HomeMy WebLinkAboutFile Documents.834 W Hallam St.0010.2018 (13).ARBK834Hallam_BuildingComments_2
Page: A-010 ACESIBILITY ELEVATIONS
File Name: Complete Permit Set Clarification 1.834
Hallam.2018.03.pdf
Author: bonniem
Subject: PlanCheck
Color:
Tub controls need to set off to
the right so that they are
between the centerline and edge
of the bathtub rather than at the
center of the tub. 2009 ICC
A117.1 607.5, see figure 607.5
Complete Permit Set Clarification 1.834 Hallam.2018.03.pdf (11)
Page: A-010 ACESIBILITY ELEVATIONS
File Name: Complete Permit Set Clarification 1.834
Hallam.2018.03.pdf
Author: bonniem
Subject: PlanCheck
Color:
The clear space for the stove
should be shown as a parallel
approach because the oven
prevents near and toe clearance
under the range.
Page: A-010 ACESIBILITY ELEVATIONS
File Name: Complete Permit Set Clarification 1.834
Hallam.2018.03.pdf
Author: bonniem
Subject: PlanCheck
Color:
Microwave controls do not
comply with the reach ranges in
309 as shown. The bottom of
the microwave is at 46" which is
the top of an obstructed high
side reach.
Page: A-202 ELEVATIONS
File Name: Complete Permit Set Clarification 1.834
Hallam.2018.03.pdf
Author: bonniem
Subject: PlanCheck
Color:
Provide the finish floor elevation
of the landing on each side of all
exterior doors. IBC 1010.1.5
Page: A-204 ELEVATIONS
File Name: Complete Permit Set Clarification 1.834
Hallam.2018.03.pdf
Author: bonniem
Subject: PlanCheck
Color:
You specify the locations for the
water and electric meters but not
the gas meter. Gas meters can
not be located below an
operable window. Specify gas
meter locations at an approved
location per Black Hills Energy
standards. `
24"24" MIN 12" MAX
33-36"
18" MIN
8-10"
REQ. BLOCKING ANSI 1003.11.1
34" MAX
38"
14-19"
39-41"
17-19"
39-41"
12" MAX
54" MIN
42" MIN
18" MIN
24-42"
REQ. BLOCKINGANSI 1003.11.1
33-36"
3-6"
34" MAX
24" MIN
15"15"
4"
6"
18" MIN
REQ. BLOCKING ANSI 1003.11.1
18"
SCALE: 1/2" = 1'-0"1 UNIT 103 BATHROOM
SCALE: 1/2" = 1'-0"3 UNIT 103 BA
SCALE: 1/2" = 1'-0"4 UNIT 103 BR
SCALE: 1/2" = 1'-0"2 UNIT 103 BATHROOM
SCALE: 1/2" = 17POWDER
Tub controls need to
set off to the right so
that they are between
the centerline and
edge of the bathtub
rather than at the
center of the tub.
2009 ICC A117.1
607.5, see figure
607.5
RGGFIC
30"
30"
48"
30"
48"
48"
12"
60"5
CHEN
NIT 103 LAUNDRY
UNIT 103
F
SCALE: 1/2" = 1'-0"103 BATHROOM PLAN
The clear space for
the stove should be
shown as a parallel
approach because the
oven prevents near
and toe clearance
under the range.
12"
36"
113/4"
SINK PER ANSI 1003.12.4
COOKTOP PER ANSI 1003.12.5.4
DW PER ANSI 1003.12.5.3
WORKSTATION PER ANSI 1003.12.3
MICROWAVE CONTROLS PER ANSI 309
SCALE: 1/2" = 1'-0"1 UNIT 103 BATHROOM
SCALE: 1/2" = 1'-0"2 UNIT 103 BAT
Microwave controls do
not comply with the
reach ranges in 309
as shown. The bottom
of the microwave is at
46" which is the top of
an obstructed high
side reach.
