HomeMy WebLinkAboutFile Documents.230 E Hopkins Ave.0089.2018 (4).ACBK0089-2018-ACBK_BuildingComments_3_Markup Summary
File Name: 230 E. Hopkins_ComCheck-Comm
Units_2019-07-26.pdf
Subject: PlanCheck
Author: nickt
Color:
Page Label: 1
Page Index: 1
Which P light is this in the
cutsheet package? If P1, the
fixture must be labeled by the
manufacturer with a maximum
wattage matching the comcheck.
Note this on Comcheck or
provide a cutsheet with max
fixture wattage.
230 E. Hopkins_ComCheck-Comm Units_2019-07-26.pdf (3)
File Name: 230 E. Hopkins_ComCheck-Comm
Units_2019-07-26.pdf
Subject: PlanCheck
Author: nickt
Color:
Page Label: 1
Page Index: 1
P3 fixture must be labeled by the
manufacturer with a maximum
wattage matching the comcheck.
Note this on Comcheck or
provide a cutsheet with max
fixture wattage.
File Name: 230 E. Hopkins_ComCheck-Comm
Units_2019-07-26.pdf
Subject: PlanCheck
Author: nickt
Color:
Page Label: 3
Page Index: 3
Fill out owner/agent
File Name: 230 E.
Hopkins_ComCheck-CommonAreas_2019-08-26.pdf
Subject: PlanCheck
Author: nickt
Color:
Page Label: 1
Page Index: 1
S6 cut sheet lists wattage as 2 x
40 = 80.
230 E. Hopkins_ComCheck-CommonAreas_2019-08-26.pdf (2)
File Name: 230 E.
Hopkins_ComCheck-CommonAreas_2019-08-26.pdf
Subject: PlanCheck
Author: nickt
Color:
Page Label: 2
Page Index: 2
Fill out owner/agent
4107Total Allowed Watts =
Proposed Interior Lighting Power
E
(C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
#2 COMMERCIAL UNIT ( Common Space Types:Office - Enclosed 322 sq.ft.)
LED 9: R3: DOWNLIGHT: Other:1 3 12 36
LED 10: TR1 & TR2: TRACK LIGHT: Other:1 12 15 180
#3 COMMERCIAL UNIT ( Common Space Types:Office - Enclosed 655 sq.ft.)
LED 11: R3: DOWNLIGHT: Other:1 13 12 156
LED 12: P: PENDANTS: Other:1 3 20 60
#4 COMMERCIAL UNIT ( Common Space Types:Office - Enclosed 1585 sq.ft.)
LED 1: R3 & R4: DOWNLIGHT: Other:1 22 12 264
LED 2: P2: PENDENT AT BATHROOM: Other:1 4 60 240
LED 3: P3: PENDENT AT BATHROOM: Other:1 1 15 15
LED 4: T1: LED STRIP AT UTILITY: Other:1 1 32 32
LED 5: S2: SCONCE: Other:1 2 9 18
LED 5 copy 1: S3: SCONCE: Other:1 3 60 180
LED 6: TR1 &TR2: TRACK: Other:1 4 15 60
LED 7: C1: PENDANT AT POOL TABLE: Other:1 1 45 45
#5 COMMERCIAL ( Common Space Types:Office - Enclosed 133 sq.ft.)
LED 18: T1: LED STRIP: Other:1 2 32 64
Project Title:
Data filename:
MOUNTAIN FORGE TENANT FINISH
P:\Current Projects\18009.00 - Mountain Forge Building Renovation &
Addition\Calculations\COMcheck\MOUNTAIN FORGE TI LTG COMCHECK.cck
07/11/19Report date:
71 ofPage
Which P light is this in
the cutsheet package?
If P1, the fixture must
be labeled by the
manufacturer with a
maximum wattage
matching the
comcheck. Note this
on Comcheck or
provide a cutsheet
with max fixture
wattage.
#2 COMMERCIAL UNIT ( Common Space Types:Office - Enclosed 322 sq.ft.)
