Loading...
HomeMy WebLinkAboutFile Documents.230 E Hopkins Ave.0046-2020-BCHO (11)0046-2020-BCHO_BuildingComments_2 Subject: PlanCheck Page: A2.0 PROPOSED BASEMENT FLOOR PLAN Page Index: 6 Author: nickt Color: File Name: 90.230 E. Hopkins Ave_Mtn Forge_Change Order 001.20210405.pdf Update structurals to show this change to the foundation wall alignment. 90.230 E. Hopkins Ave_Mtn Forge_Change Order 001.20210405.pdf (13) Subject: PlanCheck Page: A2.0 PROPOSED BASEMENT FLOOR PLAN Page Index: 6 Author: nickt Color: File Name: 90.230 E. Hopkins Ave_Mtn Forge_Change Order 001.20210405.pdf Provide interior elevations and enlarged plan to demonstrate accessibility as you have done for the other toilet rooms. Subject: PlanCheck Page: A2.1 PROPOSED•50LEVEL ONE•50FLOOR PLAN Page Index: 7 Author: nickt Color: File Name: 90.230 E. Hopkins Ave_Mtn Forge_Change Order 001.20210405.pdf Coordinate with plumbing drawings which only show 2 roof drains in this area (main and overflow). Subject: PlanCheck Page: A2.1 PROPOSED•50LEVEL ONE•50FLOOR PLAN Page Index: 7 Author: nickt Color: File Name: 90.230 E. Hopkins Ave_Mtn Forge_Change Order 001.20210405.pdf Update kitchen plan to match A9.16 drawings. Subject: PlanCheck Page: A2.1 PROPOSED•50LEVEL ONE•50FLOOR PLAN Page Index: 7 Author: nickt Color: File Name: 90.230 E. Hopkins Ave_Mtn Forge_Change Order 001.20210405.pdf Provide sheet A7.04A and update elevations and door and window schedules and any other applicable drawings to match new door design. Cloud this change and any others on all applicable sheets. Provide U-factor (max 0.37 per 2015 IECC C402.4). Provide a threshold detail (max 1/2" per 2015 IBC 1010.1.7). ME N T O F E X I S T I N G C M U ID 4 - G R I D 7 ) ME N T O F E X I S T I N G S T U D ID 2 - G R I D 4 ) ID 2 - G R I D 6 ) ME N T E O F E X I S T I N G E X T E R I O R S T U D PROPERTY LINE MECH. 2 011 ELEVATOR IT ROOM 012 STAIR #1 010 UP FD FD BUILDING ABOVE EXIST. BUILDING ABOVE EXISTING ADDITION RESTROOM COMM UNIT 4a 014 1/011 1/012 1/014 1 A6.21 W-14F A7.02 W11 A7.01 W15 SIM. A7.02 W15 SIM. A7.02 W13 A7.02 W13 A7.02 W17 A7.02 W17 A7.02 FIRE SPKR ENTRY W18 A7.02 3 A6.22REPLACEMENT CONC. FNDN. WALL BELOW CMU WALL ABV. W10 SIM A7.02 W10 SIM. A7.02 10 CO 001 STORAGE 013 1/013 Update structurals to show this change to the foundation wall alignment. 2 A4.2 2 A5.2 1 A5.2 1 A5.3AECDFB GR I D A A L I G N M E N T OU T S I D E F A C E O F E X I S T I N G C O N C R E T E @ B A S E M E N T ( G R I D 1 - G R I D 4 ) GR I D B A L I G N M E N T OU T S I D E F A C E O F E X I S T I N G CO N C R E T E @ B A S E M E N T (G R I D 3 - G R I D 4 ) OU T S I D E F A C E O F E X I S T I N G EX T E R I O R S T U D @ L E V E L 1 + L E V E L 2 (G R I D 3 - G R I D 4 ) GR I D C A L I G N M E N T OU T S I D E F A C E O F E X I S T I N G EX T E R I O R S T U D @ L E V E L 1 (G R I D 2 . 2 @ E N T R Y L O C A T I O N ) GR I D E A L I G N M E N T OU T S I D E F A C E O F E X I S T I N G C M U @ L E V E L 1 ( G R I D 4 - G R I D 7 ) GR I D F A L I G N M E N T OU T S I D E F A C E O F E X I S T I N G S T U D @ L E V E L 1 ( G R I D 2 - G R I D 4 ) @ L E V E L 2 ( G R I D 2 - G R I D 6 ) GR I D D A L I G N M E N T OU T S I D E F A C E O F E X I S T I N G E X T E R I O R S T U D @ L E V E L 1 (G R I D 2 - G R I D 2 . 