Loading...
HomeMy WebLinkAboutFile Documents.834 W Hallam St.0010.2018 (13).ARBK834Hallam_BuildingComments_2 Page: A-010 ACESIBILITY ELEVATIONS File Name: Complete Permit Set Clarification 1.834 Hallam.2018.03.pdf Author: bonniem Subject: PlanCheck Color: Tub controls need to set off to the right so that they are between the centerline and edge of the bathtub rather than at the center of the tub. 2009 ICC A117.1 607.5, see figure 607.5 Complete Permit Set Clarification 1.834 Hallam.2018.03.pdf (11) Page: A-010 ACESIBILITY ELEVATIONS File Name: Complete Permit Set Clarification 1.834 Hallam.2018.03.pdf Author: bonniem Subject: PlanCheck Color: The clear space for the stove should be shown as a parallel approach because the oven prevents near and toe clearance under the range. Page: A-010 ACESIBILITY ELEVATIONS File Name: Complete Permit Set Clarification 1.834 Hallam.2018.03.pdf Author: bonniem Subject: PlanCheck Color: Microwave controls do not comply with the reach ranges in 309 as shown. The bottom of the microwave is at 46" which is the top of an obstructed high side reach. Page: A-202 ELEVATIONS File Name: Complete Permit Set Clarification 1.834 Hallam.2018.03.pdf Author: bonniem Subject: PlanCheck Color: Provide the finish floor elevation of the landing on each side of all exterior doors. IBC 1010.1.5 Page: A-204 ELEVATIONS File Name: Complete Permit Set Clarification 1.834 Hallam.2018.03.pdf Author: bonniem Subject: PlanCheck Color: You specify the locations for the water and electric meters but not the gas meter. Gas meters can not be located below an operable window. Specify gas meter locations at an approved location per Black Hills Energy standards. ` 24"24" MIN 12" MAX 33-36" 18" MIN 8-10" REQ. BLOCKING ANSI 1003.11.1 34" MAX 38" 14-19" 39-41" 17-19" 39-41" 12" MAX 54" MIN 42" MIN 18" MIN 24-42" REQ. BLOCKINGANSI 1003.11.1 33-36" 3-6" 34" MAX 24" MIN 15"15" 4" 6" 18" MIN REQ. BLOCKING ANSI 1003.11.1 18" SCALE: 1/2" = 1'-0"1 UNIT 103 BATHROOM SCALE: 1/2" = 1'-0"3 UNIT 103 BA SCALE: 1/2" = 1'-0"4 UNIT 103 BR SCALE: 1/2" = 1'-0"2 UNIT 103 BATHROOM SCALE: 1/2" = 17POWDER Tub controls need to set off to the right so that they are between the centerline and edge of the bathtub rather than at the center of the tub. 2009 ICC A117.1 607.5, see figure 607.5 RGGFIC 30" 30" 48" 30" 48" 48" 12" 60"5 CHEN NIT 103 LAUNDRY UNIT 103 F SCALE: 1/2" = 1'-0"103 BATHROOM PLAN The clear space for the stove should be shown as a parallel approach because the oven prevents near and toe clearance under the range. 