ASBESTOS ABATEMENT CLEARANCE REPORT
DATE
06/06/2018
CLIENT
834 West Hallam Associates, LLC.
c/o Matt Brown
625 E Main St, Suite 102A
Aspen CO 81611
PROJECT PROPERTY ADDRESS
834 West Hallam Street, Aspen, Colorado 81611
For orientation purposes, the front door faces south.
CLIENT BACKGROUND
The Client, 834 West Hallam Associates, LLC., hired HealthSafe Inspections, Inc. (hereinafter,
HealthSafe) to perform a post-abatement clearance for the recent abatement of asbestos-
containing sheet vinyl flooring layers. The ACM sheet vinyl was abated from the second-floor
north restroom and the main floor center restrooms. This required an asbestos abatement permit
from the CDPHE (Permit Notice #18P12699A dated 05/04/2018) and a certified asbestos
abatement contractor to perform the abatement. Prestige Environmental Services, Inc. provided
the asbestos abatement and Matt Brown called for the abatement clearance inspection and PCM
air sampling once their abatement of the sheet vinyl flooring layers was completed.
VISUAL INSPECTION & LABORATORY FINDINGS
An asbestos post-abatement visual clearance inspection and PCM air sampling was conducted by
Jim Baker of HealthSafe on Friday May 31, 2018. The visual clearance verified that all friable
sheet vinyl flooring had been completely removed from the plywood subfl ooring in the main
floor central restrooms and the second-floor north restroom. This visual inspection determined
that all lose debris was removed and the remaining subfloors were virtually dust-free. No further
abatement or cleaning procedures were required.
Following the visual post-abatement clearance, five rotary vane sampling pumps were warmed
up for 5 minutes and site calibrated using a rotameter for each location where the abatement took
place. A box fan was deployed at a 45°angle off the east wall of the bathroom on the main floor
inside the containment and the containment area blown with a leaf blower as required by the
regulations for clearances. PCM samples were set in locations representing the distribution of air
throughout the containment-abatement space. A trip blank and two field blanks, opened for 30
seconds, were included in the batch of five PCM air samples per location, but were not required
to be analyzed by the laboratory. Five PCM air samples were collected inside each containment.
The following photos reveal the conditions at the time of inspection and air sampling:
HEALTHSAFE PCM LABORATORY DATA
Regarding the five PCM air samples in the second-floor bathroom containment, total volumes
between 683 and 770 liters of air all had less than 0.005 fibers detected (<0.005 f/cc) per cubic
centimeter of air. These five PCM air samples for the second-floor bathroom containment are
below the 0.01 f/cc level for clearance. This second-floor restroom passes the abatement
requirements.
Regarding the five PCM air samples in the first-floor bathroom(s) central restroom area
containment, total volumes between 665 and 700 liters of air all had less than 0.005 fibers
detected (<0.005 f/cc) per cubic centimeter of air. These five PCM air samples for the first-floor
restroom containment are below the 0.01 f/cc level for clearance. The first-floor restroom area
passes the abatement requirements. See attached Hayes laboratory report #18016915.
CONCLUSIONS
Based on the visual post-abatement verification clearance inspections and based on the post-
abatement PCM air sampling data for the property at 834 W Hallam St in Aspen, the containment
area of the dining and bathrooms spaces has fully passed asbestos abatement clearance criteria.
The containments and equipment can be disassembled and removed. Demolition and/or
remodeling can commence at once.
Sincerely Submitted,
Jim Baker
HMC #18016915
contact@hayesmicrobial.com
http://hayesmicrobial.com/
Analysis Report prepared for
HealthSafe Inspections
390 Apple Drive
Basalt, CO. 81621 USA
Phone: 970-920-2100
Job Name: 834 West Hallam & Assoc.
834 W. Hallam St.
Aspen, CO 81611
Date Sampled: 05-31-2018
Date Analyzed: 06-01-2018
Report Date: 06-01-2018
EPA Laboratory ID# VA01419
NVLAP Lab Code: 500096-0 Asbestos License: 300435 License: #PH-0198
Page 1 of 5
HMC #18016915
HealthSafe Inspections
390 Apple Drive
Basalt, CO 81621 USA
June 1, 2018
Client Job Number:
Client Job Name:834 West Hallam & Assoc.
834 W. Hallam St.
Aspen, CO 81611
Dear HealthSafe Inspections,
We would like to thank you for trusting Hayes Microbial for your analytical needs. On June 1, 2018 we received 10 samples by FedEx for the job
referenced above. 10 samples were received in good condition.
The results in this analysis pertain only to this job, collected on the stated date and should not be used in the interpretation of any other job. This report
may not be duplicated, except in full, without the written consent of Hayes Microbial Consulting, LLC.
This laboratory bears no responsibility for sample collection activities, analytical method limitations, or your use of the test results. Interpretation and
use of test results are your responsibility. Any reference to health effects or interpretation of mold levels is strictly the opinion of Hayes Microbial
Consulting. In no event, shall Hayes Microbial Consulting or any of its employees be liable for lost profits or any special, incidental or consequential
damages arising out of your use of the test results.
