HomeMy WebLinkAboutFile Documents.230 E Hopkins Ave.0046-2020-BCHO (11)0046-2020-BCHO_BuildingComments_2
Subject: PlanCheck
Page: A2.0 PROPOSED BASEMENT FLOOR PLAN
Page Index: 6
Author: nickt
Color:
File Name: 90.230 E. Hopkins Ave_Mtn Forge_Change Order
001.20210405.pdf
Update structurals to show this
change to the foundation wall
alignment.
90.230 E. Hopkins Ave_Mtn Forge_Change Order 001.20210405.pdf (13)
Subject: PlanCheck
Page: A2.0 PROPOSED BASEMENT FLOOR PLAN
Page Index: 6
Author: nickt
Color:
File Name: 90.230 E. Hopkins Ave_Mtn Forge_Change Order
001.20210405.pdf
Provide interior elevations and
enlarged plan to demonstrate
accessibility as you have done
for the other toilet rooms.
Subject: PlanCheck
Page: A2.1 PROPOSED•50LEVEL ONE•50FLOOR PLAN
Page Index: 7
Author: nickt
Color:
File Name: 90.230 E. Hopkins Ave_Mtn Forge_Change Order
001.20210405.pdf
Coordinate with plumbing
drawings which only show 2 roof
drains in this area (main and
overflow).
Subject: PlanCheck
Page: A2.1 PROPOSED•50LEVEL ONE•50FLOOR PLAN
Page Index: 7
Author: nickt
Color:
File Name: 90.230 E. Hopkins Ave_Mtn Forge_Change Order
001.20210405.pdf
Update kitchen plan to match
A9.16 drawings.
Subject: PlanCheck
Page: A2.1 PROPOSED•50LEVEL ONE•50FLOOR PLAN
Page Index: 7
Author: nickt
Color:
File Name: 90.230 E. Hopkins Ave_Mtn Forge_Change Order
001.20210405.pdf
Provide sheet A7.04A and
update elevations and door and
window schedules and any other
applicable drawings to match
new door design. Cloud this
change and any others on all
applicable sheets. Provide
U-factor (max 0.37 per 2015
IECC C402.4). Provide a
threshold detail (max 1/2" per
2015 IBC 1010.1.7).
ME
N
T
O
F
E
X
I
S
T
I
N
G
C
M
U
ID
4
-
G
R
I
D
7
)
ME
N
T
O
F
E
X
I
S
T
I
N
G
S
T
U
D
ID
2
-
G
R
I
D
4
)
ID
2
-
G
R
I
D
6
)
ME
N
T
E
O
F
E
X
I
S
T
I
N
G
E
X
T
E
R
I
O
R
S
T
U
D
PROPERTY LINE
MECH. 2
011
ELEVATOR
IT ROOM
012
STAIR #1
010 UP
FD
FD
BUILDING ABOVE
EXIST. BUILDING ABOVE
EXISTING ADDITION
RESTROOM
COMM UNIT 4a
014
1/011
1/012
1/014
1
A6.21
W-14F
A7.02
W11
A7.01
W15 SIM.
A7.02
W15 SIM.
A7.02
W13
A7.02
W13
A7.02
W17
A7.02
W17
A7.02
FIRE
SPKR
ENTRY
W18
A7.02
3
A6.22REPLACEMENT
CONC. FNDN. WALL
BELOW CMU WALL
ABV.
W10 SIM
A7.02
W10 SIM.
A7.02
10
CO 001
STORAGE
013
1/013
Update structurals to
show this change to
the foundation wall
alignment.
2
A4.2
2
A5.2
1
A5.2
1
A5.3AECDFB
GR
I
D
A
A
L
I
G
N
M
E
N
T
OU
T
S
I
D
E
F
A
C
E
O
F
E
X
I
S
T
I
N
G
C
O
N
C
R
E
T
E
@ B
A
S
E
M
E
N
T
(
G
R
I
D
1
-
G
R
I
D
4
)
GR
I
D
B
A
L
I
G
N
M
E
N
T
OU
T
S
I
D
E
F
A
C
E
O
F
E
X
I
S
T
I
N
G
CO
N
C
R
E
T
E
@
B
A
S
E
M
E
N
T
(G
R
I
D
3
-
G
R
I
D
4
)
OU
T
S
I
D
E
F
A
C
E
O
F
E
X
I
S
T
I
N
G
EX
T
E
R
I
O
R
S
T
U
D
@
L
E
V
E
L
1
+
L
E
V
E
L
2
(G
R
I
D
3
-
G
R
I
D
4
)
GR
I
D
C
A
L
I
G
N
M
E
N
T
OU
T
S
I
D
E
F
A
C
E
O
F
E
X
I
S
T
I
N
G
EX
T
E
R
I
O
R
S
T
U
D
@ L
E
V
E
L
1
(G
R
I
D
2
.