Provide the finish floor elevation of the landing on each side of all exterior doors. IBC
1010.1.5
9'-0"
9'-0"
9'-2"
3'-8"
27'-77/8"
218
006007
220 219
28
56
31
35
51
53
51
53
56
55
63
43
T.O SLAB @ LOWER LEVEL@ BUILDING C: 89'-0"
T.O PLY @ MAIN LEVEL@ BUILDING C: 98'-0"
T.O PLY @ SECOND LEVEL@ BUILDING C: 107'-0"
T.O PLY @ THIRD LEVEL@ BUILDING C: 116'-2"
SG
SG SG
0 2'4'8'
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
CASEMENT GAL
PANEL TO BE NONO MORE THAN
GARAGE SLAB T
EGRESS SILL 44
SNOW STOPS FONARROW, PAINT
DOWNSPOUT: R
GUTTER: HALF-R
WASHER/DRYER
EAST SIDE YARDPER RES NO. 24
DISTANCE BETWPER RES NO. 24
NORTHWEST BUSTREET PER RE
NEW CONSTRUCOF 37 SQ FT, WIT
NORTHWEST BUEIGHTH STREET
MAILBOXES
FDC
EXTERIOR LIGH
EXTERIOR LIGH
SNOW STOPS FOPAINTED ALUMIN
HISTORIC WOODCOLUMNS SALVA
ORNAMENTAL TRFRONT PIECE, A
WOOD FRONT PREPLICATE HIST
You specify the
locations for the water
and electric meters but
not the gas meter.
Gas meters can not be
located below an
operable window.
Specify gas meter
locations at an
approved location per
Black Hills Energy
standards. `
Page: A-302 SECTIONS
File Name: Complete Permit Set Clarification 1.834
Hallam.2018.03.pdf
Author: bonniem
Subject: PlanCheck
Color:
Additional detailing is required to
clearly depict which walls and
ceilings will be serving as the fire
partitions and show that they will
be continuous throughout. In
section view indicate which walls
and ceiling are serving as the
fire partitions. Then provide
details at the interior floor ceiling
intersections.
Page: A-501 ASEMBLIES
File Name: Complete Permit Set Clarification 1.834
Hallam.2018.03.pdf
Author: bonniem
Subject: PlanCheck
Color:
For clarity include the entire floor
ceiling assembly ie:
F-4+C-1+FF1 all in the same
detail. Because the components
act together to provide both the
fire-resistance and
sound-resistance they should be
shown together as one detail.
Page: A-502 EXTERIOR ONSTRUCTION DETAIL
File Name: Complete Permit Set Clarification 1.834
Hallam.2018.03.pdf
Author: bonniem
Subject: PlanCheck
Color:
It appears that spray foam will
serve as the required air barrier
(2015 IECC Table R402.4.1.1).
Provide additional notes in the
exterior details to show where
additional air sealing will be
provided to achieve the
continuous air barrier. Refer to
the City of Aspen's sample air
barrier details.
Page: A-502 EXTERIOR ONSTRUCTION DETAIL
File Name: Complete Permit Set Clarification 1.834
Hallam.2018.03.pdf
Author: bonniem
Subject: PlanCheck
Color:
This detail does not match the
detail shown on S402 #6.
