HomeMy WebLinkAboutFile Documents.802 W Main St.0170.2018 (28).ARBK0170-2018-ARBK_BuildingComments_1revised7-13-18 Page: 1.0 PROJECT OVERVIEW File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Add the following codes: 2017 NEC, 2015 IFC, ICC/A117.1-2009 Architectural Plans.802 West Main.2018.06.pdf (62) Page: 2.3 SITE PLAN | PROPOSE1:10 File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Provide a landing at the bottom of the exterior stair that is at least as deep as the width of the stair (2015 IBC 1011.6). 12" handrail extension may not encroach more than 4" into the required width of travel (2015 IBC 1003.3.3). Page: 2.3 SITE PLAN | PROPOSE1:10 File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Revise this area of the site plan to correspond with the civil grading plan and to clearly show slopes and steps. Provide accessible route to all ground floor units. 2015 IBC 1107.4 Page: 2.3 SITE PLAN | PROPOSE1:10 File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Trash enclosure doors may not swing into right of way. Page: 2.3 SITE PLAN | PROPOSE1:10 File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Provide an accessible route into the trash enclosure without leaving property. (2015 IBC 1104.2, 1104.3) PARCEL ID# .............................................................. LEGAL DESCRIPTION:……LOTS Q,R, & S, BLOC CODES:………………………..2015 IBC, 2015 IEC Add the following codes: 2017 NEC, 2015 IFC, ICC/A117.1-2009 90.00' 10 0 .00 ' 7926 7926 7 9 2 5 7 9 2 6 7 9 2 7 1234567891011121314151617 UP20RISER(6 11/16")19TREADS(11") 10 ' - 0 " PROPERTY LINE SETBACK LINE SETBACK LINE 7925 7926 Provide a landing at the bottom of the exterior stair that is at least as deep as the width of the stair (2015 IBC 1011.6). 12" handrail extension may not encroach more than 4" into the required width of travel (2015 IBC 1003.3.3). 10 0 .00 ' 7927 7928 7 9 2 7 1234567891011121314151617181920 DN 20RISER(6 11/16") 19TREADS(11") SETBACK LIN SETBACK LINE 7926 7927 7928 79 2 7 Revise this area of the site plan to correspond with the civil grading plan and to clearly show slopes and steps. Provide accessible route to all ground floor units. 2015 IBC 1107.4 S75°09'11"E 7926 7926 Trash enclosure doors may not swing into right of way. S75°09'11"E 10 0 .00 ' 2 7927 7926 7926 7927 Provide an accessible route into the trash enclosure without leaving property. (2015 IBC 1104.2, 1104.3) See revised sheet 1.0 See revised sheet 2.3 and Landscape and Civil drawings. We have moved the trash enclosure as well as revised the doors to sliders. See revised sheet 2.3 and Landscape and Civil drawings outlining the accessible route to the trash. See revised sheet 2.3 and Landscape and Civil drawings. See revised sheet 2.3 and Landscape and Civil drawings. 08/14/18 Page: 3.1 BASEMENT FLOOR PL File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: The floor of unit 102 is over this exterior space in the basement. Provide a floor assembly and detail for this location indicating air sealing and insulation value (minimum R-38 2015 IECC R402.1.2). Page: 3.2 MAIN LEVELFLOOR P File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Add wall type callouts referencing the wall assemblies to your floor plans or sections to aid in determining which fire resistant assemblies are used where. Page: 3.2 MAIN LEVELFLOOR P File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Clean up the graphics at the entrances. It looks like the slats above are showing. Page: 3.2 MAIN LEVELFLOOR P File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Revise this area of the main floor plan to correspond with the civil grading plan and to clearly show slopes and steps. Provide accessible route to all ground floor units. 2015 IBC 1107.4 Page: 3.6 MAIN FLOOR REFLEC CEILING PLAN File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: Smoke Alarms Author: nickt Color: Show the location of smoke alarms and carbon monoxide detectors on the RCPs or floor plans per 2015 IBC 907.2.11 and Municipal Code Title 8. 1 2 3 4 5 6 7 8 9 UP 18 RI S E R (6 17 TR E A D 90'-0"T.O. SLAB 90'-0"T.O. SLAB 000 011 J5.6 GE STAIR 003 LIFT 003 7 109 11 1412813B5.1 14.1 The floor of unit 102 is over this exterior space in the basement. Provide a floor assembly and detail for this location indicating air sealing and insulation value (minimum R-38 2015 IECC R402.1.2). 36 ' - 5 " 0" 10 ' - 8 " J K 44.4 Add wall type callouts referencing the wall assemblies to your floor plans or sections to aid in determining which fire resistant assemblies are used where. CO A AF F O R D A B L E HO U S I N G 80 2 WE S T MA I N ST . AS P E N , CO DRAWING ISSUE DRAWN BY: PROJECT No:1702 PERMIT 06-14-18 CPF All ideas, designs, arrangements and plansindicated or represented by this drawing areowned by and are the property of David JohnstonArchitects, PC and developed for use and inconjunction with the specified project. Noneof the ideas, designs, arrangements or plansshall be used by or disclosed for any purposewhatsoever without the written authorizationof David Johnston Architects, PC. 3.2 MAIN LEVELFLOOR PLAN Sheet No. DN UP RG RG RG W DW DW DW 11'-31/2"11'-31/2"10'-4"1'-7"5'-31/2"5'-33/4"6'-41/4"15'-31/2"2'-7" 2'- 7 " 16'-31/2" 10' - 8 " 6'-101/2" 5'-01/2" 5'-111/2" 5'- 4 " 5'- 4 " 5'-111/2" 81'-3" 75'-111/2" 100'-2"T.O.F.F. J5.6 A0 A03A04 A05 A06 A07 A10 A11 A12 A13 A14 A16A17A18 A19A20A21A22 A23 A24 A25 A26 A33 100'-8"T.O. PIER 143 LIFT DN 141/2" 141/2" 141/2" DN BEDROOM102-1 ENTRY102-0 BATHROOM102-4 KITCHEN102-3 CL.102-7 CL.102-8 LIVING ROOM102-2 BEDROOM101-1 ENTRY101-0 BATHROOM101-4 HEN1-3 CL.101-8 LIVING ROOM101-2 BEDROOM105-1 ENTRY105-0 BATHROOM105-4 CL.105-8 LIVING ROOM105-2 BEDROOM104-1 ENTRY104-0 BATHROOM104-4 KITCHEN104-3 CL.104-7 CL.104-8 LIVING ROOM104-2 DR W W DR DR REF REF RE F W 3 7 109 11 14 1615125 E J N M G H C 8 D F K L 1346 100'-2"HIGH POINT T.O.F.F. 99'-63/4"T.O.F.F. 98'-111/2"T.O.F.F. 100'-11/4"T.O. SLAB 100'-0"T.O. PLY 100'-11/4"T.O. SLAB 98'-103/4"T.O. SLAB 98'-103/4"T.O. SLAB 100'-0"T.O. PLY 100'-11/4"T.O. SLAB A5.1 A5.1 B5.1 B5.1 C5.2 D5.2 D5.2 E5.3 F5.4 H5.5 H5.5 14.1 24.2 10 0 101 102 103 104 105 106 107 108 109 110 11 1 112 113 114 115 11 7 118 119 120121 12 2 124 12 5 126 127 128 129 130 13 1 132 133 135 136 137 14 0 141 142 AH UNIT102 STAIR003 AH UNIT101 AH UNIT105 AH UNIT104 AH UNIT103 DECK1 BEDROOM103-1 LIVING ROOM103-2 MUDROOM103-5 ENTRY103-0 CL.103-7 CL.103-6 BATHROOM103-4 KITCHEN103-3CL.A209 MUDROOM102-5 CL.102-6 CL.101-9 M CL.105-9 CL.104-9 MUDROOM104-5 CL.104-6 G5.5 G5.5 0 2'4'8' Clean up the graphicsat the entrances. Itlooks like the slatsabove are showing. DN 11'-5"11'-31/2"11'-31/2"5'-31/2"5'-01/2"6'-101/2"5'-33/4"6'-41/4" 78'-8" J5.6 A23 A24 A25 A26 100'-8" T.O. PIER DN BEDROOM105-1 ENTRY105-0 BATHROOM 105-4 CL.105-7 CL 105 BEDROOM104-1 ENTRY BATHROOM 104-4 CL 104 A3.8 W DR RE F 3 7 109 11 1258 1346 98'-103/4"T.O. SLAB 98'-103/4" T.O. SLAB A5.1 B5.1 D5.2 H5.5 34.3 10 0 10 1 104 105 106 112 113 11 7 11 8 119 1 13 8 139 14 2 STAIR101 CL. 105-9 MUDROOM105-5 CL. 105-6 CL.104-9 G5.5 Revise this area of the main floor plan to correspond with the civil grading plan and to clearly show slopes and steps. Provide accessible route to all ground floor units. 