2
@
E
N
T
R
Y
L
O
C
A
T
I
O
N
)
GR
I
D
E
A
L
I
G
N
M
E
N
T
OU
T
S
I
D
E
F
A
C
E
O
F
E
X
I
S
T
I
N
G
C
M
U
@ L
E
V
E
L
1
(
G
R
I
D
4
-
G
R
I
D
7
)
GR
I
D
F
A
L
I
G
N
M
E
N
T
OU
T
S
I
D
E
F
A
C
E
O
F
E
X
I
S
T
I
N
G
S
T
U
D
@ L
E
V
E
L
1
(
G
R
I
D
2
-
G
R
I
D
4
)
@ L
E
V
E
L
2
(
G
R
I
D
2
-
G
R
I
D
6
)
GR
I
D
D
A
L
I
G
N
M
E
N
T
OU
T
S
I
D
E
F
A
C
E
O
F
E
X
I
S
T
I
N
G
E
X
T
E
R
I
O
R
S
T
U
D
@ L
E
V
E
L
1
(G
R
I
D
2
-
G
R
I
D
2
.
2
@
E
N
T
R
Y
L
O
C
A
T
I
O
N
)
PROPERTY LINEPROPERTY LINE
EXISTING FIRST FLOOR ABOVE
COMM.UNIT 4
001
MECH. 2
011
COMM.UNIT 5
007
ELEVATOR
1
IT ROOM
012
MECH. 1CHASE / EQUIP. RM.
008
CORRIDOR
017
STAIR #1
010
COMM UNIT 6
009UP
UP
TV
FD
FD
FD
FD
U/C
REF
U/C
REF
DW
DW U/C
ICE
BUILDING ABOVE
EXIST. BUILDING ABOVE
EX
I
S
T
.
B
U
I
L
D
I
N
G
A
B
O
V
E
EXISTING ADDITION
COMM.UNIT 4
016
RESTROOM
015
COMM UNIT 4a
014
003
1/017
1/007 1/008
1/002
1/010
1/011
1/012
1/015
1/014
001A
ABV.
002
ABV.
T. O. SLAB
88'-10 5/8" VIF
1
A6.21
W15
A7.02
W17
A7.02
1
A6.25
W-14F
A7.02
W11
A7.01W17
A7.02
W15 SIM.
A7.02
W15 SIM.
A7.02
W13
A7.02
W16
A7.02
W6 W6
W13
A7.02
W17
A7.02
W17
A7.02
FIRE
SPKR
ENTRY
WATER SERVICE
ENTRY & VALVE
W18
A7.02
W16
A7.01
3
A6.22
MIC
2
A6.27
001B
2/009
CLOSET
009a M
3'-
8
"
CL
R
.
COUNTER AT
34" AFF
4
A6.26
W10(F)
A7.01
WORK TABLE
WO
R
K
T
A
B
L
E
WO
R
K
TA
B
L
E
12
REPLACEMENT
CONC. FNDN. WALL
BELOW CMU WALL
ABV.
FURRING TO ALIGN
WITH ADJACENT WALL
CHASE
ABOVE
W16
A7.01
PARTY WALL
3.1
A7.07W10
A7.02
3.1
A7.07
SIM.
W10
A7.02
W10 SIM
A7.02
W10 SIM
A7.02
W10 SIM.
A7.02
W10 SIM.
A7.02
W10
A7.02
8
A7.04A
1/009 10
CO 001
10
CO 001
STORAGE
013
1/013
Provide interior
elevations and
enlarged plan to
demonstrate
accessibility as you
have done for the
other toilet rooms.
