remain 0.00 sqft 0.00 sqft 0.00 sqft 0.00 sqft New (non-exempt)1031.00 sqft 135.00 sqft 49.00 sqftNew (exempt)Total New 1031.00 sqft 0.00 sqft 135.00 sqft 49.00 sqftTotal on site 1031.00 sqft 0.00 sqft 135.00 sqft 49.00 sqft Total Snowmelt on siteBoiler Efficiency 98.0%100%98.0% 98.0%Mitigation Payment 18,734.69$ 8,800.00$ Total Payment for Mitigation:63,304.08$ B.ON-SITE RENEWABLE CREDITS Supplemental System REMP CreditUse PV WorksheetPhotovoltaic System -$ Use Thermal WorksheetHot Water Panels -$ Use GSHP CertGround Source Heat Pump -$ Other Approved System -$ Total Mitigation Credits:-$ Onsite Renewable Offsets: How many KiloWatts of PV (solar electric) would I need? 9.22 or How many square feet of SHW (solar hot water) would I need? 281.79 R-REMP Payment:63,304.08$ Amount Previously Paid on This Permit:63,304.08$ Refund (includes minus $750): -$ C. PREPARED BY:Date: 4/16/2019 Print Name: Signature: Phone & EMail: REVIEWED:Date: 2015 IECC RESIDENTIAL RENEWABLE ENERGY MITIGATION PROGRAM CITY OF ASPEN VERSION 11.3 UPDATED DECEMBER 13, 2017 dana@rowlandbroughton.com 970-748-8520 , TOTAL R-REMP PAYMENT: Dana Ellis 1031.00 sqft David Denio, PE A1.2, M-122, M-123, M-602 970-544-9006 $35,769.39 Yes (enter sqft below on the exempt row)No The latest spec submitted shows a CEC listed Flash hottub which is exempt from REMP. Put the square footage in the New (exempt) row. PROJECT ADDRESS: Parcel ID #: Permit Number: CONTACT INFORMATION :Owner:Name:City: Address:State: Email:Zip Code: Phone: Cell Phone: Owner's Representative : Name:City: Address:State: Email:Zip Code: Phone: Cell Phone:` A.RESIDENTIAL RENEWABLE ENERGY MITIGATION PROGRAMSheets showing snowmelt, pool, spa, and solar/GSHP information: Do you have snowmelt or a spa that has been exempted by the buiding official? Hydro Snowmelt Electric Snowmelt Pool SpaExistingTo be DemoedExisting to Remain 0.00 sqft 0.00 sqft 0.00 sqft 0.00 sqftNew (non-exempt)1031.00 sqft 135.00 sqft 49.00 sqftNew (exempt)Total New 1031.00 sqft 0.00 sqft 135.00 sqft 49.00 sqftTotal on site 1031.00 sqft 0.00 sqft 135.00 sqft 49.00 sqftTotal Snowmelt on siteBoiler Efficiency 98.0%100%98.0% 98.0%Mitigation Payment 18,734.69$ 8,800.00$ Total Payment for Mitigation:63,304.08$ B.ON-SITE RENEWABLE CREDITS Supplemental System REMP CreditUse PV WorksheetPhotovoltaic System -$ Use Thermal WorksheetHot Water Panels -$ Use GSHP CertGround Source Heat Pump -$ Other Approved System -$ Total Mitigation Credits:-$ Onsite Renewable Offsets: How many KiloWatts of PV (solar electric) would I need? 9.22 or How many square feet of SHW (solar hot water) would I need? 281.79 R-REMP Payment:63,304.08$ Amount Previously Paid on This Permit:63,304.08$ Refund (includes minus $750): -$ C. PREPARED BY:Date: 4/16/2019 Print Name: Signature: Phone & EMail: REVIEWED:Date: 2015 IECC RESIDENTIAL RENEWABLE ENERGY MITIGATION PROGRAM CITY OF ASPEN VERSION 11.3 UPDATED DECEMBER 13, 2017 dana@rowlandbroughton.com 970-748-8520 , TOTAL R-REMP PAYMENT: Dana Ellis 1031.00 sqft David Denio, PE A1.2, M-122, M-123, M-602 970-544-9006 $35,769.39 Yes (enter sqft below on the exempt row)No Fill out all of section 1 of the REMP worksheet. 