The special inspection
agreement must be signed by
the owner.
Architectural Plans.802 West Main.2018.010-BLUEBEAM.pdf (4)
Page: 5.2 BUILDING SECTIONS
File Name: Architectural Plans.802 West
Main.2018.010-BLUEBEAM.pdf
Subject: PlanCheck
Author: nickt
Color:
Wrap the edge of the balcony at
this location to protect the side of
the F5 assembly from fire from
the adjacent property (this is an
egress balcony).
(Egress balcony must be 10'
from
lot line (2015 1021.4). The
portion of the balcony within 10'
of the lot line must also be 1
hour fire rated on the edge and
underside).
Page: 7.6 ROOF ASSEMBLIES & DETAILS
File Name: Architectural Plans.802 West
Main.2018.010-BLUEBEAM.pdf
Subject: PlanCheck
Author: nickt
Color:
In this location the joists do
indeed run parallel to the wall,
however there are 4 pack LVL
beams that run perpendicular
and must penetrate the
membrane. Perhaps the APA
rim board detail would work
here?
Page: G1.15 ACCESSIBILITY
File Name: Architectural Plans.802 West
Main.2018.010-BLUEBEAM.pdf
Subject: PlanCheck
Author: nickt
Color:
The 30" dimension is no longer
aligned with the oven
clearspace.
NG 802 WEST MAIN ST
The special inspection agreement
must be signed by the owner.
SECOND LEVEL
110'-5"
Wrap the edge of the balcony at this
location to protect the side of the F5
assembly from fire from the adjacent
property (this is an egress balcony).
(Egress balcony must be 10' from
lot line (2015 1021.4). The portion of
the balcony within 10' of the lot line
must also be 1 hour fire rated on the
edge and underside).
5/
8
"
11
7/
8
"
3
/
4
"
3"
TYPICAL SL FIRE-RATED WALL/ROOF CONDITION
T. O. SHEATHING
SEE PLAN
GL
FIRE SEPARATION
CONTINUES TO UNDERSIDE
OF ROOF SHEATHING
@ RATED WALLS
AIRSEAL SOFFIT TO
SHEATHING
R2 W4
W6
In this location the
joists do indeed run
parallel to the wall,
however there are 4
pack LVL beams that
run perpendicular and
must penetrate the
membrane. Perhaps
the APA rim board
detail would work
here?
DW
2'-1"
2'-
6
"
CL
REF
2'-1"2'-1"
CL
RG
K
L
5'
-
1
"
30"x48"<-
3
0
"
x
4
8
"
30"x48
1 B
AN
TY
The 30" dimension is
no longer aligned with
the oven clearspace.
See the attached signed Special Inspection
Form attached.
Detail 4/7.3 shows protection on the side of
the F5 assembly.
We have revised the detail to show an APA
rim joist. This condition applies for both detail
4&6/7.6. Detail 2/S3.3 coordinates with these
details.
The dimension has been moved to align with
the oven clearspace.
12/06/2018