2 @ E N T R Y L O C A T I O N ) PROPERTY LINEPROPERTY LINE EXISTING FIRST FLOOR ABOVE COMM.UNIT 4 001 MECH. 2 011 COMM.UNIT 5 007 ELEVATOR 1 IT ROOM 012 MECH. 1CHASE / EQUIP. RM. 008 CORRIDOR 017 STAIR #1 010 COMM UNIT 6 009UP UP TV FD FD FD FD U/C REF U/C REF DW DW U/C ICE BUILDING ABOVE EXIST. BUILDING ABOVE EX I S T . B U I L D I N G A B O V E EXISTING ADDITION COMM.UNIT 4 016 RESTROOM 015 COMM UNIT 4a 014 003 1/017 1/007 1/008 1/002 1/010 1/011 1/012 1/015 1/014 001A ABV. 002 ABV. T. O. SLAB 88'-10 5/8" VIF 1 A6.21 W15 A7.02 W17 A7.02 1 A6.25 W-14F A7.02 W11 A7.01W17 A7.02 W15 SIM. A7.02 W15 SIM. A7.02 W13 A7.02 W16 A7.02 W6 W6 W13 A7.02 W17 A7.02 W17 A7.02 FIRE SPKR ENTRY WATER SERVICE ENTRY & VALVE W18 A7.02 W16 A7.01 3 A6.22 MIC 2 A6.27 001B 2/009 CLOSET 009a M 3'- 8 " CL R . COUNTER AT 34" AFF 4 A6.26 W10(F) A7.01 WORK TABLE WO R K T A B L E WO R K TA B L E 12 REPLACEMENT CONC. FNDN. WALL BELOW CMU WALL ABV. FURRING TO ALIGN WITH ADJACENT WALL CHASE ABOVE W16 A7.01 PARTY WALL 3.1 A7.07W10 A7.02 3.1 A7.07 SIM. W10 A7.02 W10 SIM A7.02 W10 SIM A7.02 W10 SIM. A7.02 W10 SIM. A7.02 W10 A7.02 8 A7.04A 1/009 10 CO 001 10 CO 001 STORAGE 013 1/013 Provide interior elevations and enlarged plan to demonstrate accessibility as you have done for the other toilet rooms. Coordinate with plumbing drawings which only show 2 roof drains in this area (main and overflow). Update kitchen plan to match A9.16 drawings. Provide sheet A7.04A and update elevations and door and window schedules and any other applicable drawings to match new door design. Cloud this change and any others on all applicable sheets. Provide U-factor (max 0.37 per 2015 IECC C402.4). Provide a threshold detail (max 1/2" per 2015 IBC 1010.1.7). RESPONSE: SEE UPDATED S2.0 WITH RELATED FOUNDATION CHANGE RESPONSE: UPDATED A2.1 PROVIDED ARCHITECTURAL NOTE REVISED TO DEFER TO PLUMBING RESPONSE: REVISED A2.1 PROVIDED WITH UPDATED KITCHEN LAYOUT TO MATCH A9.16 RESPONSE: SEE UPDATED AND NEW SHEET INFORMATION PROVIDED: A2.1 A7.04A A7.05A A4.1 A5.1 A8.0 A8.1 A8.1b RESPONSE: SEE UPDATED A9.1A FOR ACCESSIBILITY INFORMATION RESPONSE: DOOR U-FACTOR COMPLIES WITH C402.4.4 AND TABLE C402.4 FOR VERTICAL FENESTRATION & ENTRANCE DOORS = 0.77 U-FACTOR REQUIRED 0.31 U-FACTOR PROVIDED (PER ATTACHED PACMILL GLAZING DATA SHEET) 05/19/2021 Subject: PlanCheck Page: A2.1T TEMPORARY CONSTRUCTION SAFEGUARD LEVEL 1 PLAN Page Index: 8 Author: nickt Color: File Name: 90.230 E. Hopkins Ave_Mtn Forge_Change Order 001.20210405.pdf Revise backgrounds of Temp construction plan to match proposed/as-built. Subject: PlanCheck Page: A2.4 PROPOSED•50UPPER ROOF PLAN Page Index: 9 Author: nickt Color: File Name: 90.230 E. Hopkins Ave_Mtn Forge_Change Order 001.20210405.pdf Indicate finish elevations. There appear to be 3 risers vs 5 risers going from same elevation to same elevation. Subject: PlanCheck Page: A2.4 PROPOSED•50UPPER ROOF PLAN Page Index: 9 Author: nickt Color: File Name: 90.230 E. Hopkins Ave_Mtn Forge_Change Order 001.20210405.pdf Put handrails back in. Subject: PlanCheck Page: A2.4 PROPOSED•50UPPER ROOF PLAN Page Index: 9 Author: nickt Color: File Name: 90.230 E. Hopkins Ave_Mtn Forge_Change Order 001.20210405.pdf What are these? Where is the pool mechanicals access? Subject: PlanCheck Page: A2.4 PROPOSED•50UPPER ROOF PLAN Page Index: 9 Author: nickt Color: File Name: 90.230 E. Hopkins Ave_Mtn Forge_Change Order 001.20210405.pdf To comply with