Page: A0.00 COVER
File Name: PLANS.pdf
Subject: PlanCheck
Author: nickt
Color:
Is this a single family building or
are there are dwellings
attached? If so, show the
location of the other dwelling(s).
PLANS.pdf (8)
Page: A0.00 COVER
File Name: PLANS.pdf
Subject: PlanCheck
Author: nickt
Color:
Special inspections are required
per 2015 IBC 1704 for the
structural steel welding and
bolting. Revise your cover sheet,
provide a signed special
inspection agreement, and
provide a statement of special
inspections stamped by the
engineer on the structural plans.
Page: A0.00 COVER
File Name: PLANS.pdf
Subject: PlanCheck
Author: nickt
Color:
Provide information on the
fireplace alterations;
demonstrate compliance with
2015 IRC chapter 10.
Page: A0.00 COVER
File Name: PLANS.pdf
Subject: PlanCheck
Author: nickt
Color:
Revise to 2017 NEC
Page: A0.00 COVER
File Name: PLANS.pdf
Subject: PlanCheck
Author: nickt
Color:
By covering outdoor space you
are increasing the fire area.
Provide fire area calculations of
the entire building (see definition
of fire area in 2015 IBC 202; it
includes covered outdoor areas).
If the entire building is greater
than 5000sqft, fire sprinklers will
be required due to this increase.
Please discuss with the fire
marshal.
81
1
E
.
H
O
P
K
I
N
S
D
E
C
K
R
E
N
O
V
A
T
I
O
N
81
1
E
.
H
O
P
K
I
N
S
A
V
E
.
,
A
S
P
E
N
,
C
O
FE
L
L
M
A
N
C
O
N
D
O
S
U
B
D
I
V
I
S
I
O
N
U
N
I
T
1
PA
R
C
E
L
I
D
#
2
7
3
7
1
8
2
0
8
0
3
1
KINS DECK RENOVATION
PKINS AVE., ASPEN, CO
ONDO SUBDIVISION UNIT 1
EL ID# 273718208031
Is this a single family building or are
there are dwellings attached? If so, show
the location of the other dwelling(s).
PROJECT DIRECTORY:
LIST OF DRAWINGS:
SCOPE OF WORK:
A.ALL DESIGN CRITERIA NOT SHOWN ON THESE PLANS ARE TO CONFORM TO STANDARD FRAMING PER LOCAL AND NATIONAL CODES.B.ALL INFORMATION CONTAINED WITHIN THESE DRAWINGS AND ALL ENGINEERING CALCULATIONS ARE INTENDED TO MEET OR EXCEED CURRENT LOCAL AND INTERNATIONAL CODES.C.ALL CONSTRUCTION SHALL CONFORM TO THE CURRENT EDITION OF THE INTERNATIONAL BUILDING CODE AND ALL OTHER APPLICABLE CODES AND REGULATIONS.D.THE CONTRACTOR SHALL SUPERVISE AND DIRECT THE PROJECT, USING HIS/HER BEST SKILL AND ATTENTION. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR ALL CONSTRUCTIONMEANS, METHODS, TECHNIQUES, SEQUENCES AND PROCEDURES AND FOR COORDINATING ALL PORTIONS OF THE WORK UNDER THE CONTRACT.E.THE CONTRACTOR SHALL INSPECT THE PREMISES IMMEDIATELY TO CHECK EXISTING CONDITIONS. SHOULD THE CONTRACTOR FIND CONDITIONS WHICH HE/SHE BELIEVES WOULD IMPEDEHIS/HER WORK, THEN SUCH CONDITIONS MUST BE REPORTED IMMEDIATELY TO THE OWNER AND ARCHITECT. FAILURE TO DO SO WILL CONSTITUTE NOTICE THAT THE CONTRACTOR ISFULLY SATISFIED WITH THE EXISTING CONDITIONS AND THAT HE/SHE INTENDS TO PERFORM HIS/HER OBLIGATIONS WITH NO ALLOWANCE EITHER IN TIME OR MONEY FOR ANY IMPEDIMENTTO HIS/HER WORK.F.THE CONTRACTOR SHALL FAMILIARIZE HIMSELF/HERSELF WITH THE PROJECT THROUGH INSPECTION OF THE JOB SITE, DRAWINGS AND SPECIFICATIONS, SO AS TO THOROUGHLYUNDERSTAND THE WORK. ANY AND ALL DISCREPANCIES AND OMISSIONS SHALL BE REPORTED AND CLARIFICATION SHALL BE OBTAINED FROM THE OWNER AND ARCHITECT PRIOR TOWORK BEING DONE. IF DIMENSIONAL ERROR OCCURS OR CONDITIONS NOT COVERED IN THE DRAWINGS ARE ENCOUNTERED, CONTRACTOR SHALL NOTIFY THE ARCHITECT BEFORECOMMENCING THAT PORTION OF THE WORK. WRITTEN DIMENSIONS SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS. DO NOT SCALE DRAWINGS. ALL WRITTEN DIMENSIONS TO BEVERIFIED IN THE FIELD.G.THE CONTRACTOR SHALL BE RESPONSIBLE AT ALL TIMES FOR THE PROPER PROTECTION OF THE EXISTING FACILITY. THE CONTRACTOR SHALL IDENTIFY, PRIOR TO BEGINNING OF WORK,ANY AREAS OF EXISTING DAMAGE. THE CONTRACTOR SHALL BE RESPONSIBLE TO PATCH AND REPAIR, AT HIS/HER OWN COST OF ANY DAMAGE TO THE PREMISES OR ADJACENT WORKCAUSED BY HIS/HER OPERATION OR THAT OF HIS/HER SUBCONTRACTORS OR SUPPLIERS. IN ADDITION, THE CONTRACTOR SHALL FOLLOW ALL SAFETY REQUIREMENTS OF AUTHORITIESHAVING JURISDICTION OVER HIS/HER WORK.H.THE CONTRACTOR SHALL GUARANTEE IN WRITING ALL LABOR, MATERIALS, AND WORKMANSHIP INSTALLED BY HIM/HER FOR A PERIOD OF NOT LESS THAN ONE (1) YEAR AFTER DATE OFACCEPTANCE OF THE WORK BY THE OWNER EXCEPT AS MODIFIED HEREIN OR ON OTHER DRAWING. SHOULD DEFECT OCCUR, ALL WORK SHALL BE REPLACED OR PROPERLY REPAIRED ATNO ADDITIONAL COST TO THE OWNER.I.CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING THE SITE IN A CLEAN AND SAFE CONDITION, INCLUDING PROPER REMOVAL OF WASTE MATERIAL. WASTE MATERIAL SHALL NOT BESTORED WITHIN OR NEAR BUILDING. DUMPSTERS