Loading...
HomeMy WebLinkAboutFile Documents.230 E Hopkins Ave.0089.2018 (10).ACBK Page 1 of 8 18 April 2019 Nick Thompson, Plans Examiner, City of Aspen Phone 970-429-2757, Fax 970-920-5440 nick.thompson@cityofaspen.com Lauren Litchet, Permit Coordinator, City of Aspen lauren.litchet@cityofaspen.com City of Aspen Building Department 517 E. Hopkins Ave Garden Level Aspen, CO 81611 PROJECT: Mountain Forge Renovation and Addition ADDRESS: 230-234 E. Hopkins Ave, Aspen, CO 81611 PERMIT: 0089.2018.ACBK SUBJECT: Responses to Building Department Comments #1 Received January 9, 2019 CC: Madigan+Co (General Contractor) 1) Page: A0.3z Net Leasable & Net Livable Calculations: Is the garage for use by the commercial or residential spaces? Is it for use by more than one unit? If only for use by a single residential unit, no accessibility requirements will apply. If for use by more than one unit of for commercial, you must provide a van accessible space. 2015 IBC 1106. Response: Garage is for the exclusive use of one residential unit – the residence on level two. Therefore, no van accessibility required. 2) Page: A0.5z Fire Separation & Thermal Envelope Diagrams: Unless you can detail how the dwelling separation fire partition membranes will extend to the underside of floor or roof sheathing above with no structural penetrations, the 1-hour horizontal assembly will be required to extend across the entire footprint from outside wall to outside wall. Coordinate with structural to ensure no penetrations occur. 2015 IBC 708.4 Response: Per 2015 IBC 708.4, Fire Partitions are required to extend from the top of the floor/ceiling assembly to the underside of the floor or roof sheathing, slab or deck OR to the fire-resistance-rated floor/ceiling or roof/ceiling assembly above. The Fire Partition walls are intended to extend from the floor assembly to the underside of the floor/ceiling or roof/ceiling assembly (e.g. Horizontal Assembly per 2015 IBC 711.2) above. While the diagrams on A0.5z indicate minimum required separations between R2 and other occupancies, the reality is that typical floor/ceiling assemblies are either F2/A7.02 or F6/A7.02, which are both 1-hour rated. This can best be seen on the building section drawings on sheets A5.1, A5.2, and A5.3. Note that A0.5z has been updated with clarifications to indicate the 1-hour horizontal assemblies being continuous from wall to wall. 3) Page: A0.5z Fire Separation & Thermal Envelope Diagrams: This portion of the exit enclosure does not stack with the rest of the enclosure. Please thoroughly detail with section cuts going each way to show how you will maintain continuity of the fire barrier. No structural penetrations are permitted; revise structural as necessary. All supporting construction must also be fire rated. 2015 IBC 707. 04/26/2019 Page 2 of 8 Response: We have added the requested sections on sheet A6.22 (drawings 2 and 3). In addition, structural documentation was revised to accommodate separate, continuous structural support for the fire barriers and horizontal floor/ceiling assemblies. Revised structural plans include S2.0, S2.1, and S2.2. 4) Page: A0.5z Fire Separation & Thermal Envelope Diagrams: The corridor serving as exit access for the dwelling unit on the 2nd floor must have a minimum 1/2 hour fire rating. Walls must be constructed as fire partitions (extend uninterrupted to the roof sheathing above or to the underside of an uninterrupted ½ hour rated horizontal assembly) and doors must be 20 minute rated. (2015 IBC 1020.1, 716.5) Response: Diagrams on A0.5z has been updated to account for this. Door schedule on A8.2 updated to reflect change to one door that was not called out as 20-minute (door 1/215). Plan indications of 20- minute fire partitions were added to A2.2. Wall assembly detail W10 was edited to include a “Sim.” Condition note where the resilient channel can be omitted from the wall while maintaining a minimum 20-minute fire resistance rating (UL assembly U305, which is 1 hour rated). A typical head and sill detail at the interface between fire partitions and horizontal assemblies has been added as drawing 4/A7.04. 