City policy for fenestration U-factor documentation, it appears you’ve submitted a calculation from AIA Industries using the Window program. This program is NFRC accredited so I think we can accept it for documentation at permit. However, to document the chain of custody and verify that the right materials are installed, an affidavit or other evidence from the manufacturer confirming compliance with the simulation is required prior to field inspection. Please verify that this is something that you can get from the manufacturer and that you will provide it prior to inspection for approval (ideally prior to installation). Revise backgrounds of Temp construction plan to match proposed/as-built. Indicate finish elevations. There appear to be 3 risers vs 5 risers going from same elevation to same elevation. Put handrails back in. What are these? Where is the pool mechanicals access? To comply with City policy for fenestration U-factor documentation, it appears you’ve submitted a calculation from AIA Industries using the Window program. This program is NFRC accredited so I think we can accept it for documentation at permit. However, to document the chain of custody and verify that the right materials are installed, an affidavit or other evidence from the manufacturer confirming compliance with the simulation is required prior to field inspection. Please verify that this is something that you can get from the manufacturer and that you will provide it prior to inspection for approval (ideally prior to installation). RESPONSE: HIGHLIGHTED AREA REPRESENTS PLACEHOLDER FOR LOCATION OF POOL EQUIPMENT ACCESS. HATCHES. SEE SHEET A2.3 FOR ADDITIONAL INFORMATION G.C. TO DETERMINE SCOPE, LOCATIONS, SIZES AND OPERATION IN COORDINATION W/ POOL MANUFACTURER AND FINAL POOL INSTALL RESPONSE: HANDRAIL CAD LAYER ACCIDENTALLY TURNED OFF SEE ATTACHED UPDATED SHEET A2.4 RESPONSE: ELEVATIONS PROVIDED ON SHEET A2.3 SEE ATTACHED SHEET RESPONSE: MANUFACTURER WILL PROVIDE AFFADAVIT AT TIME OF INSPECTION RESPONSE: UPDATED SHEET A2.1T PROVIDED 05/19/2021 Subject: PlanCheck Page: A9.1B PROPOSEDINTERIORELEVATIONS Page Index: 18 Author: nickt Color: File Name: 90.230 E. Hopkins Ave_Mtn Forge_Change Order 001.20210405.pdf Revise to match new layout and dimension 18" from door to counter for door maneuvering clearance. ICC A117.1-2009 section 404.2.3.1 Subject: PlanCheck Page: A9.16 PROPOSED INTERIOR ELEVATIONS Page Index: 19 Author: nickt Color: File Name: 90.230 E. Hopkins Ave_Mtn Forge_Change Order 001.20210405.pdf Sink clear space may not encroach on dishwasher door opening. Practically this means the center of the sink must be at least 24" from the edge of the dishwasher. ICC/A117.1-2009 section 804.5.3 Subject: PlanCheck Page: A9.16 PROPOSED INTERIOR ELEVATIONS Page Index: 19 Author: nickt Color: File Name: 90.230 E. Hopkins Ave_Mtn Forge_Change Order 001.20210405.pdf You submitted a spec for a microwave; indicate the location of it in the drawings. Should be on the counter to be within reach ranges. 