Coordinate with
plumbing drawings
which only show 2 roof
drains in this area
(main and overflow).
Update kitchen plan to
match A9.16
drawings.
Provide sheet A7.04A and
update elevations and door
and window schedules and
any other applicable
drawings to match new door
design. Cloud this change
and any others on all
applicable sheets. Provide
U-factor (max 0.37 per 2015
IECC C402.4). Provide a
threshold detail (max 1/2"
per 2015 IBC 1010.1.7).
RESPONSE:
SEE UPDATED S2.0 WITH RELATED FOUNDATION
CHANGE
RESPONSE:
UPDATED A2.1 PROVIDED
ARCHITECTURAL NOTE REVISED TO DEFER TO
PLUMBING
RESPONSE:
REVISED A2.1 PROVIDED WITH UPDATED
KITCHEN LAYOUT TO MATCH A9.16
RESPONSE:
SEE UPDATED AND NEW SHEET INFORMATION PROVIDED:
A2.1
A7.04A
A7.05A
A4.1
A5.1
A8.0
A8.1
A8.1b
RESPONSE:
SEE UPDATED A9.1A FOR ACCESSIBILITY
INFORMATION
RESPONSE:
DOOR U-FACTOR COMPLIES WITH C402.4.4 AND TABLE C402.4
FOR VERTICAL FENESTRATION & ENTRANCE DOORS
= 0.77 U-FACTOR REQUIRED
0.31 U-FACTOR PROVIDED
(PER ATTACHED PACMILL GLAZING DATA SHEET)
05/19/2021
Subject: PlanCheck
Page: A2.1T TEMPORARY CONSTRUCTION SAFEGUARD
LEVEL 1 PLAN
Page Index: 8
Author: nickt
Color:
File Name: 90.230 E. Hopkins Ave_Mtn Forge_Change Order
001.20210405.pdf
Revise backgrounds of Temp
construction plan to match
proposed/as-built.
Subject: PlanCheck
Page: A2.4 PROPOSED•50UPPER ROOF PLAN
Page Index: 9
Author: nickt
Color:
File Name: 90.230 E. Hopkins Ave_Mtn Forge_Change Order
001.20210405.pdf
Indicate finish elevations. There
appear to be 3 risers vs 5 risers
going from same elevation to
same elevation.
Subject: PlanCheck
Page: A2.4 PROPOSED•50UPPER ROOF PLAN
Page Index: 9
Author: nickt
Color:
File Name: 90.230 E. Hopkins Ave_Mtn Forge_Change Order
001.20210405.pdf
Put handrails back in.
Subject: PlanCheck
Page: A2.4 PROPOSED•50UPPER ROOF PLAN
Page Index: 9
Author: nickt
Color:
File Name: 90.230 E. Hopkins Ave_Mtn Forge_Change Order
001.20210405.pdf
What are these? Where is the
pool mechanicals access?
Subject: PlanCheck
Page: A2.4 PROPOSED•50UPPER ROOF PLAN
Page Index: 9
Author: nickt
Color:
File Name: 90.230 E. Hopkins Ave_Mtn Forge_Change Order
001.20210405.pdf
To comply with City policy for
fenestration U-factor
documentation, it appears
you’ve submitted a calculation
from AIA Industries using the
Window program. This program
is NFRC accredited so I think we
can accept it for documentation
at permit. However, to document
the chain of custody and verify
that the right materials are
installed, an affidavit or other
evidence from the manufacturer
confirming compliance with the
simulation is required prior to
field inspection. Please verify
that this is something that you
can get from the manufacturer
and that you will provide it prior
to inspection for approval (ideally
prior to installation).
Revise backgrounds
of Temp construction
plan to match
proposed/as-built.
Indicate finish
elevations. There
appear to be 3 risers
vs 5 risers going from
same elevation to
same elevation.
Put handrails back in.
What are these?
Where is the pool
mechanicals access?
To comply with City policy for fenestration U-factor documentation, it
appears you’ve submitted a calculation from AIA Industries using the
Window program. This program is NFRC accredited so I think we can
accept it for documentation at permit. However, to document the chain of
custody and verify that the right materials are installed, an affidavit or other
evidence from the manufacturer confirming compliance with the simulation
is required prior to field inspection. Please verify that this is something that
you can get from the manufacturer and that you will provide it prior to
inspection for approval (ideally prior to installation).