Page: A-503 EXTERIOR ONSTRUCTION DETAIL
File Name: Complete Permit Set Clarification 1.834
Hallam.2018.03.pdf
Author: bonniem
Subject: Group
Color:
H G F A
1A-502
1A-502
3A-502
3A-502
8A-502
7A-502
6A-502
11A-502
11A-502
11A-502
F-1 F-1 F-1
R-3
FF-1FF-1
FF-1 F-2
FF-1 F-2
FF-1 F-2
FF-1 F-2 FF-1 F-2
FF-1 F-2 FF-1 F-2
FF-1
W-4
W-6W-4 W-6
W-1 W-1
W-4
W-6 W-6
W-4W-6
W-6
W-6 W-6
W-6 W-6 W-4
R-3
R-2
R-2
W-7
W-6
W-8W-6
W-8
101/8"
8'-0"
1'-1"
7'-93/4"
1'-21/4"
7'-113/4"
1'-21/4"
9'-0"
111/8"
9'-33/4"
1'-21/4"
7'-93/4"
1'-21/4"
9'-0"
11/2"
7'-93/4"
1'-21/4"
7'-93/4"
1'-21/4"
10'-6"
CA-303DA-304
T.O SLAB @ LOWER LEVEL@ BUILDING C: 89'-0"
T.O PLY @ MAIN LEVEL@ BUILDING C: 99'-6"
T.O PLY @ SECOND LEVEL@ BUILDING C: 108'-6"
T.O PLY @ THIRD LEVEL@ BUILDING C: 116'-2"
T.O SLAB @ LOWER LEVEL@ BUILDING C: 89'-0"
T.O PLY @ MAIN LEVEL@ BUILDING C: 98'-0"
T.O PLY @ SECOND LEVEL@ BUILDING C: 107'-0"
BEDROOM 3UNIT 106
STORAGEUNIT 106
LIVINGUNIT 106
LIVINGUNIT 105
LOWERLEVELUNIT 106
BATH 1UNIT 104 BEDROOM 3UNIT 103
STORAGEUNIT 102 ENTRYUNIT 106
CLOSETUNIT 103 BEDROOM 1UNIT 103
POWDERUNIT 104
KITCHENUNIT 104 BEDROOM 3UNIT 104 BEDROOM 2UNIT 104
BEDROOM 1UNIT 105
FOYER ENTRYUNIT 104
BATH 1UNIT 106
SETBACK LINE
PROPERTY LINE
SETBACK LINE
PROPERTY LINE
STAIRUNIT 103
LAUNDRYUNIT 106
CLOSETUNIT 105
0 2'4'8'SCALE: 1/4" = 1'-0"B SECTION
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
MECHANICAL EQUIPMNON-STREET FACING
PARKING WITHIN ESTPER 26.575.020.E.5.r
PER 26.575.020.E.5.k
FENCE <42" PER 26.5
VERTICAL CIRCULATIMOST FLOOR PER 26
FRONT PORCH PER 2
MECHANICAL PROJECROOF PER 26.575.020
MU ZONE DISTRICT H
CHIMNEY PROJECTIOCONNECTION PER 26
DORMERS EXEMPT P
28' OFFSET OF MOST
1/3 POINT FROM EAVE
EXISTING GRADE
PROPOSED GRADE
WINDOW TRIM TBD
SILVER CREEK - MACRED CEDAR SHAKES
TRUDEFINITION DUR
DECK MATERIAL TBD
EXTERIOR RAILING M
EXISTING HISTORIC SREMAINHARDIEPLANK SMOOEXISTING HISTORIC SHARDIEPLANK SMOOSIDING. 5" OF EXPOSEXISTING HISTORIC WREMAINWINDOW TRIM TO MAHISTORIC TRIM
CHIMNEY TO BE RESUSING SALVAGED HIS
WINDOW WELL PER ICASEMENT GALVANIZ
NEW LIFE + SAFETY S
LINE OF EXTERIOR W
HEAT PUMP
WATER + ELECTRIC M
PATIO SNOWMELT PE
DRYER EXHAUST LOC
HANDRAIL PER IRC 3
PANEL TO BE NON-LONO MORE THAN 15 LB
GARAGE SLAB TO SL
ROOF OVERHANG
SEWAGE EJECTOR A
ELECTRICAL PANEL L
EGRESS SILL 44" AFF
RADON VENT PIPE
SNOW STOPS FOR ASNARROW, PAINTED ADOWNSPOUT: ROUND
FLUE VENT; TYP. LOCAPPROVED BY HPC S
GUTTER: HALF-ROUN
WASHER/DRYER HOO
EAST SIDE YARD SETPER RES NO. 24 OF 2DISTANCE BETWEENPER RES NO. 24 OF 2NORTHWEST BUILDINSTREET PER RES NO
NEW CONSTRUCTIONOF 37 SQ FT, WITH A M
NORTHWEST BUILDINEIGHTH STREET PER
MAILBOXES
FDC
EXTERIOR LIGHTING:
EXTERIOR LIGHTING:
SNOW STOPS FOR WPAINTED ALUMINUM,
LINE OF NO EXCAVAT
HISTORIC WOOD PORCOLUMNS SALVAGEDORNAMENTAL TRIM TFRONT PIECE, AND HWOOD FRONT PORCHREPLICATE HISTORIC
Additional detailing is
required to clearlydepict which walls and
ceilings will be servingas the fire partitions
and show that they willbe continuous
throughout. In sectionview indicate which
walls and ceiling areserving as the firepartitions. Thenprovide details at theinterior floor ceilingintersections.