1 Revise to match new layout and dimension 18" from door to counter for door maneuvering clearance. ICC A117.1-2009 section 404.2.3.1 Sink clear space may not encroach on dishwasher door opening. Practically this means the center of the sink must be at least 24" from the edge of the dishwasher. ICC/A117.1-2009 section 804.5.3 You submitted a spec for a microwave; indicate the location of it in the drawings. Should be on the counter to be within reach ranges. RESPONSE: UPDATED A9.16 WITH CORRECT CLEAR FLOOR AREA CONFIGURATIONS SHOWN AT SINK AND DISHWASHER PER 2009 ANSI A117.1 RESPONSE: UPDATED A9.16 PROVIDED WITH MICROWAVE INDICATED RESPONSE: SEE UPDATED A2.1 + A9.1B DOOR RELOCATED + ELEVATION UPDATES 05/19/2021 0016-2021-BCHO_BuildingComments_1 Subject: PlanCheck Page: 1 Page Index: 1 Author: nickt Color: File Name: 30.Interior Lighting COMCheck Compliance Mountain Forge-20210309 (003).pdf Revise to include Comm Unit 8. 30.Interior Lighting COMCheck Compliance Mountain Forge-20210309 (003).pdf (3) Subject: PlanCheck Page: 1 Page Index: 1 Author: nickt Color: File Name: 30.Interior Lighting COMCheck Compliance Mountain Forge-20210309 (003).pdf Provide updated lighting plans to match the changes to the COMcheck. Subject: PlanCheck Page: 2 Page Index: 2 Author: nickt Color: File Name: 30.Interior Lighting COMCheck Compliance Mountain Forge-20210309 (003).pdf Only 4 P9 pendants shown in comm unit 7 lighting plan. Coordinate Subject: PlanCheck Page: 1.2 >OSED•50L TWO•50>R PLAN Page Index: 2 Author: nickt Color: File Name: 90.Drawings_Change Order 002.20210407.pdf Commercial Unit 7 does has two bathrooms, disqualifying it from the single person private office accessibility exemption of 2015 IBC 1109.2 exception 1. One of the two toilet and bathing rooms must be fully accessible. Revise plans and enlarged plan and interior elevations to demonstrate compliance. 90.Drawings_Change Order 002.20210407.pdf (9) Subject: PlanCheck Page: 1.2 >OSED•50L TWO•50>R PLAN Page Index: 2 Author: nickt Color: File Name: 90.Drawings_Change Order 002.20210407.pdf Laundry equipment and counter in commercial unit 8 must be accessible. Fully detail and dimension to demonstrate compliance. ICC A117.1-2009 section 611 er A / Lamp / Wattage Per Lamp / Ballast B Lamps/ Fixture C # of Fixture Space Types:Office - Enclosed 1585 sq.ft.) 1 27 M: Other:1 4 M: Other:1 2 her:1 1 1 5 1 4 E: Other:1 1 1 1 Space Types:Office - Enclosed 520 sq.ft.) 1 10 1 10 her:1 1 Space Types:Office - Enclosed 322 sq.ft.) Revise to include Comm Unit 8. ONCE: Other:1 AL UNIT ( Common Space Types:Office - Enclosed 520 sq.ft.) WNLIGHT: Other:1 ONCE: Other:1 STRIP AT UTILITY: Other:1 AL UNIT ( Common Space Types:Office - Enclosed 322 sq.ft.) WNLIGHT: Other:1 TR2: TRACK LIGHT: Other:1 AL UNIT ( Common Space Types:Office - Enclosed 655 sq.ft.) MOUNTAIN FORGE TENANT FINISH P:\Current Projects\18009.00 - Mountain Forge Building Renovation & Addition\Calculations\COMcheck\MOUNTAIN FORGE TI LTG COMCHECK.cck Provide updated lighting plans to match the changes to the COMcheck. E (C X D) D Fixture Watt. A / Lamp / Wattage Per Lamp / Ballast B Lamps/ Fixture C # of Fixtures 1 13 13 169 1 3 20 60 Space Types:Office - Enclosed 485 sq.ft.) 1 17 13 221 1 5 20 100 r:1 3 2 8 Types:Office - Enclosed 133 sq.ft.) 1 2 32 64 1972Total Proposed Watts = Only 4 P9 pendants shown in comm unit 7 lighting plan. Coordinate Commercial Unit 7 does has two bathrooms, disqualifying it from the single person private office accessibility exemption of 2015 IBC 1109.2 exception 1. One of the two toilet and bathing rooms must be fully accessible. Revise plans and enlarged plan and interior elevations to demonstrate compliance. Laundry