PROVIDED FOR THE DISPOSAL OF WASTE MATERIAL SHALL BE REMOVED AWAY FROM THE BUILDING BUT MAY BE STORED ON SITE DAILY.J.THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING ALL COMBUSTIBLE FLUIDS INCLUDING PAINT, PRIMERS, SEALERS, SOLVENTS AND ADHESIVES COMPLY, AND ARE BEING USED INACCORDANCE WITH THE PRODUCT MANUFACTURER'S WRITTEN INSTRUCTIONS. CONTRACTOR SHALL PROVIDE STORAGE FOR SUCH MATERIALS AWAY FROM THE BUILDING. USE OF THEBUILDING FOR SUCH STORAGE IS PROHIBITED.K.ALL WALLS CONTAINING WASTE LINES SHOULD BE CONSTRUCTED ARE REQUIRED TO ACCOMMODATE PLUMBING LINES.L.ALL ITEMS EXPRESSES, DRAWN, NOTED, OR SPECIFIED WITHIN THESE DOCUMENT SHALL BE PROVIDED AND INSTALLED BY THE CONTRACTOR UNLESS NOTED OTHERWISE. ANY ITEMS NOTINCLUDED AND REQUIRED ARE THE RESPONSIBILITY OF THE CONTRACTOR.M.CONTRACTOR IS RESPONSIBLE FOR FINAL CLEAN-UP OF ALL EXPOSED SURFACES AT SUBSTANTIAL COMPLETION. R. INSTALL SUPPLEMENTARY FRAMING, BLOCKING AND BRACING IN METALFRAMING SYSTEM WHENEVER WALLS OR PARTITIONS ARE INDICATED TO SUPPORT FIXTURES, EQUIPMENT, SERVICES, CASEWORK, HEAVY TRIM AND FURNISHINGS, AND SIMILAR WORK.N.IF HAZARDOUS MATERIALS ARE FOUND TO EXIST ON THE PROJECT, THE CONTRACTOR SHALL NOTIFY THE OWNER AND ARCHITECT IN WRITING.O.THE CONTRACTOR SHALL COORDINATE THE WORK OF ALL TRADES REQUIRED TO PERFORM THE WORK. WHERE INSTALLATION AND/OR CONNECTION OF EQUIPMENT IS NOT SPECIFIED ANDWHERE SUCH INSTALLATION / CONNECTION REQUIRED FOR A COMPLETE AND OPERATIONAL FACILITY, THE CONTRACTOR SHALL BE HELP RESPONSIBLE FOR SUCH INSTALLATION /CONNECTION.P.ALL MATERIALS STORED ON SITE SHALL BE PROTECTED FROM WEATHER TO PREVENT DAMAGE AND DETERIORATION UNTIL USE. FAILURE TO PROTECT MATERIALS MAYBE CAUSE FORREJECTION OF WORK.Q.ALL INSULATION MATERIAL INCLUDING FACINGS ARE REQUIRED TO HAVE A FLAME SPREAD OF 25 OR BETTER AND A MAXIMUM SMOKE DENSITY OF 450 PER THE 2009 IBC, SECTION 719.3.R.SUBMITTALS SHALL BE DELIVERED TO THE ARCHITECT WITH A LETTER OF TRANSMITTAL. MATERIAL SELECTIONS AND PRODUCT INFORMATION SHALL BE SENT VIE EMAIL OR HARD COPY ASREQUIRED. SHOULD HARD COPIES BE PROVIDED CONTRACTOR IS TO PROVIDE 5 COPIES TO ARCHITECT FOR DISTRIBUTION. CONTRACTOR IS TO REVIEW SUBMITTALS AND SHOP DRAWINGSPRIOR TO SUBMITTING TO ARCHITECT, CONTRACTOR TO STAMP SUBMITTALS. ARCHITECT SHALL HAVE 7 BUSINESS DAYS TO REVIEW SUBMITTALS.S.ANY CHANGES OR QUESTIONS ON THE CONTRACT DRAWINGS SHALL BE PRESENTED AS AN RFI (REQUEST FOR INFORMATION).T.CHANGES TO THE CONTRACT DRAWINGS SHALL BE COMPLETED AS CHANGE ORDERS. CONTRACTOR TO PROVIDE A CHANGE ORDER REQUEST AND IS TO HAVE THE CHANGE ORDERSIGNED BY THE ARCHITECT, OWNER AND CONTRACTOR PRIOR TO COMMENCING WITH CHANGED WORK.U.ALL PRODUCT SHALL BE LOW V.O.C. AND ARE TO INCLUDE THE FOLLOWING ADHESIVES, PAINTS, PRIMERS, PLASTICS, LAMINATES, FLOORING, FRP, AND CEILINGS MATERIALS. ALL PRODUCTINSTALLED SHALL CONSIDER LEED CERTIFICATION REQUIREMENTS.V.ACCESSORIES FOR THE RESTROOM ARE PROVIDED AND INSTALLED BY THE CONTRACTOR. VERIFY ACCESSORIES WITH OWNER, PROVIDE BACKING AS NEEDED.W.ALL CONTRACTORS SHALL OBSERVE AN 8AM TO 5 PM WORK DAY. NO OUTDOOR MUSIC WILL BE PERMITTED DURING CONSTRUCTION
ARCHITECTURAL DRAWINGS:A0.00 COVER SHEETA1.01 EXISTING AND PROPOSED SITE PLAN W/ UNIT RELATIONSHIPA1.02 EXISTING UPPER LEVEL PLANA1.03 EXISTING ROOF PLANA1.04 EXISTING ELEVATIONSA1.05 PROPOSED UPPER LEVEL PLANA1.06 PROPOSED ROOF PLANA1.07 PROPOSED ELEVATIONSA1.08 DOOR AND WINDOW SCHEDULEA1.09 DETAILSA1.10 DETAILS
VICI
OWNER:TOM FELLMAN809 NORTH 96 STOMAHA, NE 68114CONTACT: TOM FELLMANT: 402-290-9906THFELLMAN@AOL.COM
ARCHITECT:RALLY DUPPS ARCHITECTPOB 3662ASPEN, CO 81612CONTACT: RALLY DUPPST: 720-481-7353rallydupps@gmail.com
PERTINENT CODE EDITIONS:
GENERAL PERMIT SUBMITTAL NOTES:
1. FIRE SPRINKLER SYSTEM NOT REQUIRED NFPA 13 D PER ORDINANCE 37, SERIES 20112. SPECIAL INSPECTIONS ARE NOT REQUIRED - REF. STRUCTURAL3. ALTERATIONS ARE PROPOSED TO EXISTING FIREPLACES4. THE PROPERTY IS NOT SUBJECT TO HPC APPROVAL5. THE PROPOSED SCOPE OF WORK DOES NOT REQUIRE HOA APPROVAL6. THE BUILDING IS CONSTRUCTION TYPE V-B7. OCCUPANCY IS TYPE IS R-3 SINGLE FAMILY RESIDENCE8. NEW SNOWMELT AREAS = 0 S.F.9. AREA SUBJECT TO RENOVATION = 623 S.F.10. NO FLOOR AREA IS PROPOSED TO BE ADDED TO THIS PERMIT11. LOT SIZE IS 6000 S.F. PER ASSESSOR12. PROVIDE CO DETECTORS PER CHAPTER 8.15 CARBON MONOXIDE DETECTORS
GENERAL NOTES:
OUR SCOPE OF WORK IS TO CONSTRUCT A ROOF OVER AND EXISTING EXTERIOR DECK, PLUS REPLACEMENT OF EXISTING DOORS AND WINDOWS WITH NEW UNITS OF AN HISTORICALLYDESIGNATED SINGLE FAMILY RESIDENCE LOCATED AT 811 E. HOPKINS AVE. IN ASPEN, CO.