12" 36" 113/4" SINK PER ANSI 1003.12.4 COOKTOP PER ANSI 1003.12.5.4 DW PER ANSI 1003.12.5.3 WORKSTATION PER ANSI 1003.12.3 MICROWAVE CONTROLS PER ANSI 309 SCALE: 1/2" = 1'-0"1 UNIT 103 BATHROOM SCALE: 1/2" = 1'-0"2 UNIT 103 BAT Microwave controls do not comply with the reach ranges in 309 as shown. The bottom of the microwave is at 46" which is the top of an obstructed high side reach. Provide the finish floor elevation of the landing on each side of all exterior doors. IBC 1010.1.5 9'-0" 9'-0" 9'-2" 3'-8" 27'-77/8" 218 006007 220 219 28 56 31 35 51 53 51 53 56 55 63 43 T.O SLAB @ LOWER LEVEL@ BUILDING C: 89'-0" T.O PLY @ MAIN LEVEL@ BUILDING C: 98'-0" T.O PLY @ SECOND LEVEL@ BUILDING C: 107'-0" T.O PLY @ THIRD LEVEL@ BUILDING C: 116'-2" SG SG SG 0 2'4'8' 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 CASEMENT GAL PANEL TO BE NONO MORE THAN GARAGE SLAB T EGRESS SILL 44 SNOW STOPS FONARROW, PAINT DOWNSPOUT: R GUTTER: HALF-R WASHER/DRYER EAST SIDE YARDPER RES NO. 24 DISTANCE BETWPER RES NO. 24 NORTHWEST BUSTREET PER RE NEW CONSTRUCOF 37 SQ FT, WIT NORTHWEST BUEIGHTH STREET MAILBOXES FDC EXTERIOR LIGH EXTERIOR LIGH SNOW STOPS FOPAINTED ALUMIN HISTORIC WOODCOLUMNS SALVA ORNAMENTAL TRFRONT PIECE, A WOOD FRONT PREPLICATE HIST You specify the locations for the water and electric meters but not the gas meter. Gas meters can not be located below an operable window. Specify gas meter locations at an approved location per Black Hills Energy standards. ` Page: A-302 SECTIONS File Name: Complete Permit Set Clarification 1.834 Hallam.2018.03.pdf Author: bonniem Subject: PlanCheck Color: Additional detailing is required to clearly depict which walls and ceilings will be serving as the fire partitions and show that they will be continuous throughout. In section view indicate which walls and ceiling are serving as the fire partitions. Then provide details at the interior floor ceiling intersections. Page: A-501 ASEMBLIES File Name: Complete Permit Set Clarification 1.834 Hallam.2018.03.pdf Author: bonniem Subject: PlanCheck Color: For clarity include the entire floor ceiling assembly ie: F-4+C-1+FF1 all in the same detail. Because the components act together to provide both the fire-resistance and sound-resistance they should be shown together as one detail. Page: A-502 EXTERIOR ONSTRUCTION DETAIL File Name: Complete Permit Set Clarification 1.834 Hallam.2018.03.pdf Author: bonniem Subject: PlanCheck Color: It appears that spray foam will serve as the required air barrier (2015 IECC Table R402.4.1.1). Provide additional notes