5) Page: A0.5z Fire Separation & Thermal Envelope Diagrams: You have numerous vents, piles, etc. running through all stories at the location of the mechanical rooms. Demonstrate how you will protect the penetrations/openings per 2015 IBC 712. If you use a shaft enclosure, detail the construction as a fire barrier. Response: The mechanical and plumbing chase is being protected using a shaft enclosure per IBC 713. Walls and horizontal assemblies will be constructed as fire barriers with continuity per IBC 713.5. The shaft enclosure will not be enclosed at the bottom for practical purposes and per IBC 713.11.3. See sections and enlarged plans added on sheet A6.26 detailing the continuity of 1-hour rated fire barriers through the shaft enclosure. Shaft wall assembly was added to A7.0C and A7.01. 6) Page: A0.5z Fire Separation & Thermal Envelope Diagrams: No Comment here. Response: No formal comment was associated with this clouded note. No response needed. 7) Page: A0.5z Fire Separation & Thermal Envelope Diagrams: The interior exit stair must be separated from the exit passageway by a 1-hour fire barrier and 60-minute fire rated door (2015 IBC 1023.1 and 716.5). Response: A 60-minute door has been added (door 3/104) to separate the interior exit stair from the exit passageway. Note that the door swings into the stair due to the low occupant load (less than 50) and to avoid a door swing conflict with door 1/104. The concrete shaft assembly W15/A7.02 (Sim.) is already designed as a minimum 1-hour fire barrier and is continuous from foundation to above the roof. 8) Page: A0.5z Fire Separation & Thermal Envelope Diagrams: Why is this portion of the exterior wall fire rated? Property line separation distance may be measured to the center of the street. (2015 IBC 202). Response: This was an error on the diagram and has been corrected on the updated sheet A0.5z. 9) Page: A0.5z Fire Separation & Thermal Envelope Diagrams: The walls, ceiling, and floor of the covered area just outside the exit must be protected with the same level of protection as the exit enclosure until the path of egress is open to the sky. Once open to the sky, the travel becomes exit discharge (egress court in this case due to the narrow width against the property line) requiring 1-hour rating for 10’ up until the alley. Please detail this and demonstrate in the fire ratings plan. 2015 IBC 1022, 1028. Response: See sections 2/A6.22 and 3/A6.22 demonstrating the continuity of the 1-hour ratings at the exit enclosure and exit discharge. The walls bordering the egress court are 1-hour rated (wall types W14/A7.02 and W8F/A7.01) for greater than 10’ above the egress court floor (slab on grade). 10) Page: A0.5z Fire Separation & Thermal Envelope Diagrams: Trash containers of 1.5 cubic yards or greater capacity require walls, openings, and overhangs within 5’ to be non-combustible (or comply with one of the exceptions). Demonstrate compliances. 2015 IFC 304.3.3 and 304.3.4. Response: Trash container sizes shall be limited to be less than 1.5 cubic yards to comply with 2015 IFC 304.3.3 and 2015 IFC 304.3.4. Any dumpster capacity of 1 cu yd (200 gallons) or greater shall be constructed of non-combustible materials or of approved materials per IFC 304.3.4. Specific trash containers shall be determined at later date by the owner along with their chosen waste collection provider. Notes have been added to indicate these requirements on sheet A2.1. 04/26/2019 Page 3 of 8 11) Page: A0.6z Plumbing & Egress Diagrams: Your design complies but here’s how we’d typically calculate: Commercial unit 1 has an occupant load of less than 15 and an exclusive single user toilet room. This satisfies the toilet requirements for unit 1. (2015 IBC 2902.2). Commercial unit 7 has the same situation. The total number of occupants minus the residential units and commercial units 1 and 7 is 34. 34/2 = 17 males, 17 females. Requirement is for 1 toilet and 1 lav for males, and one each for females. Single user unisex toilet rooms may be used instead as you show. Response: Thank you for the clarification. The calculation has been revised accordingly. Note that we have provided accessible toilet rooms in these individual units per comments later in this document (comments 18, 20). 12) Page: A0.6z Plumbing & Egress Diagrams: Add an egress diagram for the occupied roof deck. If the roof deck is only for use by the free market residential unit, it may be considered an R2 occupancy. If it is for use by more than one unit or by commercial, it will be considered an assembly occupancy and will be required to be fully accessible. This includes the spas if commercial. Response: We have updated A0.6z to include the requested egress diagram of the roof deck. This is intended for exclusive use of the free market unit (R2 occupancy). 