LOAD FORM -- APPLICATION FOR ELECTRIC SERVICE
To be submitted by Electrical Designer or Electrical Contractor
Please complete the following items in this checklist:
☐ Completed all sections of this form.
☐ Attached copies of the electrical one-line drawing and power plan.
☐ Upload this application on the City of Aspen Salesforce Applicant Portal.
Contact Information
Name of Person Submitting Request:_________________________________________________ Date:__________________
Company Name: __________________________________________________________________________________________
Phone Number:_________________________________ Email:___________________________________________________
Customer Information Billing Information
Customer Name:_____________________________________
Mailing Address:_____________________________________
___________________________________________________
Phone #:_____________ Email:________________________
City of Aspen Permit Number: _________________________
Bill To:_____________________________________________
Mailing Address:_____________________________________
___________________________________________________
Phone #:______________ Email:________________________
Electrical Contractor Information
Company Name:________________________________________________ Contact Person:______________________________
Phone #:____________________ Fax #:____________________ Email:______________________________________________
Location Information
Service Address:____________________________________________________________________ Unit #:_________________
If this is part of a multi-occupancy building, give the building’s entire address range:_______________________________________________________________
☐ New Construction ☐ Existing Structure ☐ Addition to Existing Structure ☐ Demolition Within City Limits? ☐ Yes ☐ No
Type of Building: ☐ Single Occupancy ☐ Multi-Occupancy ☐ Multi-Occupancy Core and Shell Only ☐ Multi-Occupancy Residential
Request Type
☐ New service
☐ Increase Existing Service Entrance Size (with no service upgrade)
☐ Remove Existing Meter(s), service to remain
☐ Modification of Existing Tenant Space(s)
☐ Upgrade Existing Service
☐ Add New Meter to Existing Service (with no service upgrade)
☐ Remove Existing Meter(s) and Service
☐ Other__________________________________________________
Electrical Load Information
New Equipment Load New Equipment Load
HVAC Equip. (Tons)_____ _____ Tot. KW X-Ray Equipment _____KW
Refrigeration Equip. (Tons)_____ _____ Tot. KW Washer/Dryer(s) _____KW
Electric Heat _____KW Machinery #:_____HP:_____ _____ Tot. HP
Water Heating _____KW Exhaust Fans #:_____HP:_____ _____ Tot. HP
Lighting _____KW Pumps #:_____HP:_____ _____ Tot. HP
Outlets _____KW Small Motors #:_____HP:_____ _____ Tot. HP
Office Equipment _____KW Compressors #:_____HP:_____ _____ Tot. HP
Kitchen Equipment _____KW Miscellaneous _____KW
Computers _____KW _____KW
Snow Melting Equipment _____KW _____KW
Thermoplastic Injection Equip. _____KW _____KW
Boiler _____KW Future Equipment _____KW
Elevators _____KW (Itemize on separate sheet)
Signs _____KW
Total HP
TOTAL: KW
APPLICATION FOR ELECTRIC SERVICE Page 2
ELECTRIC VEHICLE (X5)
GROUND WATER & CONDENSER PUMPS
ELECTRIC VEHICLE CHARGER (X1)
HEATING/COND PUMPS
Service Information
Existing Service Information New Service Information
☐ N/A – No Existing Service at this location ☐ N/A – Existing Service, Service Entrance will remain unchanged
Service Type:______________________________________________
Transformer Number:_______________________________________
Transformer Size:_______________________________________ Kva
Service Type:______________________________________________
Service:___________________________________________________
_________________________________________________________
Voltage: __________________________________________________
Voltage: __________________________________________________
Service terminates in:________________________________________
Service Entrance Size: Amps
Service terminates in:________________________________________
Service Entrance Size: Amps
Conductors/phase:___________ Conductor Size:_________________
Conduits: Number: Size:__________________________
Conductors/phase:___________ Conductor Size:_________________
Conduits: Number:__________ Size:__________________________
Cables: Quantity:___________ Solar: ☐ Yes ☐ No
Cables: Quantity:___________ Solar: ☐ Yes ☐ No
Meter Information
Existing Meter Information New Meter Information
N/A – No Existing Meters at this location
For multi-occupancy buildings, list all meters connected to this
service:___________________________________________________
_________________________________________________________
_________________________________________________________
N/A – Existing Meters, Service will remain unchanged
For multi-occupancy buildings, tenant meters will only be installed
for spaces being finished under this permit. Core and Shell only
projects will only receive a house meter on the C&S permit.