in the exterior details to show where additional air sealing will be provided to achieve the continuous air barrier. Refer to the City of Aspen's sample air barrier details. Page: A-502 EXTERIOR ONSTRUCTION DETAIL File Name: Complete Permit Set Clarification 1.834 Hallam.2018.03.pdf Author: bonniem Subject: PlanCheck Color: This detail does not match the detail shown on S402 #6. Page: A-503 EXTERIOR ONSTRUCTION DETAIL File Name: Complete Permit Set Clarification 1.834 Hallam.2018.03.pdf Author: bonniem Subject: Group Color: H G F A 1A-502 1A-502 3A-502 3A-502 8A-502 7A-502 6A-502 11A-502 11A-502 11A-502 F-1 F-1 F-1 R-3 FF-1FF-1 FF-1 F-2 FF-1 F-2 FF-1 F-2 FF-1 F-2 FF-1 F-2 FF-1 F-2 FF-1 F-2 FF-1 W-4 W-6W-4 W-6 W-1 W-1 W-4 W-6 W-6 W-4W-6 W-6 W-6 W-6 W-6 W-6 W-4 R-3 R-2 R-2 W-7 W-6 W-8W-6 W-8 101/8" 8'-0" 1'-1" 7'-93/4" 1'-21/4" 7'-113/4" 1'-21/4" 9'-0" 111/8" 9'-33/4" 1'-21/4" 7'-93/4" 1'-21/4" 9'-0" 11/2" 7'-93/4" 1'-21/4" 7'-93/4" 1'-21/4" 10'-6" CA-303DA-304 T.O SLAB @ LOWER LEVEL@ BUILDING C: 89'-0" T.O PLY @ MAIN LEVEL@ BUILDING C: 99'-6" T.O PLY @ SECOND LEVEL@ BUILDING C: 108'-6" T.O PLY @ THIRD LEVEL@ BUILDING C: 116'-2" T.O SLAB @ LOWER LEVEL@ BUILDING C: 89'-0" T.O PLY @ MAIN LEVEL@ BUILDING C: 98'-0" T.O PLY @ SECOND LEVEL@ BUILDING C: 107'-0" BEDROOM 3UNIT 106 STORAGEUNIT 106 LIVINGUNIT 106 LIVINGUNIT 105 LOWERLEVELUNIT 106 BATH 1UNIT 104 BEDROOM 3UNIT 103 STORAGEUNIT 102 ENTRYUNIT 106 CLOSETUNIT 103 BEDROOM 1UNIT 103 POWDERUNIT 104 KITCHENUNIT 104 BEDROOM 3UNIT 104 BEDROOM 2UNIT 104 BEDROOM 1UNIT 105 FOYER ENTRYUNIT 104 BATH 1UNIT 106 SETBACK LINE PROPERTY LINE SETBACK LINE PROPERTY LINE STAIRUNIT 103 LAUNDRYUNIT 106 CLOSETUNIT 105 0 2'4'8'SCALE: 1/4" = 1'-0"B SECTION 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 MECHANICAL EQUIPMNON-STREET FACING PARKING WITHIN ESTPER 26.575.020.E.5.r PER 26.575.020.E.5.k FENCE <42" PER 26.5 VERTICAL CIRCULATIMOST FLOOR PER 26 FRONT PORCH PER 2 MECHANICAL PROJECROOF PER 26.575.020 MU ZONE DISTRICT H CHIMNEY PROJECTIOCONNECTION PER 26 DORMERS EXEMPT P 28' OFFSET OF MOST 1/3 POINT FROM EAVE EXISTING GRADE PROPOSED GRADE WINDOW TRIM TBD SILVER CREEK - MACRED CEDAR SHAKES TRUDEFINITION DUR DECK MATERIAL TBD EXTERIOR RAILING M EXISTING HISTORIC SREMAINHARDIEPLANK SMOOEXISTING HISTORIC SHARDIEPLANK SMOOSIDING. 