HomeMy WebLinkAboutFile Documents.230 E Hopkins Ave.0046-2020-BCHO (10)0046-2020-BCHO_BuildingComments_1
Subject: PlanCheck
Page: [1] A7-01
Page Index: 5
Author: nickt
Color:
File Name: 230 E. Hopkins Ave_Assemblies_2020-07-29.pdf
Closed cell spray foam requires
a thermal barrier; 2015 IBC
2603.4.
230 E. Hopkins Ave_Assemblies_2020-07-29.pdf (2)
Subject: PlanCheck
Page: [8] A7-03
Page Index: 9
Author: nickt
Color:
File Name: 230 E. Hopkins Ave_Assemblies_2020-07-29.pdf
Any change in snowmelted area
should be shown on revised
mechanical and snowmelt plans.
Subject: PlanCheck
Page: A0.6z PLUMBING & EGRESS DIAGRAMS
Page Index: 4
Author: nickt
Color:
File Name: 230 E. Hopkins Ave_Mtn Forge_Change Order
001_2020-06-25.pdf
This section should only show
occupant counts that have their
own toilet room requirements
taken care of. The mechanical
room does not so remove it. This
will leave 39 occupants
remaining- 20 female, 20 male
230 E. Hopkins Ave_Mtn Forge_Change Order 001_2020-06-25.pdf (2)
Subject: PlanCheck
Page: A3.0 PROPOSED BASEMENT RCP
Page Index: 7
Author: nickt
Color:
File Name: 230 E. Hopkins Ave_Mtn Forge_Change Order
001_2020-06-25.pdf
Provide an updated interior
lighting COMcheck
IOR CLADDING
R3.8 CI / R20 CAVITY MIN.SCALE:
WALL ASSEMBLY (EXISTING & PROPOSED)
RETAINING/SITE WALL
1 1/2" = 1'-0"R10 CI MIN. BELOW GRADE
W4
A7.01
2x WOOD FRAMING, RE: STRUCT
INTERIOR FINISH
RE: FINISH
SCHEDULE
INTERIOR RATED
ASSEMBLY
EXT. CLADDING - RE: ELEVATIONS,
INSTALL PER MFGR REQUIREMENTS
AND PER APPROVED MOCK-UP
1.@ RAINSCREEN METAL:
PROVIDE CONCEALED
FASTENERS PER MFGR
2.@ STANDING SEAM METAL:
PROVIDE 1/2" MIN.
CONTINUOUS PRESSURE
TREATED PLYWOOD BACKING
EXTERIOR
5/8" TYPE X FIBERGLASS MAT
EXTERIOR GYPSUM SHEATHING,
INSTALL PER UL LISTING AT W8F
LOCATIONS ONLY, OMIT FROM ALL
OTHER VARIATIONS
MINERAL WOOL BATT INSULATION
TO FILL ENTIRE CAVITY (R-20 MIN)
5/8" TYPE X OR
TYPE C GYPSUM
BOARD, INSTALL PER
UL LISTING
1.5" ROCKWOOL COMFORTBOARD
CONTINUOUS INSULATION - R-6
WEATHER RESISTIVE BARRIER &
AIR BARRIER
VERT. 1X SOLID P.T. WOOD, 3/4 " EXT.
PLYWD STRAPPING OR PAINTED
METAL FURRING CHANNELS (RATED
FOR SIDING SELECTION), ATTACH TO
STUDS 16" O.C. OR PER MFGR REQ'S
SHEATHING PER STRUCTURAL, TYP.
EXISTING CONCRETE WALL
(8" MIN = MIN. 1 HOUR FIRE
RATED)
SPRAY APPLIED
CLOSED-CELL FOAM - FILL
CAVITY
GROUTED CMU DOWN
TO EXIST. FOOTER
NEW
1/2" FRAMING
GAP VARIES
FRAMED WALL RE: STRUCTURAL
MR - MOISTURE RESISTANT GYPSUM
BOARD ON ALL WALLS SUBJECT TO
HIGH HUMIDITY
CB -CEMENTITIOUS BACKER UNITS ON ALL
TUB/SHOWER WALLS TO RECEIVE TILE
SOUND ATTENUATING MINERAL WOOL
BATT INSULATION AT ALL PARTITIONS,
FRICTION FIT FULL STUD DEPTH TYP.