2015 IBC 1107.4 A5.1 B5.1 D5.2 H5.5 G5.5 Show the location of smoke alarms and carbon monoxide detectors on the RCPs or floor plans per 2015 IBC 907.2.11 and Municipal Code Title 8. See Assemebly F4 ON 7.1 Revised. See 3.2 and 2.3 for clarification Assembly tags added. See 3.5.3.6 & 3.7 for locations of smoke/ CO detectors. 08/14/18 Page: 3.7 SECOND FLOOR REFLECTED CEILING P File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: attic access Author: nickt Color: Provide minimum 20"x30" access openings to attics per 2015 IBC 1209.2. Revise RCP sheet 3.7. Page: 3.8 TRASH ENCLOSURE File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Provide trash container capacities. If any containers have a capacity in excess of 1.5 yards, the trash enclosure must either be fire sprinklered or be Type I or IIA construction. (2015 IFC 304.3.3) Page: 5.1 BUILDING SECTIONS File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Revise sections to add callouts referencing roof assemblies. Page: 5.1 BUILDING SECTIONS File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Detail the intersection of foundation wall to framed wall at grade for insulation continuity and waterproofing. Page: 5.1 BUILDING SECTIONS File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Detail your strategy for air sealing the units at this location. Air barrier must follow the thermal envelope. Ordinance 40, 2016, 2015 IECC table R402.4.1.1. 12'-41/4" A.F.F. LIVING ROOM 202-2 Provide minimum 20"x30" access openings to attics per 2015 IBC 1209.2. Revise RCP sheet 3.7. CO A AF F O R D A B L E HO U S I DRAWING DRAWN BY: PROJECT No:1 PERMIT CP 3 TRASH ENC Sh 2 2 1 1 A A C C B B 13.8 8'- 6 " 1"7'-3"7'-3"1" 14'-6" 6" 6" 1"6"6'-6"6"6'-6"6"1" 2'- 0 " 6" 1'- 0 " EDGE OF ROOF EDGE OF ROOF ED G E OF RO O F ED G E OF RO O F A3.8 A3.833.8 23.843.8 13.821 6'-51/4" 8" 1'-41/4" MPOSITENSCREEN OFURE BE STEELLUMNS MPOSITE SIDING 0 1'2'4'SCALE: 1/2" = 1'-0"1 TRASH ENCLOSURE PLAN 0 1'2'4'SCALE: 1/2" = 1'-0"4 WEST ELEVATION 0 1'2'4'SCALE: 1/2" = 1'-0"3 SOUTH ELEVATION 0 1'2'4'SCALE: 1/2" = 1'-0"A BUILDING SECTION A Provide trash container capacities. If any containers have a capacity in excess of 1.5 yards, the trash enclosure must either be fire sprinklered or be Type I or IIA construction. (2015 IFC 304.3.3) K L Revise sections to add callouts referencing roof assemblies. MAIN LEVEL 100'-0" Detail the intersection of foundation wall to framed wall at grade for insulation continuity and waterproofing. 2 7.3 Detail your strategy for air sealing the units at this location. Air barrier must follow the thermal envelope. Ordinance 40, 2016, 2015 IECC table R402.4.1.1. Detail 3 on 7.6 shows the continuity to the underside of a 1/2 hour rated assembly. See details on sheet 7.3 for various conditions. All sections now have roof assembly tags. We are reqquired to have 2yard dumpsters so the construction will be IIA. See the revised 3.8 for updated design. See revised sheet 3.7 for locations. 08/14/18 Page: 5.1 BUILDING SECTIONS File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Detail the continuity of the 1/2 hour fire partition protecting the egress balcony dead end travel condition. Must extend to top of roof sheathing or to the underside of a 1/2 hour rated assembly. 2015 IBC 708.4 Page: 5.2 BUILDING SECTIONS File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: Group Author: nickt Color: Provide a detail showing slab edge insulation. Slab-on-grade floors with a floor surface less than 12" below grade must have insulation extending downward from the top of the slab on the outside or inside of the foundation wall.The insulation must be extended for by any combination of vertical insulation, insulation extending under the slab or insulation extending out from the building. See the details below for examples. If choosing the prescriptive path, R-10 insulation must extend 4'. If not providing slab edge insulation, use REScheck/COMcheck and give the slab an R value of '0'. Revise details as necessary.(2015 IECC 402.2.10) Page: 5.3 BUILDING SECTIONS File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Show the continuity of the corridor fire partitions. Must be continuous to the roof sheathing or may be interrupted by rated horizontal assemblies. 2015 IBC 708.4 Page: 5.3 BUILDING SECTIONS File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Provide a parapet or demonstrate compliance with one of the exceptions from 2015 IBC 705.11. G H J K L M N 17.317.3 17.1SECOND LEVEL 110'-5" SECOND 110'-5" 41'-51/2" 5'-01/2"6'-101/2"10'-8"1'-0"15'-31/2"2'-7" F6F1F5 LIVING ROOM LIVING ROOMAH UNIT AH UNITMUDROOM MUDROOM 202 102102-5 202-5 202-2 102-2 Detail the continuity of the 1/2 hour fire partition protecting the egress balcony dead end travel condition. Must extend to top of roof sheathing or to the underside of a 1/2 hour rated assembly. 2015 IBC 708.4 OA AF F O R D A B L E HO U S I N G 80 2 WE S T MA I N ST . AS P E N , CO All ideas, designs, arrangements and plansindicated or represented by this drawing areowned by and are the property of David JohnstonArchitects, PC and developed for use and inconjunction with the specified project. Noneof the ideas, designs, arrangements or plansshall be used by or disclosed for any purposewhatsoever without the written authorizationof David Johnston Architects, PC. 9 10 11 12 13 14 15 16 LIVING ROOM 7.3 17.1 MAIN LEVEL100'-0" SECOND LEVEL110'-5" F1 F6F5 LIVING ROOM LIVING ROOMAH UNIT AH UNITMUDROOM #Related Zone Name 205-2 105-2105 205205-5 #Related Zone Number F7F7 0 2'4'8'SCALE: 1/4" = 1'-0"D BUILDING SECTION D Provide a detail showing slab edge insulation. Slab-on-grade floors with a floor surface less than 12" below grade must have insulation extending downward from the top of the slab on the outside or inside of the foundation wall.The insulation must be extended for by any combination of vertical insulation, insulation extending under the slab or insulation extending out from the building. See the details below for examples. If choosing the prescriptive path, R-10 insulation must extend 4'. If not providing slab edge insulation, use REScheck/COMcheck and give the slab an R value of '0'. Revise details as necessary.(2015 IECC 402.2.10) 16 15 14 13 12 11 10 9 8 7 6 5 17.2 1 7.3 1 7.3 1 7.3 F1 F1F5 F5 F1 F7 F7 F6 LIVING ROOM LIVING ROOM AH UNIT AH UNIT KITCHEN KITCHEN LIVING ROOM LIVING ROOM LIVING LIVIN 203-2 103-2 203 103 102-3 202-3 202-2 102-2 10 2 Show the continuity of the corridor fire partitions. Must be continuous to the roof sheathing or may be interrupted by rated horizontal assemblies. 