5" OF EXPOSEXISTING HISTORIC WREMAINWINDOW TRIM TO MAHISTORIC TRIM CHIMNEY TO BE RESUSING SALVAGED HIS WINDOW WELL PER ICASEMENT GALVANIZ NEW LIFE + SAFETY S LINE OF EXTERIOR W HEAT PUMP WATER + ELECTRIC M PATIO SNOWMELT PE DRYER EXHAUST LOC HANDRAIL PER IRC 3 PANEL TO BE NON-LONO MORE THAN 15 LB GARAGE SLAB TO SL ROOF OVERHANG SEWAGE EJECTOR A ELECTRICAL PANEL L EGRESS SILL 44" AFF RADON VENT PIPE SNOW STOPS FOR ASNARROW, PAINTED ADOWNSPOUT: ROUND FLUE VENT; TYP. LOCAPPROVED BY HPC S GUTTER: HALF-ROUN WASHER/DRYER HOO EAST SIDE YARD SETPER RES NO. 24 OF 2DISTANCE BETWEENPER RES NO. 24 OF 2NORTHWEST BUILDINSTREET PER RES NO NEW CONSTRUCTIONOF 37 SQ FT, WITH A M NORTHWEST BUILDINEIGHTH STREET PER MAILBOXES FDC EXTERIOR LIGHTING: EXTERIOR LIGHTING: SNOW STOPS FOR WPAINTED ALUMINUM, LINE OF NO EXCAVAT HISTORIC WOOD PORCOLUMNS SALVAGEDORNAMENTAL TRIM TFRONT PIECE, AND HWOOD FRONT PORCHREPLICATE HISTORIC Additional detailing is required to clearlydepict which walls and ceilings will be servingas the fire partitions and show that they willbe continuous throughout. In sectionview indicate which walls and ceiling areserving as the firepartitions. Thenprovide details at theinterior floor ceilingintersections. STEVENWILSON402127 STATE OFCOLORADO LICENSEDARCHITECT COPYRIGHT 04/01/2018 PROJECT NO: DRAWN BY:FORUM PHI LLC DATE OF PUBLICATION A-501 ASSEMBLIES 04/01/2018 AP + AG PARCEL ID # 273-512-304-002 LEGAL DESCRIPTION: City and Townsite of Aspen block: 10, Lot: K & L ZONE DISTRICT MU 1502.00 Aspen CO 81611834 HALLAM Aspen:715 West Main Street, #204Aspen, Colorado 81611 Basalt:104 Midland Ave, #202Basalt, CO 81612 forumphi.comp: 970.279.4157f: 866.770.5585 City and townsite of Aspenblock: 10, Lot: K & L 8"1/2" 2" 31/2" 31/2" AIR SPACECONCRETE REF STRUCT RIGID INSULATION; R-5 PER 1"DRAINAGE MATFLUID APPLIED WATERPROOFING SPRAY APPLIED CLOSED CELL FOAM INSULATION; R-6.25 PER 1"5/8" GYP W-1 EXTERIOR FOUNDATION WALL W/ 2X FURRING WALLR-33W-1 EXT INT W - EXT - CONCRETE + 2X FURRING WALL STUD; VIF HISTORIC HORIZONTAL WOOD SIDING TO REMAIN SPRAY APPLIED CLOSED CELL FOAM INSULATION; R-6.25 PER 1"GYP WATER RESISTIVE BARRIERSHEATHING REF STRUCT W-2 EXT INT EXTERIOR WOOD HISTORIC WALL TO REMAIN; VIFR-20INSULATION TO BE ADDED PER PLAN 4" HORIZONTAL COMPOSITE SIDING SPRAY APPLIED CLOSED CELL FOAM INSULATION; R-6.25 PER 1"GYP WATER RESISTIVE BARRIERSHEATHING REF STRUCT W-4W-4 EXT INT EXTERIOR WOOD WALL W/ HORIZONTAL SIDINGR-25 PER PLAN WOOD STUD5/8" GYP 5/8" GYP W-6 INTERIOR WOOD WALL W/ GYP W - INT - WD 2X - GYP 2" FINISH FLOOR PER PLANSCONCRETE REF STRUCT SCREENED ROCK RIGID INSULATION; R-5 PER 1"VAPOR BARRIER F-1 EXTERIOR FOUNDATION FLOORR-10 FLR + FF - SLAB ON GRADE + FINISH T.O.SLAB CEILING REF C-2 FINISH FLOOR PER PLANS SHEATHING REF STRUCT JOIST REF STRUCT SOUND INSULATION