STEVENWILSON402127
STATE OFCOLORADO
LICENSEDARCHITECT
COPYRIGHT
04/01/2018
PROJECT NO:
DRAWN BY:FORUM PHI LLC
DATE OF PUBLICATION
A-501
ASSEMBLIES
04/01/2018
AP + AG
PARCEL ID # 273-512-304-002
LEGAL DESCRIPTION: City and Townsite of Aspen block: 10, Lot: K & L
ZONE DISTRICT MU
1502.00
Aspen CO 81611834 HALLAM
Aspen:715 West Main Street, #204Aspen, Colorado 81611
Basalt:104 Midland Ave, #202Basalt, CO 81612
forumphi.comp: 970.279.4157f: 866.770.5585
City and townsite of Aspenblock: 10, Lot: K & L
8"1/2"
2"
31/2"
31/2"
AIR SPACECONCRETE REF STRUCT
RIGID INSULATION; R-5 PER 1"DRAINAGE MATFLUID APPLIED WATERPROOFING
SPRAY APPLIED CLOSED CELL FOAM INSULATION; R-6.25 PER 1"5/8" GYP
W-1 EXTERIOR FOUNDATION WALL W/ 2X FURRING WALLR-33W-1
EXT INT
W - EXT - CONCRETE + 2X FURRING WALL
STUD; VIF
HISTORIC HORIZONTAL WOOD SIDING TO REMAIN
SPRAY APPLIED CLOSED CELL FOAM INSULATION; R-6.25 PER 1"GYP
WATER RESISTIVE BARRIERSHEATHING REF STRUCT
W-2
EXT INT
EXTERIOR WOOD HISTORIC WALL TO REMAIN; VIFR-20INSULATION TO BE ADDED
PER PLAN
4"
HORIZONTAL COMPOSITE SIDING
SPRAY APPLIED CLOSED CELL FOAM INSULATION; R-6.25 PER 1"GYP
WATER RESISTIVE BARRIERSHEATHING REF STRUCT
W-4W-4
EXT INT
EXTERIOR WOOD WALL W/ HORIZONTAL SIDINGR-25
PER PLAN
WOOD STUD5/8" GYP
5/8" GYP
W-6 INTERIOR WOOD WALL W/ GYP
W - INT - WD 2X - GYP
2"
FINISH FLOOR PER PLANSCONCRETE REF STRUCT
SCREENED ROCK
RIGID INSULATION; R-5 PER 1"VAPOR BARRIER
F-1 EXTERIOR FOUNDATION FLOORR-10
FLR + FF - SLAB ON GRADE + FINISH
T.O.SLAB
CEILING REF C-2
FINISH FLOOR PER PLANS
SHEATHING REF STRUCT
JOIST REF STRUCT
SOUND INSULATION
F-2 UNIT SEPARATION FLOOR
FIRE RATING: 1/2 Hour per IBC Table 722.2.1.4(2)STC: 51 per California Office of Noise Control pg. 143 of 175
T.O.SUBFLOOR
FLR + FF - WD JOIST + FINISH
51/2"VIF
CLASS B CEDAR SHINGLESCLASS A RATED UNDERLAYMENTFULLY ADHERED ROOF MEMBRANESHEATHING REF STRUCTSPRAY APPLIED CLOSED CELL FOAMINSULATION; R-6.25 PER 1"RAISED TIE TRUSS; VIFCEILING PER PLAN
R-1 EXISTING HISTORIC ROOF STRUCTURE TO REMAINR-34DEMO ASPHALT SHINGLES + REPLACE WITH CEDAR SHINGLES. ADD INSULATIONCLASS A RATED PER ESR-2053
T.O.SHEATHING
SLOPE PERPLAN
51/2"
CLASS A RATED ASPHALT SHINGLEFULLY ADHERED ROOF MEMBRANESHEATHING REF STRUCTSPRAY APPLIED CLOSED CELL FOAMINSULATION; R-6.25 PER 1"RAISED TIE TRUSS; REF STRUCT
CEILING PER PLAN
R-2 ARCHITECTURAL SHINGLE ROOFR-34
CLASS A RATED PER UL ER2453-02
T.O.SHEATHING
SLOPE PERPLAN
PER PLAN
HORIZONTAL COMPOSITE SIDING TO MATCH HISTORIC
SPRAY APPLIED CLOSED CELL FOAM INSULATION; R-6.25 PER 1"GYP
WATER RESISTIVE BARRIERSHEATHING REF STRUCT
W-3W-3
EXT INT
EXTERIOR WOOD WALL W/ HORIZONTAL SIDING TO MATCH HISTORICR-20
PER PLAN
4"