2015 IBC 708.4 US I N G All ideas, indicated owned by Architect conjuncti of the ide shall be u whatsoev of David J 3 2 1 1 7.3 Provide a parapet or demonstrate compliance with one of the exceptions from 2015 IBC 705.11. Detail 3 on 7.6 shows the continuity to the underside of a 1/2 hour rated assembly. The interior slab on grade condition has been revised to crawlspace. The associated details are on 7.3 See details 3/7.1 and 3/7.6 We are using exception 6 for the Western wall. 08/14/18 Page: 5.5 BUILDING SECTIONS File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Detail the continuity of the 1/2 hour fire partition protecting the egress balcony dead end travel condition. Must extend to top of roof sheathing or to the underside of a 1/2 hour rated assembly. 2015 IBC 708.4 Page: 7.1 FLOOR ASSEMBLIES DETAILS File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Detail your strategy for air sealing the units at detail 1/A7.1. Air barrier must follow the thermal envelope. Ordinance 40, 2016, 2015 IECC table R402.4.1.1. Page: 7.1 FLOOR ASSEMBLIES DETAILS File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Provide the full UL L570 install instructions specific to the system you are proposing. This will provide screw requirements. Page: 7.1 FLOOR ASSEMBLIES DETAILS File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Revise F8 to show the rigid insulation. Page: 7.1 FLOOR ASSEMBLIES DETAILS File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Provide documentation to prove the STC/IIC numbers for the UL L570 floor assembly dwelling separation (2015 IBC 1207). 15 16 2 7.3 SECOND LEVEL 110'-5" G H J K SECOND LEVEL 110'-5" 5'-01/2"6'-101/2"10'-8"1'-0" 41'-51/2" BATHRO CL. BATHROOM F3F5 AH UNIT AH UNIT 201-4201-9 101-4 201 101 Detail the continuity of the 1/2 hour fire partition protecting the egress balcony dead end travel condition. Must extend to top of roof sheathing or to the underside of a 1/2 hour rated assembly. 2015 IBC 708.4 11 7/8" 3/4" 3" TREATED PLATE & SHIM /2" MAX. RISE ADA THRESHOLD, THERMALLY BROKEN AT EXTERIOR APPLICATION SLAB F7 1 ½" = T. O. SLAB SEE PLAN T. O. FIN. FLOOR SEE PLAN 1 ½" = 1'-0"1 TYPICAL THRESHOLD DETAIL @ EXTERIOR DOORS GL F5 F1 Detail your strategy for air sealing the units at detail 1/A7.1. Air barrier must follow the thermal envelope. Ordinance 40, 2016, 2015 IECC table R402.4.1.1. 4/25/2018 USG Design Studio UL L570 or GA-FC-5011 Wood Engineered Joist Fire Rating Unrestraine System Thickness N/A SLAB ON GRAD F8 1 ½" = 1'-0" Provide the full UL L570 install instructions specific to the system you are proposing. This will provide screw requirements. 6" 4" WASH UNDIS OR CO CONC. R-11 R T. O SEE Revise F8 to show the rigid insulation. 9/32 " ETAIL & ASSE ETAIL & ASSE DESIGN BASED ON UL L570 1 HOUR RATING STC 60-64/IIC 62 Provide documentation to prove the STC/IIC numbers for the UL L570 floor assembly dwelling separation (2015 IBC 1207). F8 is an exterior slab with no insulation and F9 is the basement slab with R-11 insulation. 7.4 has the assembly with instructions. Detail 3 on 7.1 shows the air barrier following the thermal envelope. Detail 3 on 7.6 shows the continuity to the underside of a fire-rated assembly. The listed assembly is using sound test RAL-TL-81-87 IIC test no: RAL-0T03-03/04 listed on 7.4 08/14/18 Page: 7.2 WALL ASSEMBLIES & DETAILS File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Indicate all insulation values on the plans. Comply with prescriptive requirements of 2015 IECC R402.1.2 or provide a REScheck. Page: 7.2 WALL ASSEMBLIES & DETAILS File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: The basement walls require one of the following: R-15 continuous insulation; R19 cavity insulation; or a combination of R-13 cavity and R-5 continuous insulation. 2015 IECC R402.1.2 Page: 7.2 WALL ASSEMBLIES & DETAILS File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: If the stucco is synthetic (EIFS), either a water resistive barrier with drainage plane or a special inspection is required per 2015 IBC 1705.16. Indicate on the plans how you will comply. Page: 7.2 WALL ASSEMBLIES & DETAILS File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Specify the the type of continuous insulation used in the exterior walls. Page: 7.2 WALL ASSEMBLIES & DETAILS File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Provide the full UL U311 install instructions specific to the system you are proposing. This will provide screw requirements. L U311 - Fire Resistant Assembly, Fire Rated Assembly, Fire Rated Detail dams, Chicago, IL. 60661 : www.usgdesignstudio.com o.com/assembly.asp?id=920592&assemblyCategory=921052 311 CAD  · REVIT  Load-bearing) 1 hour System Thickness5-1/4" sum board applied horizontally or vertically channels installed horizontally spaced 24 in. OC uds spaced max. 16 in. OC ck mineral wool batts or glass fiber insulation sum board applied horizontally or vertically 11/2"SEE PLAN 3/4"51/2"3/4"1"1/2"3/4"51/2"3/4"1"1/4" 3/4"51/2"3/4"1"1/4" 8" 71/4" 6" BACKFILL W/ SCREENED GRAVEL R-11 RIGID INSULATION FIBERGLASS FILTER CLOTH CONC. WALL RE: STRUCT. FOUNDATION WATERPROOFING - CONTINUE TOBOTTOM OF FOOTING (SHOWN DASHED) VAPOR RETARDER 5/8" TYPE X GYPSUM WALL BOARD LAP COMPOSITE SIDING, BLIND FASTENING REQUIRED 5/8" FIBERGLASS MAT SHEATHING 1/2" PLYWOOD FURRING STRIPS (ALIGN WITH STUDS) TAPE ALL JOINTS FOR AIR BARRIER CONTINUOUS INSULATION (R-6) BLOWN-IN CELLULOSE INSULATION VAPOR RETARDER 5/8" TYPE X GYPSUM WALL BOARD COMPOSITE PANEL SIDING (SEE ELEVATIONS FOR LAYUP) 5/8" FIBERGLASS MAT SHEATHING 1/2" PLYWOOD FURRING STRIPS (ALIGN WITH STUDS) TAPE ALL JOINTS FOR AIR BARRIER CONTINUOUS INSULATION (R-6) BLOWN-IN CELLULOSE INSULATION VAPOR RETARDER 5/8" TYPE X GYPSUM WALL BOARD STUCCO (3 COATS) 5/8" FIBERGLASS MAT SHEATHING TAPE ALL JOINTS FOR AIR BARRIER CONTINUOUS INSULATION (R-6) W/DRAINAGE CHANNELS BLOWN-IN CELLULOSE INSULATION WATER BARRIER SELF-FURRING METAL LATH 1 ½" = 1'-0" INSULATED FOUNDATION WALLW2 W3 1 ½" = 1'-0" EXTERIOR WALL (SECTION) W/ SIDING GL W6 1 ½" = 1'-0" EXTERIOR WALL (SECTION) W/ COMPOSITE PANEL GL W5 1 ½" = 1'-0" EXTERIOR WALL (SECTION) W/ STUCCOOF TERMINATION NOTE:ANY PENETRATIONS TO MEET 1 HOUR FIRE RATING STANDARDS MUST BE PROTECTED PER 713. (SEE MECH. DRAWINGSFOR DETAILS) FIRE SEPARATION CONTINUES TOUNDERSIDE OF ROOF SHEATHING W4 Indicate all insulation values on the plans. Comply with prescriptive requirements of 2015 IECC R402.1.2 or provide a REScheck. All i indi own Arch con of th shal wha of D 3/4"SEE PLAN 3/4" BACKFILL W/ SCREENED GRAVEL R-11 RIGID INSULATION FOUNDATION WATERPROOFING - CONTINUE TO BOTTOM OF FOOTING (SHOWN DASHED) GL 0" OR WALL (TYPICAL)The basement walls require one of the following: R-15 continuous insulation; R19 cavity insulation; or a combination of R-13 cavity and R-5 continuous insulation. 