F-2 UNIT SEPARATION FLOOR FIRE RATING: 1/2 Hour per IBC Table 722.2.1.4(2)STC: 51 per California Office of Noise Control pg. 143 of 175 T.O.SUBFLOOR FLR + FF - WD JOIST + FINISH 51/2"VIF CLASS B CEDAR SHINGLESCLASS A RATED UNDERLAYMENTFULLY ADHERED ROOF MEMBRANESHEATHING REF STRUCTSPRAY APPLIED CLOSED CELL FOAMINSULATION; R-6.25 PER 1"RAISED TIE TRUSS; VIFCEILING PER PLAN R-1 EXISTING HISTORIC ROOF STRUCTURE TO REMAINR-34DEMO ASPHALT SHINGLES + REPLACE WITH CEDAR SHINGLES. ADD INSULATIONCLASS A RATED PER ESR-2053 T.O.SHEATHING SLOPE PERPLAN 51/2" CLASS A RATED ASPHALT SHINGLEFULLY ADHERED ROOF MEMBRANESHEATHING REF STRUCTSPRAY APPLIED CLOSED CELL FOAMINSULATION; R-6.25 PER 1"RAISED TIE TRUSS; REF STRUCT CEILING PER PLAN R-2 ARCHITECTURAL SHINGLE ROOFR-34 CLASS A RATED PER UL ER2453-02 T.O.SHEATHING SLOPE PERPLAN PER PLAN HORIZONTAL COMPOSITE SIDING TO MATCH HISTORIC SPRAY APPLIED CLOSED CELL FOAM INSULATION; R-6.25 PER 1"GYP WATER RESISTIVE BARRIERSHEATHING REF STRUCT W-3W-3 EXT INT EXTERIOR WOOD WALL W/ HORIZONTAL SIDING TO MATCH HISTORICR-20 PER PLAN 4" HORIZONTAL COMPOSITE SIDING SPRAY APPLIED CLOSED CELL FOAM INSULATION; R-6.25 PER 1"GYP - TYPE X WATER RESISTIVE BARRIERSHEATHING REF STRUCT W-5 EXT INT EXTERIOR WOOD WALL W/ HORIZONTAL SIDINGR-25FIRE RATING: 1 HOUR PER UL 263; DESIGN NO. U354 PER PLAN STAGGERED WOOD STUD + SOUND INSULATION 5/8" TYPE X GYP 5/8" ACOUSTICAL TYPE-X GYP PLYWOOD W-7 W - INT - SHEER WALLS INTERIOR FIRE RATED UNIT SEPARATION WALL W/ SHEATHING FIRE RATING: 1/2 HOUR PER IBC TABLE 722.2.1.4(2)STC: 51 per California Office of Noise Control pg. 63 of 175 CEILING REF C-3 FINISH FLOOR PER PLANS SHEATHING REF STRUCT JOIST REF STRUCT SOUND INSULATION F-3 SEPARATION FLOOR BETWEEN UNIT AND TRASH ENCLOSURE FIRE RATING: 1 Hour per IBC Table 722.2.1.4(2)STC: 51 per California Office of Noise Control pg. 143 of 175 T.O.SUBFLOOR FLR + FF - WD JOIST + FINISH CEILING REF C-1 FINISH FLOOR PER PLANS SHEATHING REF STRUCT JOIST REF STRUCT F-4 TYP FLOOR WITHIN UNIT T.O.SUBFLOOR CEILING REF C-1 WATERPROOF MEMBRANEFINISH FLOOR PER PLANS SHEATHING REF STRUCT JOIST REF STRUCTSPRAY APPLIED CLOSED CELL FOAMINSULATION; R-6.25 PER 1" R-3 T.O.SHEATHING EXTERIOR FLOOR OVER INTERIORR-49 SOUND ISOLATION MAT WOOD VINYL PRODUCT FF-1 WOOD VINYL COMPOSITE FF - WOOD T.O. FF T.O.STRUCT WATERPROOFING MEMBRANE SOFFIT PER PLAN FINISH FLOOR PER PLANS SHEATHING REF STRUCT JOIST REF STRUCTSPRAY APPLIED CLOSED CELL FOAMINSULATION; R-6.25 PER 1"SHEATHING REF STRUCT F-5 T.O.SUBFLOOR INTERIOR FLOOR OVER EXTERIORR-56 SOUND CLIP5/8" GYP