5/8" TYPE 'X' GWB EACH SIDE -OMIT AT
INSIDE OF FURRING WALL LOCATIONS
USE QUIET ROCK SHEATHING (ES-MR
MOLD RESISTANT WHERE APPLICABLE)
WHERE RESTROOMS ARE ADJACENT
TO LIVING SPACE. ONLY USE WHERE
CEMENT BOARD IS NOT REQUIRED
HEAD JUNCTION
CEILING PERIMETER TAPE BY KINETICS
NOISE CONTROL BOTH SIDES OF WALL
FIRE RATED NON-HARDENING RESILIENT
ACOUSTICAL SEALANT @ GWB PERIMETER
BOTH SIDES OF WALL (TYP)
DRYWALL TAPE AND MUD
SOLID 2X BLOCKING (SIM @ FLOOR
JOIST/ROOF RAFTER JUNCTION)
DOUBLE WOOD TOP PLATE CEILING
MEMBRANE PENETRATION ALLOWED
PER IBC 714.4.2 EXCEPTION 7
ACOUSTIC ISOLATION PAD CONT. @
TOP PLATE (TYP); WALLMAT BY
KINETICS OR EQUAL
1 HOUR CEILING ASSEMBLY
POLYETHYLENE
VAPOR RETARDER,
CONTINUOUS, LAP
TAPE & SEAL ALL
JOINTS
NOTE:
APPLY BEAD OF ACOUSTICAL SEALANT
AT PERIMETER OF GWB @ HEAD AND
SILL JUNCTIONS TYP.
W8(F): PROVIDE 1 HR PROTECTION
@ PENETRATIONS
STUDPER PLANS
TYP. BASE TRIM
3(F) "SIM" - 1-HOUR FIRE RATED ASS'Y
EXIST. CMU WALL ASSEMBLY AS SHOWN
CEPT:
MIT FURRING, THERMAX INSULATION AND
ADDING AT EXTERIOR SIDE OF EXISTING CMU
ALL DUE TO PROXIMITY TO LOT-LINE
INTED EXTERIOR FINSH PER SCHED.
ALL TYPE 3.1(F) 1-HOUR FIRE RATED
NEW CMU WALL ASSEMBLY AS SHOWN EXCEPT:
GRADE TO 2" THERMAX (CI - R13) @ EXTERIOR
OUR PROTECTION @
ONS @ RATED WALL LOCATIONS
W8 SIM. LOCATIONS:
EXT. FURRED WALL
NO FIRE RATING
REQUIRED
INSTALL PER
ASSEMBLY SHOWN
EXCEPT:
1. NO INTERIOR GWB
2. NO VAPOR BARRIER
3. REPLACE BATT
INSULATION W/ 6" MIN
(R-39 MIN) CLOSED
CELL SPRAY FOAM
INSULATION
4. NO EXTERIOR
ROCKWOOL INSUL.
5. NO 3/4" EXTERIOR
STRAPPING/FURRING
ACOUSTIC ISOLATION SILL PAD CONT.
@ BOTTOM PLATE (TYP)
W8(F): 1-HOUR FIRE RATED
ASSEMBLY, INSTALL PER UL-U305 EXCEPT:
1.EXT. PLYWOOD SHEATHING
2.VAPOR BARRIER
3.WRB, EXT. INSULATION & SIDING (ADDITIONAL)
@ W8(F)SIM LOCATION REPLACE CAVITY INSULATION W/
R-39 SPRAY APPLIED CLOSED CELL INSULATION,
ENSURE INSTALLATION OF 5/8" TYPE X FIBERGLASS MAT
EXTERIOR GYPSUM SHEATHING, AND REMOVE VAPOR
RETARDER, EXTERIOR FURRING AND CONTINUOUS
INSULATION, EXTERIOR FINISH TO REPLACE EXISTING
@ W8 LOCATIONS: NO FIRE RATING REQ'D
INSTALL PER ASSEMBLY SHOWN EXCEPT:
5/8" TYPE 'X' GLASS MAT EXTERIOR SHEATHING
10
CO 001
Revision:
CONSTRUCTION DO
08.28.2018
80% PRICING
02.08.2019
CD/PRICING SET
04.18.2019
CONSTRUCTION DO
03.08.2019
ASI-001
05.22.2019
ASI-002
06.11.2019
STAIR REVISION
06.28.2019
CONSTRUCTION DO
08.16.2019
ASI-003
12.20.2019
ASI-004
06.29.2020
CHANGE ORDER 00110
CO 001
REVISION 005
01.31.2020
REVISION 009
06.09.2020
Closed cell spray foam
requires a thermal
barrier; 2015 IBC
2603.4.