1-COMMON AREAS (Common Space Types:Corridor/Transition <8 ft wide)2060 0.66 1360 1360Total Allowed Watts = Proposed Interior Lighting Power E (C X D) D Fixture Watt. A Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast B Lamps/ Fixture C # of Fixtures COMMON AREAS ( Common Space Types:Corridor/Transition <8 ft wide 2060 sq.ft.) LED 1: R3 & R4: DOWNLIGHT: Other:1 53 13 689 LED 2: P2: PENDENT AT BATHROOM: Other:1 2 13 26 LED 3: P3: PENDENT AT BATHROOM: Other:1 2 15 30 LED 4: F2: LED STRIP AT UTILITY: Other:1 5 32 160 905Total Proposed Watts = Interior Lighting Compliance Statement Compliance Statement: The proposed interior lighting alteration project represented in this document is consistent with the building plans, specifications, and other calculations submitted with this permit application. The proposed interior lighting systems have been designed to meet the 90.1 (2013) Standard requirements in COMcheck Version 4.0.8.0 and to comply with any applicable mandatory requirements listed in the Inspection Checklist. Name - Title Signature Date Interior Lighting PASSES Project Title: Data filename: MOUNTAIN FORGE REMODEL P:\Current Projects\18009.00 - Mountain Forge Building Renovation & Addition\Calculations\COMcheck\MOUNTAIN FORGE LTG COMCHECK.cck 07/30/18Report date: 71 ofPage STANTON HUMPHRIES, PE 7/30/18 Provide a lighting schedule and cutsheets for each fixture. The cutsheets should have the maximum wattage highlighted (and this should match the comcheck) and the listing by a nationally recognized testing lab highlighted. Page: 1 File Name: COMCHECK.pdf Subject: PlanCheck Author: nickt Color: I have not received a new comcheck so am including my old comments from the last round. Page: 1 File Name: COMCHECK.pdf Subject: PlanCheck Author: nickt Color: Include the S2 and S6 fixtures from the common restrooms. Page: 1 File Name: COMCHECK.pdf Subject: PlanCheck Author: nickt Color: Provide a lighting comcheck for the commercial units. Page: 1 File Name: COMCHECK.pdf Subject: PlanCheck Author: nickt Color: I count 51 R3 and R4 fixtures in the common areas. Revise comcheck. Page: 2 File Name: COMCHECK.pdf Subject: PlanCheck Author: nickt Color: I count 11 EX3 fixtures. Revise comcheck. COMcheck Software Version 4.0.8.0 Interior Lighting Compliance Certificate Project Title: 90.1 (2013) Standard Project Type:Alteration Construction Site:200-234 E. HOPKINSASPEN, CO 81611 Owner/Agent:Designer/Contractor:Stanton HumphriesAECAvon, CO970-748-8520stan@aec-vail.com Project Information Energy Code: MOUNTAIN FORGE REMODEL Allowed Interior Lighting Power A Area Category B Floor Area (ft2) C Allowed Watts / ft2 D Allowed Watts (B X C) 1-COMMON AREAS (Common Space Types:Corridor/Transition <8 ft wide)2060 0.66 1360 1360Total Allowed Watts = Proposed Interior Lighting Power E (C X D) D Fixture Watt. A Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast B Lamps/ Fixture C # of Fixtures COMMON AREAS ( Common Space Types:Corridor/Transition <8 ft wide 2060 sq.ft.) LED 1: R3 & R4: DOWNLIGHT: Other:1 53 13 689 LED 2: P2: PENDENT AT BATHROOM: Other:1 2 13 26 LED 3: P3: PENDENT AT BATHROOM: Other:1 2 15 30 LED 4: F2: LED STRIP AT UTILITY: Other:1 5 32 160 905Total Proposed Watts = Interior Lighting Compliance Statement Interior Lighting PASSES I have not received a new comcheck so am including my old comments from the last round. Project Title: 90.1 (2013) Standard Project Type:Alteration Construction Site: 200-234 E. HOPKINS ASPEN, CO 81611 Owner/Agent:Designer/Contractor: Stanton Humphries AECAvon, CO970-748-8520 stan@aec-vail.com Project Information Energy Code: MOUNTAIN FORGE REMODEL Allowed Interior Lighting Power A Area Category B Floor Area (ft2) C Allowed Watts / ft2 D Allowed Watts (B X C) 1-COMMON AREAS (Common Space Types:Corridor/Transition <8 ft wide)2060 0.66 1360 1360Total Allowed