HORIZONTAL COMPOSITE SIDING
SPRAY APPLIED CLOSED CELL FOAM INSULATION; R-6.25 PER 1"GYP - TYPE X
WATER RESISTIVE BARRIERSHEATHING REF STRUCT
W-5
EXT INT
EXTERIOR WOOD WALL W/ HORIZONTAL SIDINGR-25FIRE RATING: 1 HOUR PER UL 263; DESIGN NO. U354
PER PLAN
STAGGERED WOOD STUD + SOUND INSULATION
5/8" TYPE X GYP
5/8" ACOUSTICAL TYPE-X GYP
PLYWOOD
W-7
W - INT - SHEER WALLS
INTERIOR FIRE RATED UNIT SEPARATION WALL W/ SHEATHING
FIRE RATING: 1/2 HOUR PER IBC TABLE 722.2.1.4(2)STC: 51 per California Office of Noise Control pg. 63 of 175
CEILING REF C-3
FINISH FLOOR PER PLANS
SHEATHING REF STRUCT
JOIST REF STRUCT
SOUND INSULATION
F-3 SEPARATION FLOOR BETWEEN UNIT AND TRASH ENCLOSURE
FIRE RATING: 1 Hour per IBC Table 722.2.1.4(2)STC: 51 per California Office of Noise Control pg. 143 of 175
T.O.SUBFLOOR
FLR + FF - WD JOIST + FINISH
CEILING REF C-1
FINISH FLOOR PER PLANS
SHEATHING REF STRUCT
JOIST REF STRUCT
F-4 TYP FLOOR WITHIN UNIT
T.O.SUBFLOOR
CEILING REF C-1
WATERPROOF MEMBRANEFINISH FLOOR PER PLANS
SHEATHING REF STRUCT
JOIST REF STRUCTSPRAY APPLIED CLOSED CELL FOAMINSULATION; R-6.25 PER 1"
R-3
T.O.SHEATHING
EXTERIOR FLOOR OVER INTERIORR-49
SOUND ISOLATION MAT
WOOD VINYL PRODUCT
FF-1
WOOD VINYL COMPOSITE
FF - WOOD
T.O. FF
T.O.STRUCT
WATERPROOFING MEMBRANE
SOFFIT PER PLAN
FINISH FLOOR PER PLANS
SHEATHING REF STRUCT
JOIST REF STRUCTSPRAY APPLIED CLOSED CELL FOAMINSULATION; R-6.25 PER 1"SHEATHING REF STRUCT
F-5
T.O.SUBFLOOR
INTERIOR FLOOR OVER EXTERIORR-56
SOUND CLIP5/8" GYP
C-1
B.O.STRUCT
PER PLAN
STAGGERED WOOD STUD + SOUND INSULATION5/8" TYPE X GYP
5/8" ACOUSTICAL TYPE-X GYP
W-8
W - INT - DEMISING
INTERIOR FIRE RATED UNIT SEPARATION WALL
FIRE RATING: 1/2 HOUR PER IBC TABLE 722.2.1.4(2)STC: 51 per California Office of Noise Control pg. 63 of 175
CEILING REF C-2
WATERPROOF MEMBRANECONCRETE TOPPING REF STRUCT
SHEATHING REF STRUCT
JOIST REF STRUCTSPRAY APPLIED CLOSED CELL FOAMINSULATION; R-6.25 PER 1"
R-4
T.O.SHEATHING
TRASH ROOM FLOOR OVER INTERIORR-49FIRE RATING: 1 Hour per IBC Table 722.2.1.2(1) + 722.2.1.2(2) + 722.2.1.4(2)STC: 58 per California Office of Noise Control pg 160 of 175
SOUND CLIP5/8" TYPE X GYP
C-2
B.O.STRUCTSOUND CLIP5/8" TYPE X GYP
5/8" TYPE X GYP
C-3
B.O.STRUCT
WATERPROOFING MEMBRANE
SOFFIT PER PLAN
FINISH FLOOR PER PLANS
SHEATHING REF STRUCT
JOIST REF STRUCTSPRAY APPLIED CLOSED CELL FOAMINSULATION; R-6.25 PER 1"SHEATHING REF STRUCT
F-5
T.O.SUBFLOOR
INTERIOR FLOOR OVER EXTERIORR-56
W-2
For clarity include theentire floor ceilingassembly ie:F-4+C-1+FF1 all in thesame detail. Becausethe components acttogether to provideboth thefire-resistance andsound-resistance theyshould be showntogether as one detail.