REINFORCED CONCRETE SLAB - RE:
CIVIL & LANDSCAPE
HIGH-DENSITY SUB-SLAB RIGID
INSULATION - R-20 MIN.
COMPACTED BASE PER GEOTECH
RADIANT SNOWMELT TUBING TIED TO
REBAR AS REQUIRED - RE: MEP -
PROVIDE TUBING COVERAGE PER
MANUFACTURER
RE: LANDSCAPE FOR SURFACE
TEXTURE AND JOINTING, TYP.
EXTERIOR
RA
T
E
D
A
S
S
E
M
B
L
Y
DR
O
P
C
L
G
VA
R
I
E
S
RE
:
R
C
P
S
MECH. SPACE
HYDROTECH HYDROFLEX 30
PROTECTION COURSE
(SLOPED)
5/8" SECUROCK GLASS
MAT ROOF SUBSTRATE
BOARD (SLOPED)- GC
OPTION TO OMIT IF NOT
REQUIRED TO PROTECT
SLOPPED INSULATION
HYDRODRAIN
SETTING BED OR 1 12" CONC. TOPPING SLAB (SLOPED)
RADIANT SNOWMELT TUBING PER
MECHANICAL FOR LOCATIONS
SLOPE TO DRAIN
RE: PLANS
1/8" PER FT. MIN.
NOTE:
SEE 4/A7.04 FOR TYPICAL PARTITION HEAD/BASE DETAIL
REQ'S @ HORIZONTAL ASSEMBLIES
ANY REQUIRED STUD
FRAMING TO BE METAL
OR P.T. WOOD, RATED
FOR EXTERIOR
LOCATIONS
Any change in
snowmelted area
should be shown on
revised mechanical
and snowmelt plans.
PROPERTY LINE
PRO
P
E
R
T
Y
L
I
N
E
PROPERTY LINE
10'-0"SETBAC
PRO
P
E
R
T
Y
L
I
N
E
DN UP
FEC
SCALE:
PROPOSEDLEVEL TWO FLOOR PLAN
3/32" = 1'-0"
3
A0.2z
COMM. #7
482 SF
5 OCCUPANTS
39'-7" MAX. PATH OF
TRAVEL
STAIR
RES. #1
2,384 SF
12 OCCUPANTS
97'-1" MAX. PATH OF TRAVEL*
* PER 1006.3.2(1) SECOND STORY R-2 MAXIMUM
COMMON PATH OF TRAVEL = 125'
PER IBC 2015 1006.2.1 TWO EXITS AND
EXIT ACCESS DOORWAYS FROM ANY
SPACE SHALL BE PROVIDED WHERE
THE DESIGN OCCUPANT LOAD OR
COMMON PATH OF EGRESS TRAVEL
DISTANCE EXCEEDS THE VALUES
LISTED IN TABLE 1006.2.1
PLUMBING FIXTURE CALCULATIONS
PLUMBING FIXTURES :