Steve Hayes, BSMT(ASCP)
Laboratory Director
Hayes Microbial Consulting, LLC
Page 2 of 5
HMC #18016915
Asbestos PCM AnalysisHealthSafe Inspections
390 Apple Drive
Basalt, CO 81621 USA
Phone: 970-920-2100
Job Number:
Collected by:
Email:
Jim Baker
healthsafeinspections@gmail.com
Job Name:834 West Hallam & Assoc.
834 W. Hallam St.
Aspen, CO 81611
Date Collected:
Date Received:
Date Reported:
05/31/2018
06/01/2018
06/01/2018
page1
HMC ID Number: 18016915 - 4 Sample Media: Air - Asbestos
Sample ID Number: 0022 Sample Name: F2-S1
Sample Volume Fiber Count Fibers/mm2 Fibers/CC Notes
770.00 1 / 100 <0.005
HMC ID Number: 18016915 - 5 Sample Media: Air - Asbestos
Sample ID Number: 0171 Sample Name: F2-S2
Sample Volume Fiber Count Fibers/mm2 Fibers/CC Notes
732.00 1 / 100 <0.005
HMC ID Number: 18016915 - 6 Sample Media: Air - Asbestos
Sample ID Number: 9921 Sample Name: F2-S3
Sample Volume Fiber Count Fibers/mm2 Fibers/CC Notes
751.00 1 / 100 <0.005
HMC ID Number: 18016915 - 7 Sample Media: Air - Asbestos
Sample ID Number: 0131 Sample Name: F2-S4
Sample Volume Fiber Count Fibers/mm2 Fibers/CC Notes
751.00 1 / 100 <0.005
HMC ID Number: 18016915 - 8 Sample Media: Air - Asbestos
Sample ID Number: 9890 Sample Name: F2-S5
Sample Volume Fiber Count Fibers/mm2 Fibers/CC Notes
683.00 1 / 100 <0.005
Signature: Date:06/01/2018 Reviewed by: Date:06/01/2018
Page 3 of 5
HMC #18016915
Asbestos PCM AnalysisHealthSafe Inspections
390 Apple Drive
Basalt, CO 81621 USA
Phone: 970-920-2100
Job Number:
Collected by:
Email:
Jim Baker
healthsafeinspections@gmail.com
Job Name:834 West Hallam & Assoc.
834 W. Hallam St.
Aspen, CO 81611
Date Collected:
Date Received:
Date Reported:
05/31/2018
06/01/2018
06/01/2018
HMC ID Number: 18016915 - 12 Sample Media: Air - Asbestos
Sample ID Number: 0162 Sample Name: F1-S1
Sample Volume Fiber Count Fibers/mm2 Fibers/CC Notes
700.00 1 / 100 <0.005
HMC ID Number: 18016915 - 13 Sample Media: Air - Asbestos
Sample ID Number: 9908 Sample Name: F1-S2
Sample Volume Fiber Count Fibers/mm2 Fibers/CC Notes
700.00 1 / 100 <0.005
HMC ID Number: 18016915 - 14 Sample Media: Air - Asbestos
Sample ID Number: 99932 Sample Name: F1-S3
Sample Volume Fiber Count Fibers/mm2 Fibers/CC Notes
665.00 1 / 100 <0.005
HMC ID Number: 18016915 - 15 Sample Media: Air - Asbestos
Sample ID Number: 9903 Sample Name: F1-S4
Sample Volume Fiber Count Fibers/mm2 Fibers/CC Notes
683.00 1 / 100 <0.005
HMC ID Number: 18016915 - 16 Sample Media: Air - Asbestos
Sample ID Number: 9982 Sample Name: F1-S5
Sample Volume Fiber Count Fibers/mm2 Fibers/CC Notes
683.00 1 / 100 <0.005
Signature: Date:06/01/2018 Reviewed by: Date:06/01/2018
Page 4 of 5
HMC #18016915
Asbestos - Additional InformationHealthSafe Inspections
390 Apple Drive
Basalt, CO 81621 USA
Phone: 970-920-2100
All samples were received in acceptable condition unless otherwise noted on the report. The Report must not be used by the client to claim product certification, approval, or
endorsement by: AIHA, NIST, NVLAP NY ELAP, or any agency. The results relate only to the items tested. The results include an inherent uncertainty of measurement associated with
estimating percentages by polarized light microscopy. Measurement uncertainty data can be provided when requested. None detected: Below the detected reporting limit of 1% unless
point counting is performed, then the detected, reporting limit is .25%. Per NY ELAP198.6 (NOB) TEM is the only reliable method to declare an NOB material as Non-Asbestos
Containing. Hayes Microbial Consulting reserves the right to dispose of all samples after a period of 60 days in compliance with state and federal guidelines.
Signature: Date:06/01/2018 Reviewed by: Date:06/01/2018