13) Page: A0.6z Plumbing & Egress Diagrams: The designated trash area of 105 sqft appears to encroach on the minimum required egress width of 44” (2015 IBC 1028.4) Response: The designated trash area of 105 SF is simply an area that is required to remain clear for access to trash and recycling receptacles and therefore shall not impact the required 44” egress width. See added note on A2.1. 14) Page: A0.6z Plumbing & Egress Diagrams: Include occupant loads for the mechanical rooms at 300 sqft per person per 2015 IBC 1004. Include these occupants in your plumbing calcs as well. Response: Sheet A0.6z has been updated per this requested. 15) Page: A1.2 Proposed Snowmelt & REMP Sheet: Provide documentation showing that the proposed spas are either CEC or APSP-14 listed. Otherwise, it will be subject to RREMP. Ord. 40, 2016. Response: The roof deck configuration has been adjusted for a different spa configuration. Please see updated A1.2, A2.3. R-REMP calculation has been adjusted to indicate the revised specifications. 16) Page: A2.0 Proposed Basement Floor Plan: Detail the kitchenette in commercial unit 4 to demonstrate compliance with accessibility requirements. 2015 IBC 1109.4. Response: Kitchenette has been revised to meet 2015 IBC 1109.4. See updated sheet A2.0. Passthrough kitchen provides 44” clearance between millwork, 34” high countertop, parallel approach to sink and accessible appliances. 17) Page: A2.0 Proposed Basement Floor Plan: Provide handrails on both sides of all stairs. 2015 IBC 1011.11 Response: Handrails at 36” above nosing have been added to plan and 42” high guardrails as required. See revised A6.23 for more detail. Note that one exterior door/stair out of Commercial Unit #4/001 has been removed, so there is only one stair documented. 18) Page: A2.1 Proposed Level One Floor Plan: Commercial 1 bathroom must be accessible. Demonstrate compliance (including the width of the door which you have not specified in the door schedule). 2015 IBC 1109.2. Response: Door approach, maneuvering clearance, turning space, and clear floor space has been added to plan. Door 1/101 noted as 3’-0” wide on door schedule A8.2. 04/26/2019 Page 4 of 8 19) Page: A2.1 Proposed Level One Floor Plan: If garage must be accessible (see comment on Net Leasable drawings), door 1/103 must also be accessible. Provide door maneuvering clearances. ICC A117.1-2009 section 404.2.3.1 Response: Garage is for the exclusive use of one residential unit, therefore door 1/103 is not required to be accessible. 20) Page: A2.2 Proposed Level Two Floor Plan: Restroom 222 must be accessible. Demonstrate compliance. 2015 IBC 1109.2. Response: Restroom 222 modified for accessibility. Door approach, maneuvering clearance, turning space, and clear floor space has been added to floorplan 1/A2.2. 21) Page: A2.2 Proposed Level Two Floor Plan: Revise to correctly show door maneuvering clearances at doors 1/214 and 1/213. ICC Response: Janitor Closet 213 is designated as an employee work area per ADA Access Board Section 203.9. Work areas require access for approach, entry, and exit. Turning space is not required. Door 1/213 has been increased to 32” width and clear space has been provided at push and pull side. Door 1/214 has been removed to provide greater access to the space. 22) Page: A2.3 Proposed Roof Plan: Provide installation instructions for the gas fire pit and demonstrate compliance with the required clearances. Response: See roof top firepit and planter drawings on A6.14 as well as included cut sheet for the prefabricated linear gas burner. 23) Page: A2.3 Proposed Roof Plan: Detail the height of the parapet above the hot tub edge. If the hot tub edge is 18" or less in width, then the parapet must be at least 18" above it. If the width is greater than 18", the guard must be at least 42" above per City Policy. Response: An 18” glass guard has been provided when pool edge is less than 18”, 42” glass guard has been provided where pool edge is more than 18” - See sections 2/A5.2 and 2/A5.3 for additional information. 24) Page: A2.3 Proposed Roof Plan: Provide riser height of the steps at the roof deck and provide handrails. Response: See revised floor plan A2.3 for new stair and handrail configuration. Riser heights have been noted on A2.3. Handrails and guards have been provided as required per the R2 occupancy of the roof deck. At the proposed deck elevation changes where three or fewer risers are provided, no handrail is required (2015 IBC 1011.11 Exception 4). 