OCCUPANCY: BUSINESS GROUP B
COMM. #8
197 SF
2 OCCUPANTS
34'-2" MAX. PATH OF TRAVEL
RES. #1
1,534 SF
8 OCCUPANTS
57'-8" MAX. PATH OF TRA
MECH. #3
53 SF
1 OCC.
16' MAX. PATH OF
TRAVEL
OCCUPANTS / REQ'D PROVIDED
COMM. #4 15 OCCUPANTS 1 EXCLUSIVE SINGLE USER TOILET ROOM PROVIDED
COMM. #7 5 OCCUPANTS 1 EXCLUSIVE SINGLE USER TOILET ROOM PROVIDED
RES. #1 22 (12 + 8 + 2) OCCUPANTS
AHU 5 (3+2) OCCUPANTS
MECHANICAL 4
34 OCC. REMAINING (17 MALE / 17 FEMALE)
WATER CLOSETS 2 WC (1 MALE, 1 FEMALE)2X SINGLE USER UNISEX TOILET ROOMS PROVIDED
LAVATORIES 2 LAV (1 MALE, 1 FEMALE)2X SINGLE USER UNISEX TOILET ROOMS PROVIDED
WATER COOLER 1 PER 100 / 1 REQUIRED 1 PROVIDED
20 OCCUPANTS
OCCUPANT LOAD CALCULATIONS
10CO 001
SPACE FUNCTION OF SPACE(per IBC Table 1004.1.1)UNIT PEROCCUPANT MEASUREMENTTYPE AREA
ROOMOCCUPANTLOAD
COMM. #5 BUSINESS 100 SF NET 124 2
100 SF NET 529 6
MECH. #1 MECHANICAL 300 SF NET 129 1
AHU - BASEMENT RESIDENTIAL 200 SF NET 587 3
AHU - LEVEL ONE RESIDENTIAL SF NET 366 2
COMM. #1 BUSINESS 1,274 13
COMM. #2 BUSINESS SF NET 324 4
200
100
100
COMM. #3 BUSINESS SF NET 622 7100
RES. #1 - GARAGE GARAGE
RES. #1 RESIDENTIAL SF NET 2,384 12200
COMM. #7 SF NET 482 5100
200 2361
COMM. #4 BUSINESS 100 SF NET 1,499 15
COMM. #6 BUSINESS
SF NET
SF NET
BUSINESS
COMM. #8 BUSINESS
SF NET
SF NET100 197 2
53 1
TOTAL OCCUPANTS 85
RES. #1 - ROOF RESIDENTIAL SF NET200 1,534 8
MECH. #3 MECHANICAL 300
MECH. #2 MECHANICAL 300 SF NET 51 1
ELEC. AND COMM.MECHANICAL 300 SF NET 65 1
File
P
a
t
h
:
P
:
\
P
r
o
j
-
2
0
1
7
\
2
1
7
1
8
.
0
0
_
M
t
n
F
o
r
g
e
\
0
6
_
D
o
c
u
m
e
n
t
a
t
i
o
n
\
0
1
_
D
r
a
w
i
n
g
s
\
F
A
R
S
t
u
d
y
(
t
e
m
p
)
\
2
1
7
1
8
_
A
0
-
6
z
.
d
w
g
Plot D
a
t
e
/
T
i
m
e
:
J
u
n
e
2
5
,
2
0
2
0
-
4
:
0
4
p
m
This section should
only show occupant
counts that have their
own toilet roomrequirements taken
care of. The
mechanical room doesnot so remove it. Thiswill leave 39
occupants remaining-
20 female, 20 male
UP
UP
FD
FD
FD
EX5
S1 S1
R1 E
T1
T1 T1
R3
8'-7"
8'-9"
8'-5"
8'-1"
COMM.UNIT 4
COMM.UNIT 5
007
ELEVATOR
1
MECH. 1CHASE / EQUIP. RM.
008
STAIR #1
010
COMM.UNIT 6
009
COMM.UNIT 4
016
MECH. 2
011
T1T1
DE
P
O
C
K
E
T
R3 R3 R3 R3
EF2
P3
P3
R3
R3R3R3R3
R3
7'-9"
EXIT
IT ROOM
012
CORRIDOR
017
COMM UNIT 4a
014
RESTROOM
015
EXIT
R3 R3
CLOSET
009a
MECH.
009b
R3R3
R3
R3 R3
R3 R3
R3 R3
R3 R3
TR
R3 R3R3
TR2
TR1
TR1
TR2
P2P2P2P2
S3
S3
S4
S4
R4
R4
R3R3R3R3
S4 S S4
R1 R1
EXITR3 R3
R3 R3
S5
S5S5
R4 R4R4
R3
8'-7"
9'-7"
8'-5"
8'-5"
7'-3"
8'-3"
EF2
EF2
7'-7"
2'-0"
R3
R3
ALIGNCLG
SOFFIT&
COFFER
W/ BAR
EACH
SIDE
S4 S4
R3
S4
2'-
4
"
2'-4"
2'-
4
"
R3 R3R3
R3
T1
R3
10
CO 001
10
CO 001
R4
EXIT
7'-9"
STORAGE
013
Provide an updatedinterior lightingCOMcheck
RB Response 01.13.2021: See separate attached documents for additional information and clarification.
Wall type W8 (sim) shall only be installed as an exterior furred wall and installed over either an 8” concrete or 7 5/8” CMU (wall type
W14 sim. / A7.02), located along Grid 6 at the concrete stair core. Concrete and CMU shall act as thermal barrier.
RB Response 01.13.2021:
No change to snowmelted area. Radiant tubing shown in assembly to ensure GC coordinated all necessary snowmelt locations per
Permit approved plans.
RB Response 01.13.2021: See separate attached documents for additional information and clarification.
See updated sheet A0.6z and plumbing calculations.
Updated Comm. Unit occupant count, 34 remaining occupants – 17 female, 17 male
RB Response 01.13.2021: See separate attached documents for additional information and clarification.
See updated lighting COMcheck
02/01/2021