RESPONSE:
HIGHLIGHTED AREA REPRESENTS PLACEHOLDER
FOR LOCATION OF POOL EQUIPMENT ACCESS.
HATCHES.
SEE SHEET A2.3 FOR ADDITIONAL INFORMATION
G.C. TO DETERMINE SCOPE, LOCATIONS, SIZES AND
OPERATION IN COORDINATION W/ POOL
MANUFACTURER AND FINAL POOL INSTALL
RESPONSE:
HANDRAIL CAD LAYER ACCIDENTALLY TURNED OFF
SEE ATTACHED UPDATED SHEET A2.4
RESPONSE:
ELEVATIONS PROVIDED ON SHEET A2.3
SEE ATTACHED SHEET
RESPONSE:
MANUFACTURER WILL PROVIDE AFFADAVIT AT TIME
OF INSPECTION
RESPONSE:
UPDATED SHEET A2.1T PROVIDED
05/19/2021
Subject: PlanCheck
Page: A9.1B PROPOSEDINTERIORELEVATIONS
Page Index: 18
Author: nickt
Color:
File Name: 90.230 E. Hopkins Ave_Mtn Forge_Change Order
001.20210405.pdf
Revise to match new layout and
dimension 18" from door to
counter for door maneuvering
clearance. ICC A117.1-2009
section 404.2.3.1
Subject: PlanCheck
Page: A9.16 PROPOSED INTERIOR ELEVATIONS
Page Index: 19
Author: nickt
Color:
File Name: 90.230 E. Hopkins Ave_Mtn Forge_Change Order
001.20210405.pdf
Sink clear space may not
encroach on dishwasher door
opening. Practically this means
the center of the sink must be at
least 24" from the edge of the
dishwasher. ICC/A117.1-2009
section 804.5.3
Subject: PlanCheck
Page: A9.16 PROPOSED INTERIOR ELEVATIONS
Page Index: 19
Author: nickt
Color:
File Name: 90.230 E. Hopkins Ave_Mtn Forge_Change Order
001.20210405.pdf
You submitted a spec for a
microwave; indicate the location
of it in the drawings. Should be
on the counter to be within reach
ranges.
1
Revise to match new
layout and dimension
18" from door to
counter for door
maneuvering
clearance. ICC
A117.1-2009 section
404.2.3.1
Sink clear space may
not encroach on
dishwasher door
opening. Practically
this means the center
of the sink must be at
least 24" from the
edge of the
dishwasher.
ICC/A117.1-2009
section 804.5.3
You submitted a spec for a
microwave; indicate the
location of it in the drawings.
Should be on the counter to
be within reach ranges.
RESPONSE:
UPDATED A9.16 WITH CORRECT CLEAR FLOOR
AREA CONFIGURATIONS SHOWN AT SINK AND
DISHWASHER PER 2009 ANSI A117.1
RESPONSE:
UPDATED A9.16 PROVIDED WITH MICROWAVE
INDICATED
RESPONSE:
SEE UPDATED A2.1 + A9.1B
DOOR RELOCATED + ELEVATION UPDATES
05/19/2021
0016-2021-BCHO_BuildingComments_1
Subject: PlanCheck
Page: 1
Page Index: 1
Author: nickt
Color:
File Name: 30.Interior Lighting COMCheck Compliance
Mountain Forge-20210309 (003).pdf
Revise to include Comm Unit 8.
30.Interior Lighting COMCheck Compliance Mountain Forge-20210309 (003).pdf (3)
Subject: PlanCheck
Page: 1
Page Index: 1
Author: nickt
Color:
File Name: 30.Interior Lighting COMCheck Compliance
Mountain Forge-20210309 (003).pdf
Provide updated lighting plans to
match the changes to the
COMcheck.
Subject: PlanCheck
Page: 2
Page Index: 2
Author: nickt
Color:
File Name: 30.Interior Lighting COMCheck Compliance
Mountain Forge-20210309 (003).pdf
Only 4 P9 pendants shown in
comm unit 7 lighting plan.