25) Page: A3.0 Proposed Basement RCP: Show the location of smoke alarms and carbon monoxide detectors on the RCPs per 2015 IBC 907.2.11 and Municipal Code Tittle 8. Response: Smoke and carbon monoxide detectors are shown on Fire Protection drawings F0.00-F1.03. Smoke and carbon monoxide detector locations have been duplicated on RCPs A3.0-A3.2 for convenience. 26) Page: A4.2 Proposed Exterior Elevations: Provide a diagram of the north elevation demonstrating compliance with 2015 IBC 705.8. Be sure to measure each floor separately. Response: See 1.1/A4.2 for diagram. 27) Page: A5.2 Proposed Building Sections: The dwelling separation needs to be continuous. Either make R2 1 hour fire rated or detail another method for keeping a fire from spreading in the direction of the arrow I've drawn. 2015 IBC 708, 711. Response: R2 has been modified to provide an alternative, 1-hour fire-rated version where required. The designation R2F has been created for this situation. The callout has been adjusted on the building section drawings. 04/26/2019 Page 5 of 8 28) Page: A5.2 Proposed Building Sections: Provide parapets at all exterior walls required to be rated due to proximity to property line (or demonstrate how you meet one of the exceptions). 2015 IBC 705.11. Response: Existing non-conforming condition (low existing parapet height on a portion of the existing building beyond the setback line) should not be expanded per City of Aspen Zoning Dept. However, a parapet conforming to the min. 30” height per IBC 705.11.1 is not required since the roof/ceiling assembly (R2/A7.03) is 1-hour rated and is comprised of roofing materials which are not less than Class B rated, which conforms to 2015 IBC 705.11 exception 4. 29) Page: A5.2 Proposed Building Sections: This wall is a dwelling separation wall. This makes it a fire partition which must extend to the underside the roof sheathing without interruption by structure OR to the underside of a 1 hour fire rated horizontal assembly ceiling. Also, please provide a callout for the wall assembly type. 2015 IBC 708.4. Response: This wall has been called out on the plan drawing A2.2 as a fire partition. The wall assembly for all walls in Corridor 2/216 is W10/A7.01. A head detail has been added as 4/A7.04. 30) Page: A6.21 Enlarged Plans Main Stair: Provide a barrier at the level of exit discharge per 2015 IBC 1023.8. Response: See revised plans 2/A6.21 for barrier location. 31) Page: A6.21 Enlarged Plans Main Stair: Where handrails are not continuous between flights, the handrails must extend horizontally not less than 12 inches beyond the top riser and continue to slope for the depth of one tread beyond the bottom riser. Landings may not be encroached on so you may need to increase the size of the stair enclosure. 2015 IBC 1014.6. Response: Stairs have been reconfigured to comply with handrail requirements. See revised plans 1 and 2/A6.21. 32) Page: A6.22 Section at Main Stair: Provide riser heights. 2015 IBC 1011.5. Response: See 1/A6.22. Riser heights are noted in dimension string at each landing, example: 10R @ 6-13/16” = 5’-8” 33) Page: A6.23 Courtyard Stair Drawings: Provide riser heights. 2015 IBC 1011.5. Response: See 1/A6.23. Riser heights are noted in dimension string under landing, example: 16R @ 6- 13/16” = 9’-1 ¼” 34) Page: A6.24 AHU Stair Drawing: Provide riser heights. 2015 IBC 1011.5. Response: See 3/A6.24. Riser heights are noted in dimension string to the right of stairs, example: 7R @ 7-1/2” = 4’-4 7/16” 35) Page: A7.0A Code Listed Assemblies: This assembly requires carpet to achieve the listed STC. Choose another assembly to match your floor finish. Response: We have selected a new, tested assembly to meet this requirement. See updated assembly ICC-ESR-3207 on sheet A7.0B, along with manufacturer’s sound test data sheets. 36) Page: A7.01 Building Assemblies Response: No comment provided 37) Page: A7.02 Building Assemblies: Dwelling separation horizontal assemblies also require an IIC rating of 50 or greater. Demonstrate how assemblies F2 and F6 will comply. 2015 IBC 1207. Response: F2 and F6 have been updated to reflect a revised, tested assembly which meets the requirements of 2015 IBC 1207 (min. STC and IIC of 50). 38) Page: A7.10 Details: Handrail extensions must return. 2015 IBC 1011.11. Response: Handrail returns to guardrail post, see 1/A6.23 and 8/A7.10. 04/26/2019 Page 6 of 8 39) Page: A8.1 Window Schedule: Windows serving common and commercial spaces that face East, South, and West must have solar heat gain coefficient of 0.45 or less if the projection factor is less than 0.2. 2015 IECC C402.4.3. Response: See general note 8 on A8.1. All commercial windows to have SHGC .45 or lower. 