LED 9: R3: DOWNLIGHT: Other:
LED 10: TR1 & TR2: TRACK LIGHT: Other:
#3 COMMERCIAL UNIT ( Common Space Types:Office - Enclosed 655 sq.ft.)
LED 11: R3: DOWNLIGHT: Other:
LED 12: P: PENDANTS: Other:
#4 COMMERCIAL UNIT ( Common Space Types:Office - Enclosed 1585 sq.ft.)
LED 1: R3 & R4: DOWNLIGHT: Other:
LED 2: P2: PENDENT AT BATHROOM: Other:
LED 3: P3: PENDENT AT BATHROOM: Other:
LED 4: T1: LED STRIP AT UTILITY: Other:
LED 5: S2: SCONCE: Other:
LED 5 copy 1: S3: SCONCE: Other:
LED 6: TR1 &TR2: TRACK: Other:
LED 7: C1: PENDANT AT POOL TABLE: Other:
#5 COMMERCIAL ( Common Space Types:Office - Enclosed 133 sq.ft.)
LED 18: T1: LED STRIP: Other:
Project Title:
Data filename:
MOUNTAIN FORGE TENANT FINISH
P:\Current Projects\18009.00 - Mountain Forge Building Renovation &
Addition\Calculations\COMcheck\MOUNTAIN FORGE TI LTG COMCHECK.cck
P3 fixture must be
labeled by the
manufacturer with a
maximum wattage
matching the
comcheck. Note this
on Comcheck or
provide a cutsheet
with max fixture
wattage.
COMcheck Software Version 4.1.1.0
Exterior Lighting Compliance Certificate
90.1 (2013) Standard
Alteration
Site:
HOPKINS
81611
Owner/Agent:Designer/Contractor:
Stanton Humphries
AEC
Avon, CO
970-748-8520
stan@aec-vail.com
ormation
MOUNTAIN FORGE TENANT FINISH
2 (Residential mixed use area)ng Zone
xterior Lighting Power
A
Area/Surface Category
B
Quantity
C
Allowed
Watts / Unit
D
Tradable
Wattage
E
Allowed Watts
(B X C)
Total Tradable Watts (a) =
Total Allowed Watts =
Total Allowed Supplemental Watts (b) =
0
0
600
e tradeoffs are only allowed between tradable areas/surfaces.
Fill out owner/agent
Watt.Fixture Fixtures
e Types:Corridor/Transition <8 ft wide 2060 sq.ft.)
1 56 12 666
M: Other:1 2 60 120
M: Other:1 2 15 30
ther:1 6 28 168
her:1 9 6 57
her:1 2 20 40
1081Total Proposed Watts =
tatement
ed interior lighting alteration project represented in this document is consistent with the
her calculations submitted with this permit application. The proposed interior lighting
et the 90.1 (2013) Standard requirements in COMcheck Version 4.1.1.0 and to comply with
ents listed in the Inspection Checklist.
Signature Date
EMODEL
18009.00 - Mountain Forge Building Renovation &
07/11/19Report date:
71 ofPage
S6 cut sheet lists
wattage as 2 x 40 = 80.
COMcheck Software Version 4.1.1.0
Exterior Lighting Compliance Certificate
90.1 (2013) Standard
Alteration
e:
OPKINS
1611
Owner/Agent:Designer/Contractor:
Stanton Humphries
AEC
Avon, CO
970-748-8520
stan@aec-vail.com
rmation
MOUNTAIN FORGE REMODEL
2 (Residential mixed use area) Zone
erior Lighting Power
A
Area/Surface Category
B
Quantity
C
Allowed
Watts / Unit
D
Tradable
Wattage
E
Allowed Watts
(B X C)
L (Entry canopy)300 ft2 0.25 Yes 75
Entry canopy)600 ft2 0.25 Yes 150
(Walkway >= 10 feet wide)1809 ft2 0.14 Yes 253
Total Tradable Watts (a) =478
Fill out owner/agent
P3 is ordered as a set of component parts. LED lamping at
120v from the factory is 4w. P3's note in the luminaire
schedule is updated to require mfr label indicating "max 15w
lamp" in order to comply wiht ComCheck calculation.