C-1 B.O.STRUCT PER PLAN STAGGERED WOOD STUD + SOUND INSULATION5/8" TYPE X GYP 5/8" ACOUSTICAL TYPE-X GYP W-8 W - INT - DEMISING INTERIOR FIRE RATED UNIT SEPARATION WALL FIRE RATING: 1/2 HOUR PER IBC TABLE 722.2.1.4(2)STC: 51 per California Office of Noise Control pg. 63 of 175 CEILING REF C-2 WATERPROOF MEMBRANECONCRETE TOPPING REF STRUCT SHEATHING REF STRUCT JOIST REF STRUCTSPRAY APPLIED CLOSED CELL FOAMINSULATION; R-6.25 PER 1" R-4 T.O.SHEATHING TRASH ROOM FLOOR OVER INTERIORR-49FIRE RATING: 1 Hour per IBC Table 722.2.1.2(1) + 722.2.1.2(2) + 722.2.1.4(2)STC: 58 per California Office of Noise Control pg 160 of 175 SOUND CLIP5/8" TYPE X GYP C-2 B.O.STRUCTSOUND CLIP5/8" TYPE X GYP 5/8" TYPE X GYP C-3 B.O.STRUCT WATERPROOFING MEMBRANE SOFFIT PER PLAN FINISH FLOOR PER PLANS SHEATHING REF STRUCT JOIST REF STRUCTSPRAY APPLIED CLOSED CELL FOAMINSULATION; R-6.25 PER 1"SHEATHING REF STRUCT F-5 T.O.SUBFLOOR INTERIOR FLOOR OVER EXTERIORR-56 W-2 For clarity include theentire floor ceilingassembly ie:F-4+C-1+FF1 all in thesame detail. Becausethe components acttogether to provideboth thefire-resistance andsound-resistance theyshould be showntogether as one detail. SNOWSTOP PER MFR It appears that spray foam will serve as the required air barrier (2015 IECC Table R402.4.1.1). Provide additional notes in the exterior details to show where additional air sealing will be provided to achieve the continuous air barrier. Refer to the City of Aspen's sample air barrier details. W-2,3,4 F-2 W-8 FF-1 W-8 SILL PLATE TYPE-X GYP FIRE BARRIER BLOCKING SOUND CLIP FIRE CAULKING SAFF METAL DRIP EDGE FLASHING WATERPROOF MEMBRANE MEMBER REF STRUCT MEMBER REF STRUCT BLOCKING AS REQ'D FASCIA REF PLAN SOFFIT REF PLAN BLOCKING BLOCKING ROOF OVERHANG BEYOND SCALE: 1 1/2"= 1'-0"12 FIRE-RATED INT STACKED WALLS SCALE: 1 1/2"= 11 TYP RA This detail does not match the detail shown on S402 #6. COPYRIGHT PROJECT NO: DRAWN BY: FORUM PHI LLC DATE OF PUBLICATION A-503 EXTERIOR CONSTRUCTION DETAILS 04/01/2018 AP + AG PARCEL ID # 273-512-304-002 LEGAL DESCRIPTION: City and Townsite of Aspen block: 10, Lot: K & L ZONE DISTRICT MU 1502.00 R-3 W-4 F-2 1/2"CONTINUOUS WATERPROOFING CONTINUOUS METAL FLASHING- FOLDED AND SOLDERED @JOINTS AND CORNERSMEMBER REF STRUCT BLOCKING DOOR PER SCHEDULE THRESHOLD TO BE FLUSH WITHFINISH FLOORS CONCRETE SILLEXT EXT INT INT SLOPE PER PLAN F-2 W-8 FF-1 W-6 FIRE CAULKING TYPE-X GYP FIRE BARRIER SOUND CLIP SILL PLATE SCALE: 1 1/2"= 1'-0"14 TYP DOOR SILL SCALE: 1 1/2"= 1'-0"13 FIRE-RATED INT OFFSET WALLS Page: S-402 DETAILS