Max. Potential # of Meters at Build out: _______COM _______Res
Meter Number: Size: Meter Will: Size and Number of New Meters Being Requested
_____________ _______Amps ☐ Remain ☐ Be Removed Commercial Meters Residential Meters
_____________ _______Amps ☐ Remain ☐ Be Removed
_____________ _______Amps ☐ Remain ☐ Be Removed ______Ph ____ W____/___V ______Ph ____ W____/___V
_____________ _______Amps ☐ Remain ☐ Be Removed
_____________ _______Amps ☐ Remain ☐ Be Removed Number of Meters Needed: Number of Meters Needed:
_____________ _______Amps ☐ Remain ☐ Be Removed ______@__________Amps ______@__________Amps
_____________ _______Amps ☐ Remain ☐ Be Removed ______@__________Amps ______@__________Amps
_____________ _______Amps ☐ Remain ☐ Be Removed
_____________ _______Amps ☐ Remain ☐ Be Removed
_____________ _______Amps ☐ Remain ☐ Be Removed
______@__________Amps
______@__________Amps
______@__________Amps
______@__________Amps
______@__________Amps
______@__________Amps
CUSTOMER SIGNATURE AND ADDITIONAL INFORMATION
LOAD DATA MUST BE AS COMPLETE AS POSSIBLE. COST OF CHANGES DUE TO INADEQUATE/INACCURATE INFORMATION
WILL BE BORNE BY HE PROPERTY OWNER OR ELECTRICIAN.
LOAD DATA FORMS WITHOUT PLANS MAY BE DELAYED AND/OR NOT PROCESSED.
SITE GRADING, UTILITY, AND LANDSCAPING PLANS ARE REQUIRED WHEN PRIMARY ELECTRICAL EXTENSIONS ARE
NECESSARY.
NOTE: A METER WILL NOT BE INSTALLED UNTIL THE PERSON FINANCIALLY RESPONSIBLE FOR THE BILLING HAS
SET UP AN ACCOUNT WITH THE CITY OF ASPEN’S UTILITY BILLING DPEARTMENT, LOCATED AT 130 S. GALENA ST.,
ASPEN, CO 81611, PHONE # 970.920.5030.
FORM WILL NOT BE PROCESSED WITHOUT SIGNATURE.
Signature of Authorized Party:________________________________________________________________ Date:_______________________
For City of Aspen Use Only
City of Aspen Electric Utility Approved by (print name):____________________________________________________________
Signature of City Approver:________________________________________________________ Date:____________________
City of Aspen Electric Department - Phone: 970.920.5148
G
J
3
4
20
T45P T45S
21
5
22
24
T45P T45S
25 26 27
28
7
#3/0 BLDG STEEL
AND WATER ENTRY
FEEDER SCHEDULEFEEDER SCHEDULE