We have provided for 3 j-boxes for a
future tenant supplied pendant (tenant
has not chosen this yet which is why
these are labeled "P"). So wattages in
commcheck are the max tenant will be
allowed to install.
Yes, this is correct. ComCheck has
been updated
All owner/agent fields have been updated. See updated
ComChecks.
All owner/agent fields have been updated.
See updated ComChecks.
09/06/2019
File Name: 230 E.
Hopkins_Drawings_Architectural--NICK_2019-08-07.pdf
Subject: PlanCheck
Author: nickt
Color:
Page Label: A2.0 PROPOSED BASEMENT FLOOR PLAN
Page Index: 23
Provide more information on
Commercial Unit 5. It now
appears to be a commercial
kitchen. What is the intended
use and is it related/accessory to
any other units? As a
commercial kitchen, it is an
employee work area only
requiring an accessible
entrance, turnaround, and exit.
However, if it is a break room for
another office, then it must be
fully accessible (provide
enlarged plan and elevations
demonstrating compliance). If it
is a commercial kitchen, exhaust
is required and a type II and/or
type I hood may be required
depending on the equipment
installed. If the dishwasher is a
residential level model, and a
hood is not required by the
install instructions, then no hood
will be required. It appears that it
may be serving as a back of
house kitchen to Unit 4. If unit 4
is to become a restaurant,
provide seating layout and
occupant calculations and
update plumbing fixture
calculations.
In future, please provide a
document outlining any changes
you have made since the last
round that are not in response to
comments.
230 E. Hopkins_Drawings_Architectural--NICK_2019-08-07.pdf (6)
File Name: 230 E.
Hopkins_Drawings_Architectural--NICK_2019-08-07.pdf
Subject: PlanCheck
Author: nickt
Color:
Page Label: A2.0 PROPOSED BASEMENT FLOOR PLAN
Page Index: 23
Provide enlarged plan and
elevations with dimensions
demonstrating accessibility at
the Unit 4 bar. This includes:
-Centerline of sink must be 24"
from edge of dishwasher to allow
for clearspace to be out of
dishwasher door swing.
-A portion of the bar seating
must be accessible. Minimum 5'
wide (to accommodate a
companion) portion of the
counter at 34" max height for full
depth of counter with knee and
toe clearance.
File Name: 230 E.
Hopkins_Drawings_Architectural--NICK_2019-08-07.pdf
Subject: PlanCheck
Author: nickt
Color:
Page Label: A5.1 PROPOSED BUILDING SECTIONS
Page Index: 33
Provide an enlarged detail of this
condition where the dwelling
separation continuity is wrapped
up to the underside of the floor
sheathing without interruption by
the joists or other structure.
Provide details at any other
similar conditions.
ˆ
)')'
83
83
%UDVV)DXFHWV6WLOOQHVV.7˝˙
'1
83
79$%29(
79
0(',$',63/$<
83
)'
)(&
:+\
)'
)'
)'
)'
)'
*2/)6,08/$725
8&5()8&5()':
)'
':8&,&(
%8,/',1*$%29(
(;,
6
7
%
8
,
/
'
,
1
*
$
%
2
9
(
%8
,
/
'
,
1
*
$
%
2
9
(
%8,/',1*$%29(
%8
,
/
'
,
1
*
$
%
2
9
(
:+
$($&')*%
ˇ
ˆ
ˇˆ
˘
ˇ˙
3523(57</,1(
352
3
(
5
7
<
/
,
1
(
3523(57</,1(
352
3
(
5
7
<
/
,
1
(
˘˙˙
6(7%$&./,1(
6(7
%
$
&
.
/
,
1
(
6(7%$&./,1(
6(7
%
$
&
.
/
,
1
(
021$5&+675((7
+2
3
.
,
1
6
$
9
(
1
8
(
$//
(
<
$˘
˙˙
˘˙˙˙
(;,67,1*$'',7,21
$˘
(;,
6
7
,
1
*
$'
'
,
7
,
2
1
(;,
6
7
,
1
*
$'
'
,
7
,
2
1
$˘
6&$/(˛
352326('
%$6(0(17)/2253/$1
ˇ $3/ 12
&20081,7
&2857<$5'
&20081,7˘ˆ
(/(9$725
5(675220
0(&+&+$6((48,350˙
&255,'25ˆ
67$,5 &20081,7ˇ
˝
$+8
1(:
:,1'2::(//,1&5($6('(37+)25&2'(&203/,$17(*5(66
)520%('522066,//$70$;)520),1,6+)/225
˙
&20081,7
ˇ
&/
2
6
(
7
5(675220
0(&+
˘
˘
˙˝
%('5220
%('5220
0(&+6725$*(
˘
$+8%$7+
ˇ
ˆ
ˆ˙
˘
ˇ
˝
˘
$
$%9
$%9
$%9
ˇ
$%9(;,67&2/801
$%9
˘
$%9
ˇ
$%9
ˆ
726/$%˙˙˘˙
0(&+
:˘$ˆ
:ˆ$ˆ:$ˆ
$ˇ˘
:$ˆ
:)$ˆ:ˆ)$ˆ
:˘6,0
$ˆ
:˘6,0$ˆ
:
$ˆ
:ˇ
$ˆ
:ˇ$ˆ:ˇ$ˆ
+$//
$ˇ
726/$%(˙˙˘˙
:$ˆ:$ˆ:
$ˆ
:
$ˆ:$ˆ
:$ˆ
')
$ˇ
$ˇ
:˘$ˆ
:˘$ˆ
),5(63.5
(175<
ˇ˙
˘ˇ
˘ˇ
˘˘˙˙˝ˇ˘˙
ˇ
˙
:$7(56(59,&((175<9$/9(
:˙
$ˆ
:ˇ$ˆ
5(/2&$7('(/(&3$1(/
0,&523,/(:$//
0,&523,/(:$//
3/$
1
7
,
1
*
*
$
3
$ˇˆ
*8$5'5$,/
$ˇˆ
72&2857<$5'˝˝˙
%
˝˝
&/26(7
˝D 0(&+
˝E
˙&/5 &2817(5$7
$))
$ˇˇ
:$ˆ
:ˇ$ˆ
0,&
5
2
3
,
/
(
:
$
/
/
:'
:25.7$%/(
:25
.
7
$
%
/
(
:25
.
7$%
/
(
$ˆ
ˆ
)855,1*72$/,*1
:,7+$'-$&(17:$//
:$ˆ
&+$6($%29(:ˇ$ˆ
3$57<:$//;ˇ$,5*$3;
$ˆˆ$ˆˆ
),(/'9(5,)<(;7(1762)(;,67&21&)'1:$//#/9/%($0
%($5,1*327(17,$/1(:&2/801
:$ˆ
6,0 6,0
$ˆˆ
6,0
(;,67&21&:$//72
5(0$,1
Provide more information on Commercial Unit 5.
It now appears to be a commercial kitchen. What
is the intended use and is it related/accessory to
any other units? As a commercial kitchen, it is an
employee work area only requiring an accessible
entrance, turnaround, and exit. However, if it is a
break room for another office, then it must be
fully accessible (provide enlarged plan and
elevations demonstrating compliance). If it is a
commercial kitchen, exhaust is required and a
type II and/or type I hood may be required
depending on the equipment installed. If the
dishwasher is a residential level model, and a
hood is not required by the install instructions,
then no hood will be required. It appears that it
may be serving as a back of house kitchen to
Unit 4. If unit 4 is to become a restaurant,provide seating layout and occupant calculationsand update plumbing fixture calculations.In future, please provide a document outliningany changes you have made since the last roundthat are not in response to comments.
ˆ
)')'
'1
79$%29(
79
83
)'
)(&
:+\)'
)'
8&
5()
8&
5()
':
':8&
,&(
%8
,
/
'
,
1
*
$
%
2
9
(
%8,/',1*$%29(
3523(57</,1(
35
2
3
(
5
7
<
/
,
1
(
6(
7
%
$
&
.
/
,
1
(
&20081,7
&2857<$5'
&200
81,7˘
ˆ
(/(9$725
&255,'25
ˆ
1(:
:,1'2::(//
,1&5($6('(37+)2
&2'(&203/,$17(*5
)520%('52206
6,//$70$;)52
),1,6+)/225
˙
&20081,7
ˇ
˘
˙˝
%('5220
%
ˆ
ˆ˙
˘
$
$%9
$%9
$%9
ˇ
$%9(;,67
&2/801
$%9
˘
$%9
ˇ
$%9
ˆ
$ˇ˘:ˇ
$ˆ
:ˇ
$ˆ
$ˇ
726/$%(
˙˙˘˙
:
$ˆ
:
$ˆ
:
$ˆ
$ˇ
:˘
$ˆ
:˘
$ˆ
:$7(56(59,&(
(175<9$/9(
3/
$
1
7
,
1
*
*
$
3
$ˇˆ
*8$5'
5$,/
$ˇˆ
72&2857<$5'
˝˝˙
%
˙&/
5 &2817(5$7
$)):
$ˆ
:25.7$%/(
:2
5
.
7
$
%
/
(
:2
5
.
7$
%
/
(
$ˆ
:
$ˆ
3$57<:$//
;ˇ
$,5*$3
;
$ˆˆ$ˆˆ
),(/'9(5,)<(;7(176
2)(;,67&21&)'1
:$//#/9/%($0
%($5,1*327(17,$/
1(:&2/801
:
$ˆ
6,0 6,0
Provide enlarged plan
and elevations with
dimensions
demonstrating
accessibility at the
Unit 4 bar. This
includes:
-Centerline of sink
must be 24" from edge
of dishwasher to allow
for clearspace to be
out of dishwasher door
swing.
-A portion of the bar
seating must be
accessible. Minimum
5' wide (to
accommodate a
companion) portion of
the counter at 34" max
height for full depth of
counter with knee and
toe clearance.
6&$/(˛
352326('%8,/',1*6(&7,21
ˇ $˘
$//(<
˘˘
˙
723/</(9(/7:2(
˙
72&21&%$6(0(17
˙˙˘˙
723/<522)(˙
ˆ˙
ˆ˙
72522)'(&.$
˙
723$5$3(7
ˇˆ
ˇ
35
2
3
(
5
7
<
/
,
1
(
6(
7
%
$
&
.
5
$ˆ
5
$ˆ
˙
*8(6768,7(
˝
*8(6768,7(
ˇ
)ˇ
$ˆ
)ˇ
$ˆ
)
$ˆ
6,0
$+8%$7+
ˇ
6/23('1
7233,1*6/$%21
&20326,7('(&.
˙˙
)ˆ
$ˆ
/,1(2)352326('
*5$'(5(˛&,9,/
75$6+5(&<&/(
%,16
$+8
˝
˘
$ˆ
)
$ˆ
)
$ˆ
8220 $+8%('5220
$+8
&20081,7
:
$ˆ
723/</(9(/21(%<1'
723/</(9(/21($'8
˝˝ˇ
ˆ
$ˆ6,02+
0,&523,/(:$//
5(˛6+25,1*
'(6,*1
˙
5
$ˆ
Provide an enlarged
detail of this condition
where the dwelling
separation continuity
is wrapped up to the
underside of the floor
sheathing without
interruption by the
joists or other
structure. Provide
details at any other
similar conditions.
Sheet A9.5B has been added.
Commercial Unit 5 is a staging facility only. No food
preparation will be done in this room. An exhaust fan has
been added. It will be rented as its own unit.
See sheets A5.1 - A5.3 building sections - occupancy separation continuity details keyed at wall/floor transitions.
See A7 series for enlarged detail info.
See new details on sheet A7.07A.
09/06/2019
File Name: 230 E.
Hopkins_Drawings_Architectural--NICK_2019-08-07.pdf
Subject: PlanCheck
Author: nickt
Color:
Page Label: A6.26 MECH. SHAFT DRAWINGS
Page Index: 45
W9/A7.01 references UL U415
which is a vertical assembly.
Systems tested vertically (walls)
may not be used horizontally per
UL general notes.
File Name: 230 E.
Hopkins_Drawings_Architectural--NICK_2019-08-07.pdf
Subject: PlanCheck
Author: nickt
Color:
Page Label: A6.26 MECH. SHAFT DRAWINGS
Page Index: 45
The shaft details are
complicated and do not appear
to be constructible. Installing two
layers of drywall with tape and
mud on the inside of the shaft
seems infeasible after rough ins
have been installed. Why the
double wall? Also, you are now
enclosing the bottom of the shaft
which relieves the need to rate
the mechanical room.
File Name: 230 E.
Hopkins_Drawings_Architectural--NICK_2019-08-07.pdf
Subject: PlanCheck
Author: nickt
Color:
Page Label: A7.09 DETAILS
Page Index: 59
Include detail 09 21 16.23.163
Shaft Wall Intermediate Floor
Base Overhang in the plans and
reference it here.
File Name: 230 E.
Hopkins_Drawings_Mechanical_2019-07-26.pdf
Subject: PlanCheck
Author: nickt
Color:
Page Label: M-110 BASEMENT HVAC PLAN
Page Index: 2
Commerical unit 5 now appears
to be a commercial kitchen.
Provide appropriate ventilation
and exhaust per requirements of
2015 IMC chapters 4 and 5.
230 E. Hopkins_Drawings_Mechanical_2019-07-26.pdf (1)
File Name: 230 E.
Hopkins_Drawings_Structural_2019-07-26.pdf
Subject: PlanCheck
Author: nickt
Color:
Page Label: S2.2 LEVEL TWO FLOOR FRAMING PLAN
Page Index: 14
Fire rate all columns that support
the roof joists that extending out
from Grid 7 (this is for 2015 IBC
705.11 exception 4.2 parapet
exception). Columns must be
individually encapsulated per
2015 IBC 704.2.
230 E. Hopkins_Drawings_Structural_2019-07-26.pdf (1)
1-HOU
HORIZ
FLOO
ASSE
F6
A7.02 SIM.
F2
A7.02
COMM.UNIT 1
100
SHAFT
ENCLOSURE
SHAFT ENCLOSURE
PENETRATIONS
SHALL BE
PROTECTED BY
DAMPERS AS
REQUIRED BY CODE -
RE: MECHANICAL
DOCUMENTATIONW10
A7.01
1-HOUR HORIZONTAL
FLOOR/CEILING
ASSEMBLY
EXIST. FDN
WALL TO
REMAIN;
1-HOUR RATED
NOTE: DUCTS
RUNNING UP INTO
SHAFT ENCLOSURE
SHALL BE
PROTECTED BY FIRE
DAMPERS AT THIS
LEVEL PER IBC
713.11.3.
GARAGE
103
1-HOUR BARRIER
(SHAFT WALL)
INSTALL FROM
SHAFT SIDE
W9
A7.01
1-HOUR BARRIER
(SHAFT WALL);
INSTALL FROM
SHAFT SIDE @
THIS LOCATION
EXISTING WALL TO
REMAIN;
1 HOUR FIRE RATED;
COMPLETE INSTALL
PRIOR TO INSTALL
OF ADJACENT
SHAFT WALL
1
H
O
U
R
S
H
A
F
T
W
A
L
L
1-HO
BARR
(SHA
W9
A7.01
1-HOUR
HORIZONTAL
FLOOR/CEILING
ASSEMBLY
FACE OF STUD FRAMING TO
ALIGN W/ FACE OF EXISTING
GLU-LAM BEAM THIS SIDE
TERMINATE
SHAFT WALL @
CONC. FDN WALL
PER UL REQ'S
1
A7.09
SIM.
3 1/4" +/-
FLOOR
OVERHANG
(FIELD VERIFY)
1-HOUR
HORIZONTAL
ENCLOSURE @
BOTTOM OF
SHAFT, INSTALL
PER UL REQ'S
W9
A7.01
FURRED WALL
FURR
1-HOUR RATED WALL
W9/A7.01 references
UL U415 which is a
vertical assembly.
Systems tested
vertically (walls) may
not be used
horizontally per UL
general notes.
T.O. PLY
LEVEL TWO (E)
111'-1 3/8"
0
2
ISTING WALL TO
MAIN;
HOUR FIRE RATED;
OMPLETE INSTALL
IOR TO INSTALL OF
HOUR BARRIER
HAFT WALL)
STALL FROM
HAFT SIDE @
IS LOCATION
HOUR HORIZONTAL
OOR/CEILING
SEMBLY
HOUR BARRIER
HAFT WALL)
ONTINUOUS
Revision:
The shaft details are
complicated and do not
appear to be constructible.
Installing two layers of drywall
with tape and mud on the
inside of the shaft seems
infeasible after rough ins have
been installed. Why the
double wall? Also, you are
now enclosing the bottom of
the shaft which relieves the
need to rate the mechanical
room.
Include detail 09 21
16.23.163 Shaft Wall
Intermediate Floor
Base Overhang in the
plans and reference it
here.
FEC
FD
DW U/C
ICE
COMM.
UNIT 5
007
1
MECH. 1
CHASE / EQUIP.
008
CORRIDOR
017
BEDROOM
002
BEDROOM
013
EH
1
F
2
2" FLUE &
2" COMBUSTION AIR
B
2
WH
1
EF
4
SF
4
A 125-R
18 x 3
A 125-R
18 x 3
A 535-R
54 x 3
9" OSA
4" DRYER EXH
1 1
8"
8" Ø 12x10 UP
3
WH
2
TF-2
26x10
(28x12)
26
x
1
0
(2
8
x
1
2
)
F/S
F/S
6
6
12BD
D
8/8 (10/10)
8"Ø (11"Ø) (TYP. OF 3)
7"Ø (10"Ø)
7"Ø (10"Ø)
BDD6" OSA
10
T
EH-1
12" OSA
8" OSA
8
2
14
14
2" FLUE &
2" COMBUSTION AIR
MD
9
M
A 1810-R
24x24
Commerical unit 5
now appears to be a
commercial kitchen.
Provide appropriate
ventilation and
exhaust per
requirements of 2015
IMC chapters 4 and 5.
A
7
B C D E F
2
3
4
5
6
100'-0"
10'-5 1/4"18'-8"5'-8 1/8"26'-4 3/4"14'-8 1/2"
60'-0"
5'-5 3/8"
15'-0 3/4"
6'-7 1/4"
8'-1 3/8"
17'-11 1/4"
6'-10"
(E) W10x22(E) W10x22(E) W10x22(E) W10x22
(E)W12x26
(E
)
W
1
6
x
3
1
(E) 5.125x12 GLB(E) 5.125x12 GLB(E) 5.125x12 GLB(E) 8.75x18 GLB
T/SHE
111'-
T
W14
14
"
T
J
I
3
6
0
@
1
6
"
O
C
(3) 7
HS S4 x4x1 /
9 1/2 TJI 210@16"OC
(E) 2x6@16"OC
(E) 10" TJI@16"OC
9 1
/
2
T
J
I
2
1
0
@
1
6
"
O
C
(E) 10" TJI/35@16"OC
(E) 12" TJI/35@16"OC
H SS 4x4 x5 /1 6
H S S4 x4 x1 /4
HS S 4x 4x 1/4
MO
M
E
N
T
F
R
A
M
E
HSS 4x 4x1/4
H SS 4x4 x1/4
1
H SS 4x4 x5 /1 6
W1
8
x
3
5
1S4.2
11 7/8 TJI 210@16"OC
(2) 9 1/2" LVL(2)
9
1
/
2
"
L
V
L
T/SHEATHING
111'-1 3/8"
EXISTING
T/SHEATHING
111'-1 3/8"A3
5S4.1
7S4.1
(2) 14" LVL
(E) W18x65
H S S4 x4x1 /4
H SS 4 x4 x1/4
6S4.2
6"
44
K
W1
4
x
6
1
49
K
(E) W18x65 12K
47
K
W14
x
6
1
27
K
2
6'-0 3/4"
9 1/2 TJI 210@16"OC
9 1/2" LVL@16"OC
AT FIREPLACE
A2
R
H SS4 x4 x1 /4
2
A 18
13S4.2
2 2 22
HS S 4x 4x 1/4 HSS4x4x1/4
15S4.2 16S4.3
1S4.3
7 1/4" LVL@
6S4.3
3
W1
110'-1
5K
6K W8x15
110'-5 7/8"
6K 6K W8x15
110'-5 7/8"
6K
HS S4x4x1/4
(2) 11 7/8" LVL
11
7
/
8
"
T
J
I
2
1
0
@
1
6
"
O
C
16S4.3
(2) 11 7/8" LVL
(E) 5.125x15 GLB
H4
H4
H3
H3
H2
H3
H4
H10
H10
H10
H12 H12
H12
6 3/4"
17S4.3
17S4.3
1
1
HS S4x4x1/4
HS
S
4
x
4
x
1
/
4
HSS4x4x1/4
(2) 7 1/4" LVL
1S4.4
H14
H14
2
4S4.4
(E
)
W
1
8
x
6
5
T/CONC
111'-4"
4
SIM
T/CMU
110'-11 1/8"
B/CONC111'-0 5/8"
(E
)
W
1
2
x
2
6
(E
)
W
1
2
x
2
6
11
7
/
8
"
T
J
I
2
1
0
@
1
6
"
O
C
11
7
/
8
"
T
J
I
2
1
0
@
1
6
"
O
C
(2
)
9
1
/
2
"
L
V
L
5
Fire rate all columns
that support the roof
joists that extending
out from Grid 7 (this is
for 2015 IBC 705.11
exception 4.2 parapet
exception). Columns
must be individually
encapsulated per 2015
IBC 704.2.
Bottom of shaft has been designed to terminate at a
mechanical room separated with 1 hour fire barriers.
Enclosure at the bottom of the shaft has been removed as
clarified in our telephone conversation.
See sheet A6.26
Design of the shaft has been simplified for constructability.
See sheets: A6.26 / A7.09 / A2.0 - A2.2 floor plan sheets.
New shaft wall UL U415 System F (alternate) selected for the project. See sheet A7.0C & W9/A7.01
Shaft dwg info has been updated. See sheet A6.26 & A7.09
Floor/shaft wall junction details added - see sheet A7.0C
Commercial Unit 5 is a staging facility only. An exhaust fan
has been added.
See building sections 1/A5.1 + 1/A5.2 for detail callouts and 1 hour encapsulation @ beams @ Level 2 and supporting structure
See sheet A7.08 for enlarged details and 1 hour beam encapsulation
See sheet A/2.1 Level 1 floor plan & A/2.0 Basement floor plan for supporting column 1 hour protection detail callouts
See sheet A7.30D for Design No. X528 UL Design 263 UL 1 hour column protection
09/06/2019
File Name: 230 E. Hopkins_Lighting_Spec
Package_2019-07-26.pdf
Subject: PlanCheck
Author: nickt
Color:
Page Label: D1
Page Index: 2
Provide cut sheet showing listing
by a nationally recognized
testing lab.
230 E. Hopkins_Lighting_Spec Package_2019-07-26.pdf (2)
File Name: 230 E. Hopkins_Lighting_Spec
Package_2019-07-26.pdf
Subject: PlanCheck
Author: nickt
Color:
Page Label: P2.1
Page Index: 4
Provide cut sheet showing listing
by a nationally recognized
testing lab.
T1711BN
tskirt Flush Mount
ushed Nickel
DETAILS
Material: Aluminum
Glass/Shade Descri
Remote Included: N
LAMPING
Light Source: Integr
Provide cut sheet
showing listing by a
nationally recognized
testing lab.
VIE
Home / Catalogue / Pendant Light / Brompton, Size 2 Anthracite Glass Pendant
U
PRODUCTS ABOUT US NEWS CONTACT
Provide cut sheet
showing listing by a
nationally recognized
testing lab.
Additional page added
to lighting package
indicating the fixture is
ETL-Intertek listed
Page P2.3 shows the
UL listed label, pages
2.4 & 2.5 shows mfr.
install instructions with
UL label and max
wattages.
09/06/2019