SNOWSTOP PER MFR
It appears that spray foam will
serve as the required air barrier
(2015 IECC Table R402.4.1.1).
Provide additional notes in the
exterior details to show where
additional air sealing will be
provided to achieve the
continuous air barrier. Refer to
the City of Aspen's sample air
barrier details.
W-2,3,4
F-2
W-8
FF-1
W-8
SILL PLATE
TYPE-X GYP FIRE BARRIER
BLOCKING
SOUND CLIP
FIRE CAULKING
SAFF
METAL DRIP EDGE FLASHING
WATERPROOF MEMBRANE
MEMBER REF STRUCT
MEMBER REF STRUCT
BLOCKING AS REQ'D
FASCIA REF PLAN
SOFFIT REF PLAN
BLOCKING
BLOCKING
ROOF OVERHANG BEYOND
SCALE: 1 1/2"= 1'-0"12 FIRE-RATED INT STACKED WALLS
SCALE: 1 1/2"= 11 TYP RA
This detail does not
match the detail
shown on S402 #6.
COPYRIGHT
PROJECT NO:
DRAWN BY:
FORUM PHI LLC
DATE OF PUBLICATION
A-503
EXTERIOR
CONSTRUCTION DETAILS
04/01/2018
AP + AG
PARCEL ID # 273-512-304-002
LEGAL DESCRIPTION: City and Townsite of Aspen block: 10, Lot: K & L
ZONE DISTRICT MU
1502.00
R-3
W-4
F-2
1/2"CONTINUOUS WATERPROOFING
CONTINUOUS METAL FLASHING- FOLDED AND SOLDERED @JOINTS AND CORNERSMEMBER REF STRUCT
BLOCKING
DOOR PER SCHEDULE
THRESHOLD TO BE FLUSH WITHFINISH FLOORS
CONCRETE SILLEXT
EXT
INT
INT
SLOPE PER PLAN
F-2
W-8
FF-1
W-6
FIRE CAULKING
TYPE-X GYP FIRE BARRIER
SOUND CLIP
SILL PLATE
SCALE: 1 1/2"= 1'-0"14 TYP DOOR SILL
SCALE: 1 1/2"= 1'-0"13 FIRE-RATED INT OFFSET WALLS
Page: S-402 DETAILS
File Name: Complete Permit Set Clarification 1.834
Hallam.2018.03.pdf
Author: bonniem
Subject: PlanCheck
Color:
This detail does not match the
wall assembly, and architectural
conditions presented on
A501-502. The Simpson Hanger
is for use with a hour assembly,
so if using this method, it will
need to be a 1-hour wall rather
than 30 minutes.