2015 IECC R402.1.2 STUCCO (3 COATS) TAPE ALL JOINTS FOR AIR BARRIER SELF-FURRING METAL LATH W1RTY WALL (PLAN) If the stucco is synthetic (EIFS), either a water resistive barrier with drainage plane or a special inspection is required per 2015 IBC 1705.16. Indicate on the plans how you will comply. CO A AF F O R D A B L E HO U S I N G 80 2 WE S T MA I N ST . AS P E N , CO DRAWING ISSUE DRAWN BY:PROJECT No:1702 PERMIT 06-14-18 CPF All ideas, designs, arrangements and plansindicated or represented by this drawing areowned by and are the property of David JohnstonArchitects, PC and developed for use and inconjunction with the specified project. Noneof the ideas, designs, arrangements or plansshall be used by or disclosed for any purposewhatsoever without the written authorizationof David Johnston Architects, PC. 7.2 WALL ASSEMBLIES &DETAILS Sheet No. USG Design Studio | UL U311 - Fire Resistant Assembly, Fire Rated Assembly, Fire Rated Detail psum Company : 550 W. Adams, Chicago, IL. 60661 : www.usgdesignstudio.com ttp://www.usgdesignstudio.com/assembly.asp?id=920592&assemblyCategory=921052 stem Design - UL U311 ector  UL U311 CAD  · REVIT  - Featured ions - Wood Stud (Load-bearing) 1 hour st SA-830702 System Thickness5-1/4" n oard - 5/8 in. thick gypsum board applied horizontally or verticallyhannel -25 ga. furring channels installed horizontally spaced 24 in. OCs -2 in. x 4 in. wood studs spaced max. 16 in. OCBlankets -Min. 3 in. thick mineral wool batts or glass fiber insulation oard -5/8 in. thick gypsum board applied horizontally or vertically 11/2"SEE PLAN 3/4"SEE PLAN 3/4" 3/4"51/2"3/4"1"1/2" 3/4"3/4"31/2" SEE PLAN31/2"3/4"3/4" 3/4"51/2"3/4"1"1/4" 3/4"51/2"3/4"1"1/4" 8" /2"31/2"1/2"1/2" 71/4" 6" 71/4" 6" BACKFILL W/ SCREENED GRAVEL R-11 RIGID INSULATION FIBERGLASS FILTER CLOTH CONC. WALL RE: STRUCT. FOUNDATION WATERPROOFING - CONTINUE TOBOTTOM OF FOOTING (SHOWN DASHED) 5/8" GYPSUM WALL BOARD OR OTHER INTERIORFINISH - SEE SCHEDULE VAPOR RETARDER 5/8" TYPE X GYPSUM WALL BOARD LAP COMPOSITE SIDING, BLIND FASTENINGREQUIRED 5/8" FIBERGLASS MAT SHEATHING 1/2" PLYWOOD FURRING STRIPS (ALIGN WITH STUDS) TAPE ALL JOINTS FOR AIR BARRIER CONTINUOUS INSULATION (R-6) BLOWN-IN CELLULOSE INSULATION ON OPPOSITE SIDES TO BE STAGGERED.APPLY "PRECORA" ACOUSTICAL SEALANT TOVERTICAL JOINTS AND AT PENETRATIONS, ROOFDECK & FLOOR SLABS UNFACED GLASS FIBER BATT INSULATION,FRICTION FIT BETWEEN STUDS AND RUNNERS ONBOTH SIDES OF PARTY WALL VAPOR RETARDER 5/8" TYPE X GYPSUM WALL BOARD COMPOSITE PANEL SIDING(SEE ELEVATIONS FOR LAYUP) 5/8" FIBERGLASS MAT SHEATHING 1/2" PLYWOOD FURRING STRIPS (ALIGN WITH STUDS) TAPE ALL JOINTS FOR AIR BARRIER CONTINUOUS INSULATION (R-6) BLOWN-IN CELLULOSE INSULATION VAPOR RETARDER 5/8" TYPE X GYPSUM WALL BOARD STUCCO (3 COATS) 5/8" FIBERGLASS MAT SHEATHING TAPE ALL JOINTS FOR AIR BARRIER CONTINUOUS INSULATION (R-6) W/DRAINAGE CHANNELS BLOWN-IN CELLULOSE INSULATION WATER BARRIER SELF-FURRING METAL LATH 1/2" PLYWOOD SHEATHING 1 ½" = 1'-0" INSULATED FOUNDATION WALLW2 GL 1 ½" = 1'-0" INTERIOR WALL (TYPICAL)W1 W3 W4 1 ½" = 1'-0"EXTERIOR WALL (SECTION) W/ SIDING 1 ½" = 1'-0" 1-HOUR BEARING PARTY WALL (PLAN) GL W6 1 ½" = 1'-0"EXTERIOR WALL (SECTION) W/ COMPOSITE PANEL GL W5 1 ½" = 1'-0" EXTERIOR WALL (SECTION) W/ STUCCO GL (SECTION) W/ WOOD SIDING D WALL-ROOF TERMINATION NOTE:ANY PENETRATIONS TO MEET 1 HOUR FIRE RATINGSTANDARDS NOTE: PENETRATIONS OF FIRE-RATED ASSEMBLIESMUST BE PROTECTED PER 713. (SEE MECH. DRAWINGSFOR DETAILS) FIRE SEPARATION CONTINUES TOUNDERSIDE OF ROOF SHEATHING W4 Specify the the type of continuous insulation used in the exteriorwalls. Fire Rated System Design - UL U311 Home  System Selector  UL U311 CA UL U311 - Featured Interior Partitions - Wood Stud (Load- Fire Rating 1 ½" = 1'-0" Provide the full UL U311 install instructions specific to the system you are proposing. This will provide screw requirements. 7.2 has been revised. 7.2 has been revised. W5 Wall assembly shows drainage channels and a water barrier. The continuous insulation will be mineral wool. 7.4 & 7.5 shows the full UL listings. 08/14/18 Page: 7.2 WALL ASSEMBLIES & DETAILS File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Provide callouts pointing to wall assemblies on sections or floor plans Page: 7.3 ROOF ASSEMBLIES & DETAILS File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Provide documentation to prove that the roof assemblies are Class A. This is typically either an ESR or UL report. Revise you roof details to match the report, including any required underlayments. (Ordinance 40, 2016) Page: 7.3 ROOF ASSEMBLIES & DETAILS File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Coordinate the roof gutter detail with the trusses shown in the structurals. Those top plates are in the way. Page: 8.1 WINDOW SCHEDULES File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: The following windows must be 20 minute fire rated per (2015 IBC 1021.2, 1020.1, 716.6): A19, A20, A21, A22. Revise window schedule. Page: 8.1 WINDOW SCHEDULES File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: safety Glazing windows Author: nickt Color: Indicate which windows require safety glazing per 2015 IBC 2406.4. Revise the window schedule or elevations. The following windows should be safety glazed: B02, B06, B10, B13, B18 COMPOSITE PANEL SIDING (SEE ELEVATIONS FOR LAYUP) W2CTION) W/ STUCCO Provide callouts pointing to wall assemblies on sections or floor plans Provide documentation to prove that the roof assemblies are Class A. This is typically either an ESR or UL report. Revise you roof details to match the report, including any required underlayments. (Ordinance 40, 2016) PREFAB TRUSSES RE: STRUCTURAL CAP FLASHING PED ROOF GUTTER DETAIL W3 Coordinate the roof gutter detail with the trusses shown in the structurals. Those top plates are in the way. A14 A15 A16 A17 A18 A19 A20 A21 A22 A23 A24 A25 A26 A27 A28 A33 The following windows must be 20 minute fire rated per (2015 IBC 1021.2, 1020.1, 716.6): A19, A20, A21, A22. Revise window schedule. Indicate which windows require safety glazing per 2015 IBC 2406.4. Revise the window schedule or elevations. The following windows should be safety glazed: B02, B06, B10, B13, B18 Revised on 8.1 Per 1020.1 ex.5 these walls and openings are greater than 30' from the PL and therefore not required to be rated. We are modifying the trusses to scissor trusses so this detail will work better with the gutter system per our detail. See floor plans and sections for wall assembly tags. 7.5 has a UL listed assembly for the roof. 08/14/18 Page: 8.4 DOOR SCHEDULE File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: The following user passage doors must provide a minimum 31 3/4" clear opening width with door open to 90 degrees. Revise door schedule and plans as necessary do demonstrate compliance. (ICC A117.1-2009 section 1004.5.2) 104, 105 112, 113 107, 114, 128 126, 127 129, 130 Page: 8.4 DOOR SCHEDULE File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Storage room doors in the basement must provide a minimum 32" clear opening width. Revise door schedule and plans as necessary. (2015 IBC 1010.1.1) Page: 8.4 DOOR SCHEDULE File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Door 214 must be 20 minute fire rated (2015 IBC 1021.2, 1020.1, 716.5) Page: G1.08 OCCUPANCY File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Single exit S occupancies are permitted a maximum exit access travel distance of 75'. This may be increased to 100' if an NFPA 13 (not NFPA 13R) fire sprinkler system is installed per 2015 IBC table 1006.3.2(2). Revise note on G1.08 to read 91'<100' and provide an NFPA 13 system. Page: G1.08 OCCUPANCY File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: The central stair is an exit access stair but does not comply with any of the conditions of 2015 IBC 1019.3. You could comply with condition 1 by separating the stair so it only communicates with 2 stories. We will accept a smoke proof door at the basement level separating the stair from the lift. Essentially, just a landing at the bottom of the stair, then a door. Alternatively, a door at the top of the basement stairs. MENT/ FOUNDATIONS, EVEL, ND LEVEL, 000 001 002 003 004 005 006 007 008 009 010 011 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 135 136 137 138 139 140 141 142 143 200 201 202 203 204 205 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2'-10" 2'-10" 2'-10" 2'-10" 2'-10" 2'-10" 2'-10" 2'-10" 2'-10" 2'-10" 3'-0" 3'-0" 2'-8" 4'-0" 5'-0" 3'-5" 2'-3" 2'-3" 2'-2" 2'-8" 2'-8" 2'-8" 4'-0" 2'-2" 2'-3" 2'-3" 2'-8" 4'-0" 3'-5" 2'-8" 4'-0" 2'-2" 2'-8" 4'-0" 2'-2" 5'-0" 3'-0" 3'-0" 2'-3" 2'-3" 2'-2" 2'-3" 2'-3" 2'-10" 2'-10" 2'-10" 3'-0" 3'-0" 3'-0" 3'-5" 5'-0" 3'-5" 5'-0" 2'-10" 3'-0" 4'-0" 2'-8" 4'-0" 2'-10" 2'-8" 2'-2" 6'-8" 6'-8" 6'-8" 6'-8" 6'-8" 6'-8" 6'-8" 6'-8" 6'-8" 6'-8" 8'-0" 8'-0" 6'-8" 6'-8" 6'-8" 6'-8" 6'-8" 6'-8" 6'-8" 6'-8" 6'-8" 6'-8" 6'-8" 6'-8" 6'-8" 6'-8" 6'-8" 6'-8" 6'-8" 6'-8" 6'-8" 6'-8" 6'-8" 6'-8" 6'-8" 6'-8" 8'-0" 8'-0" 6'-8" 6'-8" 6'-8" 6'-8" 6'-8" 8'-0" 8'-0" 8'-0" 8'-0" 8'-0" 8'-0" 6'-8" 6'-8" 6'-8" 6'-8" 8'-0" 8'-0" 6'-8" 6'-8" 6'-8" 8'-0" 6'-8" 6'-8" TEMPERED VIEW LIGHT TEMPERED VIEW LIGHT TEMPERED VIEW LIGHT TEMPERED VIEW LIGHT TEMPERED VIEW LIGHT TEMPERED VIEW LIGHT TEMPERED VIEW LIGHT TEMPERED VIEW LIGHT TEMPERED VIEW LIGHT TEMPERED VIEW LIGHT TEMPERED VIEW LIGHT 20 MINUTE 20 MINUTE VIEW LIGHT VIEW LIGHT VIEW LIGHT VIEW LIGHT VIEW LIGHT VIEW LIGHT VIEW LIGHT VIEW LIGHT VIEW LIGHT VIEW LIGHT VIEW LIGHT 18.89 18.89 18.89 18.89 18.89 18.89 18.89 18.89 18.89 18.89 27.22 27.22 19.13 26.67 33.33 22.78 15.00 15.00 14.44 17.78 17.78 19.13 26.67 14.44 15.00 15.00 17.78 26.67 22.78 19.13 26.67 14.44 19.13 26.67 14.44 33.33 27.22 27.22 15.00 15.00 14.44 15.00 15.00 25.86 25.86 25.86 27.22 27.22 27.22 22.78 33.33 22.78 33.33 25.86 27.22 26.67 19.13 26.67 25.86 17.78 14.44 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 5'-0" 2'-8" 3'-0" 3'-0" 2'-10" 2'-8" 4'-0" 3'-5" 5'-0" 5'-0" 3'-5" 3'-5" 5'-0" 2'-3" 2'-3" 2'-3" 6'-8" 6'-8" 8'-0" 8'-0" 8'-0" 6'-8" 6'-8" 6'-8" 6'-8" 6'-8" 6'-8" 6'-8" 6'-8" 6'-8" 6'-8" 6'-8" 682'-8" The following user passage doors must provide a minimum 31 3/4" clear opening width with door open to 90 degrees. Revise door schedule and plans as necessary do demonstrate compliance. (ICC A117.1-2009 section1004.5.2) 104, 105 112, 113 107, 114, 128 126, 127 129, 130 DOOR SCHEDULE S, QUANTITY 1 1 1 1 1 1 1 1 1 1 1 1 1 WIDTH 2'-10" 2'-10" 2'-10" 2'-10" 2'-10" 2'-10" 2'-10" 2'-10" 2'-10" 2'-10" 3'-0" 3'-0" 2'-8" HEIGHT 6'-8" 6'-8" 6'-8" 6'-8" 6'-8" 6'-8" 6'-8" 6'-8" 6'-8" 6'-8" 8'-0" 8'-0" 6'-8" MANUFACTURER C TEMPERED Storage room doors in the basement must provide a minimum 32" clear opening width. Revise door schedule and plans as necessary. (2015 IBC 1010.1.1) 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Door 214 must be 20 minute fire rated (2015 IBC 1021.2, 1020.1, 716.5) DN UP TRAVEL DISTANCE 91'<125' OCCUPANT LOAD S 1:300 SF3 OCCUPANTS 1 3 7 109 11 14 1615125 J J N N M M 2 8 K K L L 1346 0 4'8'1 SCALE: 1/8" = 1'-0"-1 BASEMENT/ FOUNDATIONS OCCUPANCY Single exit S occupancies are permitted a maximum exit access travel distance of 75'. This may be increased to 100' if an NFPA 13 (not NFPA 13R) fire sprinkler system is installed per 2015 IBC table 1006.3.2(2). Revise note on G1.08 to read 91'<100' and provide an NFPA 13 system. A AF F O R D A B L E HO U S I N G 80 2 WE S T MA I N ST . AS P E N , CO All ideas, designs, arrangements and plansindicated or represented by this drawing areowned by and are the property of David JohnstonArchitects, PC and developed for use and inconjunction with the specified project. Noneof the ideas, designs, arrangements or plansshall be used by or disclosed for any purposewhatsoever without the written authorizationof David Johnston Architects, PC. DN UP TRAVEL DISTANCE 91'<125' OCCUPANT LOADS1:300 SF3 OCCUPANTS 3 7 109 11 14 1615125 J N M G H 8 K L 1346 0 4'8'16'" = 1'-0" EMENT/ FOUNDATIONS OCCUPANCY The central stair is an exit access stair but does not comply with any of the conditions of 2015 IBC 1019.3. You could comply with condition 1 by separating the stair so it only communicates with 2 stories. We will accept a smoke proof door at the basement level separating the stair from the lift. Essentially, just a landing at the bottom of the stair, then a door. Alternatively, a door at the top of the basement stairs. The floor plans and the door schedule have been revised to comply. A 2'-10" door comlplies with this code. REVISED G1.08 has been revised to a travel distance of 50' G1.08 has been revised to include a smoke-proof door. 08/14/18 Page: G1.08 OCCUPANCY File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Measure travel paths to end once no longer under the building (the paths don't end at the unit doors). For example, unit 103's entrance door opens into a corridor, which is still exit access, not exit discharge. Page: G1.09 OCCUPANCY File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Measure common path travel distance from the furthest location in each unit, through the unit, out the door, and along the deck until there is a choice of two travel paths. Max common path is 125' per 2015 IBC table 1006.2.1. Revise G1.09. Page: G1.09 OCCUPANCY File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Measure exit access travel distance from the furthest location in each unit, through the unit, out the door, along the deck, and down the stairs. Max is 250' per 2015 IBC table 1017.2. Revise G1.09. Page: G1.10 FIRE AREA File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Measure fire area to the inside of exterior walls, not the outside per 2015 IBC 202. Includes exterior covered areas as you have done. Revise G1.10 and G1.11. Page: G1.12 FIRE SEPARATION File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Walls less than 5' from property lines must be 1 hour fire rated (assembly must be rated from both sides). 