HomeMy WebLinkAboutFile Documents.230 E Hopkins Ave.0089.2018 (30).ACBKCOMcheck Software Version 4.1.1.0
Interior Lighting Compliance Certificate
Project Title:
90.1 (2013) Standard
Project Type:Alteration
Construction Site:
200-234 E. HOPKINS
ASPEN, CO 81611
Owner/Agent:
Peter Gluck
360 Hexagon LLC
119 Hyslop Road
Brookline, MA 02445
Designer/Contractor:
Stanton Humphries
AEC
Avon, CO
970-748-8520
stan@aec-vail.com
Project Information
Energy Code:
MOUNTAIN FORGE TENANT FINISH
Allowed Interior Lighting Power
A
Area Category
B
Floor Area
(ft2)
C
Allowed
Watts / ft2
D
Allowed Watts
(B X C)
2-#4 COMMERCIAL UNIT (Common Space Types:Office - Enclosed)1585 1.11 1759
3-#6 COMMERCIAL UNIT (Common Space Types:Office - Enclosed)520 1.11 577
1-#2 COMMERCIAL UNIT (Common Space Types:Office - Enclosed)322 1.11 357
4-#3 COMMERCIAL UNIT (Common Space Types:Office - Enclosed)655 1.11 727
5-#7 COMMERCIAL UNIT (Common Space Types:Office - Enclosed)485 1.11 538
6-#5 COMMERCIAL (Common Space Types:Office - Enclosed)133 1.11 148
4107Total Allowed Watts =
Proposed Interior Lighting Power
E
(C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
#4 COMMERCIAL UNIT ( Common Space Types:Office - Enclosed 1585 sq.ft.)
LED 1: R3 & R4: DOWNLIGHT: Other:1 22 13 286
LED 2: P2: PENDENT AT BATHROOM: Other:1 4 13 52
LED 3: P3: PENDENT AT BATHROOM: Other:1 1 15 15
LED 4: T1: LED STRIP AT UTILITY: Other:1 1 32 32
LED 5: S2 & S3: SCONCE: Other:1 5 20 100
LED 6: TR1 &TR2: TRACK: Other:1 4 20 80
LED 7: C1: PENDANT AT POOL TABLE: Other:1 1 45 45
#6 COMMERCIAL UNIT ( Common Space Types:Office - Enclosed 520 sq.ft.)
LED 7: R3: DOWNLIGHT: Other:1 10 13 130
LED 8: S4: SCONCE: Other:1 10 20 200
LED 9: S4: LED STRIP AT UTILITY: Other:1 1 32 32
#2 COMMERCIAL UNIT ( Common Space Types:Office - Enclosed 322 sq.ft.)
LED 9: R3: DOWNLIGHT: Other:1 3 13 39
LED 10: TR1 & TR2: TRACK LIGHT: Other:1 12 20 240
#3 COMMERCIAL UNIT ( Common Space Types:Office - Enclosed 655 sq.ft.)
LED 11: R3: DOWNLIGHT: Other:1 13 13 169
Project Title:
Data filename:
MOUNTAIN FORGE TENANT FINISH
P:\Current Projects\18009.00 - Mountain Forge Building Renovation &
Addition\Calculations\COMcheck\MOUNTAIN FORGE TI LTG COMCHECK.cck
09/04/19Report date:
61 ofPage
09/06/2019
09/13/2019
nickt
E
(C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
LED 12: P1: PENDANTS: Other:1 3 20 60
#7 COMMERCIAL UNIT ( Common Space Types:Office - Enclosed 485 sq.ft.)
LED 13: R3: DOWNLIGHT: Other:1 13 13 169
LED 14: P9: PENDANT: Other:1 4 20 80
LED 15: UC3: UNDERCABINET: Other:1 3 2 8
#5 COMMERCIAL ( Common Space Types:Office - Enclosed 133 sq.ft.)
LED 18: T1: LED STRIP: Other:1 2 32 64
1800Total Proposed Watts =
Interior Lighting Compliance Statement
Compliance Statement: The proposed interior lighting alteration project represented in this document is consistent with the
building plans, specifications, and other calculations submitted with this permit application. The proposed interior lighting
systems have been designed to meet the 90.1 (2013) Standard requirements in COMcheck Version 4.1.1.0 and to comply with
any applicable mandatory requirements listed in the Inspection Checklist.