PROJECT VALUATION = $150,000S.F. OF WORK AREA = 321 S.F.UNIT 1 S.F. = 9486 S.F. PER ASSESSORLOT SIZE = 12,000 S.F. PER ASSESSOR (UNIT 1 = 9000 S.F.)DISTURBED AREA ON THE SITE PLAN = 0 S.F.S.F. OF LANDSCAPE WORK = 0 S.F.DEMOLISHED AREA = 0 S.FNEW S.F. = 0 S.F.S.F. OF PROPOSED ROOMS WITH UTILITY WORK = 0 S.F
CITY OF ASPEN BUILDING CODES AS ADOPTED BY ORDINANCE 40, SERIES 2016:
2015 IBC, APPENDICES C: GROUP U - AGRICULTURAL BUILDINGS, E: SUPPLEMENTARY ACCESSIBILITY REQUIREMENTS, I: PATIO COVERS, J: GRADING2015 IRC CHAPTERS 1-10, APPENDICES E: MANUFACTURED HOUSING USED AS DWELLINGS, F: RADON CONTROL METHODS, H: PATIO COVERS, J: EXISTING BUILDINGS AND STRUCTURES, K:SOUND TRANSMISSION, R: LIGHT STRAW-CLAY CONSTRUCTION, S: STRAWBALE CONSTRUCTION, U: SOLAR-READY PROVISIONS2015 INTERNATIONAL PLUMBING CODE2015 INTERNATIONAL MECHANICAL CODE2015 INTERNATIONAL FUEL GAS CODE2015 INTERNATIONAL EXISTING BUILDING CODE2015 INTERNATIONAL SWIMMING POOL AND SPA CODE2015 INTERNATIONAL SOLAR ENERGY PROVISIONSICC.A117.1-2009 ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES2014 NATIONAL ELECTRIC CODE2015 INTERNATIONAL ENERGY CONSERVATION CODE
CLIMACTIC AND GEOGRAPHICAL DESIGN CRITERIA PER TABLE R301.2(1)
GROUND SNOW LOAD: 100 PSFWIND SPEED / EXPOSURE CATEGORY: 89/BSEISMIC DESIGN CATEGORY: CWEATHERING: SEVEREFROST LINE DEPTH: 36"TERMITE: NONE TO SLIGHTDECAY: NONE TO SLIGHTWINTER DESIGN TEMP: -15 DEG. FSUMMER DESIGN TEMP: 82 DEG. FICE SHIELD UNDERLAYMENT REQUIRED: YESAIR FREEZING INDEX: 2000MEAN ANNUAL TEMPERATURE: 40 DEG. F
FIXTURE COUNT:
BATHTUB
CLIMATE ZONE: 7FENESTRATION U FACTOR: 0.28 PER ASPEN RESOLUTION AND NOTE BSKYLIGHT U FACTOR: 0.55 PER NOTE BCEILING R VALUE: 49WOOD FRAME WALL R VALUE: 20+5 OR 13+10MASS WALL R VALUE: 19 / 21 PER NOTE IFLOOR R VALUE: 38 OR R-19 MIN. PER NOTE GBASEMENT WALL R VALUE: 15 / 19 PER NOTE CSLAB R VALUE AND DEPTH: 10, 4 FT, HEATED SLAB R-5 PER NOTE DCRAWL SPACE WALL R VALUE: 15 / 19 PER NOTE C
2015 IECC TABLE R402.1.2
FIXTURE
TOILET
LAVATORY (WASH BASIN)
SHOWER
KITCHEN SINK
DISHWASHER
LAUNDRY, BAR, UTILITY SINK
CLOTHES WASHER
FLOOR SINK
FLOOR DRAIN
WATER HEATER
# GAS OUTLETS
WATER TREATMENT
OTHER - INDOOR POOL
PROPOSED
11
EXISTING
11
6
14
7
2
6
5
0
0
3
1
1
PROPOSED
STRUCTURAL ENGINEER:SGM ENGINEERS101 FOUNDERS PL # 102ASPEN, CO 81611CONTACT: MINDY NASTALT: 970-384-9053MindyN@sgm-inc.com
ASBESTOS TEST:REI LABRESERVOIRS ENVIRONMENTAL LLCC/O HELPERS DISASTER RESTORATION LLC11 DUROUX LANEBASALT, CO 81621CONTACT: ANTHONY PISTONOT: 303-964-1986
STRUCTURAL DRAWINGS:S1 STRUCTURAL NOTES, FRAMING PLANS AND DETAILS
CHANGE
1
6
811 E. HOPKINS DECK
811 E. HOPKINS AVE
FELLMAN CONDO SUBD
PARCEL ID# 2737
0
0
0
0
0
0
0
0
0
0
0
0
0
0
GENERAL CONTRACTOR:GARRET CONSTRUCTION INC.3892 CRYSTAL BRIDGE DRIVECARBONDALE, CO 81623CONTACT: TODD CERRONET: 970-948-3695todd@garretconstruction.com 14
7
2
2 2
6
5
0
0
0
1
1
0
ARCHITECTURAL DRAWINGS:D1.01 DEMOLITION PLANZ1.01 ZONING SUMMARY AND APPROVALSZ1.02 DEMOLITION CALCULATIONSZ1.03 DEMOLITION CALCULATIONS
Special inspections are required per2015 IBC 1704 for the structuralsteel welding and bolting. Reviseyour cover sheet, provide a signedspecial inspection agreement, andprovide a statement of special
inspections stamped by theengineer on the structural plans.
PROJECT DIRECTORY:
LIST OF DRAWINGS:
SCOPE OF WORK:
WHERE SUCH INSTALLATION / CONNECTION REQUIRED FOR A COMPLETE AND OPERATIONAL FACILITY, THE CONTRACTOR SHALL BE HELP RESPONSIBLE FOR SUCH INSTALLATION /CONNECTION.
P.ALL MATERIALS STORED ON SITE SHALL BE PROTECTED FROM WEATHER TO PREVENT DAMAGE AND DETERIORATION UNTIL USE. FAILURE TO PROTECT MATERIALS MAYBE CAUSE FOR
REJECTION OF WORK.
Q.ALL INSULATION MATERIAL INCLUDING FACINGS ARE REQUIRED TO HAVE A FLAME SPREAD OF 25 OR BETTER AND A MAXIMUM SMOKE DENSITY OF 450 PER THE 2009 IBC, SECTION 719.3.R.SUBMITTALS SHALL BE DELIVERED TO THE ARCHITECT WITH A LETTER OF TRANSMITTAL. MATERIAL SELECTIONS AND PRODUCT INFORMATION SHALL BE SENT VIE EMAIL OR HARD COPY A
REQUIRED. SHOULD HARD COPIES BE PROVIDED CONTRACTOR IS TO PROVIDE 5 COPIES TO ARCHITECT FOR DISTRIBUTION. CONTRACTOR IS TO REVIEW SUBMITTALS AND SHOP DRAWING
PRIOR TO SUBMITTING TO ARCHITECT, CONTRACTOR TO STAMP SUBMITTALS. ARCHITECT SHALL HAVE 7 BUSINESS DAYS TO REVIEW SUBMITTALS.S.ANY CHANGES OR QUESTIONS ON THE CONTRACT DRAWINGS SHALL BE PRESENTED AS AN RFI (REQUEST FOR INFORMATION).