equipment and counter in commercial unit 8 must be accessible. Fully detail and dimension to demonstrate compliance. ICC A117.1-2009 section 611 RESPONSE: RESTROOM 220 RE-DESIGNED TO BE FULLY ACCESSIBLE SEE UPDATED SHEET A9.1D + A2.2 + A2.2D RESPONSE: COMM UNIT 8: LAUNDRY EQUIPMENT MEETS ICC A117.1-2009 SECTION 611. CLEARANCES NOTED ON PLAN AND SEPCIFICATION INCLUDED WITH HEIGHT NOTED FOR LOADING. SEE UPDATED SHEET A2.2 RESPONSE: Revised COMCheck dated 04/20/2021 includes Comm Unit 8. RESPONSE: Updated lighting plans have been provided to include the changes to the COMcheck. RESPONSE: COMcheck has been updated to show only (4) P9 pendants. 05/19/2021 Subject: PlanCheck Page: A2.2d PROPOSED•50LEVEL TWO•50DIMENSION PLAN Page Index: 3 Author: nickt Color: File Name: 90.Drawings_Change Order 002.20210407.pdf Door maneuvering clearspace required on both sides of door to bath 220. ICC A117.1-2009 section 404.2.3 Subject: PlanCheck Page: A2.2d PROPOSED•50LEVEL TWO•50DIMENSION PLAN Page Index: 3 Author: nickt Color: File Name: 90.Drawings_Change Order 002.20210407.pdf One of the lavatories must be fully accessible per ICC A117.1-2009 ch 6. Subject: PlanCheck Page: A2.2d PROPOSED•50LEVEL TWO•50DIMENSION PLAN Page Index: 3 Author: nickt Color: File Name: 90.Drawings_Change Order 002.20210407.pdf This window is now in a hazardous location (shower) and must be safety glazed. 2015 IBC 2406 Subject: PlanCheck Page: A2.2d PROPOSED•50LEVEL TWO•50DIMENSION PLAN Page Index: 3 Author: nickt Color: File Name: 90.Drawings_Change Order 002.20210407.pdf Grab bars required at water closet per ICC A117.1-2009 ch 6. Subject: PlanCheck Page: A2.2d PROPOSED•50LEVEL TWO•50DIMENSION PLAN Page Index: 3 Author: nickt Color: File Name: 90.Drawings_Change Order 002.20210407.pdf Accessible roll in shower must comply with the following per ICC A117.1-2009: -Seat must fold up (608.2.2.3) -Lavatory may only encroach on outside of shower clearspace if it is on the wall opposite the bench (608.2.2.2) -No enclosure or door allowed (608.2.2.1, 608.7) -Grab bars must be installed and dimensioned per 608.3.2. -Controls and hand shower must be on the long back wall (the wall with the window in this case) 608.4.2 -Handshower required (608.5) -Threshold max height is 1/2" (608.6) Door maneuvering clearspace required on both sides of door to bath 220. ICC A117.1-2009 section 404.2.3 One of the lavatories must be fully accessible per ICC A117.1-2009 ch 6. This window is now in a hazardous location (shower) and must be safety glazed. 2015 IBC 2406 Grab bars required at water closet per ICC A117.1-2009 ch 6. Accessible roll in shower must comply with the following per ICC A117.1-2009: -Seat must fold up (608.2.2.3) -Lavatory may only encroach on outside of shower clearspace if it is on the wall opposite the bench (608.2.2.2) -No enclosure or door allowed (608.2.2.1, 608.7) -Grab bars must be installed and dimensioned per 608.3.2. -Controls and hand shower must be on the long back wall (the wall with the window in this case) 608.4.2 -Handshower required (608.5) -Threshold max height is 1/2" (608.6) RESPONSE: DOOR RELOCATED + MANEUVERING CLEARSPACE PROVIDED BOTH SIDES SEE UPDATED A9.1D + A2.2 + A2.2D RESPONSE: ANSI COMPLIANT GRAB BARS PROVIDED SEE UPDATED A9.1D RESPONSE: SAFETY GLAZING PROVIDED SEE UPDATED A9.1D + A8.0 RESPONSE: SEE UPDATED SHEETS