Watts = Proposed Interior Lighting Power E (C X D) D Fixture Watt. A Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast B Lamps/ Fixture C # of Fixtures COMMON AREAS ( Common Space Types:Corridor/Transition <8 ft wide 2060 sq.ft.) LED 1: R3 & R4: DOWNLIGHT: Other:1 53 13 689 LED 2: P2: PENDENT AT BATHROOM: Other:1 2 13 26 LED 3: P3: PENDENT AT BATHROOM: Other:1 2 15 30 LED 4: F2: LED STRIP AT UTILITY: Other:1 5 32 160 905Total Proposed Watts = Interior Lighting Compliance Statement Compliance Statement: The proposed interior lighting alteration project represented in this document is consistent with the building plans, specifications, and other calculations submitted with this permit application. The proposed interior lightingsystems have been designed to meet the 90.1 (2013) Standard requirements in COMcheck Version 4.0.8.0 and to comply withany applicable mandatory requirements listed in the Inspection Checklist. Name - Title Signature Date Interior Lighting PASSES Project Title: Data filename: MOUNTAIN FORGE REMODEL P:\Current Projects\18009.00 - Mountain Forge Building Renovation &Addition\Calculations\COMcheck\MOUNTAIN FORGE LTG COMCHECK.cck 07/30/18Report date: 71 ofPage STANTON HUMPHRIES, PE 7/30/18 Include the S2 and S6 fixtures from the common restrooms. heck Software Version 4.0.8.0 ior Lighting Compliance Certificate 90.1 (2013) Standard Alteration Owner/Agent:Designer/Contractor: Stanton Humphries AEC Avon, CO 970-748-8520 stan@aec-vail.com MOUNTAIN FORGE REMODEL Power A Area Category B Floor Area (ft2) C Allowed Watts / ft2 D Allowed Watts (B X C) pace Types:Corridor/Transition <8 ft wide)2060 0.66 1360 Provide a lighting comcheck for the commercial units. COMcheck Software Version 4.0.8.0 Interior Lighting Compliance Certificate Project Title: 90.1 (2013) Standard Project Type:Alteration Construction Site: 200-234 E. HOPKINS ASPEN, CO 81611 Owner/Agent:Designer/Contractor: Stanton Humphries AEC Avon, CO 970-748-8520 stan@aec-vail.com Project Information Energy Code: MOUNTAIN FORGE REMODEL Allowed Interior Lighting Power A Area Category B Floor Area (ft2) C Allowed Watts / ft2 D Allowed Watts (B X C) 1-COMMON AREAS (Common Space Types:Corridor/Transition <8 ft wide)2060 0.66 1360 1360Total Allowed Watts = Proposed Interior Lighting Power E (C X D) D Fixture Watt. A Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast B Lamps/ Fixture C # of Fixtures COMMON AREAS ( Common Space Types:Corridor/Transition <8 ft wide 2060 sq.ft.) LED 1: R3 & R4: DOWNLIGHT: Other:1 53 13 689 LED 2: P2: PENDENT AT BATHROOM: Other:1 2 13 26 LED 3: P3: PENDENT AT BATHROOM: Other:1 2 15 30 LED 4: F2: LED STRIP AT UTILITY: Other:1 5 32 160 905Total Proposed Watts = Interior Lighting Compliance Statement Compliance Statement: The proposed interior lighting alteration project represented in this document is consistent with the building plans, specifications, and other calculations submitted with this permit application. The proposed interior lighting systems have been designed to meet the 90.1 (2013) Standard requirements in COMcheck Version 4.0.8.0 and to comply with any applicable mandatory requirements listed in the Inspection Checklist. Name - Title Signature Date Interior Lighting PASSES STANTON HUMPHRIES, PE 7/30/18 I count 51 R3 and R4 fixtures in the common areas. Revise comcheck. Exterior Lighting Compliance Certificate Project Title: 90.1 (2013) Standard Project Type:Alteration Construction Site:200-234 E. HOPKINSASPEN, CO 81611 