T.CHANGES TO THE CONTRACT DRAWINGS SHALL BE COMPLETED AS CHANGE ORDERS. CONTRACTOR TO PROVIDE A CHANGE ORDER REQUEST AND IS TO HAVE THE CHANGE ORDER
SIGNED BY THE ARCHITECT, OWNER AND CONTRACTOR PRIOR TO COMMENCING WITH CHANGED WORK.
U.ALL PRODUCT SHALL BE LOW V.O.C. AND ARE TO INCLUDE THE FOLLOWING ADHESIVES, PAINTS, PRIMERS, PLASTICS, LAMINATES, FLOORING, FRP, AND CEILINGS MATERIALS. ALL PRODUC INSTALLED SHALL CONSIDER LEED CERTIFICATION REQUIREMENTS.
V.ACCESSORIES FOR THE RESTROOM ARE PROVIDED AND INSTALLED BY THE CONTRACTOR. VERIFY ACCESSORIES WITH OWNER, PROVIDE BACKING AS NEEDED.
W.ALL CONTRACTORS SHALL OBSERVE AN 8AM TO 5 PM WORK DAY. NO OUTDOOR MUSIC WILL BE PERMITTED DURING CONSTRUCTION
ARCHITECTURAL DRAWINGS:
A0.00 COVER SHEETA1.01 EXISTING AND PROPOSED SITE PLAN W/ UNIT RELATIONSHIP
A1.02 EXISTING UPPER LEVEL PLAN
A1.03 EXISTING ROOF PLAN
OWNER:TOM FELLMAN
809 NORTH 96 ST
OMAHA, NE 68114
CONTACT: TOM FELLMANT: 402-290-9906THFELLMAN@AOL.COM
ARCHITECT:
RALLY DUPPS ARCHITECTPOB 3662
ASPEN, CO 81612
CONTACT: RALLY DUPPST: 720-481-7353rallydupps@gmail.com
PERTINENT CODE EDITIONS:
GENERAL PERMIT SUBMITTAL NOTES:
1. FIRE SPRINKLER SYSTEM NOT REQUIRED NFPA 13 D PER ORDINANCE 37, SERIES 20112. SPECIAL INSPECTIONS ARE NOT REQUIRED - REF. STRUCTURAL3. ALTERATIONS ARE PROPOSED TO EXISTING FIREPLACES
4. THE PROPERTY IS NOT SUBJECT TO HPC APPROVAL
5. THE PROPOSED SCOPE OF WORK DOES NOT REQUIRE HOA APPROVAL6. THE BUILDING IS CONSTRUCTION TYPE V-B
7. OCCUPANCY IS TYPE IS R-3 SINGLE FAMILY RESIDENCE
8. NEW SNOWMELT AREAS = 0 S.F.
9. AREA SUBJECT TO RENOVATION = 623 S.F.10. NO FLOOR AREA IS PROPOSED TO BE ADDED TO THIS PERMIT
11. LOT SIZE IS 6000 S.F. PER ASSESSOR
12. PROVIDE CO DETECTORS PER CHAPTER 8.15 CARBON MONOXIDE DETECTORS
OUR SCOPE OF WORK IS TO CONSTRUCT A ROOF OVER AND EXISTING EXTERIOR DECK, PLUS REPLACEMENT OF EXISTING DOORS AND WINDOWS WITH NEW UNITS OF AN HISTORICALLYDESIGNATED SINGLE FAMILY RESIDENCE LOCATED AT 811 E. HOPKINS AVE. IN ASPEN, CO.
PROJECT VALUATION = $150,000S.F. OF WORK AREA = 321 S.F.
UNIT 1 S.F. = 9486 S.F. PER ASSESSOR
LOT SIZE = 12,000 S.F. PER ASSESSOR (UNIT 1 = 9000 S.F.)
DISTURBED AREA ON THE SITE PLAN = 0 S.F.S.F. OF LANDSCAPE WORK = 0 S.F.
DEMOLISHED AREA = 0 S.F
NEW S.F. = 0 S.F.
S.F. OF PROPOSED ROOMS WITH UTILITY WORK = 0 S.F
CITY OF ASPEN BUILDING CODES AS ADOPTED BY ORDINANCE 40, SERIES 2016:
2015 IBC, APPENDICES C: GROUP U - AGRICULTURAL BUILDINGS, E: SUPPLEMENTARY ACCESSIBILITY REQUIREMENTS, I: PATIO COVERS, J: GRADING
2015 IRC CHAPTERS 1-10, APPENDICES E: MANUFACTURED HOUSING USED AS DWELLINGS, F: RADON CONTROL METHODS, H: PATIO COVERS, J: EXISTING BUILDINGS AND STRUCTURES, K:
SOUND TRANSMISSION, R: LIGHT STRAW-CLAY CONSTRUCTION, S: STRAWBALE CONSTRUCTION, U: SOLAR-READY PROVISIONS
2015 INTERNATIONAL PLUMBING CODE2015 INTERNATIONAL MECHANICAL CODE
2015 INTERNATIONAL FUEL GAS CODE
2015 INTERNATIONAL EXISTING BUILDING CODE
2015 INTERNATIONAL SWIMMING POOL AND SPA CODE2015 INTERNATIONAL SOLAR ENERGY PROVISIONS
ICC.A117.1-2009 ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES
2014 NATIONAL ELECTRIC CODE
2015 INTERNATIONAL ENERGY CONSERVATION CODE
STRUCTURAL ENGINEER:SGM ENGINEERS
101 FOUNDERS PL # 102
ASPEN, CO 81611CONTACT: MINDY NASTALT: 970-384-9053
MindyN@sgm-inc.com
ASBESTOS TEST:
REI LAB
RESERVOIRS ENVIRONMENTAL LLCC/O HELPERS DISASTER RESTORATION LLC
11 DUROUX LANE
BASALT, CO 81621
CONTACT: ANTHONY PISTONOT: 303-964-1986
STRUCTURAL DRAWINGS:
S1 STRUCTURAL NOTES, FRAMING PLANS AND DET
GENERAL CONTRACTOR:GARRET CONSTRUCTION INC.
3892 CRYSTAL BRIDGE DRIVE
CARBONDALE, CO 81623
CONTACT: TODD CERRONET: 970-948-3695
todd@garretconstruction.com
ARCHITECTURAL DRAWINGS:
D1.01 DEMOLITION PLANZ1.01 ZONING SUMMARY AND APPROVALS
Z1.02 DEMOLITION CALCULATIONS
Z1.03 DEMOLITION CALCULATIONS
Provide information on
the fireplace
alterations;
demonstrate
compliance with 2015
IRC chapter 10.
PROJECT DIRECTORY:
O.THE CONTRACTOR SHALL COORDINATE THE WORK OF ALL TRADES REQUIRED TO PERFORM THE WORK. WHERE INSTALLATION AND/OR CONNECTION OF EQUIP
WHERE SUCH INSTALLATION / CONNECTION REQUIRED FOR A COMPLETE AND OPERATIONAL FACILITY, THE CONTRACTOR SHALL BE HELP RESPONSIBLE FOR S
CONNECTION.