2015 IBC table 602 and section 705.5. Revise fire separation plans and call out and provide a listed assembly. 1 E J N M G H 2 D F K L DN UP RG RG RG RG DW DW DW DW TR A V E L DI S T A N C E 36 '< 12 5 ' TR A V E L DI S T A N C E 36 '< 12 5 ' TR A V E L DIS T A N C E 39 '< 12 5 ' TRAVEL DISTANCE 37'<125' DR W W W DR DR DR REF REF REF REF W 1 3 7 109 11 14 1615125 E E J J N N M M G G H H 2 8 D D F F K K L L 1346 OCCUPANT LOADR21:200 SF3 OCCUPANTS OCCUPANT LOADR21:200 SF3 OCCUPANTS OCCUPANT LOADR21:200 SF3 OCCUPANTS OCCUPANT LOADR21:200 SF3 OCCUPANTS OCCUPANT LOADR21:200 SF3 OCCUPANTS SCALE: 1/8" = -1 BASEM 0 4'8'16'SCALE: 1/8" = 1'-0"1 MAIN LEVEL OCCUPANCY Measure travel paths to end once no longer under the building (the paths don't end at the unit doors). For example, unit 103's entrance door opens into a corridor, which is still exit access, not exit discharge. RG DW TR A V E L DI S T A N C E 37 '< 12 5 ' REF W DR 1 3 J N M 2 K L 4 OCCUPANT L R2 1:200 SF 3 OCCUPAN 2 SECOND LEVEL OCC Measure common path travel distance from the furthest location in each unit, through the unit, out the door, and along the deck until there is a choice of two travel paths. Max common path is 125' per 2015 IBC table 1006.2.1. Revise G1.09. RG DW TR A V E L DI S T A N C E 3 1 3 N M 2 L 4 OCCUPANT R2 1:200 S 3 OCCUPA SCALE: 1/8" = 1'-0"2 SECOND LEVEL OCC Measure exit access travel distance from the furthest location in each unit, through the unit, out the door, along the deck, and down the stairs. Max is 250' per 2015 IBC table 1017.2. Revise G1.09. DN FIRE AREA 1,467.06 sq ft 1 A 3 7 109 1 5 E J G H C 2 B 8 D F K L 4 6 UP RG RG RG DW DW DW DR DR DR REF RE F RE F W A 14 161512 E J G H C B D F K L 13 Measure fire area to the inside of exterior walls, not the outside per 2015 IBC 202. Includes exterior covered areas as you have done. Revise G1.10 and G1.11. RG DW 4'-01/2" 4'-61/2" 2'- 6 " 3'-6" SETBACK LINE W DR REF 1 3 75 J N M G H 2 F K L 4 6 SCALE: 1/8" = 1'-0"1 MAIN LEVEL FIRE SEPARATION Walls less than 5' from property lines must be 1 hour fire rated (assembly must be rated from both sides). 2015 IBC table 602 and section 705.5. Revise fire separation plans and call out and provide a listed assembly. See G1.12 for revision. See G1.10 & G1.11 for revision. G1.09 has been revised G1.09 has been revised G1.08 has been revised 08/14/18 Page: G1.12 FIRE SEPARATION File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: This wall is not required to be fire rated (it is an exit access stair serving an egress balcony with two exits and is greater than 10' from center of alley) Page: G1.13 FIRE SEPERATION File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: Group Author: nickt Color: Egress balcony must be 10' from lot line (2015 1021.4). Provide a 1 hour fire rated wall to protect it. The portion of the balcony within 10' of the lot line must also be 1 hour fire rated on the edge and underside. Page: G1.13 FIRE SEPERATION File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Split the allowable opening calculation up by story. 2015 IBC 705.8.1. Page: G1.13 FIRE SEPERATION File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: This wall is not required to be fire rated (it is an exit access stair serving an egress balcony with two exits and is greater than 10' from center of alley) Page: G1.13 FIRE SEPERATION File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Walls less than 5' from property lines must be 1 hour fire rated (assembly must be rated from both sides). 2015 IBC table 602 and section 705.5. Revise fire separation plans and call out and provide a listed assembly. 1 A E C 2 B D F DN UP RG DW SETBACK LINE SETBACK LINE W DR RE F A 7 109 11 14 161512 E C B 8 D F 13 This wall is not required to be fire rated (it is an exit access stair serving an egress balcony with two exits and is greater than 10' from center of alley) RG DW REF W DR E J G H F K L Egress balcony must be 10' from lot line (2015 1021.4). Provide a 1 hour fire rated wall to protect it. The portion of the balcony within 10' of the lot line must also be 1 hour fire rated on the edge and underside. 10'-0" CO A AF F O R D A DRAW DRAWN PROJECT PERMIT FIRE S 19.47 sq ft 19.47 sq ft BASEMENT/ FOUNDATIONS 90'-0" MAIN LEVEL 100'-0" SECOND LEVEL 110'-5" 829.99 sq ft 22.00 sq ft 22.00 sq ft 1 HR RATED FLOOR/ CEILING ASSEMBLY TOTAL AREA OPENING AREA PERCENT OF OPEN AREA 829.99 SF 82.94 SF 10% 0 4'8'16' ISTANCE Split the allowable opening calculation up by story. 2015 IBC 705.8.1. DN UP RG DW W DR RE F 7 109 11 1412581346This wall is not required to be fire rated (it is an exit access stair serving an egress balcony with two exits and is greater than 10' from center of alley) RG DW REF W DR 1 3 75 J N M G H 2 F K L 4 6 SCALE: 1/8" = 1'-0"2 SECOND LEVEL FIRE SEPARATION Walls less than 5' from property lines must be 1 hour fire rated (assembly must be rated from both sides). 2015 IBC table 602 and section 705.5. Revise fire separation plans and call out and provide a listed assembly. See revised G1.13 and W3 on 7.2 See revised G1.13 See revised G1.13 Revised See revised assembly 08/14/18 Page: G1.13 FIRE SEPERATION File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Projections such as the balcony within 5' of the property line must be 1 hour fire rated per 2015 IBC 705.2.3. Revise fire separation plans and call out and provide a listed assembly. Page: G1.13 FIRE SEPERATION File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: These walls and openings must be protected as they are on a dead end. Walls must be 1/2 hour fire rated and windows and doors must be 20 minute rated (2015 IBC 1021.2, 1020.1, 716.5, 716.6). Revise fire separation plans and call out and provide a listed assembly. Page: G1.14 ACCESSIBILITY File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Provide door maneuvering clearance on both sides of the accessible storage room door and turnaround inside. (2015 IBC 1108.3, 1104). Page: G1.14 ACCESSIBILITY File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Provide accessible door maneuvering clearance to lift (on both levels). Page: G1.15 ACCESSIBILITY File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Indicate on the plans that the kitchen minimum 60" clear width measurement is to the furthest projecting finished surface or appliance (not including handles). ICC/A117.1-2009 section 1004.12.1.2 W DR 1 A 3 5 E J G H C 2 B D F 4 6 Projections such as the balcony within 5' of the property line must be 1 hour fire rated per 2015 IBC 705.2.3. Revise fire separation plans and call out and provide a listed assembly. DN DN RG RG DW DW W W W DR DR DR REF REF W DR A E J M G H C B D F K L These walls and openings must be protected as they are on a dead end. Walls must be 1/2 hour fire rated and windows and doors must be 20 minute rated (2015 IBC 1021.2, 1020.1, 716.5, 716.6). Revise fire separation plans and call out and provide a listed assembly. <- 6 0 " x 5 6 " Provide door maneuvering clearance on both sides of the accessible storage room door and turnaround inside. (2015 IBC 1108.3, 1104). 