TRANSFORMER FEEDER SCHEDULE
600D
800D
1000D
1200D
ELEV
45D (3#6+#10G)1"C
400D
450D
500D
350D
300D
175D
225D
250D
200D
110D
90D
125D
150D
100D
80D
60D
70D
50D
(3-350KCMIL+#4G)2-1/2"C
(3-500KCMIL+#3G)3"C
(3-250KCMIL+#4G)2-1/2"C
(3#2/0+#6G)2"C
(3#4/0+#4G)2"C
(3#3/0+#6G)2"C
(3#1+#6G)1-1/2"C
(3#2+#8G)1-1/4"C
(3#1/0+#6G)1-1/2"C
(3#1+#6G)1-1/2"C
(3#1+#8G)1-1/2"C
(3#3+#8G)1-1/4"C
(3#4+#10G)1-1/4"C
(3#4+#8G)1-1/4"C
(3#6+#10G)1"C
WIRE AND CONDUIT SIZE - 3∅, 3W
35D
40D
30D
(3#8+#10G)3/4"C
(3#8+#10G)3/4"C
(3#10+#10G)3/4"C
(3#10+#10G)3/4"C
4[(3-350KCMIL+#3/0G)3"C]
3[(3-400KCMIL+#2/0G)2-1/2"C]
3[(3-300KCMIL+#1/0G)2-1/2"C]
2[(3-250KCMIL+#2G)2-1/2"C]
2[(3-350KCMIL+#1G)2-1/2"C]
2[(3#4/0+#2G)2"C]
2[(3#3/0+#3G)2"C]
2500Y
3000Y
4000Y
800Y
1000Y
1200Y
1600Y
2000Y
11[(4-500KCMIL+500KCMIL G)4"C]
8[(4-500KCMIL+400KCMIL G)3-1/2"C]
7[(4-500KCMIL+350KCMIL G)3-1/2"C]
6[(4-400KCMIL+250KCMIL G)3"C]
5[(4-400KCMIL+#4/0G)3"C]
4[(4-350KCMIL+#3/0G)3"C]
3[(4-400KCMIL+#2/0G)3"C]
3[(4-300KCMIL+#1/0G)2-1/2"C]
175Y
350Y
400Y
450Y
500Y
600Y
300Y
225Y
250Y
200Y
110Y
125Y
150Y
100Y
90Y
80Y
60Y
70Y
50Y
(4#2/0+#6G)2"C
2[(4-250KCMIL+#2G)2-1/2"C]
(4-350KCMIL+#4G)3"C
(4-500KCMIL+#3G)3"C
2[(4-350KCMIL+#1G)3"C]
(4-250KCMIL+#4G)2-1/2"C
(4#4/0+#4G)2-1/2"C
2[(4#4/0+#2G)2"C]
2[(4#3/0+#3G)2-1/2"C]
(4#3/0+#6G)2"C
(4#2+#8G)1-1/4"C
(4#1+#6G)1-1/2"C
(4#1/0+#6G)2"C
(4#1+#6G)1-1/2"C
(4#1+#8G)1-1/2"C
(4#3+#8G)1-1/4"C
(4#4+#10G)1-1/4"C
(4#4+#8G)1-1/4"C
(4#6+#10G)1"C
WIRE AND CONDUIT SIZE - 3∅, 4W
45Y
35Y
40Y
30Y
(4#6+#10G)1"C
(4#8+#10G)1"C
(4#8+#10G)1"C
(4#10+#10G)3/4"C
1600U 5[(4-400KCMIL)3"C] + (1)4"C SPR
MECH REFER TO MECHANICAL SCHEDULE
WIRE AND CONDUIT SIZE - 3∅
3[(4-400KCMIL+#3/0G)3"C]
(4#1/0+#6G)2"C
(3#3+#8G)1-1/4"C
2[(3#4/0+#2G)2"C]
T300S
T300P
T45S
T45P
(4#2+#8G)1-1/4"C
(3#6+#10G)1"C
T30S
T30P
ELEV-R (4#4+#8G)1"C
U
1
6
2
16
89
10 11
13 14
18
19
15
23
1-1/2"C 1-1/2"C 1-1/2"C 1-1/2"C
17
(4#2+#6G)1 1/4"C
(4#2+#6G)1 1/4"C
(4#2+#6G)1 1/4"C
MSP
D
SP
D
M
M
MIDDLE LEVEL
MAIN LEVEL
ROOF
BASEMENT LEVEL
UPPER LEVEL
CITY OF ASPEN
ELECTRICAL
UTILITY PADMOUNT
TRANSFORMER WITH
PRECAST
TRANSFORMER VAULT
BY EC. PER COA
REQUIREMENTS
1. PROVIDE DEMAND METERS, COMPATIBLE WITH METERING
SYSTEM, TO MONITOR PANEL AND EQUIPMENT AS NOTED.