Coordinate
Subject: PlanCheck
Page: 1.2 >OSED•50L TWO•50>R PLAN
Page Index: 2
Author: nickt
Color:
File Name: 90.Drawings_Change Order 002.20210407.pdf
Commercial Unit 7 does has two
bathrooms, disqualifying it from
the single person private office
accessibility exemption of 2015
IBC 1109.2 exception 1. One of
the two toilet and bathing rooms
must be fully accessible. Revise
plans and enlarged plan and
interior elevations to
demonstrate compliance.
90.Drawings_Change Order 002.20210407.pdf (9)
Subject: PlanCheck
Page: 1.2 >OSED•50L TWO•50>R PLAN
Page Index: 2
Author: nickt
Color:
File Name: 90.Drawings_Change Order 002.20210407.pdf
Laundry equipment and counter
in commercial unit 8 must be
accessible. Fully detail and
dimension to demonstrate
compliance. ICC A117.1-2009
section 611
er
A
/ Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixture
Space Types:Office - Enclosed 1585 sq.ft.)
1 27
M: Other:1 4
M: Other:1 2
her:1 1
1 5
1 4
E: Other:1 1
1 1
Space Types:Office - Enclosed 520 sq.ft.)
1 10
1 10
her:1 1
Space Types:Office - Enclosed 322 sq.ft.)
Revise to include
Comm Unit 8.
ONCE: Other:1
AL UNIT ( Common Space Types:Office - Enclosed 520 sq.ft.)
WNLIGHT: Other:1
ONCE: Other:1
STRIP AT UTILITY: Other:1
AL UNIT ( Common Space Types:Office - Enclosed 322 sq.ft.)
WNLIGHT: Other:1
TR2: TRACK LIGHT: Other:1
AL UNIT ( Common Space Types:Office - Enclosed 655 sq.ft.)
MOUNTAIN FORGE TENANT FINISH
P:\Current Projects\18009.00 - Mountain Forge Building Renovation &
Addition\Calculations\COMcheck\MOUNTAIN FORGE TI LTG COMCHECK.cck
Provide updated
lighting plans to match
the changes to the
COMcheck.
E
(C X D)
D
Fixture
Watt.
A
/ Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
1 13 13 169
1 3 20 60
Space Types:Office - Enclosed 485 sq.ft.)
1 17 13 221
1 5 20 100
r:1 3 2 8
Types:Office - Enclosed 133 sq.ft.)
1 2 32 64
1972Total Proposed Watts =
Only 4 P9 pendants
shown in comm unit 7
lighting plan.
Coordinate
Commercial Unit 7
does has two
bathrooms,
disqualifying it from
the single person
private office
accessibility
exemption of 2015
IBC 1109.2 exception
1. One of the two toilet
and bathing rooms
must be fully
accessible. Revise
plans and enlarged
plan and interior
elevations to
demonstrate
compliance.
Laundry equipment
and counter in
commercial unit 8
must be accessible.
Fully detail and
dimension to
demonstrate
compliance. ICC
A117.1-2009 section
611
RESPONSE:
RESTROOM 220 RE-DESIGNED TO BE FULLY
ACCESSIBLE
SEE UPDATED SHEET A9.1D + A2.2 + A2.2D
RESPONSE:
COMM UNIT 8:
LAUNDRY EQUIPMENT MEETS ICC A117.1-2009
SECTION 611. CLEARANCES NOTED ON PLAN
AND SEPCIFICATION INCLUDED WITH HEIGHT
NOTED FOR LOADING.
SEE UPDATED SHEET A2.2
RESPONSE:
Revised COMCheck dated 04/20/2021 includes Comm
Unit 8.
RESPONSE:
Updated lighting plans have been provided to include
the changes to the COMcheck.
RESPONSE:
COMcheck has been updated to show only (4) P9
pendants.
05/19/2021
Subject: PlanCheck
Page: A2.2d PROPOSED•50LEVEL TWO•50DIMENSION PLAN
Page Index: 3
Author: nickt
Color:
File Name: 90.Drawings_Change Order 002.20210407.pdf
Door maneuvering clearspace
required on both sides of door to
bath 220. ICC A117.1-2009
section 404.2.3
Subject: PlanCheck
Page: A2.2d PROPOSED•50LEVEL TWO•50DIMENSION PLAN
Page Index: 3
Author: nickt
Color:
File Name: 90.Drawings_Change Order 002.20210407.pdf
One of the lavatories must be
fully accessible per ICC
A117.1-2009 ch 6.