File Name: Complete Permit Set Clarification 1.834 Hallam.2018.03.pdf Author: bonniem Subject: PlanCheck Color: This detail does not match the wall assembly, and architectural conditions presented on A501-502. The Simpson Hanger is for use with a hour assembly, so if using this method, it will need to be a 1-hour wall rather than 30 minutes. Page: P.1.04 THIRD LEVEL PLUMBING PLAN File Name: plumbing drawings.pdf Author: bonniem Subject: PlanCheck Color: P.1.04 repeats the main level plumbing plan where the 3rd level plumbing plan should be shown. plumbing drawings.pdf (2) Page: P.6.01 PLUMBING RISER DIAGRAMS File Name: plumbing drawings.pdf Author: bonniem Subject: PlanCheck Color: It appears that all levels are draining to the sump in the basement of unit 106. All levels which can drain to gravity are required to do so per 2015 IPC 712.1 2"2"2" EQ EQ C TYPICAL BOT PLATE NAILING,RE: TYPICAL DETAILS TYPICAL TOP PLATE NAILING,RE: TYPICAL DETAILS SIMPSON FIRE RATED DRYWALL HANGER,RE: HANGER SCHEDULE SHEATHING SHOULD NOTPENETRATE DRYWALL FIRE RATED STUD WALL,RE: ARCH BOT PLATE TO JOIST ORBLOCKING, RE: TYPICAL DETAILS T/SHEATHING 1" = 1'-0"6 EXISTING STRUCTURE FRAMING DETAIL This detail does not match the wall assembly, and architectural conditions presented on A501-502. The Simpson Hanger is for use with a hour assembly, so if using this method, it will need to be a 1-hour wall rather than 30 minutes. UNIT 103 E E C C 55 22 88 A A F F G G H H 77 44 33 11 BEDROOM 1UNIT 103 ENTRYUNIT 102 F F D D B B DW DWRG 66 RG POWDERUNIT 107 TRASH ENCLOSURE STORAGEUNIT 105 STORAGEUNIT 104 STORAGEUNIT 103 STORAGEUNIT 106 STORAGEUNIT 102 STORAGEUNIT 101STORAGEUNIT 107 LIVINGUNIT 101 BATHROOM 1UNIT 103 LIVINGUNIT 107 ENTRYUNIT 107 KITCHENUNIT 102 LIVINGUNIT 102 KITCHENUNIT 101 ENTRYUNIT 101 ENTRYUNIT 103 LIVING UNIT 106 ENTRYUNIT 105 LAUNDRYUNIT 103 DW FOYER KITCHENUNIT 103 ENTRYUNIT 104 RG ENTRY 3 SH-1 1 LV-1 2 WC-1 KS-1 4 5 CWB KS-14 KS-1 4 1.112" W, 112" V, 12" CW & 12" HW TO LV-1. 2.3" W, 2" V & 12" CW TO WC-1. 3.2" W, 1-1/2" V & 1/2" CW & HW TO SH-1. 4.2" W, 1-1/2" V & 1/2" CW & HW TO KS-1.EXTEND HW & IW LINE TO DISHWASHER. 5.3" W, 2" V, & 1/2" CW & HW TO CWB. 6.3/4" CW TO FPHB-1. 7.4" W OUT OF THE BUILDING. PROVIDE COTG.VERIFY LOCATION, SIZE & INVERTS WITHCIVIL DRAWINGS. 8.2" CW SERVICE - VERIFY LOCATION ANDFINAL SIZES WITH FIRE SUPPRESSIONCONTRACTOR & CIVIL ENGINEER. INSTALLMETER ASSEMBLY PER THE TOWN OF ASPENWATER DISTRICT STANDARDS. Plumbing Notes: SYMBOL USED FOR NOTE DESIGNATION General Plumbing Notes: 1.PC TO PROVIDE CLEANOUTS AND ACCESS AT EACHCHANGE OF DIRECTION FOR W PIPING. 