PROVIDE SIZE AS REQUIRED FOR METERED PANEL.
COORDINATE AND VERIFY EXACT TYPE WITH OWNER
PRIOR TO ORDERING.
2. REFER TO OWNER EQUIPMENT SCHEDULE ON E6.0 FOR
FEEDER SIZE.
3. PROVIDE ARC FLASH ENERGY REDUCTION PER NEC 240.87.
4. PROVIDE 250KW/312KVA NATURAL GAS STANDBY
GENERATOR. DERATE FOR ALTITUDE. REFER TO E7.1 FOR
CALCULATIONS.
5. ELECTRICAL CONTRACTOR TO PROVIDE CONNECTION TO
LINE SIDE OF EACH UPS. UPSs ARE PROVIDED BY OWNER
A. LOCAL ELECTRICAL UTILITY IS COA (CITY OF ASPEN
UTILITY). ELECTRICAL CONTRACTOR TO MEET COA
REQUIREMENTS FOR INSTALLATION.
B. GENERATOR MUST MEET OR EXCEED THE CALIFORNIA
SOUTH COAST AIR QUALITY MANAGEMENT DISTRICT
REQUIREMENTS TO ACHIEVE WELL BUILDING POINT.
C. PROVIDE BACKFED TYPE BREAKERS WHERE REQUIRED
FOR PV SYSTEM.
ONE-LINE DIAGRAM FLAG NOTES:
ONE-LINE DIAGRAM GENERAL NOTES:
1 4
3
2
1
5
5
1
M
PANEL
LB
PANEL
M1
PANEL
L1
PANEL
M2
PANEL
L2
PANEL
M3
PANEL
L3
PANEL
SB
PANEL
MB
PANEL
SL3
PANEL
SLB
PANEL
MBA
PANEL
MDFA
SOLAR
COLLECTOR
PANEL
UTILITY
PRIMARY
1600U
NEMA 3R OUTDOOR
SERVICE ENTRY - MSD1
1600A, 480Y/277V, 3PH, 4W
1600A
3P
1600Y
BASEMENT POWER
AND LIGHTING
ELEV
450A
3P
ELEV
MAIN SWITCHBOARD MSB1-1600A, 480Y/277V, 3PH, 4W
ELEV
CONTROLLER
N
G
#4 UFER
MAIN
MECHANICAL
MAIN POWER
AND LIGHTING
MIDDLE
MECHANICAL
MIDDLE
POWER AND
LIGHTING
UPPER
MECHANICAL
UPPER
POWER AND
LIGHTING
30A
3P
400A
SPACE
60A
3P
60Y
25A
30AF
400A
3P
ATS
400A3P
400Y
400Y
400A3P
250A
3P
250Y
BASEMENT
MECHANICAL
SPACES:
(3) 200A3P
(3) 100A3P
400Y
ELEV
#6 GROUND ROD
100Y
200A
3P
400A
3P
200Y 400Y
400A
3P
200A
3P
400Y 200Y
LBDP, 1000A-208Y/120V, 3PH, 4W
1000A
MCB
T-LBDP
300 KVA
480V-120/208
T-SLB
45 KVA
480V-120/208
T300S
T300P
400A
3P
400Y
400A
3P
400Y
200A
3P
200Y
100A
3P
E-4
100A
SPACE
100A
SPACE
100A
SPACE
100A
SPACE
FUTURE
CAR CHARGER
RE: E1.0
FUTURE
CAR CHARGER
RE: E1.0
FUTURE
CAR CHARGER
RE: E1.0
FUTURE
CAR CHARGER
RE: E1.0
GFCI
60A
3P
60Y
#3/0G
#6G
90A
3P
150Y
BASEMENT
MECHANICAL
T-MDFA
45 KVA
480V-120/208 #8G
100A
90AF
UPPER
POWER AND
LIGHTING
UPS-A
UPS-B
90Y
90Y
3P
70A
ELEV-R
70A
100AF
ELEV-R
ELEV-RIO
ELEV
CONTROLLER
30
FAULT CURRENT CALCULATIONS
Maximum Available Fault Current (IAIC)
I SCA = (I AIC x M)
Where M = 1 / (1+f), and f = (1.732 x L x I AIC) / (C x n x E)
Po
i
n
t
Fault Location
Le
n
g
t
h
,
f
e
e
t
Co
n
d
u
c
t
o
r
s
si
z
e
#
co
n
d
u
c
t
o
r
s
pe
r
p
h
a
s
e
Cu
(1)
Al
(2)Co
n
d
u
i
t
Ma
g
n
e
t
i
c
(
1
)
No
n
m
a
g
n
.
