HomeMy WebLinkAboutFile Documents.427 Rio Grande Pl.0016.2019 (37).ACBKCOMcheck Software Version 4.1.1.0
Interior Lighting Compliance Certificate
Project Title:
2015 IECC
Project Type:New Construction
Construction Site:
425 Rio Grande Place
Aspen, CO 81611
Owner/Agent:
City of Aspen
130 S. Galena Street
Aspen, CO 81611
970-309-7638
jeff.pendarvis@cityofaspen.com
Designer/Contractor:
Shaw Construction
760 Horizon Drive
Suite 201
Grand Junction, CO 81506
970-242-9236
brianthomas@shawconstruction.net
Project Information
Energy Code:
Aspen City Offices at Galena
Reduced interior lighting power. Requirements are implicitly enforced within interior lighting allowance calculations.
Additional Efficiency Package(s)
Allowed Interior Lighting Power
A
Area Category
B
Floor Area
(ft2)
C
Allowed
Watts / ft2
D
Allowed Watts
(B X C)
1-Town Hall 35984 0.80 28823
28823Total Allowed Watts =
Proposed Interior Lighting Power
E
(C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
1-Town Hall
LED 1: A: 6" Downlight: Other:1 30 20 615
LED 2: B: Perimeter Fixture (per foot): Other:1 207 4 828
LED 3: C: 4' Strip: Other:1 102 32 3264
LED 4: D: 4' Stairwell: Other:1 13 48 624
LED 5: F: Narrow Depth Downlight: Other:1 6 15 90
LED 7: J: Stair Tape Light: Other:1 96 10 960
LED 6: Q: Pendant: Other:1 1 33 33
6414Total Proposed Watts =
Interior Lighting Compliance Statement
Compliance Statement: The proposed interior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed interior lighting systems have been
designed to meet the 2015 IECC requirements in COMcheck Version 4.1.1.0 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist.
Name - Title Signature Date
Interior Lighting PASSES: Design 78% better than code
Project Title:
Data filename:
Aspen City Offices at Galena
\\files\Corporate\Offices\Denver\MKK\01-Denver\2016.01.0223 & 2016.01.0224 Aspen City Hall -
Galena Plaza & Rio Grande\Engr\Energy\2019-06-14_ComCheck.cck
03/10/20Report date:
81 ofPage
Carrie Burgardt - Electrical Engineer 03/10/2020
COMcheck Software Version 4.1.1.0
Exterior Lighting Compliance Certificate
Project Title:
2015 IECC
Project Type:New Construction
Construction Site:
425 Rio Grande Place
Aspen, CO 81611
Owner/Agent:
City of Aspen
130 S. Galena Street
Aspen, CO 81611
970-309-7638
jeff.pendarvis@cityofaspen.com
Designer/Contractor:
Shaw Construction
760 Horizon Drive
Suite 201
Grand Junction, CO 81506
970-242-9236
brianthomas@shawconstruction.net
Project Information
Energy Code:
Aspen City Offices at Galena
2 (Neighborhood business district)Exterior Lighting Zone
Allowed Exterior Lighting Power
A
Area/Surface Category
B
Quantity
C
Allowed
Watts / Unit
D
Tradable
Wattage
E
Allowed Watts
(B X C)
Main entry 6 ft of door 20 Yes 120
Other door (not main entry)68 ft of door 20 Yes 1360
Stairway 1100 ft2 1 Yes 1100
Walkway < 10 feet wide 200 ft of 0.7 Yes 140
Entry canopy 850 ft2 0.25 Yes 212
Total Tradable Watts (a) =
Total Allowed Watts =
Total Allowed Supplemental Watts (b) =
2932
2932
600
(a)Wattage tradeoffs are only allowed between tradable areas/surfaces.
(b)A supplemental allowance equal to 600 watts may be applied toward compliance of both non-tradable and tradable areas/surfaces.
Proposed Exterior Lighting Power
E
(C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
Main entry (6 ft of door width): Tradable Wattage
LED 4 copy 1: SD: All per foot: Other:1 10 15 150
Other door (not main entry) (68 ft of door width): Tradable Wattage
LED 1: SA: Other:1 18 27 486
Stairway (1100 ft2): Tradable Wattage
LED 3: SC: Step Light: Other:1 33 8 264
Walkway < 10 feet wide (200 ft of walkway length): Tradable Wattage
LED 2: SB: Other:1 15 11 165
Entry canopy (850 ft2): Tradable Wattage
LED 4: SD: All per foot: Other:1 154 15 2310
3375Total Tradable Proposed Watts =
Project Title:
Data filename:
Aspen City Offices at Galena
\\files\Corporate\Offices\Denver\MKK\01-Denver\2016.01.0223 & 2016.01.0224 Aspen City Hall -
Galena Plaza & Rio Grande\Engr\Energy\2019-06-14_ComCheck.cck
03/10/20Report date:
82 ofPage
Exterior Lighting Compliance Statement
Compliance Statement: The proposed exterior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed exterior lighting systems have been
designed to meet the 2015 IECC requirements in COMcheck Version 4.1.1.0 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist.