Page: P.1.04 THIRD LEVEL PLUMBING PLAN
File Name: plumbing drawings.pdf
Author: bonniem
Subject: PlanCheck
Color:
P.1.04 repeats the main level
plumbing plan where the 3rd
level plumbing plan should be
shown.
plumbing drawings.pdf (2)
Page: P.6.01 PLUMBING RISER DIAGRAMS
File Name: plumbing drawings.pdf
Author: bonniem
Subject: PlanCheck
Color:
It appears that all levels are
draining to the sump in the
basement of unit 106. All levels
which can drain to gravity are
required to do so per 2015 IPC
712.1
2"2"2"
EQ
EQ
C
TYPICAL BOT PLATE NAILING,RE: TYPICAL DETAILS
TYPICAL TOP PLATE NAILING,RE: TYPICAL DETAILS
SIMPSON FIRE RATED DRYWALL HANGER,RE: HANGER SCHEDULE
SHEATHING SHOULD NOTPENETRATE DRYWALL
FIRE RATED STUD WALL,RE: ARCH
BOT PLATE TO JOIST ORBLOCKING, RE: TYPICAL DETAILS
T/SHEATHING
1" = 1'-0"6 EXISTING STRUCTURE FRAMING DETAIL
This detail does not
match the wall
assembly, and
architectural
conditions presented
on A501-502. The
Simpson Hanger is for
use with a hour
assembly, so if using
this method, it will
need to be a 1-hour
wall rather than 30
minutes.
UNIT 103
E
E
C
C
55
22
88
A
A
F
F
G
G
H
H
77
44
33
11
BEDROOM 1UNIT 103
ENTRYUNIT 102
F F
D
D
B
B
DW
DWRG
66
RG
POWDERUNIT 107
TRASH ENCLOSURE
STORAGEUNIT 105
STORAGEUNIT 104
STORAGEUNIT 103
STORAGEUNIT 106
STORAGEUNIT 102
STORAGEUNIT 101STORAGEUNIT 107
LIVINGUNIT 101
BATHROOM 1UNIT 103
LIVINGUNIT 107
ENTRYUNIT 107
KITCHENUNIT 102
LIVINGUNIT 102
KITCHENUNIT 101
ENTRYUNIT 101
ENTRYUNIT 103
LIVING
UNIT 106
ENTRYUNIT 105
LAUNDRYUNIT 103
DW
FOYER
KITCHENUNIT 103
ENTRYUNIT 104
RG
ENTRY
3 SH-1
1
LV-1
2
WC-1
KS-1
4
5
CWB
KS-14
KS-1 4
1.112" W, 112" V, 12" CW & 12" HW TO LV-1.
2.3" W, 2" V & 12" CW TO WC-1.
3.2" W, 1-1/2" V & 1/2" CW & HW TO SH-1.
4.2" W, 1-1/2" V & 1/2" CW & HW TO KS-1.EXTEND HW & IW LINE TO DISHWASHER.
5.3" W, 2" V, & 1/2" CW & HW TO CWB.
6.3/4" CW TO FPHB-1.
7.4" W OUT OF THE BUILDING. PROVIDE COTG.VERIFY LOCATION, SIZE & INVERTS WITHCIVIL DRAWINGS.
8.2" CW SERVICE - VERIFY LOCATION ANDFINAL SIZES WITH FIRE SUPPRESSIONCONTRACTOR & CIVIL ENGINEER. INSTALLMETER ASSEMBLY PER THE TOWN OF ASPENWATER DISTRICT STANDARDS.
Plumbing Notes:
SYMBOL USED FOR NOTE DESIGNATION
General Plumbing Notes:
1.PC TO PROVIDE CLEANOUTS AND ACCESS AT EACHCHANGE OF DIRECTION FOR W PIPING.
2.SOME PIPING, EQUIPMENT AND DUCTWORKSHOWN OFFSET FOR CLARITY. OFFSET PIPING ASREQUIRED TO ROUTE AROUND STRUCTURALMEMBERS - ANY STRUCTURAL MEMBERPENETRATION SHALL BE APPROVED BYSTRUCTURAL ENGINEER. COORDINATE ANYCONFLICTS WITH ARCHITECT, OWNER AND OTHERTRADES.
3.PROVIDE FREEZE PROTECTION TO ALL PIPINGSUBJECT TO EXPOSURE TO THE OUTDOORS.