(
2
)
Vo
l
t
a
g
e
Ph
a
s
e
"C" Value
Pr
e
v
i
o
u
s
fa
u
l
t
v
a
l
u
e
Fault value
U Service Transformer Secondary Winding per CCA 20,200
1 OUTDOOR SERVICE ENTRY 10 400 5 1 2 480 3 24296 20,200 20,080
2 MSB1 50 400 5 1 2 480 3 24296 20,080 19,498
3 T-LBDP 5 "4/0" 2 1 1 480 3 15082 19,498 19,273
5 PANEL LBDP 5 400 3 1 1 208 3 20565 17,091 16,896
6 PANEL LB 15 "3/0" 1 1 1 208 3 12843 16,896 14,511
7 SOLAR COLLECTOR PANEL 60 2 1 1 1 208 3 5906 16,896 6,955
8 PANEL M1 50 "3/0" 2 1 1 208 3 12843 16,896 13,264
9 PANEL L1 50 "3/0" 2 1 1 208 3 12843 16,896 13,264
10 PANEL M2 50 "3/0" 2 1 1 208 3 12843 16,896 13,264
11 PANEL L2 50 "3/0" 2 1 1 208 3 12843 16,896 13,264
13 PANEL M3 60 "3/0" 2 1 1 208 3 12843 16,896 12,717
14 PANEL L3 60 "3/0" 2 1 1 208 3 12843 16,896 12,717
15 PANEL MB 10 250 1 1 1 480 3 16483 19,498 18,700
16 ELEV-1 GALENA 25 10 1 1 1 480 3 981 19,498 6,981
17 PANEL MBA 130 "1/0" 1 1 1 480 3 8924 17,674 9,162
18 ATS-SB 70 300 3 1 1 480 3 18176 19,498 17,883
19 PANEL SB 10 300 3 1 1 480 3 18176 17,883 17,674
20 T-SLB 5 "3/0" 1 1 1 480 3 12843 17,674 17,246
22 PANEL SLB 10 "3/0" 1 1 1 208 3 12843 3,769 3,679
23 PANEL SL3 60 300 3 1 1 208 3 18176 3,679 3,559
24 T-MDFA 25 3 1 1 1 480 3 4760 17,674 13,239
26 PANEL MDFA 5 "1/0" 1 1 1 208 3 8924 3,664 3,603
27 UPS-A 20 2 1 1 1 208 3 5906 3,603 3,270
28 UPS-B 5 2 1 1 1 208 3 5906 3,603 3,513
For Second Transformer:
f = ( I SCA pri x E PRI x 1.732 x (%Z)) / (100000 x KVA)
I SCA sec = (E pri x M x I SCA pri) /E sec
Po
i
n
t
Fault Location Size, kVA
Pr
i
m
a
r
y
vo
l
t
a
g
e
,
V
Se
c
o
n
d
a
r
y
Vo
l
t
a
g
e
,
V
%Z
Ph
a
s
e
Pr
e
v
i
o
u
s
f
a
u
l
t
va
l
u
e
Fault value
4 T-LBDP 300.0 480 208 3 3 19,273 17,091
21 T-SLB 45.0 480 208 3 3 17,246 3,769
25 T-MDFA 45.0 480 208 3 3 13,239 3,664
CHARLES
CUNNIFFE
ARCHITECTS
COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC
SHEET NO.
JOB NO.