Owner/Agent:Designer/Contractor:Stanton HumphriesAEC Avon, CO970-748-8520stan@aec-vail.com Project Information Energy Code: MOUNTAIN FORGE REMODEL 2 (Residential mixed use area)Exterior Lighting Zone Allowed Exterior Lighting Power A Area/Surface Category B Quantity C Allowed Watts / Unit D Tradable Wattage E Allowed Watts (B X C) LOWER LEVEL (Entry canopy)300 ft2 0.25 Yes 75 MAIN LEVEL (Entry canopy)600 ft2 0.25 Yes 150 Total Tradable Watts (a) = Total Allowed Watts = Total Allowed Supplemental Watts (b) = 225 225 600 (a)Wattage tradeoffs are only allowed between tradable areas/surfaces. (b)A supplemental allowance equal to 600 watts may be applied toward compliance of both non-tradable and tradable areas/surfaces. Proposed Exterior Lighting Power E (C X D) D Fixture Watt. A Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast B Lamps/ Fixture C # of Fixtures LOWER LEVEL ( Entry canopy 300 ft2): Tradable Wattage LED 1: EX3: DOWNLIGHT: Other:1 2 23 46 LED 2: EX1: STEPLIGHT: Other:1 2 4 8 LED 3: EX5: SCONCE: Other:1 2 11 22 MAIN LEVEL ( Entry canopy 600 ft2): Tradable Wattage LED 4: EX1: STEPLIGHT: Other:1 6 4 23 LED 5: EX3: DOWNLIGHT: Other:1 9 23 207 LED 6: EX4: SCONCE: Other:1 3 15 45 LED 7: EX2: SCONCE: Other:1 5 11 55 LED 8: EX6: ACCENT: Other:1 2 9 17 423Total Tradable Proposed Watts = Project Title: Data filename: MOUNTAIN FORGE REMODEL P:\Current Projects\18009.00 - Mountain Forge Building Renovation &Addition\Calculations\COMcheck\MOUNTAIN FORGE LTG COMCHECK.cck 07/30/18Report date: 72 ofPage I count 11 EX3 fixtures. Revise comcheck. Page: 2 File Name: COMCHECK.pdf Subject: PlanCheck Author: nickt Color: I count 4 EX4 fixtures. Revise comcheck. Page: 1 File Name: CREMP.pdf Subject: PlanCheck Author: nickt Color: Fill out all of section 1 of the REMP worksheet. CREMP.pdf (2) Page: 1 File Name: CREMP.pdf Subject: PlanCheck Author: nickt Color: Revise so that A1.2 and the REMP worksheet show the same thing. Project Title: 90.1 (2013) Standard Project Type:Alteration Construction Site:200-234 E. HOPKINSASPEN, CO 81611 Owner/Agent:Designer/Contractor:Stanton HumphriesAEC Avon, CO970-748-8520stan@aec-vail.com Project Information Energy Code: MOUNTAIN FORGE REMODEL 2 (Residential mixed use area)Exterior Lighting Zone Allowed Exterior Lighting Power A Area/Surface Category B Quantity C AllowedWatts / Unit D TradableWattage E Allowed Watts(B X C) LOWER LEVEL (Entry canopy)300 ft2 0.25 Yes 75 MAIN LEVEL (Entry canopy)600 ft2 0.25 Yes 150 Total Tradable Watts (a) = Total Allowed Watts = Total Allowed Supplemental Watts (b) = 225 225 600 (a)Wattage tradeoffs are only allowed between tradable areas/surfaces. (b)A supplemental allowance equal to 600 watts may be applied toward compliance of both non-tradable and tradable areas/surfaces. Proposed Exterior Lighting Power E(C X D)DFixture Watt. A Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast BLamps/ Fixture C# of Fixtures LOWER LEVEL ( Entry canopy 300 ft2): Tradable Wattage LED 1: EX3: DOWNLIGHT: Other:1 2 23 46 LED 2: EX1: STEPLIGHT: Other:1 2 4 8 LED 3: EX5: SCONCE: Other:1 2 11 22 MAIN LEVEL ( Entry canopy 600 ft2): Tradable Wattage LED 4: EX1: STEPLIGHT: Other:1 6 4 23 LED 5: EX3: DOWNLIGHT: Other:1 9 23 207 LED 6: EX4: SCONCE: Other:1 3 15 45 LED 7: EX2: SCONCE: Other:1 5 11 55 LED 8: EX6: ACCENT: Other:1 2 9 17 423Total Tradable Proposed Watts = Project Title: Data filename: MOUNTAIN FORGE REMODEL P:\Current Projects\18009.00 - Mountain Forge Building Renovation &Addition\Calculations\COMcheck\MOUNTAIN