2.SOME PIPING, EQUIPMENT AND DUCTWORKSHOWN OFFSET FOR CLARITY. OFFSET PIPING ASREQUIRED TO ROUTE AROUND STRUCTURALMEMBERS - ANY STRUCTURAL MEMBERPENETRATION SHALL BE APPROVED BYSTRUCTURAL ENGINEER. COORDINATE ANYCONFLICTS WITH ARCHITECT, OWNER AND OTHERTRADES. 3.PROVIDE FREEZE PROTECTION TO ALL PIPINGSUBJECT TO EXPOSURE TO THE OUTDOORS. LV-1 WC-1 2 SHEET NUMBER: DRAWN BY: CHECKED BY: PROJECT MANAGER: SHEET TITLE: SEAL: NO.ISSUE DATE PROJECT NUMBER: SCALE: of PO BOX 810825A CHAMBERS AVENUEEAGLE, CO 81631800.543.9365www.randhmechanical.com 170915-01 BW ajs BW AS NOTED Permit Documents To w n s i t e o f A s p e n b l o c k : 1 0 , L o t K & L 11 BID DOC 10/19/2017 NO.REVISIONS DATE CITY STAMPS: 12 PERMIT DRAWINGS 11/20/2017 PEAK DESIGN GROUP LLC1338 GRAND AVE NO315GLENWOOD SPRINGS CO 81601970-688-0102www.peakdesign.org 3 PERMIT DRAWINGS MODS 11/20/2017 5 7 P.1.04 THIRD LEVELPLUMBING PLAN P.1.04 repeats themain level plumbingplan where the 3rdlevel plumbing planshould be shown. WC-1 LV-1 SH-1 SP-1 SH-1 WC-1 LV-1 FCO KS-1 WC-1 LL ML LL ML SH-1 LV-1 LL ML SH-1 WC-1 SH-1 WC-1 LV-1 FCO LV-1SH-1 LL WC-1 ML 2nd SH-1 LL ML ML LL ML LL ML LL CWB KS-1 ML CWB LV-1 WC-1 FCO LV-1 WC-1 FCO LV-1 SH-1 KS-1 ML ML LL LV-1 WC-1 SH-1 WC-1 LV-1 KS-1 LL ML LL COTG WC-1 FCO LV-1SH-1 ML WC-1 LV-1 ML LL LL LL LL LL LV-1 WC-1 SH-1 KS-1 VTR 2nd 2nd 2nd 2nd LLFCO LV-1 WC-1 SH-1 VTR ML 2nd 2nd LL ML CWB VTR KS-1 LL ML LL ML CWB 2nd 2nd 2nd 2nd 2nd LL LL LL LL 2nd 2nd 2nd 2nd LL CWB 2nd 2nd 2nd 2nd 2nd Waste & Vent Piping Isometric NO SCALE WH-1 SH-1 WC-1 LV-1 12" 12" 34" 1" 3rd 3rd 3rd CWB 3rd 12" KS-1 3rd 12" Unit 105 Water Piping Isometric WH-1 Unit 104 Water Piping Isometric SH-1 WC-1 LV-1 CWB KS-1 12" 12" 12" 12"1"1"WH-1 1" SH-1 WC-1 SH-1 LV-1 ML SH-1 ML WC-1 ML 1" 12"12" 34" 34" Unit 103 Water Piping Isometric WH-1 1" CWB 12"SH-1 WC-1 SH-1 12" 34" 2nd KS-1 34" DRAWN BY: PROJECT MANAGER: SHEET TITLE: SEAL: NO.ISSUE DATE PROJECT NUMBER: PO BOX 810825A CHAMBERS AVENUEEAGLE, CO 81631800.543.9365www.randhmechanical.com 170915-01 BW ajs To w n s i t e o f A s p e n b l o c k : 1 0 , L o t K & L 11 BID DOC 10/19/2017 NO.REVISIONS DATE CITY STAMPS: 12 PERMIT DRAWINGS 11/20/2017 PEAK DESIGN GROUP LLC1338 GRAND AVE NO315GLENWOOD SPRINGS CO 81601970-688-0102www.peakdesign.org 3 PERMIT DRAWINGS MODS 11/20/2017 PLUMBINGRISER DIAGRAMS It appears that alllevels are draining to the sump in the basement of unit 106.All levels which candrain to gravity arerequired to do so per2015 IPC 712.1