P.ALL MATERIALS STORED ON SITE SHALL BE PROTECTED FROM WEATHER TO PREVENT DAMAGE AND DETERIORATION UNTIL USE. FAILURE TO PROTECT MATER
REJECTION OF WORK.
Q.ALL INSULATION MATERIAL INCLUDING FACINGS ARE REQUIRED TO HAVE A FLAME SPREAD OF 25 OR BETTER AND A MAXIMUM SMOKE DENSITY OF 450 PER THE
R.SUBMITTALS SHALL BE DELIVERED TO THE ARCHITECT WITH A LETTER OF TRANSMITTAL. MATERIAL SELECTIONS AND PRODUCT INFORMATION SHALL BE SENT
REQUIRED. SHOULD HARD COPIES BE PROVIDED CONTRACTOR IS TO PROVIDE 5 COPIES TO ARCHITECT FOR DISTRIBUTION. CONTRACTOR IS TO REVIEW SUBMI
PRIOR TO SUBMITTING TO ARCHITECT, CONTRACTOR TO STAMP SUBMITTALS. ARCHITECT SHALL HAVE 7 BUSINESS DAYS TO REVIEW SUBMITTALS.
S.ANY CHANGES OR QUESTIONS ON THE CONTRACT DRAWINGS SHALL BE PRESENTED AS AN RFI (REQUEST FOR INFORMATION).
T.CHANGES TO THE CONTRACT DRAWINGS SHALL BE COMPLETED AS CHANGE ORDERS. CONTRACTOR TO PROVIDE A CHANGE ORDER REQUEST AND IS TO HAVE
SIGNED BY THE ARCHITECT, OWNER AND CONTRACTOR PRIOR TO COMMENCING WITH CHANGED WORK.
U.ALL PRODUCT SHALL BE LOW V.O.C. AND ARE TO INCLUDE THE FOLLOWING ADHESIVES, PAINTS, PRIMERS, PLASTICS, LAMINATES, FLOORING, FRP, AND CEILING
INSTALLED SHALL CONSIDER LEED CERTIFICATION REQUIREMENTS.
V.ACCESSORIES FOR THE RESTROOM ARE PROVIDED AND INSTALLED BY THE CONTRACTOR. VERIFY ACCESSORIES WITH OWNER, PROVIDE BACKING AS NEEDED
W.ALL CONTRACTORS SHALL OBSERVE AN 8AM TO 5 PM WORK DAY. NO OUTDOOR MUSIC WILL BE PERMITTED DURING CONSTRUCTION
OWNER:
TOM FELLMAN
809 NORTH 96 ST
OMAHA, NE 68114
CONTACT: TOM FELLMAN
T: 402-290-9906
THFELLMAN@AOL.COM
PERTINENT CODE EDITIONS:
GENERAL PERMIT SUBMITTAL NOTES:
1. FIRE SPRINKLER SYSTEM NOT REQUIRED NFPA 13 D PER ORDINANCE 37, SERIES 2011
2. SPECIAL INSPECTIONS ARE NOT REQUIRED - REF. STRUCTURAL
3. ALTERATIONS ARE PROPOSED TO EXISTING FIREPLACES
4. THE PROPERTY IS NOT SUBJECT TO HPC APPROVAL
5. THE PROPOSED SCOPE OF WORK DOES NOT REQUIRE HOA APPROVAL
6. THE BUILDING IS CONSTRUCTION TYPE V-B
7. OCCUPANCY IS TYPE IS R-3 SINGLE FAMILY RESIDENCE
8. NEW SNOWMELT AREAS = 0 S.F.
9. AREA SUBJECT TO RENOVATION = 623 S.F.
10. NO FLOOR AREA IS PROPOSED TO BE ADDED TO THIS PERMIT
11. LOT SIZE IS 6000 S.F. PER ASSESSOR
12. PROVIDE CO DETECTORS PER CHAPTER 8.15 CARBON MONOXIDE DETECTORS
CITY OF ASPEN BUILDING CODES AS ADOPTED BY ORDINANCE 40, SERIES 2016:
2015 IBC, APPENDICES C: GROUP U - AGRICULTURAL BUILDINGS, E: SUPPLEMENTARY ACCESSIBILITY REQUIREMENTS, I: PATIO COVERS, J: GRADING
2015 IRC CHAPTERS 1-10, APPENDICES E: MANUFACTURED HOUSING USED AS DWELLINGS, F: RADON CONTROL METHODS, H: PATIO COVERS, J: EXISTING BUILDINGS
SOUND TRANSMISSION, R: LIGHT STRAW-CLAY CONSTRUCTION, S: STRAWBALE CONSTRUCTION, U: SOLAR-READY PROVISIONS
2015 INTERNATIONAL PLUMBING CODE
2015 INTERNATIONAL MECHANICAL CODE
2015 INTERNATIONAL FUEL GAS CODE
2015 INTERNATIONAL EXISTING BUILDING CODE
2015 INTERNATIONAL SWIMMING POOL AND SPA CODE
2015 INTERNATIONAL SOLAR ENERGY PROVISIONS
ICC.A117.1-2009 ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES
2014 NATIONAL ELECTRIC CODE
2015 INTERNATIONAL ENERGY CONSERVATION CODE
STRUCTURAL ENGINEER:
SGM ENGINEERS
101 FOUNDERS PL # 102
ASPEN, CO 81611
CONTACT: MINDY NASTAL
T: 970-384-9053
MindyN@sgm-inc.com
Revise to
2017 NEC
PROJECT DIRECTORY:
LIST OF DRAWINGS:
SCOPE OF WORK:
A.ALL DESIGN CRITERIA NOT SHOWN ON THESE PLANS ARE TO CONFORM TO STANDARD FRAMING PER LOCAL AND NATIONAL CODES.B.ALL INFORMATION CONTAINED WITHIN THESE DRAWINGS AND ALL ENGINEERING CALCULATIONS ARE INTENDED TO MEET OR EXCEED CURRENT LOCAL AND INTERNATIONAL CODES.C.ALL CONSTRUCTION SHALL CONFORM TO THE CURRENT EDITION OF THE INTERNATIONAL BUILDING CODE AND ALL OTHER APPLICABLE CODES AND REGULATIONS.D.THE CONTRACTOR SHALL SUPERVISE AND DIRECT THE PROJECT, USING HIS/HER BEST SKILL AND ATTENTION. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR ALL CONSTRUCTIONMEANS, METHODS, TECHNIQUES, SEQUENCES AND PROCEDURES AND FOR COORDINATING ALL PORTIONS OF THE WORK UNDER THE CONTRACT.E.THE CONTRACTOR SHALL INSPECT THE PREMISES IMMEDIATELY TO CHECK EXISTING CONDITIONS. SHOULD THE CONTRACTOR FIND CONDITIONS WHICH HE/SHE BELIEVES WOULD IMPEDEHIS/HER WORK, THEN SUCH CONDITIONS MUST BE REPORTED IMMEDIATELY TO THE OWNER AND ARCHITECT. FAILURE TO DO SO WILL CONSTITUTE NOTICE THAT THE CONTRACTOR ISFULLY SATISFIED WITH THE EXISTING CONDITIONS AND THAT HE/SHE INTENDS TO PERFORM HIS/HER OBLIGATIONS WITH NO ALLOWANCE EITHER IN TIME OR MONEY FOR ANY IMPEDIMENTTO HIS/HER WORK.F.THE CONTRACTOR SHALL FAMILIARIZE HIMSELF/HERSELF WITH THE PROJECT THROUGH INSPECTION OF THE JOB SITE, DRAWINGS AND SPECIFICATIONS, SO AS TO THOROUGHLYUNDERSTAND THE WORK. ANY AND ALL DISCREPANCIES AND OMISSIONS SHALL BE REPORTED AND CLARIFICATION