Name - Title Signature Date
Interior Lighting PASSES
Project Title:
Data filename:
MOUNTAIN FORGE TENANT FINISH
P:\Current Projects\18009.00 - Mountain Forge Building Renovation &
Addition\Calculations\COMcheck\MOUNTAIN FORGE TI LTG COMCHECK.cck
09/04/19Report date:
62 ofPage
9/4/19Stanton O. Humphries, PE
09/06/2019
Inspection Checklist
Requirements: 0.0% were addressed directly in the COMcheck software
COMcheck Software Version 4.1.1.0
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Energy Code: 90.1 (2013) Standard
Section
#
& Req.ID
Plan Review Complies?Comments/Assumptions
4.2.2,
8.4.1.1,
8.4.1.2,
8.7
[PR6]2
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the electrical systems
and equipment and document where
exceptions are claimed. Feeder
connectors sized in accordance with
approved plans and branch circuits
sized for maximum drop of 3%.
Complies
Does Not
Not Observable
Not Applicable
4.2.2,
9.4.3, 9.7
[PR4]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the interior lighting
and electrical systems and equipment
and document where exceptions to
the standard are claimed. Information
provided should include interior
lighting power calculations, wattage of
bulbs and ballasts, transformers and
control devices.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
MOUNTAIN FORGE TENANT FINISH
P:\Current Projects\18009.00 - Mountain Forge Building Renovation &
Addition\Calculations\COMcheck\MOUNTAIN FORGE TI LTG COMCHECK.cck
09/04/19Report date:
63 ofPage
09/06/2019
Section
#
& Req.ID
Rough-In Electrical Inspection Complies?Comments/Assumptions
8.4.2
[EL10]2
At least 50% of all 125 volt 15- and
20-Amp receptacles are controlled by
an automatic control device.
Complies
Does Not
Not Observable
Not Applicable
9.4.1.1
[EL1]2
Automatic control requirements
prescribed in Table 9.6.1, for the
appropriate space type, are installed.
Mandatory lighting controls (labeled
as 'REQ') and optional choice controls
(labeled as 'ADD1' and 'ADD2') are
implemented.
Complies
Does Not
Not Observable
Not Applicable
9.4.1.1
[EL2]2
Independent lighting controls installed
per approved lighting plans and all
manual controls readily accessible and
visible to occupants.
Complies
Does Not
Not Observable
Not Applicable
9.4.1.2
[EL11]2
Parking garage lighting is equipped
with required lighting controls and
daylight transition zone lighting.
Complies
Does Not
Not Observable
Not Applicable
9.4.1.1f
[EL13]1
Daylight areas under skylights and
roof monitors that have more than
150 W combined input power for
general lighting are controlled by
photocontrols.
Complies
Does Not
Not Observable
Not Applicable
9.4.1.3
[EL4]1
Separate lighting control devices for
specific uses installed per approved
lighting plans.
Complies
Does Not
Not Observable
Not Applicable
9.6.2
[EL8]1
Additional interior lighting power
allowed for special functions per the
approved lighting plans and is
automatically controlled and
separated from general lighting.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
MOUNTAIN FORGE TENANT FINISH
P:\Current Projects\18009.00 - Mountain Forge Building Renovation &
Addition\Calculations\COMcheck\MOUNTAIN FORGE TI LTG COMCHECK.cck
09/04/19Report date:
64 ofPage
09/06/2019
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
8.7.1
[FI16]3
Furnished as-built drawings for
electric power systems within 30 days
of system acceptance.
Complies
Does Not
Not Observable
Not Applicable
8.7.2
[FI17]3
Furnished O&M instructions for
systems and equipment to the
building owner or designated
representative.
Complies
Does Not
Not Observable
Not Applicable
9.2.2.3
[FI18]1
Interior installed lamp and fixture
lighting power is consistent with what
is shown on the approved lighting
plans, demonstrating proposed watts
are less than or equal to allowed
watts.
Complies
Does Not
Not Observable
Not Applicable
See the Interior Lighting fixture schedule for values.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
MOUNTAIN FORGE TENANT FINISH
P:\Current Projects\18009.00 - Mountain Forge Building Renovation &
Addition\Calculations\COMcheck\MOUNTAIN FORGE TI LTG COMCHECK.cck
09/04/19Report date:
65 ofPage
09/06/2019
Project Title:
Data filename:
MOUNTAIN FORGE TENANT FINISH
P:\Current Projects\18009.00 - Mountain Forge Building Renovation &
Addition\Calculations\COMcheck\MOUNTAIN FORGE TI LTG COMCHECK.cck
09/04/19Report date:
66 ofPage
09/06/2019