IMEG Corp
7600 E. Orchard Rd. Suite 250-S
Greenwood Village, CO 80111
p: 303-796-6000
f: 303-796-6099
IMEG Proj. No.: 2016.01.0223
11
/
1
2
/
2
0
2
0
1
0
:
2
8
:
5
1
A
M
E4.0
2016.01.0223
ELECTRICAL
ONE LINE
DIAGRAM
AS
P
E
N
C
I
T
Y
O
F
F
I
C
E
S
42
5
R
I
O
G
R
A
N
D
E
P
L
A
C
E
AS
P
E
N
,
C
O
ISSUE: DATE:
ASI 009 03/05/20
100%DD INT 4/3/20
Permit CO #02 4/17/20
Permit CO #03 4/24/20
100%CD INT 5/22/20
PERMIT INT 6/11/20
RIO VE
REVISIONS
11/13/20
30
RFI 183
RFI 183
J
E
{LS19}
{LS19}
{LS19}
E
600
L1- 2
L1- 2 L1- 2
L1- 2
SC
L3- 4
602
SD
SD SD
SD
202
ELEC RM
605
604604
MSB1-8,10,12
E-4
119
120
120
Z61
Z62
Z62Z62
Z62
SC
605
L3-4
Z60
608
608
M3-14
HEAT TRACE
M3-14
HEAT TRACE
31
CHARLES
CUNNIFFE
ARCHITECTS
COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC
SHEET NO.
JOB NO.
IMEG Corp
7600 E. Orchard Rd. Suite 250-S
Greenwood Village, CO 80111
p: 303-796-6000
f: 303-796-6099
IMEG Proj. No.: 2016.01.0223
11
/
1
7
/
2
0
2
0
9
:
4
8
:
1
8
A
M
E1.0
2016.01.0223
ELECTRICAL
SITE PLAN
AS
P
E
N
C
I
T
Y
O
F
F
I
C
E
S
42
5
R
I
O
G
R
A
N
D
E
P
L
A
C
E
AS
P
E
N
,
C
O
1" = 20'-0"1 ELECTRICAL SITE PLAN
FLAG NOTES (THIS SHEET)
119 TYPICAL OF (32) FIXTURES, SEE LANDSCAPE PLANS FOR MOUNTING DEATILS AND EXACT
LOCATIONS.
120 SEE LANDSCAPES DRAWINGS FOR MOUNTING DETAILS AND EXACT LOCATIONS.
202 PROVIDE FOUR-(4) 4" SERVICE ENTRANCE CONDUITS WITH PULL WIRES FOR TELEPHONE, DATA,
AND CATV AS NEEDED FROM THE TELECOM/DATA ROOM TO THE NEAREST UTILITY PEDESTAL OR
MANHOLE AS DIRECTED BY VENDOR. ROUTE CONDUITS IN TO BASEMENT LEVEL CEILING SPACE.
COORDINATE AND VERIFY EXACT ROUTING OF CONDUIT AND LOCATION OF PEDESTAL OR
MANHOLE PRIOR TO INSTALLATION.
600 SEE SHEET E3.1 FOR ELECTRIC SERVICE DETAILS.
602 PHOTOVOLTAIC SYSTEM TO BE DESIGNED BY OTHERS.
604 PROVIDE (4#1+#8G)1-1/2"C FROM MAIN ELECTRICAL ROOM AND (1) 1-1/2" SPARE CONDUIT FROM
DATA CENTER ROOM IN BASEMENT FOR CAR CHARGING STATION. COORDINATE EXACT
REQUIREMENTS WITH OWNER'S VENDOR.
605 PROVIDE (2) 1-1/2" CONDUITS STUBBED FROM MAIN ELECTRICAL ROOM AND (2) 1-1/2" CONDUITS
STUBBED FROM DATA CENTER ROOM IN BASEMENT TO PARKING LOT FOR FUTURE CAR CHARGING
STATIONS.
608 PROVIDE (1) 1" CONDUIT STUBBED FROM MAIN ELECTRICAL ROOM IN BASEMENT TO PARKING LOT
FOR FUTURE PARKING LOT LIGHTS.