1 2 3 UP60 " x 5 6 " - > 7 1095846 Provide accessible door maneuvering clearance to lift (on both levels). UP RG DW REF 7 109 11 1258 136 1'-4"2'-05/8"1'-51/4"1'-3"1'-4" 5'- 1 " 50 " x 4 8 " - > <- 6 0 " x 5 6 " 50 " x 4 8 " - > <- 6 0 " x 5 6 " 60 " x 4 8 " 30"x48" 56"x48" 60 " x 4 8 " 30"x48"<- 3 0 " x 4 8 " 30 " x 4 8 " 30"x48" <-50"x48"60"x56"-> 30 1 BEDROOM UNIT ANSI A117.1-2009 TYPE B, OPTION A Indicate on the plans that the kitchen minimum 60" clear width measurement is to the furthest projecting finished surface or appliance (not including handles). ICC/A117.1-2009 section 1004.12.1.2 See G1.14 for revised clearances. See G1.14 for revised clearances. See G1.15 for clarification The edge of the deck was pull Ease 3" to allow for 5'-1" clear to the property line. See G1.13 for revised fire separation. The window and door schedule are updated to reflect the proper ratings. 08/14/18 Page: G1.15 ACCESSIBILITY File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: The door swings into the clear space of the sink in the corner unit bathroom. Indicate a 30"x48" clearspace in the bathroom that does not overlap a fixture or the door swing. ICC/A117.1-2009 section 1004.11.2.1 Page: G1.15 ACCESSIBILITY File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Washing machines and Dryers must be front loading to work with the forward approach. (ICC/A117.1-2009 section 1004.10.1). Provide a spec. Also, verify that the bifold doors will accommodate the clear spaces when full open. Often, they do not open far enough. Page: G1.15 ACCESSIBILITY File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Flip the 60"x48" clearspace so that the 60" side is parallel to the tub. Water closet and lavatory may encroach. ICC/A117.1-2009 figure 1004.11.3.1.3.2. Page: G1.15 ACCESSIBILITY File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: 33" minimum required space for water closet between tub and lavatory, revise all bathrooms affected. ICC/A117.1-2009 section 1004.11.3.1.2.2.4. Page: G1.15 ACCESSIBILITY File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Provide interior elevations depicting requirements for blocking at future grab bar locations per ICC/A117.1-2009 section 1004.11.1. CO A AF F O R D A B L E H DRAWIN PERMIT ACCESSIB DN UP RG RG DW DR W DR REF W J N M K L 2'-05/8" 2'-37/8" 1'- 3 " 1'- 4 " 5'-51/8" 30 30 30 " x 4 8 <-50"x48"60"x56"-> 30 " x 4 8 " 56 " x 4 8 " 60"x48" 30 " x 4 8 " 30 " x 4 8 " 30 " x 4 8 " 30"x48"30"x48" <- 3 0 " x 4 8 " 1 BEDROOM UNIT ANSI A117.1-2009 TYPE B, OPTION A The door swings into the clear space of the sink in the corner unit bathroom. Indicate a 30"x48" clearspace in the bathroom that does not overlap a fixture or the door swing. ICC/A117.1-2009 section 1004.11.2.1 RG W DR REF J H K L 5'- 1 " 30"x48" <- 5 0 " x 4 8 " 60 " x 5 6 " - > 30"x48" x4 8 " x4 8 " 30"x48" Washing machines and Dryers must be front loading to work with the forward approach. (ICC/A117.1-2009 section 1004.10.1). Provide a spec. Also, verify that the bifold doors will accommodate the clear spaces when full open. Often, they do not open far enough. DW DR REF-05/8"1'-51/4"1'-3"1'-4"2'-05/8"1'-51/4"1'-3"1'-4" 5' - 1 " "" 30"x48" x48" 56"x48" 60 " x 4 8 " 30"x48" 56"x48" 60 " x 4 8 " 30"x48"<- 3 0 " x 4 8 " 30 " x 4 8 " 30"x48" 1 BEDROOM UNIT ANSI A117.1-2009 TYPE B, OPTION A Flip the 60"x48" clearspace so that the 60" side is parallel to the tub. Water closet and lavatory may encroach. ICC/A117.1-2009 figure 1004.11.3.1.3.2. DW REF 2'-05/8"1'-51/4"1'-3"1'-4"2'-05/8"1'-51/4"1'-3"1'-4" 5' - 1 " 30"x48" <- 6 0 " x 5 6 " <- 6 0 " x 5 6 " 30"x48" 56"x48" 60 " x 4 8 " 30"x48" 56"x48" 60 " x 4 8 " 30"x48"<- 3 0 " x 4 8 " 30 " x 4 8 " 30"x48" 1 B AN TY 1 BEDROOM UNIT ANSI A117.1-2009 TYPE B, OPTION A 33" minimum required space for water closet between tub and lavatory, revise all bathrooms affected. ICC/A117.1-2009 section 1004.11.3.1.2.2.4. RG DW W DR REF J N M K L 2'-05/8"1'-51/4"1'-3"1'-4"2'-051'-51/4"1'-3"1'-4" 5'- 1 " 30"x48" <- 5 0 " x 4 8 " 60 " x 5 6 " - > 30"x48" 50 " x 4 8 " - > <- 6 0 " x 5 6 " 50 " x 4 8 " - > <- 6 0 " x 5 6 " 30"x48" 56"x48" 60 " x 4 8 " 30"x 56"x48" 60 " x 4 8 " 30"x48"<- 3 0 " x 4 8 " 30 " x 4 8 " 30"x48" 1 BEDROOM UNIT ANSI A117.1-2009 TYPE B, OPTION A Provide interior elevations depicting requirements for blocking at future grab bar locations per ICC/A117.1-2009 section 1004.11.1. The door is now an outswing door. See sheet G1.15 for revised clearances. See dimension clarifications on G1.15 See sheet G1.15 for blocking diagrams. See the spec attached to allow for the forward approach. See plans for revised clearances to allow for the bi-fold doors. 08/14/18 Page: G1.15 ACCESSIBILITY File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Center the lavatory clearspace on the lavatory. Center of lavatory will need to be 24" off the finish surface of the side wall. It looks close at all units. ICC/A117.1-2009 section 1004.11.3.1.1 Page: G1.15 ACCESSIBILITY File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Indicate that the clearspaces must be centered on the sinks and ranges. ICC/A117.1-2009 section 1004.12.2.1 and 1004.12.2.3. Page: G1.16 ACCESSIBILITY File Name: Architectural Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: The units on the second level are not required to be Type B accessible due to the lack of an elevator (2015 IBC 1107.7.1). Unless you are proposing to make the units Type B accessible for the future installation of an elevator, please delete G1.16 second level accessibility plans to reduce confusion. If you do wish to make the second level Type B accessible, the primary entrance doors must have 32" clear openings (ICC A117.1-2009 section 1004.5.1) and make the accessibility fixes that I've called out for the main level. Page: [7] C6 DRAINAGE PLAN File Name: Civil Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Provide an accessible route to the outdoor seating area (2015 IBC 1104.2 and 1104.3). Crusher fines are not an accessible surface (must