Subject: PlanCheck
Page: A2.2d PROPOSED•50LEVEL TWO•50DIMENSION PLAN
Page Index: 3
Author: nickt
Color:
File Name: 90.Drawings_Change Order 002.20210407.pdf
This window is now in a
hazardous location (shower) and
must be safety glazed. 2015 IBC
2406
Subject: PlanCheck
Page: A2.2d PROPOSED•50LEVEL TWO•50DIMENSION PLAN
Page Index: 3
Author: nickt
Color:
File Name: 90.Drawings_Change Order 002.20210407.pdf
Grab bars required at water
closet per ICC A117.1-2009 ch
6.
Subject: PlanCheck
Page: A2.2d PROPOSED•50LEVEL TWO•50DIMENSION PLAN
Page Index: 3
Author: nickt
Color:
File Name: 90.Drawings_Change Order 002.20210407.pdf
Accessible roll in shower must
comply with the following per
ICC A117.1-2009:
-Seat must fold up (608.2.2.3)
-Lavatory may only encroach on
outside of shower clearspace if it
is on the wall opposite the bench
(608.2.2.2)
-No enclosure or door allowed
(608.2.2.1, 608.7)
-Grab bars must be installed and
dimensioned per 608.3.2.
-Controls and hand shower must
be on the long back wall (the
wall with the window in this
case) 608.4.2
-Handshower required (608.5)
-Threshold max height is 1/2"
(608.6)
Door maneuvering
clearspace required
on both sides of door
to bath 220. ICC
A117.1-2009 section
404.2.3
One of the lavatories
must be fully
accessible per ICC
A117.1-2009 ch 6.
This window is now in
a hazardous location
(shower) and must be
safety glazed. 2015
IBC 2406
Grab bars required at
water closet per ICC
A117.1-2009 ch 6.
Accessible roll in
shower must comply
with the following per
ICC A117.1-2009:
-Seat must fold up
(608.2.2.3)
-Lavatory may only
encroach on outside of
shower clearspace if it
is on the wall opposite
the bench (608.2.2.2)
-No enclosure or door
allowed (608.2.2.1,
608.7)
-Grab bars must be
installed and
dimensioned per
608.3.2.
-Controls and hand
shower must be on the
long back wall (the
wall with the window in
this case) 608.4.2
-Handshower required
(608.5)
-Threshold max height
is 1/2" (608.6)
RESPONSE:
DOOR RELOCATED + MANEUVERING
CLEARSPACE PROVIDED BOTH SIDES
SEE UPDATED A9.1D + A2.2 + A2.2D
RESPONSE:
ANSI COMPLIANT GRAB BARS PROVIDED
SEE UPDATED A9.1D
RESPONSE:
SAFETY GLAZING PROVIDED
SEE UPDATED A9.1D + A8.0
RESPONSE:
SEE UPDATED SHEETS A9.1D + A2.2 + A2.2D
ALTERNATE ROLL-IN TYPE SHOWER PROVIDED
PER 608.4.3 (c)
1. FOLDING SEAT PROVIDED
2. SHOWER LAYOUT RE-DESIGNED RE: UPDATED
PLANS
3. SHOWER DOOR + ENCLOSURE REMOVED
4. ANSI COMPLIANT GRAB BARS PROVIDED AS
SHOWER
5. SHOWER CONTROLS RELOCATED AS ALLOWED
PER 608.4.3 (a)
6. HAND SHOWER PROVIDED
7. ZERO CLEARANCE THRESHOLD PROVIDED
RESPONSE:
ACCESSIBLE SINKS PROVIDED
SEE UPDATED A9.1D + A2.2 + A2.2D
05/19/2021
Subject: PlanCheck
Page: A9.1D PROPOSEDINTERIORELEVATIONS
Page Index: 4
Author: nickt
Color:
File Name: 90.Drawings_Change Order 002.20210407.pdf
See comments on plan sheets.
Bath 220 must be fully
accessible with no future
accommodations allowed.