FORGE LTG COMCHECK.cck 07/30/18Report date: 72 ofPage I count 4 EX4 fixtures. Revise comcheck. PROJECT ADDRESS: Parcel ID #: Permit Number: CONTACT INFORMATION :Owner:Name:City: Address:State: Email:Zip Code: Phone: Cell Phone: Owner's Representative : Name:City: Address:State: Email:Zip Code: Phone: Cell Phone: A.COMMERCIAL RENEWABLE ENERGY MITIGATION PROGRAMSheets showing snowmelt, pool, spa, and solar/GSHP information: Do you have snowmelt or a spa that has been exempted by the buiding official? Hydro Snowmelt Electric Snowmelt Pool SpaExistingTo be DemoedExisting to Remain 0.00 sqft 0.00 sqft 0.00 sqft 0.00 sqftNew (non-exempt)798.00 sqftNew (exempt)111.00 sqftTotal New 909.00 sqft 0.00 sqft 0.00 sqft 0.00 sqftTotal on site 909.00 sqft 0.00 sqft 0.00 sqft 0.00 sqftTotal Snowmelt on siteBoiler Efficiency 95.0%100%75.0% 75.0%Mitigation Payment -$ -$ Total Payment for Mitigation:$50,400.00B.ON-SITE RENEWABLE CREDITS Supplemental System REMP CreditUse PV WorksheetPhotovoltaic System -$ Use Thermal WorksheetHot Water Panels -$ Use GSHP CertGround Source Heat Pump -$ Other Approved System -$ Total Mitigation Credits:-$ Onsite Renewable Offsets: How many KiloWatts of PV (solar electric) would I need? 7.34or How many square feet of SHW (solar hot water) would I need? 224.35 C-REMP Payment:50,400.00$ Amount Previously Paid on This Permit:-$ 50,400.00$ Refund (includes minus $750): -$ C. PREPARED BY:Date: 7/30/2018 Print Name: Signature: Phone & EMail: REVIEWED:Date: David Denio, PE $50,400.00 A1.2, M-120, M-121, M-602 970-748-8520, david@aec-vail.com Dana Ellis 970-544-9006 TOTAL C-REMP PAYMENT: dana@rowlandbroughton.com 909.00 sqft 2015 IECC COMMERCIAL RENEWABLE ENERGY MITIGATION PROGRAM CITY OF ASPEN VERSION 11.3 UPDATED DECEMBER 13, 2017 Mountain Forge Yes (enter sqft below on the exempt row)No Fill out all of section 1of the REMPworksheet. CONTACT INFORMATION : Owner: Name:City: Address:State: Email:Zip Code: Phone: Cell Phone: Owner's Representative : Name:City: Address:State: Email:Zip Code: Phone: Cell Phone: A.COMMERCIAL RENEWABLE ENERGY MITIGATION PROGRAM Sheets showing snowmelt, pool, spa, and solar/GSHP information: Do you have snowmelt or a spa that has been exempted by the buiding official? Hydro Snowmelt Electric Snowmelt Pool Spa Existing To be DemoedExisting to Remain 0.00 sqft 0.00 sqft 0.00 sqft 0.00 sqft New (non-exempt)798.00 sqft New (exempt)111.00 sqft Total New 909.00 sqft 0.00 sqft 0.00 sqft 0.00 sqft Total on site 909.00 sqft 0.00 sqft 0.00 sqft 0.00 sqft Total Snowmelt on siteBoiler Efficiency 95.0%100%75.0% 75.0% Mitigation Payment -$ -$ Total Payment for Mitigation:$50,400.00 B.ON-SITE RENEWABLE CREDITS Supplemental System REMP Credit Use PV Worksheet Photovoltaic System -$ Use Thermal Worksheet Hot Water Panels -$ Use GSHP Cert Ground Source Heat Pump -$ Other Approved System -$ Total Mitigation Credits:-$ Onsite Renewable Offsets: How many KiloWatts of PV (solar electric) would I need? 7.34 or How many square feet of SHW (solar hot water) would I need? 224.35 C-REMP Payment:50,400.00$ Amount Previously Paid on This Permit:-$ 50,400.00$ Refund (includes minus $750): -$ C. PREPARED BY:Date: 7/30/2018 Print Name: Signature: Phone & EMail: REVIEWED:Date: David Denio, PE $50,400.00 A1.2, M-120, M-121, M-602 970-748-8520, david@aec-vail.com Dana Ellis 970-544-9006 TOTAL C-REMP PAYMENT: dana@rowlandbroughton.com 909.00 sqft Yes (enter sqft below on the exempt row)No Revise so that A1.2 and the REMP worksheet show the same thing.