ISSUE: DATE:
Permit CO #03 4/24/20
100%CD INT 5/22/20
PERMIT INT 6/11/20
RFI #312 8/7/20
RFI 341 11/09/20
BCHO
COMMENTS
11/09/20
RFI 473 11/17/20
GENERAL NOTES (LIGHTING)
A WHERE LUMINAIRE QUANTITIES OR LAYOUT DIFFER BETWEEN ARCHITECTURAL REFLECTED CEILING
PLANS AND ELECTRICAL LIGHTING PLANS, HIGHER QUANTITY SHALL TAKE PRECEDENCE.
CONTRACTOR SHALL CONFIRM QUANTITY AND LAYOUT WITH DESIGN TEAM.
B ALL FIXTURES LABELED 'E' OR SHOWN SHADED SHALL BE CONTROLLED WITH OTHER NORMAL
POWER LUMINAIRES IN THEIR ASSIGNED ZONE UNDER NORMAL POWER. DURING LOSS OF NORMAL
POWER ALL LUMINAIRES LABELED 'E' OR SHOWN SHADED SHALL BE POWERED FROM THE INTEGRAL
OR REMOTE MOUNTED BATTERY BALLAST COMPATIBLE WITH FIXTURE AND PROVIDE 100% LIGHT
OUTPUT. PROVIDE EMERGENCY ILLUMINATION OF NO LESS THAN 1 FOOTCANDLE AVERAGE (0.1FC
MIN) IN THE PATH OF EGRESS FOR EMERGENCY EVENTS PER NFPA. PROVIDE AUTOMATIC
SELF-TESTING EMERGENCY POWER UNITS.
C ALL DRAWINGS ARE DIAGRAMMATICAL ONLY. SYMBOLS ARE NOT NECESSARILY TO SCALE. USE
ARCHITECTURAL PLANS FOR DIMENSIONS. IF THESE DRAWINGS DIFFER SUBSTANTIALLY FROM
ARCHITECTURAL DRAWINGS, NOTIFY ARCHITECT IMMEDIATELY FOR A RESOLUTION.
D ALL EXIT SIGNS ARE TO BE CONNECTED TO LOCAL LIGHTING CIRCUIT AHEAD OF LOCAL SWITCHING.
E #B PUSH BUTTON REFERS TO SCENE QUANTITY. COORDINATE NUMBER OF BUTTONS FOR CONTROL
STATIONS WITH LIGHTING CONTROL MANUFACTURER. CONTROL SHALL BE CAPABLE OF DIMMING
UP/DOWN AND SWITCHING ON/OFF FOR MULTIPLE ZONES AS INDICATED AND PER LIGHTING
SEQUENCE OF OPERATIONS
F Z## INDICATES ZONING AND REFLECTS A LIGHTING CONTROL GROUP. PROVIDE RELAYS AS
REQUIRED TO ALLOW LUMINAIRES WITHIN THE DEFINED ZONE TO FUNCTION TOGETHER DURING
NORMAL POWER.
G {L##} DENOTES LIGHTING SEQUENCE OF OPERATIONS. REFER TO SHEET E6.0 FOR LIGHTING
CONTROL SEQUENCE OF OPERATIONS SCHEDULE.
H REFER TO SHEET E6.1 FOR LUMINAIRE SCHEDULE.
I SENSORS SHOWN ARE FOR REFERENCE ONLY. REFER TO LIGHTING CONTROL SEQUENCE OF
OPERATIONS. PROVIDE QUANTITY, LOCATE AND INSTALL PER MANUFACTURER'S
RECOMMENDATIONS AND REQUIREMENTS. PROVIDE APPROPRIATE SENSORS TO COVER AT
MINIMUM 90% OF THE SPACE INDICATED
J COORDINATE LUMINAIRE LOCATIONS AND MOUNTING WITH ALL EQUIPMENT, DEVICES, CONDUIT,
AND DUCTS.
RFI 109
RFI 220
RFI 341