LV-1 WC-1 2
SHEET NUMBER:
DRAWN BY:
CHECKED BY:
PROJECT MANAGER:
SHEET TITLE:
SEAL:
NO.ISSUE DATE
PROJECT NUMBER:
SCALE:
of
PO BOX 810825A CHAMBERS AVENUEEAGLE, CO 81631800.543.9365www.randhmechanical.com
170915-01
BW
ajs
BW
AS NOTED
Permit Documents
To
w
n
s
i
t
e
o
f
A
s
p
e
n
b
l
o
c
k
:
1
0
,
L
o
t
K
&
L
11 BID DOC 10/19/2017
NO.REVISIONS DATE
CITY STAMPS:
12 PERMIT DRAWINGS 11/20/2017
PEAK DESIGN GROUP LLC1338 GRAND AVE NO315GLENWOOD SPRINGS CO 81601970-688-0102www.peakdesign.org
3 PERMIT DRAWINGS MODS 11/20/2017
5 7
P.1.04
THIRD LEVELPLUMBING PLAN
P.1.04 repeats themain level plumbingplan where the 3rdlevel plumbing planshould be shown.
WC-1
LV-1
SH-1
SP-1
SH-1
WC-1
LV-1
FCO
KS-1
WC-1
LL
ML
LL
ML
SH-1
LV-1
LL
ML
SH-1
WC-1
SH-1
WC-1
LV-1
FCO
LV-1SH-1
LL
WC-1
ML
2nd
SH-1
LL
ML
ML
LL
ML
LL
ML
LL
CWB
KS-1
ML
CWB
LV-1
WC-1
FCO
LV-1
WC-1 FCO
LV-1
SH-1
KS-1
ML
ML
LL
LV-1 WC-1
SH-1
WC-1
LV-1
KS-1
LL
ML
LL
COTG
WC-1
FCO
LV-1SH-1
ML
WC-1
LV-1
ML
LL
LL
LL
LL
LL
LV-1
WC-1
SH-1
KS-1
VTR
2nd
2nd
2nd
2nd
LLFCO
LV-1
WC-1
SH-1
VTR
ML
2nd
2nd
LL
ML
CWB
VTR
KS-1
LL
ML
LL
ML
CWB
2nd
2nd
2nd
2nd
2nd
LL
LL
LL
LL
2nd
2nd
2nd
2nd
LL
CWB
2nd
2nd
2nd
2nd
2nd
Waste & Vent Piping Isometric
NO SCALE
WH-1
SH-1
WC-1
LV-1
12"
12"
34"
1"
3rd
3rd
3rd
CWB
3rd
12"
KS-1
3rd
12"
Unit 105 Water Piping Isometric
WH-1
Unit 104 Water Piping Isometric
SH-1
WC-1 LV-1
CWB
KS-1
12"
12"
12"
12"1"1"WH-1
1"
SH-1
WC-1
SH-1
LV-1
ML
SH-1
ML
WC-1
ML
1"
12"12"
34"
34"
Unit 103 Water Piping Isometric
WH-1
1"
CWB
12"SH-1
WC-1
SH-1
12"
34"
2nd
KS-1
34"
DRAWN BY:
PROJECT MANAGER:
SHEET TITLE:
SEAL:
NO.ISSUE DATE
PROJECT NUMBER:
PO BOX 810825A CHAMBERS AVENUEEAGLE, CO 81631800.543.9365www.randhmechanical.com
170915-01
BW
ajs
To
w
n
s
i
t
e
o
f
A
s
p
e
n
b
l
o
c
k
:
1
0
,
L
o
t
K
&
L
11 BID DOC 10/19/2017
NO.REVISIONS DATE
CITY STAMPS:
12 PERMIT DRAWINGS 11/20/2017
PEAK DESIGN GROUP LLC1338 GRAND AVE NO315GLENWOOD SPRINGS CO 81601970-688-0102www.peakdesign.org
3 PERMIT DRAWINGS MODS 11/20/2017
PLUMBINGRISER DIAGRAMS
It appears that alllevels are draining to
the sump in the
basement of unit 106.All levels which candrain to gravity arerequired to do so per2015 IPC 712.1