A9.1D + A2.2 + A2.2D ALTERNATE ROLL-IN TYPE SHOWER PROVIDED PER 608.4.3 (c) 1. FOLDING SEAT PROVIDED 2. SHOWER LAYOUT RE-DESIGNED RE: UPDATED PLANS 3. SHOWER DOOR + ENCLOSURE REMOVED 4. ANSI COMPLIANT GRAB BARS PROVIDED AS SHOWER 5. SHOWER CONTROLS RELOCATED AS ALLOWED PER 608.4.3 (a) 6. HAND SHOWER PROVIDED 7. ZERO CLEARANCE THRESHOLD PROVIDED RESPONSE: ACCESSIBLE SINKS PROVIDED SEE UPDATED A9.1D + A2.2 + A2.2D 05/19/2021 Subject: PlanCheck Page: A9.1D PROPOSEDINTERIORELEVATIONS Page Index: 4 Author: nickt Color: File Name: 90.Drawings_Change Order 002.20210407.pdf See comments on plan sheets. Bath 220 must be fully accessible with no future accommodations allowed. Subject: PlanCheck Page: A9.1D PROPOSEDINTERIORELEVATIONS Page Index: 4 Author: nickt Color: File Name: 90.Drawings_Change Order 002.20210407.pdf Bottom of mirror reflecting surface max height of 40". ICC A117.1-2009 ch 6. Subject: PlanCheck Page: [1] 18009-M2-M-112 Page Index: 1 Author: nickt Color: File Name: Mechanical 90.Drawings_Change Order 002.20210407.pdf Protect penetration of 1 hour rated wall by duct per 2015 IBC 714.3.1 Mechanical 90.Drawings_Change Order 002.20210407.pdf (2) Subject: PlanCheck Page: [1] 18009-M2-M-112 Page Index: 1 Author: nickt Color: File Name: Mechanical 90.Drawings_Change Order 002.20210407.pdf Fire and smoke damper required at penetration of shaft wall. Subject: PlanCheck Page: 1 Page Index: 1 Author: nickt Color: File Name: Plumbing 90.Drawings_Change Order 002.20210407.pdf Shower controls must be on a different wall. See comments on architectural set and coordinate. Plumbing 90.Drawings_Change Order 002.20210407.pdf (1) See comments on plan sheets. Bath 220 must be fully accessible with no future accommodations allowed. Bottom of mirror reflecting surface max height of 40". ICC A117.1-2009 ch 6. PROPERTY SETBACK LINE E RESIDENCE KITCHEN 202 COMM. UNIT 8 214 O FC-1. TAKE-OFF DUCT FROM THE LOWER PORTION OF THE MAIN TRUCK DUCT TO AVOID BEAM. TAKE-OFF DUCT FROM THE UPPER PORTION OF THE MAIN TRUCK DUCT TO MAXIMIZE CEILING HEIGHTS. 10"Ø KITCHEN EXHAUST (BY OTHERS, SHOWN FOR REFERENCE. VERIFY SIZING & TERMINATION WITH HOOD MANUFACTURER) AC 1 1 9 10 EXISTIN PROPERTY 24x6 (26x8) A 450-S 36x3 8x6 (10x8)16x6 (18x8) 4" DRYER EXHAUST WALL CAP CONNECT 4" DRYER EXHAUST TO DRYER AND ROUTE TO EXTERIOR 1 Protect penetration of 1 hour rated wall by duct per 2015 IBC 714.3.1 DN UP FEC BATH 220 REST 2 MECH. 3 218 C U (3) 4" BOILER FLUE & 4" COMBUSTION AIR UP & DOWN 5" (8") OSA AC 1 EF 12 16/8 (18/10) 16/8 (18/10) 12x12 DN, 14x14 UP F/S F/S 20x10 (23x13) UP & 14x12 (17x15) DN F/S FD T FC-1 ZD-1B BDD BDD T FC-66" 8" 5" (8") 7 8 1 FD FD 8" 8"Ø (11"Ø) - TYP. OF 4 A480-S 60x3 A600-R 60 x 3 M MD 14 FD FC 6 1 14/6 (16/8) 14/6 (16/8) FD FD FC 1 18/8 (20/10) 20 / 6 (2 2 / 8 ) 10/6 (12/8) 18/8 (20/10) 12/6 (14/8) M ZD 1A M 8" H 1 FD FD FD BD 1 FC 7 1 HC 3 14/4 7 24x6 (26x8) A 600-R 60x3 A60-S 6x3 BDD8" 5" (8") EF 14 Fire and smoke damper required at penetration of shaft wall. Shower controls must be on a different wall. See comments on architectural set and coordinate. RESPONSE: BATHROOM RE-DESIGNED TO BE FULLY ACCESSIBLE SEE UPDATED SHEET A9.1D RESPONSE: MIRROR UPDATED TO COMPLY SEE UPDATED SHEET A9.1D RESPONSE: NOTED ON UPDATED MECH DRAWING RESPONSE: NOTED ON UPDATED MECH DRAWING RESPONSE: NOTED ON UPDATED PLUMBING DRAWING 05/19/2021