SHALL BE OBTAINED FROM THE OWNER AND ARCHITECT PRIOR TOWORK BEING DONE. IF DIMENSIONAL ERROR OCCURS OR CONDITIONS NOT COVERED IN THE DRAWINGS ARE ENCOUNTERED, CONTRACTOR SHALL NOTIFY THE ARCHITECT BEFORECOMMENCING THAT PORTION OF THE WORK. WRITTEN DIMENSIONS SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS. DO NOT SCALE DRAWINGS. ALL WRITTEN DIMENSIONS TO BEVERIFIED IN THE FIELD.G.THE CONTRACTOR SHALL BE RESPONSIBLE AT ALL TIMES FOR THE PROPER PROTECTION OF THE EXISTING FACILITY. THE CONTRACTOR SHALL IDENTIFY, PRIOR TO BEGINNING OF WORK,ANY AREAS OF EXISTING DAMAGE. THE CONTRACTOR SHALL BE RESPONSIBLE TO PATCH AND REPAIR, AT HIS/HER OWN COST OF ANY DAMAGE TO THE PREMISES OR ADJACENT WORKCAUSED BY HIS/HER OPERATION OR THAT OF HIS/HER SUBCONTRACTORS OR SUPPLIERS. IN ADDITION, THE CONTRACTOR SHALL FOLLOW ALL SAFETY REQUIREMENTS OF AUTHORITIESHAVING JURISDICTION OVER HIS/HER WORK.H.THE CONTRACTOR SHALL GUARANTEE IN WRITING ALL LABOR, MATERIALS, AND WORKMANSHIP INSTALLED BY HIM/HER FOR A PERIOD OF NOT LESS THAN ONE (1) YEAR AFTER DATE OFACCEPTANCE OF THE WORK BY THE OWNER EXCEPT AS MODIFIED HEREIN OR ON OTHER DRAWING. SHOULD DEFECT OCCUR, ALL WORK SHALL BE REPLACED OR PROPERLY REPAIRED ATNO ADDITIONAL COST TO THE OWNER.I.CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING THE SITE IN A CLEAN AND SAFE CONDITION, INCLUDING PROPER REMOVAL OF WASTE MATERIAL. WASTE MATERIAL SHALL NOT BESTORED WITHIN OR NEAR BUILDING. DUMPSTERS PROVIDED FOR THE DISPOSAL OF WASTE MATERIAL SHALL BE REMOVED AWAY FROM THE BUILDING BUT MAY BE STORED ON SITE DAILY.J.THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING ALL COMBUSTIBLE FLUIDS INCLUDING PAINT, PRIMERS, SEALERS, SOLVENTS AND ADHESIVES COMPLY, AND ARE BEING USED INACCORDANCE WITH THE PRODUCT MANUFACTURER'S WRITTEN INSTRUCTIONS. CONTRACTOR SHALL PROVIDE STORAGE FOR SUCH MATERIALS AWAY FROM THE BUILDING. USE OF THEBUILDING FOR SUCH STORAGE IS PROHIBITED.K.ALL WALLS CONTAINING WASTE LINES SHOULD BE CONSTRUCTED ARE REQUIRED TO ACCOMMODATE PLUMBING LINES.L.ALL ITEMS EXPRESSES, DRAWN, NOTED, OR SPECIFIED WITHIN THESE DOCUMENT SHALL BE PROVIDED AND INSTALLED BY THE CONTRACTOR UNLESS NOTED OTHERWISE. ANY ITEMS NOTINCLUDED AND REQUIRED ARE THE RESPONSIBILITY OF THE CONTRACTOR.M.CONTRACTOR IS RESPONSIBLE FOR FINAL CLEAN-UP OF ALL EXPOSED SURFACES AT SUBSTANTIAL COMPLETION. R. INSTALL SUPPLEMENTARY FRAMING, BLOCKING AND BRACING IN METALFRAMING SYSTEM WHENEVER WALLS OR PARTITIONS ARE INDICATED TO SUPPORT FIXTURES, EQUIPMENT, SERVICES, CASEWORK, HEAVY TRIM AND FURNISHINGS, AND SIMILAR WORK.N.IF HAZARDOUS MATERIALS ARE FOUND TO EXIST ON THE PROJECT, THE CONTRACTOR SHALL NOTIFY THE OWNER AND ARCHITECT IN WRITING.O.THE CONTRACTOR SHALL COORDINATE THE WORK OF ALL TRADES REQUIRED TO PERFORM THE WORK. WHERE INSTALLATION AND/OR CONNECTION OF EQUIPMENT IS NOT SPECIFIED ANDWHERE SUCH INSTALLATION / CONNECTION REQUIRED FOR A COMPLETE AND OPERATIONAL FACILITY, THE CONTRACTOR SHALL BE HELP RESPONSIBLE FOR SUCH INSTALLATION /CONNECTION.P.ALL MATERIALS STORED ON SITE SHALL BE PROTECTED FROM WEATHER TO PREVENT DAMAGE AND DETERIORATION UNTIL USE. FAILURE TO PROTECT MATERIALS MAYBE CAUSE FORREJECTION OF WORK.Q.ALL INSULATION MATERIAL INCLUDING FACINGS ARE REQUIRED TO HAVE A FLAME SPREAD OF 25 OR BETTER AND A MAXIMUM SMOKE DENSITY OF 450 PER THE 2009 IBC, SECTION 719.3.R.SUBMITTALS SHALL BE DELIVERED TO THE ARCHITECT WITH A LETTER OF TRANSMITTAL. MATERIAL SELECTIONS AND PRODUCT INFORMATION SHALL BE SENT VIE EMAIL OR HARD COPY ASREQUIRED. SHOULD HARD COPIES BE PROVIDED CONTRACTOR IS TO PROVIDE 5 COPIES TO ARCHITECT FOR DISTRIBUTION. CONTRACTOR IS TO REVIEW SUBMITTALS AND SHOP DRAWINGSPRIOR TO SUBMITTING TO ARCHITECT, CONTRACTOR TO STAMP SUBMITTALS. ARCHITECT SHALL HAVE 7 BUSINESS DAYS TO REVIEW SUBMITTALS.S.ANY CHANGES OR QUESTIONS ON THE CONTRACT DRAWINGS SHALL BE PRESENTED AS AN RFI (REQUEST FOR INFORMATION).T.CHANGES TO THE CONTRACT DRAWINGS SHALL BE COMPLETED AS CHANGE ORDERS. CONTRACTOR TO PROVIDE A CHANGE ORDER REQUEST AND IS TO HAVE THE CHANGE ORDERSIGNED BY THE ARCHITECT, OWNER AND CONTRACTOR PRIOR TO COMMENCING WITH CHANGED WORK.U.ALL PRODUCT SHALL BE LOW V.O.C. AND ARE TO INCLUDE THE FOLLOWING ADHESIVES, PAINTS, PRIMERS, PLASTICS, LAMINATES, FLOORING, FRP, AND CEILINGS MATERIALS. ALL PRODUCTINSTALLED SHALL CONSIDER LEED CERTIFICATION REQUIREMENTS.V.ACCESSORIES FOR THE RESTROOM ARE PROVIDED AND INSTALLED BY THE CONTRACTOR. VERIFY ACCESSORIES WITH OWNER, PROVIDE BACKING AS NEEDED.W.ALL CONTRACTORS SHALL OBSERVE AN 8AM TO 5 PM WORK DAY. NO OUTDOOR MUSIC WILL BE PERMITTED DURING CONSTRUCTION