40) Page: A8.2 Door Schedule: Door 1/107 opens into an exit discharge egress court with a width of less than 10’, requiring the door to have a 45 minute fire rating. 2015 IBC 1028.4.2. Response: Door 1/107 has been noted with 45-minute fire rating. See revised door schedule A8.2. 41) Page: A8.2 Door Schedule: Indicate the hardware and locking arrangements for the interior exit stair enclosure. Doors must be openable from both sides without a key unless one of the exceptions is met. This includes door 1/303 and 2/104, in addition to the other stair doors. 2015 IBC 1010.1.9.11. Response: See door hardware grouping list and updated door schedule on A8.2. 42) Page: A8.2 Door Schedule: Doors serving the exit enclosure stair must be 60 min fire rated. 2015 IBC 716.5. Revise 1/010, 1/104, 1/217, 1/303. Response: See revised door schedule A8.2, 1/010, 1/104, 1/217, 1/303 noted with 60-minute fire rating. 43) Page: A9.1 Proposed Interior Elevations: Show and dimension clear spaces at each toilet and lavatory. Also show a clear space beyond the swing of the door. ICC A117.1-2009 chapter 6. Response: Clear spaces have been diagramed and dimensioned at toilet and lavatories. See revised keyplans A, B, and C / A9.1 44) Page: 1 Comcheck: Provide a lighting schedule and cutsheets for each fixture. The cutsheets should have the maximum wattage highlighted (and this should match the comcheck) and listing by a nationally recognized testing lab highlighted. Response: Lighting cut sheet for each known fixture has been provided. Wattage for known fixtures has been highlighted. 45) Page: 1 Comcheck: Include the S2 and S6 fixtures from the common restrooms. Response: Fixtures have been included. 46) Page: 1 Comcheck: Provide lighting comcheck for the commercial units. Response: Lighting comm check for the commercial units has been generated. 47) Page: 1 Comcheck: I count 51 R3 and R4 fixtures in common areas. Revise comcheck. Response: Fixture count has been revised. 48) Page: 2 Comcheck: I count 11 EX3 fixtures. Revise concheck. Response: Fixture count has been revised. 49) Page: 2 Comcheck: I count 4 EX4 fixtures. Revise comcheck. Response: Fixture count has been revised. 50) Page: [6] 18009 e1-E2.0: FYI note: Dimmer Switches. General-use dimmer switches shall be used only to control permanently installed incandescent luminaires unless listed for the control of other loads and installed accordingly. no dimmers allowed Response: Okay. 51) Page: [7] 18009 e1-E2.1: These panels penetrate the dwelling separation wall. Demonstrate how you will maintain the 1 hour fire and STC 50 rating. 2015 IBC 420, 1207. Response: Panel AHU has been moved to the lower level of the housing unit at the bottom of the stairs. Panel Comm#1 has been moved to its current location on the electrical plans. 04/26/2019 Page 7 of 8 52) Page: [7] 18009 e1-E2.1: Section 420.7 Electrical vehicle charging. In Group R Occupancies, 3 percent of the total number of parking spaces, but not less than one, shall be electric vehicle charging stations (EVCS) capable of supporting future EVCS and shall be identified on the construction documents. Construction documents shall indicate the location of the proposed EVCS. At least one EVCS shall be located in common use areas and available for use by all residents. 420.7.1 Single EVCS required. When only one EVCS space is required, a 208/240-volt individual branch circuit or a listed raceway to accommodate a future individual branch circuit shall be installed. The raceway shall not be less than trade size 1 (nominal 1-inch inside diameter). The raceway shall originate at the main service or subpanel and shall terminate into a listed cabinet, box or other enclosure in close proximity to the proposed location of the electric vehicle charger. Construction documents shall identify the raceway termination point. The service panel or subpanel circuit directory shall provide capacity to install a 40- ampere minimum dedicated branch circuit and space(s) reserved to permit installation of a branch circuit overcurrent device. Electrical vehicle supply equipment shall be installed in accordance with NFPA 70. Response: One space is classified as electric vehicle charging station. 1-1/2” conduit has been specified as well as a 50A2P circuit has been reserved on panel F1. 