Subject: PlanCheck
Page: A9.1D PROPOSEDINTERIORELEVATIONS
Page Index: 4
Author: nickt
Color:
File Name: 90.Drawings_Change Order 002.20210407.pdf
Bottom of mirror reflecting
surface max height of 40". ICC
A117.1-2009 ch 6.
Subject: PlanCheck
Page: [1] 18009-M2-M-112
Page Index: 1
Author: nickt
Color:
File Name: Mechanical 90.Drawings_Change Order
002.20210407.pdf
Protect penetration of 1 hour
rated wall by duct per 2015 IBC
714.3.1
Mechanical 90.Drawings_Change Order 002.20210407.pdf (2)
Subject: PlanCheck
Page: [1] 18009-M2-M-112
Page Index: 1
Author: nickt
Color:
File Name: Mechanical 90.Drawings_Change Order
002.20210407.pdf
Fire and smoke damper required
at penetration of shaft wall.
Subject: PlanCheck
Page: 1
Page Index: 1
Author: nickt
Color:
File Name: Plumbing 90.Drawings_Change Order
002.20210407.pdf
Shower controls must be on a
different wall. See comments on
architectural set and coordinate.
Plumbing 90.Drawings_Change Order 002.20210407.pdf (1)
See comments on plan sheets. Bath 220 must be
fully accessible with no future accommodations
allowed.
Bottom of mirror
reflecting surface max
height of 40". ICC
A117.1-2009 ch 6.
PROPERTY
SETBACK LINE
E
RESIDENCE
KITCHEN
202
COMM.
UNIT 8
214
O FC-1.
TAKE-OFF DUCT FROM THE LOWER PORTION OF THE MAIN TRUCK
DUCT TO AVOID BEAM.
TAKE-OFF DUCT FROM THE UPPER PORTION OF THE MAIN TRUCK
DUCT TO MAXIMIZE CEILING HEIGHTS.
10"Ø KITCHEN EXHAUST (BY OTHERS,
SHOWN FOR REFERENCE. VERIFY
SIZING & TERMINATION WITH HOOD
MANUFACTURER)
AC
1
1
9
10
EXISTIN
PROPERTY
24x6
(26x8)
A 450-S
36x3
8x6 (10x8)16x6
(18x8)
4" DRYER EXHAUST
WALL CAP
CONNECT 4"
DRYER EXHAUST
TO DRYER AND
ROUTE TO
EXTERIOR
1
Protect penetration of
1 hour rated wall by
duct per 2015 IBC
714.3.1
DN UP
FEC
BATH
220
REST
2
MECH. 3
218
C
U
(3) 4" BOILER FLUE &
4" COMBUSTION AIR
UP & DOWN
5" (8") OSA
AC
1
EF
12
16/8
(18/10)
16/8
(18/10)
12x12 DN, 14x14 UP
F/S
F/S
20x10 (23x13) UP &
14x12 (17x15) DN
F/S
FD
T
FC-1
ZD-1B
BDD
BDD
T
FC-66"
8"
5" (8")
7
8
1
FD
FD
8"
8"Ø (11"Ø)
- TYP. OF 4
A480-S
60x3
A600-R
60 x 3
M
MD
14
FD
FC
6
1
14/6 (16/8)
14/6 (16/8)
FD
FD
FC
1
18/8
(20/10)
20
/
6
(2
2
/
8
)
10/6 (12/8)
18/8
(20/10)
12/6 (14/8)
M ZD
1A M
8"
H
1 FD
FD
FD
BD
1
FC
7
1
HC
3
14/4
7
24x6
(26x8)
A 600-R
60x3
A60-S
6x3
BDD8"
5" (8")
EF
14
Fire and smoke
damper required at
penetration of shaft
wall.
Shower controls must
be on a different wall.
See comments on
architectural set and
coordinate.
RESPONSE:
BATHROOM RE-DESIGNED TO BE FULLY
ACCESSIBLE
SEE UPDATED SHEET A9.1D
RESPONSE:
MIRROR UPDATED TO COMPLY
SEE UPDATED SHEET A9.1D
RESPONSE:
NOTED ON UPDATED MECH DRAWING
RESPONSE:
NOTED ON UPDATED MECH DRAWING
RESPONSE:
NOTED ON UPDATED PLUMBING DRAWING
05/19/2021