ARCHITECTURAL DRAWINGS:A0.00 COVER SHEETA1.01 EXISTING AND PROPOSED SITE PLAN W/ UNIT RELATIONSHIPA1.02 EXISTING UPPER LEVEL PLANA1.03 EXISTING ROOF PLANA1.04 EXISTING ELEVATIONSA1.05 PROPOSED UPPER LEVEL PLANA1.06 PROPOSED ROOF PLANA1.07 PROPOSED ELEVATIONSA1.08 DOOR AND WINDOW SCHEDULEA1.09 DETAILSA1.10 DETAILS
VICINITY MAP:
OWNER:TOM FELLMAN809 NORTH 96 STOMAHA, NE 68114CONTACT: TOM FELLMANT: 402-290-9906THFELLMAN@AOL.COM
ARCHITECT:RALLY DUPPS ARCHITECTPOB 3662ASPEN, CO 81612CONTACT: RALLY DUPPST: 720-481-7353rallydupps@gmail.com
PERTINENT CODE EDITIONS:
GENERAL PERMIT SUBMITTAL NOTES:
1. FIRE SPRINKLER SYSTEM NOT REQUIRED NFPA 13 D PER ORDINANCE 37, SERIES 20112. SPECIAL INSPECTIONS ARE NOT REQUIRED - REF. STRUCTURAL3. ALTERATIONS ARE PROPOSED TO EXISTING FIREPLACES4. THE PROPERTY IS NOT SUBJECT TO HPC APPROVAL5. THE PROPOSED SCOPE OF WORK DOES NOT REQUIRE HOA APPROVAL6. THE BUILDING IS CONSTRUCTION TYPE V-B7. OCCUPANCY IS TYPE IS R-3 SINGLE FAMILY RESIDENCE8. NEW SNOWMELT AREAS = 0 S.F.9. AREA SUBJECT TO RENOVATION = 623 S.F.10. NO FLOOR AREA IS PROPOSED TO BE ADDED TO THIS PERMIT11. LOT SIZE IS 6000 S.F. PER ASSESSOR12. PROVIDE CO DETECTORS PER CHAPTER 8.15 CARBON MONOXIDE DETECTORS
GENERAL NOTES:
OUR SCOPE OF WORK IS TO CONSTRUCT A ROOF OVER AND EXISTING EXTERIOR DECK, PLUS REPLACEMENT OF EXISTING DOORS AND WINDOWS WITH NEW UNITS OF AN HISTORICALLYDESIGNATED SINGLE FAMILY RESIDENCE LOCATED AT 811 E. HOPKINS AVE. IN ASPEN, CO.
PROJECT VALUATION = $150,000S.F. OF WORK AREA = 321 S.F.UNIT 1 S.F. = 9486 S.F. PER ASSESSORLOT SIZE = 12,000 S.F. PER ASSESSOR (UNIT 1 = 9000 S.F.)DISTURBED AREA ON THE SITE PLAN = 0 S.F.S.F. OF LANDSCAPE WORK = 0 S.F.DEMOLISHED AREA = 0 S.FNEW S.F. = 0 S.F.S.F. OF PROPOSED ROOMS WITH UTILITY WORK = 0 S.F
CITY OF ASPEN BUILDING CODES AS ADOPTED BY ORDINANCE 40, SERIES 2016:
2015 IBC, APPENDICES C: GROUP U - AGRICULTURAL BUILDINGS, E: SUPPLEMENTARY ACCESSIBILITY REQUIREMENTS, I: PATIO COVERS, J: GRADING2015 IRC CHAPTERS 1-10, APPENDICES E: MANUFACTURED HOUSING USED AS DWELLINGS, F: RADON CONTROL METHODS, H: PATIO COVERS, J: EXISTING BUILDINGS AND STRUCTURES, K:SOUND TRANSMISSION, R: LIGHT STRAW-CLAY CONSTRUCTION, S: STRAWBALE CONSTRUCTION, U: SOLAR-READY PROVISIONS2015 INTERNATIONAL PLUMBING CODE2015 INTERNATIONAL MECHANICAL CODE2015 INTERNATIONAL FUEL GAS CODE2015 INTERNATIONAL EXISTING BUILDING CODE2015 INTERNATIONAL SWIMMING POOL AND SPA CODE2015 INTERNATIONAL SOLAR ENERGY PROVISIONSICC.A117.1-2009 ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES2014 NATIONAL ELECTRIC CODE2015 INTERNATIONAL ENERGY CONSERVATION CODE
CLIMACTIC AND GEOGRAPHICAL DESIGN CRITERIA PER TABLE R301.2(1)
GROUND SNOW LOAD: 100 PSFWIND SPEED / EXPOSURE CATEGORY: 89/BSEISMIC DESIGN CATEGORY: CWEATHERING: SEVEREFROST LINE DEPTH: 36"TERMITE: NONE TO SLIGHTDECAY: NONE TO SLIGHTWINTER DESIGN TEMP: -15 DEG. FSUMMER DESIGN TEMP: 82 DEG. FICE SHIELD UNDERLAYMENT REQUIRED: YESAIR FREEZING INDEX: 2000MEAN ANNUAL TEMPERATURE: 40 DEG. F
FIXTURE COUNT:
BATHTUB
CLIMATE ZONE: 7FENESTRATION U FACTOR: 0.28 PER ASPEN RESOLUTION AND NOTE BSKYLIGHT U FACTOR: 0.55 PER NOTE BCEILING R VALUE: 49WOOD FRAME WALL R VALUE: 20+5 OR 13+10MASS WALL R VALUE: 19 / 21 PER NOTE IFLOOR R VALUE: 38 OR R-19 MIN. PER NOTE GBASEMENT WALL R VALUE: 15 / 19 PER NOTE CSLAB R VALUE AND DEPTH: 10, 4 FT, HEATED SLAB R-5 PER NOTE DCRAWL SPACE WALL R VALUE: 15 / 19 PER NOTE C
2015 IECC TABLE R402.1.2
FIXTURE
TOILET
LAVATORY (WASH BASIN)
SHOWER
KITCHEN SINK
DISHWASHER
LAUNDRY, BAR, UTILITY SINK
CLOTHES WASHER
FLOOR SINK
FLOOR DRAIN
WATER HEATER
# GAS OUTLETS
WATER TREATMENT
OTHER - INDOOR POOL
PROPOSED
11
EXISTING
11
6
14
7
2
6
5
0
0
3
1
1
PROPOSED
STRUCTURAL ENGINEER:SGM ENGINEERS101 FOUNDERS PL # 102ASPEN, CO 81611CONTACT: MINDY NASTALT: 970-384-9053MindyN@sgm-inc.com
ASBESTOS TEST:REI LABRESERVOIRS ENVIRONMENTAL LLCC/O HELPERS DISASTER RESTORATION LLC11 DUROUX LANEBASALT, CO 81621CONTACT: ANTHONY PISTONOT: 303-964-1986
STRUCTURAL DRAWINGS:S1 STRUCTURAL NOTES, FRAMING PLANS AND DETAILS
CHANGE
1
6
811 E. HOPKINS DECK REN
811 E. HOPKINS AVE., AS
FELLMAN CONDO SUBDIVIS
PARCEL ID# 2737182
0
0
0
0
0
0
0
0
0
0
0
0
0
0
GENERAL CONTRACTOR:GARRET CONSTRUCTION INC.3892 CRYSTAL BRIDGE DRIVECARBONDALE, CO 81623CONTACT: TODD CERRONET: 970-948-3695todd@garretconstruction.com 14
7
2
2 2
6
5
0
0
0
1
1
0
ARCHITECTURAL DRAWINGS:D1.01 DEMOLITION PLANZ1.01 ZONING SUMMARY AND APPROVALSZ1.02 DEMOLITION CALCULATIONSZ1.03 DEMOLITION CALCULATIONS
By covering outdoor space youare increasing the fire area.Provide fire area calculations ofthe entire building (see definitionof fire area in 2015 IBC 202; itincludes covered outdoor areas).If the entire building is greaterthan 5000sqft, fire sprinklers willbe required due to this increase.Please discuss with the firemarshal.