53) Page: [8] 18009 e1-E2.2: Hallways. In dwelling units, hallways of 3.0 m (10 ft) or more in length shall have at least one receptacle outlet. Response: With architectural changes, receptacles have been places as required by the NEC. 54) Page: [8] 18009 e1-E2.2: Small-appliance branch circuits shall be permitted to supply receptacle outlets in the kitchen and other rooms specified in 210.52(B)(1). This does not comply Response: Receptacle has been removed. 55) Page: [8] 18009 e1-E2.2: Hallways. In dwelling units, hallways of 3.0 m (10 ft) or more in length shall have at least one receptacle outlet. Response: With architectural changes, receptacles have been places as required by the NEC. 56) Page: [9] 18009 e1-E2.3: Circulation and Sanitation System, Location. Receptacles that provide power for water-pump motors or for other loads directly related to the circulation and sanitation system shall be located at least 1.83 m (6 ft) from the inside walls of the pool. Response: Receptacle has been moved and has been located per NEC requirements. 57) Page: [9] 18009 e1-E2.3: Radiant Heating Cables Not Permitted. Radiant heating cables embedded in or below the deck shall not be permitted. Response: Radiant heating has been removed. 58) Page: [9] 18009 e1-E2.3: Radiant Heating Cables Not Permitted. Radiant heating cables embedded in or below the deck shall not be permitted. Response: Radiant heating has been removed. 59) Page: [9] 18009 e1-E2.3: Receptacles shall not be located less than 1.83 m (6 ft) from the inside walls of a storable pool, storable spa, or storable hot tub. Response: Receptacle has been moved and located per NEC requirements. 60) Page: [9] 18009 e1-E2.3: Circulation and Sanitation System, Location. Receptacles that provide power for water-pump motors or for other loads directly related to the circulation and sanitation system shall be located at least 1.83 m (6 ft) from the inside walls of the pool. Response: Section 680.8(A) states for other than storable pools, the flexible cord shall not exceed 900mm (3ft). 61) Page: [10] 18009 e1-E3.0: Provide time switch controls to control lights in all locations without occupancy sensors as called for by 2015 IECC C405.2.2. Response: Time switch controls have been provided in all locations required by 2015 IECC C405.2.2. 04/26/2019 Page 8 of 8 62) Page: [10] 18009 e1-E3.0: Provide occupancy sensor controls to control lights in all locations called for by 2015 IECC C405.2.1. Response: Occupancy sensor controls have been provided in all locations required by 2015 IECC C405.2.1. 63) Page: L-101 ROOF DECK•50MATERIALS•50PLAN: The architecturals do not show a sauna. Provide full detail and demonstrate compliance with 2015 IMC sauna provisions or eliminate from landscapes. Response: Sauna has been removed. 64) Page: [1] 18009-M1-M-001: Provide a mechanical comcheck for the mechanical equipment. Response: Mechanical comcheck for the commercial units has been generated. 65) Page: [2] 18009-M2-M-110: If this is to become a catering kitchen, provide shaft enclosure(s) for kitchen hood ducts. Response: There is no intention to turn this room into a kitchen where a range will be installed. Room name has been updated. 66) Page: [2] 18009-M2-M-110: Provide a fire damper where the outside air duct penetrates the dwelling separation. 2015 IBC 717. Response: Updated, see plans. 67) Page: [2] 18009-M2-M-110: Indicate the CFM of outside air provided to each commercial unit. Provide calculations demonstrating compliance with 2015 IMC 403. Response: Updated, see sheet M-001 for outdoor ventilation calcs. 68) Page: [4] 18009-M2-M-112: This electric unit heater penetrates the dwelling separation. Demonstrate how you will maintain the continuity of the 1 hour fire and STC 50 rating. 2015 IBC 420, 1207. Response: Unit moved out of dwelling separation wall, see plans. 69) Page: [4] 18009-P2-P-112: These overflow drain outlets could be confused with the primary drain outlet location. The intent is for a building occupant to be able to notice if water is flowing from an overflow and know that there is a problem with the primary system. (2015 IPC 1108) Response: We updated the downspout model for the overflow to differentiate from the primary drain. 70) Page: [5] 18009-P2-P-113: Show where this overflow drains to. Must drain to a conspicuous above grade location. (2015 IPC 1108) Response: Updated, see plans. 71) Page: S4.0 DETAILS: Provide micropile design drawings. If micropiles are to support a permanent load, they are permanent micropiles which must be designed with a minimum safety factor of 2 (2015 IBC 1810.3.3.1.7). Response: The micropile shoring walls are temporary. A shoring design drawing set is included with these responses. 04/26/2019