Name - Title Signature Date
Exterior Lighting PASSES: Design 4% better than code
Project Title:
Data filename:
Aspen City Offices at Galena
\\files\Corporate\Offices\Denver\MKK\01-Denver\2016.01.0223 & 2016.01.0224 Aspen City Hall -
Galena Plaza & Rio Grande\Engr\Energy\2019-06-14_ComCheck.cck
03/10/20Report date:
83 ofPage
Carrie Burgardt - Electrical Engineer 03/10/2020
Inspection Checklist
Requirements: 12.0% were addressed directly in the COMcheck software
COMcheck Software Version 4.1.1.0
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Energy Code: 2015 IECC
Section
#
& Req.ID
Plan Review Complies?Comments/Assumptions
C103.2
[PR4]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the interior lighting
and electrical systems and equipment
and document where exceptions to
the standard are claimed. Information
provided should include interior
lighting power calculations, wattage of
bulbs and ballasts, transformers and
control devices.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C103.2
[PR8]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the exterior lighting
and electrical systems and equipment
and document where exceptions to
the standard are claimed. Information
provided should include exterior
lighting power calculations, wattage of
bulbs and ballasts, transformers and
control devices.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C406
[PR9]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the additional energy
efficiency package options.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Aspen City Offices at Galena
\\files\Corporate\Offices\Denver\MKK\01-Denver\2016.01.0223 & 2016.01.0224 Aspen City Hall -
Galena Plaza & Rio Grande\Engr\Energy\2019-06-14_ComCheck.cck
03/10/20Report date:
84 ofPage
Section
#
& Req.ID
Rough-In Electrical Inspection Complies?Comments/Assumptions
C405.2.1
[EL15]1
Lighting controls installed to uniformly
reduce the lighting load by at least
50%.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C405.2.1
[EL18]1
Occupancy sensors installed in
required spaces.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C405.2.1,
C405.2.2.
3
[EL23]2
Independent lighting controls installed
per approved lighting plans and all
manual controls readily accessible and
visible to occupants.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C405.2.2.
1
[EL22]2
Automatic controls to shut off all
building lighting installed in all
buildings.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C405.2.3
[EL16]2
Daylight zones provided with
individual controls that control the
lights independent of general area
lighting.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C405.2.3,
C405.2.3.
1,
C405.2.3.
2
[EL20]1
Primary sidelighted areas are
equipped with required lighting
controls.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C405.2.3,
C405.2.3.
1,
C405.2.3.
3
[EL21]1
Enclosed spaces with daylight area
under skylights and rooftop monitors
are equipped with required lighting
controls.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C405.2.4
[EL4]1
Separate lighting control devices for
specific uses installed per approved
lighting plans.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C405.2.4
[EL8]1
Additional interior lighting power
allowed for special functions per the
approved lighting plans and is
automatically controlled and
separated from general lighting.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C405.2.5
[EL25]null
Automatic lighting controls for exterior
lighting installed. Controls will be
daylight controlled, set based on
business operation time-of-day, or
reduce connected lighting > 30%.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C405.3
[EL6]1
Exit signs do not exceed 5 watts per
face.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Aspen City Offices at Galena
\\files\Corporate\Offices\Denver\MKK\01-Denver\2016.01.0223 & 2016.01.0224 Aspen City Hall -
Galena Plaza & Rio Grande\Engr\Energy\2019-06-14_ComCheck.cck
03/10/20Report date:
85 ofPage
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Aspen City Offices at Galena
\\files\Corporate\Offices\Denver\MKK\01-Denver\2016.01.0223 & 2016.01.0224 Aspen City Hall -
Galena Plaza & Rio Grande\Engr\Energy\2019-06-14_ComCheck.cck
03/10/20Report date:
86 ofPage
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
C303.3,
C408.2.5.
2
[FI17]3
Furnished O&M instructions for
systems and equipment to the
building owner or designated
representative.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C405.4.1
[FI18]1
Interior installed lamp and fixture
lighting power is consistent with what
is shown on the approved lighting
plans, demonstrating proposed watts
are less than or equal to allowed
watts.
Complies
Does Not
Not Observable
Not Applicable
See the Interior Lighting fixture schedule for values.
C405.5.1
[FI19]1
Exterior lighting power is consistent
with what is shown on the approved
lighting plans, demonstrating
proposed watts are less than or equal
to allowed watts.
Complies
Does Not
Not Observable
Not Applicable
See the Exterior Lighting fixture schedule for values.
C408.2.5.
1
[FI16]3
Furnished as-built drawings for
electric power systems within 90 days
of system acceptance.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.3
[FI33]1
Lighting systems have been tested to
ensure proper calibration, adjustment,
programming, and operation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Aspen City Offices at Galena
\\files\Corporate\Offices\Denver\MKK\01-Denver\2016.01.0223 & 2016.01.0224 Aspen City Hall -
Galena Plaza & Rio Grande\Engr\Energy\2019-06-14_ComCheck.cck
03/10/20Report date: