File Name: Elect COMMCheck.521 E Hyman.2018.11.01.pdf
Please completely fill out this
portion of the project information
on both the Mechanical and
Interior lighting ComChecks.
Elect COMMCheck.521 E Hyman.2018.11.01.pdf (1)
Subject: PlanCheck
Page Label: 5
Author: justinh
File Name: Plan Set.521 E Hyman.2018.11.02.pdf
The original plans for this
building showed a future lift
within your space to provide an
accessible route to the second
floor. IBC 1104.5 would require
your accessible route to the
second floor to be located within
your unit unless all occupants
were required to leave you unit
to access the second floor. In
order to have this route
considered you will need to
submit a formal request to the
chief building official to have this
accepted as an alternate means
of compliance stating why the
future lift was removed and
clearly outlining how this route
will comply (doors unlocked to
common area elevator at all
times of business operation for
unassisted access, etc.)
Plan Set.521 E Hyman.2018.11.02.pdf (6)
Subject: PlanCheck
Page Label: 5
Author: justinh
File Name: Plan Set.521 E Hyman.2018.11.02.pdf
Provide an elevation showing
your compliant bench and
hanger/hook heights.
Subject: PlanCheck
Page Label: 6
Author: justinh
File Name: Plan Set.521 E Hyman.2018.11.02.pdf
Please submit a special
inspection and testing
agreement for the intemenscent
paint application and the welding
shown in your plan. Please note
that this paint application must
be continuous from base to
beam everywhere you note the
removal of the existing
monocote.
COMcheck Software Version 4.0.8.1
Interior Lighting Compliance
Project Title:
2015 IECC
Project Type:Alteration
Construction Site:
535 E. HOPKINS AVE.
ASPEN, CO 81611
Owner/Agent:Design
BG B
251
200
FOR
970-
Project Information
Energy Code:
BENTON TI
Allowed Interior Lighting Power
A
Area Category
B
Floor Area
(ft2)
Please completely fill
out this portion of the
project information on
both the Mechanical
and Interior lighting
ComChecks.
0"
ESIDENTIALUNIT 1
OPEN
STAIR #2
BENTON SECOND FLOOR
6
BENTON LANDING
5
BENTON STORAGE
7
ALL MERCHANDISE DISPLAYEDON LANDING TO BE AVAILABLE INACCESSIBLE LOCATIONS
COMM. ELEV.FOR ACCESSTO 1ST FLOOR
BENTON MECHANICAL
7B
A
B
C
EXIT FROMSECOND FLOOR
EXIT FROMBASEMENT
SHAFT
TRAVEL DISTANCEEXIT I = 32' - 9"
70
EXIT C
OCCUPANTS 7
(11' - 5")(16' - 9")
TRAVEL DISTANCE TO EXIT I = 46' - 8"
TRAVEL DISTA EXIT I = 96' - 4
(12' - 6")
EXIT A
OCCUPANTS 89
EXIT B
FROM BASEMENTOCCUPANTS 46
(26'-6")
(9' - 4")
(5'-9")
(7' - 3")
(19' - 6")
(6'-4")
(2'-7")
(2'-0")
(5'-11")
(4'-2")
(15' - 0")
(29' - 8")
(5' - 10
(23' - 4")
13+3=164
16+1+2=19
12
(3' - 0")
EXIT B
EXIT A
(3' - 0")
(1' - 8")(1' - 6")
(3' - 6")
OCCUPANCY MAREA 794 sq.ft. GROSS @ 60 sq.ft.OCCUPANT LOAD = 14
6+5+7=18
18+1=19
GREATER THAN 1/3 DIAGONAL
36' - 4"
13
3
70+19=89
(8'-8")
14
TRAVEL DISTANCE 75'-3"
(7' - 5")
(14'-4")
7
7
(15'-8")(4'-8")
(9'-3")
14
14
7
COMM. ELEV.FOR ACCESS TO2ND FLOOR
WALL @ 30" A.F.F. FORREDUCED VERTICALCLEARANCEPROTECTION PER ANSIA117.1, 307.4REFER TO SECTION1/A407
HANDRAILSPER IBC 1014
PATH
2' - 8"
CHANGING 1
The original plans for this building showed a future
lift within your space to provide an accessible route
to the second floor. IBC 1104.5 would require your
accessible route to the second floor to be located
within your unit unless all occupants were required
to leave you unit to access the second floor. In
order to have this route considered you will need
to submit a formal request to the chief building
official to have this accepted as an alternate
means of compliance stating why the future lift was
removed and clearly outlining how this route will
comply (doors unlocked to common area elevator
at all times of business operation for unassisted
access, etc.)
SHAFT
(12' - 10")
- 5")
AVEL DISTANCE TOT I = 96' - 4"
26
(6' - 4")
(4' - 8")
TRAVEL DISTANCE TOEXIT J = 76' - 0"
13
RESTROOM
4
R 2' - 6 "
R
2
' -
6
"
ACCESSIBLE RESTROOMPER ANSI A-117.1, CHPT 6
ACCESSIBLECHANGING ROOM PER
ANSI A117.1, CHPT803
(1'-0")
(9'-2")
(9'-10")
(4'-1")
(4'-8")
(8'-11")
(1'-6")
(5'-1")
13
34" HIGH POINT OF
SALE COUNTERATH
- 8"
30" X 48" CLEAR FLOOR SPACE
CHANGING 1
RESTROOM
BACK OF HOUSE
ISSUE:
521 E. HYMAN AVE.
ASPEN, COLORADO
BUILD'G PERMIT 9/11/18
TENANT REV. 11/02/18
Provide an elevation
showing your
compliant bench and
hanger/hook heights.
A
RESIDENTIAL
UNIT 1
2
A-307
2
A-407
2
A-407
6
A-603
P0
BENTON LANDING
5
STAIR
5A
F.V. EXISTING STAIRTO MAINTAIN 7" MAX.
RISE, 11" MAX RUN;ADJUST AS REQ'D
2
A-408
2
A-408
REMOVE MONOCOTE FROM
COLUMNS, APPLYINTEMENSCENT PAINT FOR1-HOUR FIRE RATING
ILDING - SECOND FLOOR
Please submit a special
inspection and testing
agreement for the
intemenscent paint application
and the welding shown in your
plan. Please note that this
paint application must be
continuous from base to beam
everywhere you note the
removal of the existing
monocote.
Subject: PlanCheck
Page Label: 19
Author: justinh
File Name: Plan Set.521 E Hyman.2018.11.02.pdf
The cutsheets provided do not
match the input watts shown for
D2 or D3, and no cutsheet was
provided for D4. Explain or
revise the input watts for D2 and
D3 and provide a cutsheet on
D4.
Subject: PlanCheck
Page Label: 21
Author: justinh
File Name: Plan Set.521 E Hyman.2018.11.02.pdf
Show the retail floor areas you
are claiming on the ComCheck,
these need to correspond to
actual displays/shelving that
showcase the retail on display.
Show how all retail lighting is
independently controlled from
the general lighting per IECC
C405.4.2.2.1, these two types of
lighting cannot be on the same
switch. As currently shown I
don't think you have compliant
general lighting if all the track
lighting (retail) was turned off.
Revise the ComCheck if needed.
Subject: PlanCheck
Page Label: 21
Author: justinh
File Name: Plan Set.521 E Hyman.2018.11.02.pdf
All lighting needs to be
accounted for on the ComCheck,
this is the initial occupation of
the space so there are not
exceptions for any "existing
lighting" not being altered. You
need to account for these
fixtures and areas in the
ComCheck.
PROVIDE TENANT
SUBMETER;COORDINATE WITH
BUILDING SUBMETERSYSTEM.
REPLACE (E) CIRCUIT BREAKER WITHNEW 225/3 CIRCUIT BREAKER. MATCH
EXISTING RATINGS. LABEL CBACCORDINGLY.
WIRING SCHEDULE - COPPER
AMPS (2WG)(3WG)(4WG)
120/208V, 3PH, 4W
225
225/3 CB
22,000
AD DESCRIPTION LOAD NO.A B C
ST FLOOR CNTR 1420 2
ST FLOOR WEST 1500 4
ST FLOOR SOUTH 148 6
ST FLOOR NORTH 1200 8
ND FLOOR 1537 10
OH 256 12
WINDOW 1 1800 14
WINDOW 2 1800 16
MATIC DOOR 1200 18
RIOR SIGN 500 20
E 22
E 24
769.6 26
769.6 28
374.4 30
374.4 32
MPER 60 34
ER 150 36
100 38
URTAIN 1020 40
1400 42
GENERAL NOTES:
SPECIFIC NOTES:
LUMINAIRE SCHEDULE
TYPE DESCRIPTION MOUNTING LUMENOUTPUT COLOR
TEMP. (K)INPUT WATTS VOLT MANUFACTURER CATALOG NUMBER SPECIFICNOTESTYPE
D1 DIMMING DECORATIVE LED PENDANT PENDANT LED 623 3000k 9 120 MODERNA P500000-009-30
D2 DIMMING DECORATIVE LED SCONCE WALL LED 636 3000K 11 MVOLT DWELED BY WAC
LIGHTING WS-69815
D3 DIMMING DECORATIVE PENDANT-SECOND FLOOR PENDANT HALOPIN G9 QT-14 --750 120 NEMO CROWN
MAJOR SUPPLIED BY TENANT
D4 RECESSED LINEAR WALL-TO-CEILING TRIMLESS LED RECESSED LED 248 LM/FT 3000K 4.4W PER
FOOT 120 BIRCHWOOD BY
LEVITON JAK-LED-225-TL-SLO-30-MTR-R-FW-120-D1
T1 2.5A CURRENT LIMITED 8FT TRACK LIGHITNG AND 6
TRACK HEADS SURFACE LED 2176 PER
HEAD 3000K 35W PER HEAD 120 WAC LIGHTING WT8-WT-WEDL2A (TRACK)WTK-1035N-930-WT (HEAD)
T2 2.5A CURRENT LIMITED 12FT TRACK LIGHITNG AND 6
TRACK HEADS SURFACE LED 2176 PER
HEAD 3000K 35W PER HEAD 120 WAC LIGHTING WT12-WT-WEDL2A (TRACK)WTK-1035N-930-WT (HEAD)
T3 2.5A CURRENT LIMITED 16FT TRACK LIGHITNG AND 8
TRACK HEADS SURFACE LED 2176 PER
HEAD 3000K 35W PER HEAD 120 WAC LIGHTING WT16-WT-WEDL2A (TRACK)WTK-1035N-930-WT (HEAD)
X1 EXIT SIGN, GREEN LETTERING, WHITE HOUSING,
BATTERY BACKUP, AND SELF DIAGNOSTICS SURFACE LED --4.3 120 EELP EDG-1-G-C-A-EM-SD
X2 EGRESS FIXTURE, WHITE HOUSING, BATTERY BACKUP,
AND SELF DIAGNOSTICS SURFACE LED --4.3 120 LITHONIA AFN X PREM
GENERAL NOTES:
A.THE LUMINAIRE SCHEDULE CAN NOT BE USED INDEPENDENTLY OF THE DRAWINGS AND SPECIFICATIONS TO OBTAIN LUMINAIRE COSTS. THE INDIVIDUAL ESTABLISHING LUMINAIRE COSTS SHALL NOT QUOTE PRICING
WITHOUT FIRST SEEING APPLICABLE ELECTRICAL DRAWINGS AND ELECTRICAL DIVISION SPECIFICATIONS. THE CONTRACTOR IS REPONSIBLE FOR PROVIDING NECESSARY DRAWINGS AND SPECIFICATIONS TO THEINDIVIDUAL QUOTING LUMINAIRE PRICING.
B.REFER TO DRAWINGS FOR FIXTURES REQUIRING EMERGENCY BATTERY BACKUP OPTION (SHOWN BY HATCH IN/OVER SYMBOL). MINIMUM LIGHT OUTPUT FOR EM BALLAST SHALL BE 600 LUMENS.
C.ALL FLUORESCENT LAMPS ARE TO BE 3500° KELVIN COLOR TEMPERATURE
SPECIFIC NOTES:
(1)
CIRCUIT SPECIFIC NOTES
BEN-40 -
MECH
SP
A
C
E
H1
M
M
M
M
15
0
/
3
40
0
/
3
40
0
/
3
10
0
/
3
10
0
/
3
10
0
/
3
10
0
/
3
10
0
/
3
22
5
/
3
10
0
/
3
10
0
/
3
10
0
/
3
M
M
M
M
40
0
(
4
W
G
)
40
0
(
4
W
G
)
15
0
(
4
W
G
)
MECH2
30
0
/
3
30
0
(
4
W
G
)
E N
L ATS
400A,
208Y/120V3ø/4P
M
M
M
M
M
M
M
M
DEMAND STYLE (kW/kWh) METERS. E-MON
D-MON CLASS 2000 METERS, AMPERAGES AS
NECESSARY. TENANT SUBMETER
FURNISHED BY TENANT, TYPICAL.
F6 F7 F8 F9
H2 22
5
ISSUE:
DESCRIPTION:
SEPT. 11, 2018
ALBUQUERQUE | AVON | DENVER | FO
Project No. 9203.12 Co
NOV. 2, 2018 TENANT REVISI
ELECTRICAL
ONE-LINE
DIAGRAM
The cutsheets provided do not
match the input watts shown for D2
or D3, and no cutsheet was
provided for D4. Explain or revise
the input watts for D2 and D3 and
provide a cutsheet on D4.
B
Show the retail floor areas you are claiming on
the ComCheck, these need to correspond to
actual displays/shelving that showcase the retail
on display. Show how all retail lighting is
independently controlled from the general
lighting per IECC C405.4.2.2.1, these two types
of lighting cannot be on the same switch. As
currently shown I don't think you have compliant
general lighting if all the track lighting (retail) was
turned off. Revise the ComCheck if needed.
45
C
BENTON
SECOND FLOOR
T3
T3
1
2
OS
S
OS
D 4
D
3
D 4
D3 D
3
a
c
b
b
a
c
4
7
T2
T1
T1
T2
T2
T3
T3
X2
X2
X2
X2
X2
8
8
8
12
TC
a
10 DL
9
D1
D1
D
3d
D 4d
D 3e d3
8
8
8
D4D4
11
S3
S3
b5
b5
b56
6S12
X1
X1
X1
All lighting needs to be
accounted for on the
ComCheck, this is the initial
occupation of the space so
there are not exceptions for
any "existing lighting" not being
altered. You need to account
for these fixtures and areas in
the ComCheck.