be firm, stable, and slip resistant - ICC/ANSI A117.1-2009 section 302.1). Civils show a step. Revise landscapes and civils. Civil Plans.802 West Main.2018.06.pdf (1) Page: E1.1 ELECTRICAL ONE LINE & PANEL SCHEDULES File Name: Electrical Plans.802 West Main.2018.05.pdf Subject: PlanCheck Author: nickt Color: Show the location of the meter bank and solar house panel in plan. Electrical Plans.802 West Main.2018.05.pdf (1) CO A AF F O R D A B L E HO U S I N G 80 2 WE S T MA I N ST . AS P E N , CO DRAWING ISSUE DRAWN BY: PROJECT No:1702 PERMIT 06-14-18 CPF G1.15 ACCESSIBILITY Sheet No. DN UP RG RG RG DW DW DW DR W W DR DR REF REF RE F W 7 109 11 14 1615125 J N M G H 8 K L 136 "1'-4"2'-05/8"1'-51/4"1'-3"1'-4" 5'-1 " 2'-05/8" 5'-1" 2'-05/8" 2'-37/8" 1'- 3 " 1'- 4 " 5'-51/8" 50" x 4 8 " - > <-6 0 " x 5 6 " 50" x 4 8 " - > <-6 0 " x 5 6 " 30"x48" <-5 0 " x 4 8 " 60" x 5 6 " - > 30"x48" 60" x 4 8 " 30"x48" 56"x48" 60" x 4 8 " 30"x48"<-3 0 " x 4 8 " 30" x 4 8 " 30"x48" 30" x 4 8 " 50"x48"-><-60"x56" 30" x 4 8 " 30 " x 4 8 " 30" x 4 8 " 30"x48"-> 30"x48" 30 " x 4 8 " <-50"x48"60"x56"-> 30 " x 4 8 " 56 " x 4 8 " 60"x48" 30" x 4 8 " 30 " x 4 8 " 30" x 4 8 " 30"x48"30"x48" <-3 0 " x 4 8 " 1 BEDROOM UNITANSI A117.1-2009 TYPE B, OPTION A 1 BEDROOM UNITANSI A117.1-2009 TYPE B, OPTION A 1 BEDROOM UNITANSI A117.1-2009 TYPE B, OPTION A 0 2'4'8' Center the lavatory clearspace on the lavatory. Center oflavatory will need to be 24" off the finish surface of the side wall. It looks close at all units. ICC/A117.1-2009 section 1004.11.3.1.1 RG DW REF N M K L 2'-05/8"1'-51/4"1'-3"1'-4" 5' - 1 " 30"x48" 56"x48" 60 " x 4 8 " 30"x48"<- 3 0 " x 4 8 " 30 " x 4 8 " 30"x48" 1 BEDROOM UNIT ANSI A117.1-2009 TYPE B, OPTION A Indicate that the clearspaces must be centered on the sinks and ranges. ICC/A117.1-2009 section 1004.12.2.1 and 1004.12.2.3. The units on the second level are not required to be Type B accessible due to the lack of an elevator (2015 IBC 1107.7.1). Unless you are proposing to make the units Type B accessible for the future installation of an elevator, please delete G1.16 second level accessibility plans to reduce confusion. If you do wish to make the second level Type B accessible, the primary entrance doors must have 32" clear openings (ICC A117.1-2009 section 1004.5.1) and make the accessibility fixes that I've called out for the main level. G Provide an accessible route to the outdoor seating area (2015 IBC 1104.2 and 1104.3). Crusher fines are not an accessible surface (must be firm, stable, and slip resistant - ICC/ANSI A117.1-2009 section 302.1). Civils show a step. Revise landscapes and civils. 1APANEL ELECTRICAL ONE-LINE DIAGRAM (2) 200ASPACES 200/2 1BPANEL 200/2 METERBANK 1200A, 120/240V, 1P, 3W 42kAlC NO SCALE NOTE: PROVIDE SHORT CIRCUIT BRACING TO MEET REQUIREMENTS NOTED AT ONE-LINE, NOTED AS "AIC AVAILABLE". SERIES RATED COMBINATION ACCEPTABLE,SUBMIT MANUFACTURER'S SERIES RATINGS WITH SHOP DRAWING REVIEW. CONTRACTOR SHALL VERIFY ALL SERVICE EQUIPMENT BEING USED WITH LOCALUTILITY. CONTRACTOR IS RESPONSIBLE FOR PROVIDING SERVICE EQUIPMENTTHAT IS ACCEPTABLE TO USE THROUGH THE UTILITY AND THE AHJ. 4[(4 #500 MCM AL) 3-1/2"C] T UTILITY TRANSFORMER PAD MOUNTED 1CPANEL 200/2 1DPANEL 200/2 1EPANEL 200/2 2APANEL 200/2 2BPANEL 200/2 2CPANEL 200/2 2DPANEL 200/2 2EPANEL 200/2 (3 #3/0 CU,1 #4 CUG)2"C OR(3 #250 MCM AL,1 #2 ALG)3"C HOUSEPANEL 400/2 1200/2 SOLARPANEL PROVIDE SOLARPRODUCTION METER AS REQUIRED BY THEUTILITY. 100/2 Show the location of the meter bank and solar house panel in plan. G1.16 has been eliminated. See dimension clarifications on G1.15 See dimension clarifications on G1.15 An alternate material has been selected and revised on the LA drawings. Shown on Plans 08/14/18 Page: L.1.02 MATERIALS P File Name: Landscape Plans.802 West Main.2018.06.pdf Subject: PlanCheck Author: nickt Color: Provide an accessible route to the outdoor seating area (2015 IBC 1104.2 and 1104.3). Crusher fines are not an accessible surface (must be firm, stable, and slip resistant - ICC/ANSI A117.1-2009 section 302.1). Civils show a step. Revise landscapes and civils. Landscape Plans.802 West Main.2018.06.pdf (1) Page: M1.0 MECHANICAL LEGEND SPECS & SEQUENCE File Name: Mechanical Plans.802 West Main.2018.05.pdf Subject: Thermostat mounting height Author: nickt Color: Revise mechanical plans to note the mounting height of thermostats. 48" max per ICC/A117.1-2009 section 1004.9. Mechanical Plans.802 West Main.2018.05.pdf (3) Page: M2.0 BASEMENT HVAC PLAN File Name: Mechanical Plans.802 West Main.2018.05.pdf Subject: PlanCheck Author: nickt Color: The mechanical room only has a unit heater in it. What is the intent for the use of this space? Page: M2.1 1ST FLOOR HVAC PLAN File Name: Mechanical Plans.802 West Main.2018.05.pdf Subject: PlanCheck Author: nickt Color: Exhausts may not discharge air onto a walkway (2015 IMC 501.3). Page: 1 File Name: Special Inspection.802 West Main.2018.05.pdf Subject: PlanCheck Author: nickt Color: The special inspection agreement must be signed by the special inspector, owner (or owner's agent), and fabricator (in this case the concrete installer). Special Inspection.802 West Main.2018.05.pdf (1) 7927 7926 7928 OP E R T Y L I N E 10' SETBACK 3. 5 ' S E T B A C K BENCH INTEGRATED INTO WALL; RE: 9/L.5.01 LANDSCAPE STEPPER; 7/L.5.01 CRUSHER FINES; RE: 6/L.5.01 CONCRETE SITE WALL; RE: 1/L.5.02 BENCH INTEGRATED INTO WALL; RE: 9/L.5.01 COURTYARD STEPS; RE: 3/L.5.02 CRUSHER FINES; RE: 6/L.5.01 6' TALL FENCE ALONG PROPERTY LINE; RE: 1/L.5.03 ISOLATION JOINT WHERE CONCRETE MEETS ARCH. TYP; RE: 4/L.5.01Provide an accessible route to the outdoor seating area (2015 IBC 1104.2 and 1104.3). Crusher fines are not an accessible surface (must be firm, stable, and slip resistant - ICC/ANSI A117.1-2009 section 302.1). Civils show a step. Revise landscapes and civils. AND MAY S PACE IN HE D OPER ES, 26.TEMPORARY HEATING DURING CONSTRUCTION: a.MECHANICAL EQUIPMENT SHALL NOT BE UTILIZED FOR TEMPORARY b.GAS FIRED TEMPORARY HEAT SHALL BE PROVIDED BY THE GENERAL Revise mechanical plans to note the mounting height of thermostats. 48" max per ICC/A117.1-2009 section 1004.9. UH 1 T UH 2 T BASEMENT H The mechanical room only has a unit heater in it. What is the intent for the use of this space? 1 ER WALL CAP L CAP 58 IN 3 Exhausts may not discharge air onto a walkway (2015 IMC 501.3). D. Brian Beazley 04-20-18 The special inspection agreement must be signed by the special inspector, owner (or owner's agent), and fabricator (in this case the concrete installer). The mechanical room has been reduced in size and relocated. Electrical and Sump pump will be located in this room. Revised An alternate material has been selected and revised on the LA drawings. Revised This will be signed once a concrete installer has been selected. 08/14/18