08/09/18
Page: A1.06 PROPOSED ROOF PLAN
File Name: PLANS.pdf
Subject: Heat tape
Author: nickt
Color:
Heat trace/tape must be
self-regulating type cable and
must include automatic controls
and timer capable of turning off
the system when the outdoor
temperature is above 50
degrees and during daylight
hours. (Ordinance 40, 2016).
Page: A1.06 PROPOSED ROOF PLAN
File Name: PLANS.pdf
Subject: PlanCheck
Author: nickt
Color:
Provide a snowfence at the
bottom of the roof pitch where it
sheds over the window well
below (Ordinance 40, 2016).
Page: A1.08 DOOR AND WINDOW SCHEDULE
File Name: PLANS.pdf
Subject: skylight
Author: nickt
Color:
For the skylight, provide the
thickness of the polyvinyl butyral
interlayer (minimum 30-mil per
2015 IRC R308.6).
S
M
OF
OW
INTERNAL GUTTER
TO METAL DOWNSPOUT
DRAIN TO EXISTING
TRENCH DRAIN
SL
O
P
E
1/
4
"
:
1
2
"
M
I
N
.
SLOPE
MATCH
SLOPE
EXISTING MATCHEXISTING
MEMBRANE ROOF
W/ SNOWMELT
SNOW FENCE WITH
SNOW CLIPS AND SNOWMELT
SNOW FENCE WITH
SNOW CLIPS AND SNOWMELT
SN
O
W
F
E
N
C
E
SN
O
W
F
E
N
C
E
RE
F
.
M
F
G
RE
F
.
M
F
G
NORTH
PROPOSED ROOF PLAN1
A1.06 1/4" = 1'-0"
Heat trace/tape must
be self-regulating type
cable and must include
automatic controls and
timer capable of
turning off the system
when the outdoor
temperature is above
50 degrees and during
daylight hours.
(Ordinance 40, 2016).
AIA INDUSTRIES
RIDGE SKYLIGHT SYSTEM
DASHED LINE OFLEVEL BLOW
METAL GUTTER
TO METAL DOWNSPOUT
DRAIN TO EXISTING
TRENCH DRAIN
INTERNAL GUTTER
TO METAL DOWNSPOUT
DRAIN TO EXISTING
TRENCH DRAIN
SL
O
P
E
1/4
"
:
1
2
"
M
I
N
.
SLOPE
MATCH
SLOPE
EXISTING MATCHEXISTING
MEMBRANE ROOF
W/ SNOWMELT
SNOW FENCE WITH
SNOW CLIPS AND SNOWMELT
SNOW FENCE WITH
SNOW CLIPS AND SNOWMELT
SN
O
W
F
E
N
C
E
SN
O
W
F
E
N
C
E
RE
F
.
M
F
G
RE
F
.
M
F
G
SNOW FENCE
SUPPORT AT
ROOF RIDGE-
REF. DETAILS
EXTENT OF
AFFECTED AREA
Provide a snowfence
at the bottom of the
roof pitch where it
sheds over the
window well below
(Ordinance 40,
2016).
RED BY BUILDING CODE, ENERGY CODE
OW ASSEMBLIES WITH ARCHITECT AND WINDOW REP. THE
D UNIT OPENINGS ARE TO BE VERIFIED IN FIELD BY AFTER
MODIFIED, OR NEW OPENINGS.
TURAL BUILDING ELEVATIONS. THESE ARE TO BE
ARE MEASURED FROM INTERIOR FINISH FLOOR LEVELS TO
ON BARRIER AROUND WALLS OF ENTIRE STRUCTURE, WITH
FILTRATION BARRIER. USE BUILDING WRAP AS BASE LAYER
Y FROM HEADER. INSTALL METAL FLASHING PAN AT WINDOW
N THE FRAME AND WALL ROUGH OPENINGS AROUND ALL
E BRUSHED NICKEL OR EQUIVALENT, EUROPEAN STYLE
RE TO BE SIZED PER IRC. ALL WINDOWS LOCATED WITHIN
NGINEERED WOOD OR STEEL. DOORS TO INCLUDE TRACKING
VITY POCKET.
MOUNTED DOOR PULL.
ONTRACTOR TO SPECIFY WHICH TYPE OF SAFETY GLASS IS
01
(EXTERIOR, TRIPLE)
SLIDING DOOR
STYLE TBD
MFG. TBD
REF. PLANS FOR
OPERATION
EXT. DOOR AND WINDOW U FACTOR:
ALL NEW DOORS AND WINDOWS
= 0.28 MIN
SKYLIGHT = 0.55 MIN
ENERGY CODE INTERIOR REMODEL
GENERAL NOTES:
1. ENERGY EFFICIENCY U VALUES
PER 2015 IECC TABLE R402.1.2 FOR
CLIMATE ZONE 7
2. SKYLIGHT GLASS FOR UNITS
LOCATED OVER HEATED AREAS IS
TO BE DOUBLE PANE LOW E
LAMINATED GLASS WITH
ELECTRONICALLY OPERATED BLIND
9'-
0
"
9'-
0
"
02
(EXTERIOR, DOUBLE)
SLIDING DOOR
STYLE TBD
MFG. TBD
REF. PLANS FOR
OPERATION
FIXED
For the skylight,
provide the thickness
of the polyvinyl butyral
interlayer (minimum
30-mil per 2015 IRC
R308.6).
08/09/18